8 bridgeport, connecticut 06606 com page 1 ...€¦ · permanently identifies cat. no., amps, hp...

24
8 August ?R, 1985 New Information For standard terms of sale, refer to Selling Policy 30-000 Maileu to: E, D, C/30- 1 00A, EFML-E0 1 , E02, E0 3, E0 4 Westinghouse Electric Corporation Bryant Electric, Circuit Protective Devices Bridgeport, Connecticut 06606 Catalog 30-150 Safety Switches Motor Circuit Switches Page 1 www . ElectricalPartManuals . com

Upload: trinhdang

Post on 18-Aug-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

8 August ?R, 1985 New Information For standard terms of sale, refer to Selling Policy 30-000 Maileu to: E, D, C/30- 1 00A, EFML-E0 1 , E02, E0 3, E0 4

Westinghouse Electric Corporation Bryant Electric, Circuit Protective Devices Bridgeport, Connecticut 06606

Catalog

30-150

Safety Switches Motor Circuit Switches

Page 1

www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page2

Heavy Duty Safety Switches Features

Star mounting holes at top and bottom for easy installation.

De-ion arc chute interrupts and cools arcs for longer switch life

Short circuit withstand ratings

Steel cross arm controls contacts; provides positive blade alignment

Easily-accessible

Diamond pointed jaws prevent burning and pitting

f current-carrying surfaces

fuse clips are reinforced for lower operating temperatures and long-life performance

Ample wiring room speeds installation

Line and load bases constructed of high -impact

phenolic

Door latch securely holds door closed; permits padlocking in closed position

Door interlock prevents cover from being opened

hen switch is energized

Insulated shield prevents accidental contact with

t-----line terminals

Blades are visible in open or closed position

Front-operated handle ith high-visibility

red vinyl sleeve

mple knockouts on all four sides and at rear of enclosure

Pressure-type aluminum line and load terminals can be used with copper or aluminum wire

August, 1985

0

www . El

ectric

alPar

tMan

uals

. com

f) Catalog

30-150

Page 3

Heavy Duty Safety Switches Features

DUAL PURPOSE INTER· RATING iDENTIFICATIC,''i LOCK: Prevents switch Embossed nameplate from being thrown ON enhances appearance and with cover open; prevents permanently identifies cover from being opened Westinghouse name, unless switch is OFF. catalog numbers, volts, Authorized personnel can ampere and horsepower bypass both conditions by ratings. No need to open inserting screwdriver into door to obtain data. interlock defeater (cover

slot located above handle).

TEASEPROOF SW ITCH

DURABLE FINISH: Entire MECHANISM: Over-center

enclosure is bonderized design with positive drive

inside and out and coated spring action maximizes

with baked on enamel for strength of quick-make,

maximum durability and quick-break switch mech-

resistance to rust. anism. Prevents contact

Scratches cannot spread teasing. Handle operates

even though they extend independently of cam and

through to the bare metal. crossbar, allowing cover to be opened or closed in the unlikely event of drive spring breakage.

FRONT OPERATED HANDLE: An integral part of switch mechanism, the easily accessible handle STEEL CROSS ARM AND

permanently controls con- YOKES: Steel yokes in an

tacts, permits close impact-resistant glass

ganging, does not discon- polyester insulating block

nect when door is opened. firmly engage steel cross-

Red vinyl sleeve provides arm that drives the moving

high visibility; indicates blades and provides posi·

handle position (down for tive blade alignment.

OFF; up for ON).

PADLOCKING: Operating DIAMOND-POINTED handle can be padlocked BREAK-JAWS: Moving in OFF position by three contacts extend beyond padlocks with 3/8" hasps. the break-jaws, permitting Prevents closing of con- the breaking arc to travel tacts - an essential along the outside non requirement for heavy-duty current-carrying edges of industrial applications. jaws and blades. Prevents Handle can be padlocked burning and pitting of in ON position by drilling current-carrying surfaces. hole in handle at position marked "X".

DE-ION ARC CHUTE Prevents arc damage by

REMOVABLE I!\JT interrupting and cooling hot

PARTS: All interior parts arcs. Molded material of chute is carbonizing and

''\< are easily removable from track resistant. Prolongs

the front if replacement switch life; allows maxi-

is necessary. mum horsepower ratings permitted by UL.

August,1985 www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page 4

General Duty Safety Switches Plug Fuse, Fusible and Non-Fusible

PF-311-N

F eatures-Specific:,t; • Embossed metal nameplate

permanently identifies cat. no., amps, hp ratings Front-operated handle permits close ganging. Handle is integral part of switching mechanism; provides permanent control of contacts; can be padlocked in OFF or ON position

' Red vinyl cover instantly identifies handle; indicates position Blades visible in open or closed position

• Twin reinforced blades provide maximum surface contact

• Quick-make, quick-break, tease­proof switching mechanism

' Diamond-pointed break jaws prolong blade life; keep silver-plated contact area free of pitting and burning

• Tin plated current carrying parts provide an excellent bearing surface for moving parts

• Easily accessible fuse holders suitable for standard and time delay fuses at maximum UL ratings

• Ample knockouts and wiring room • Line and load terminals suitable

for copper or aluminum wire • Door latch securely holds door

closed; permits padlocking • Door interlock prevents door

from opening when switch is energized

• Star mounting feet assure easy mounting

• UL Listed File E5189

Meet NEMA Spec. KS1-1975 • Meet Federal Spec. WS-865c

switches are Underwriters' Laboratories listed and suitable for use as Service Entrance Equipment when neutral is provided or grounding kit is employed.

RGFN-321-N GFN-321-N GFN-422-N

NEMA 1 PLUG FUSE INDOOR, NEMA 3R PLUG FUSE RAINPROOF

FUSIBLE NEMA 1 INDOOR HORSEPOWER NEMA 3R RA INPROOF __ . .•.•. .••• . !!�!!!'!§.�----· _

SYSTEM S AMPS CAT. NO. APPROX. STD.

WT. LBS. PKG. CAT. NO. APPRO X. :STD. . .. 120 V . 240 V wT. LBs. F'_I(G: iAK-�ID..:-�M�x:��:ro:

1-Pole 2-WireSN !I

vv�n: l\!Dt�t: �.,;

1-2-"Pc;l-�---

3-WireSN

30 PF-211-N 22

PF-311-N 26

10 RPF-211-N

10 RPF-311-N

17

20

FUSIBLE, 24Q_�_9LTS Ac- NEMA 1 AND 3R ENCLOSURES NEMA 1 INDOOR NEMA 3R RAINPROOF

POLES

, 2-Pole 2-Wire

AMPS

30

CAT. NO.

GFN-221 60 � ( Use 3 Wire, <I <I 100 ' 2 Pole Solid

200 ) Neutral 400 . 1 Listings

--------�--?Q() Below

' 2-Pole 3-WireSN

30 60

GFN-321-N GFN-322-N

100 GFN-323-N 200 GFN-324-N 400 GFN-325-N 600 GFN-326-N

�-----------�----·-·······----·· 3-Pole 3-Wire

30 1 l Use 4 Wire, 60 3 Pole Solid

100 Neutral 200 Listings

, Below 400 I GFN-325

!- --·-··-·--···•·· -��--'---�-"!:326

3-Pole 30 GFN-421-N 4-Wire SN 60 GFN-422-N

1 00 GFN-423-N 200 GFN-424-N 400 GFN-425-N 600 GFN-426-N

APPRO X. , STD. WT. LBS. : PKG. � <- - "-- --- __ ..., ______ - •

45

45 15 20 31

140 235

145 290

45 17 23 34

145 295

10 RGFN-221 .use 3 Wire, 12 Pole Solid

Neutral Listings Be low -"-·----- -------------· -·-

10 RGFN-321-N RGFN-322-N RGFN-323-N RGFN-324-N RGFN-325-N RGFN-326-N lUse4 Wire, 3PoleSo lid Neutral Listings Below RGFN-325 RGFN-326

10 RGFN-421-N 1 RGFN-422-N

RGFN-423-N RGFN-424-N RGFN-425-N RGFN-426-N

32

32 15 23 34

155 245

160 300

32 17 26 37

160 305

5 2

5 2

5 11/2 3 3 71/2

5 1

3 7112 10 15 71.2 15 15 30

15 25 50 50 100

75 100

50

7112

15 25 50 75

100

100

NOI\I-F�_S.IBL.S1_4_QVOLTS Ac :- NEMA 1 AND 3R ENCLOSURES 2-Pole 2-Wire

3-Pole 3-Wire

rn

30 60

100 200 400 600

l Use 3Pole Listings Below

30 GUN-321 60 GUN-322

100 GUN-323 200 GUN-324 400 GUN-325 600 GUN-326

45 16 18 32

135 290

10 1

10 1

RGUN-221 RGUN-222 luse 3Pole Listings Below

RGUN-321 RGUN-322 RGUN-323 RGUN-324 RGUN-325 RGUN-326

For price information see Bryant Price List BPL 30·125

32 15

32 17 21 36

150 300

5

5

3 10

712

15 30 50

100 100

August, 1 985 www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page 5

General Duty Safety Switches

NEMA 1 PLUG FUSE INDOOR, NEMA 3R PLUG FUSE RAINPROOF Dimensional Data, Nema 1, Nema 3R

NEMA 1 INDOOR NEMA 3R RAINPROOF

For 30 Ampere Switches

NEMA 1 INDOOR

l ;� /6

0 0

/�

D ON A

OFF

0 0 '\.V v V/ � c =1 D

For 60 through 600 Ampere Switches

NEMA 3R RAINPROOF

A D ON

For 60 through 600 Ampere Switches

PF P lug Fuse S witches, RPF Plug Fuse Switches

DIM ENSIONS· INCHES POLES A M PS

A B c D

1, 2 30 611f1s 413/16 2% 3'1e

NEMA1

1, 2 30

7%2 5%. 4% 97/32 I NEMA 3R I '

GFN Fusible Switches, GUN Non- Fusib le Switches

POLES A M PS DIMENSIONS - INCHES

A B c D

2, 3 30 713/16 7 43132 527132

2. 3 60 1615/32 85/s 517132 81/2

2, 3 100 2215/16 107/s 77/16 127116

2, 3 200 311/4 137/s 821132 1321/32

2, 3 400 t5915i32 235132 1211/32 1521/32

2, 3 600 :1:661/s 235132 1211132 1521/32

t For GUN Non-Fusible Switch: 501;s" � For GUN Non-Fusible Switch: 545/s"

RGFN Fusible Switches , RGUN Non- Fusib le Switches

POLES A M PS DIMENSIONS - INCHES

A

2, 3 30 911/32

2, 3 60 1615/32

2, 3 100 2215/16

I 2, 3 200 311/4

2, 3 400 t5915i32

2, 3 600 :j:661/s

t For RGUN Non-Fusible Switch: 50118" �For RGUN Non-Fus1ble Switch: 545/s''

B c

615/16 41/s

91/s 517132

1027/32 77/16

1327132 821132

235132 123/s

235/32 123/s

D

527/32

81/2

127/16

1321/32

1521132

1521132

All products in this catalog meet the new wire bending space requirements as identified in 1981 NEC Section 373-6 (b).

August, 1985 www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page 6

Heavy Duty Safety Switches Fusible

HFN-362 RHFN·362 WHFN-362 JH Features-Specifications • Bonderized UL Listed organic

240 VOLTS Ac, 250 VOLTS Dc,FUSIBLEcvNEMA 1,3R,4 AND 1 2 ENCLOSURES Fusible®, 240 Volts Ac or 250 Volts De

fin ish resists rust

• Dual cover interlock prevents ac­

cidental operation; door cannot be

opEMed when switch is ON ;

contacts cannot close with door

open. Both functions are defeatible

by authorized personnel

POLES

2-Pole 2-Wire

�� 2-Pole

AMPS

30 60

100 200 400 600 800�

1200 6 30

NEMA1@ NEMA 3 R NEMA4 INDOOR RAINPROOF STLS. STEEL

CAT. NO. CAT. NO. CAT. NO.

HFN-221 RHFN-221 WHFN-221 HFN-222 RHFN-222 WHFN-222 HFN-223 RHFN-223 WHFN-223 HFN-224 RHFN-224 WHFN-224 HFN-225 RHFN-225 WHFN-225 HFN-226 RHFN-226 WHFN-226 HFN-227 RHFN-227 . . . . . . HFN-228 RHFN-228 . . . . ..

HORSEPOWER RATING

240 VOLTS 250 NEMA12 @@

AcSTD. MAXIMUM VOLTS

CAT. NO. De 1¢ 34> 14> 34>

JHFN-221 1112 3 5 JHFN-222 3 10 10 JHFN-223 7112 15 20 JHFN-224 15 40 JHFN-225 JHFN-226 . . . . . . ......

1112 3 5

• Line terminal shield prevents ac­cidental contact with line terminals

• De-ion arc chute interrupts and

3-Wire SN

��� 60

100 200 400 600 800

Order2 Pole Order2 Pole � switch from � switch from above above Select neutral Select neutral

kit from kit from neutral table neutral table

Order2 Pole Order2 Pole �switch from �switch from 3 10 10 71!'.< 15 20

above above 15 40 Select neutral Select neutral

kit from kit from neutral table neutral table

1200 on page9

cools hot arcs; prevents arc damage Fustble®, 240 Volts Ac

• Embossed metal nameplate per­manently identifies catalog number, amperes and horsepower rating

3-Pole 3-Wire

��� 3-Pole

30 HFN-321 60 HFN-322

100 HFN-323 200 HFN-324 400 HFN-325 600 HFN-326 800� HFN-327

1200 HFN-328

30

on page9

RHFN-321 RHFN-322 RHFN-323 RHFN-321 RHFN-325 RHFN-326 RHFN-327 RHFN-328

on page9 on page9

WHFN-321 JHFN-321 3 7112 WHFN-322 JHFN-322 7V 15 WHFN-323 JHFN-323 15 30 WHFN-324 JHFN-324 25 60 WHFN-325 JHFN-325 50 125 50 WHFN-326 JHFN-326 75 200 . . . . . · · · - · -· · - · - · · · - · - ·

3 7112

• Front-operated handle permits

close ganging. Handle is integral

part of switching mechanism;

provides permanent control of

contacts; can be padlocked in OFF

4-Wire SN

I<<� 60

100 200 400 600 800

Order 3 Pole ! �""�" � switch from switch from above above Select neutral Select neutrat

kit from kilt rom neutral table neutral table

Order 3 Pole r .. ·- 7V 15 �switch from switch from 15 30 above above 25 60 Select neutral Select neutra 50 125 50

kit from kittrom 75 200 neutral table neutral table

or ON position 1200 on page9 on page9 on page9 on page9

4-Pole 30 HFN-421 JHFN-421 3 7'12

• Red vinyl cover instantly identifies

handle, indicates position

4-Wire 60 HFN-422 JHFN-422 7'\> 15

���� 100 HFN-423 JHFN-423 15 30 200 HFN-424 JHFN-424 25 60 400 HFN-425 50 125 600 HFN-426 75 200

• Blades visible in open or closed

position 600VOLTSAc, 600VOLTS Dc,FUSIBLE®NEMA 1, 3R, 4and 1 2 ENCLOSURES Fusible(]), 600 Volts Ac ® 600 Volts De

• Quick-make, quick-break, tease­

proof switching mechanism

• Diamond-pointed break jaws pro­

long blade life; keep contact area

free of pitting and burning

• Tin-plated current-carrying parts

have lubricated moving parts

for ease of operation

• Easily accessible fuse holders

suitable for standard, time delay

and Type J fuses (Type J for

enclosures thru 600A)

NEMA1 @ POLES AMPS INDOOR

CAT. NO.

�:����(j) 30 HFN-261 60 HFN-262

100 HFN-263·

�� 200 HFN-264 400 HFN-265 600 HFN-266 800� HFN-267

1200 HFN-268

Fusible CV, 600 Volts, Ac ®

�:����(j) 30 HFN-361 60 HFN-362

100 HFN-363

��� 200 HFN-364 400 HFN-365 600 HFN-366 800� HFN-367

1200 6 HFN-368

(j) For neutral k1ts refer to page 9.

NEMA 3 R RAINPROOF

CAT. NO.

RHFN-261 RHFN-262 RHFN-263 RHFN-264 RHFN-265 RHFN-266 RHFN-267 RHFN-268

RHFN-361 RHFN-362 RHFN-363 RHFN-364 RHFN-365 RHFN-366 RHFN-367 RHFN-368

• Ample knockouts and wiring room ® 30-600 amp switches are available with provision for Class J fuses. To order, add suffix J to catalog number.

@ 800 and 1200 ampere switches have provision for Class L • Line and load terminals suitable for fuses(1 fuse per pole)

@ NEMA 12 (30 to 200 Amp.) enclosures are available with COpper Or aluminum Wire knockouts.To order.addsuffixDto catalog number.

For new NEG terminal data see page 9.

NEMA4 STLS. STEEL

CAT. NO.

WHFN-261 WHFN-262 WHFN-263 WHFN-264 WHFN-265 WHFN-266

· - · · · · ......

WHFN-361 WHFN-362 WHFN-363 WHFN-364 WHFN-365 WHFN-366 ......

· · · - · ·

NEMA 12 CAT. NO.

JHFN-261 JHFN-262 JHFN-263 JHFN-264 JHFN-265 JHFN-266 . . .... . .....

JHFN-361 JHFN-362 JHFN-363 JHFN-364 JHFN-365 JHFN-366 . ..... . .....

HORSEPOWER RATING VOLTS Ac STD. MAXIMUM De

480V 600V 480V 600V 250 600 14> 14> 14> 14>

3 3 7112 10 10 5 10 20 25 25

10 15 30 40 40 25 30 50 50 50

I·�� 1 o��· �3:;, 03:;,· 5 7112 15 20

15 15 30 50 25 30 60 75 50 60 125 150

100 125 250 350 150 200 400 500 50

@Switches are available with proviSIOn for tang terminals. To order, add sufftx A to catalog number.

@Ac rated only. CV For Class R fuse kits. refer to page 14 .

For price information see Bryant Price List BPL 30-125 August, 1 985 www . El

ectric

alPar

tMan

uals

. com

Features-Specifications

• Door latch securely holds door

closed; permits padlocking

• Door interlock prevents door from

opening when switch is energized

• Star mounting feet assure easy mounting

• UL Listed File E5189

• GSA Certified File

(800-1200 amps) LR-28115

• Meet NEMA Spec. KS1-1975

• Meet Federal Spec. WS-865c

Application Data • All switches are Underwriters'

Laboratories listed and suitable for use as Service Entrance Equipment when neutral is provided or grounding kit is employed.

• All Heavy Duty Safety Switches, when used with Class R or J fuses, are rated for 100,000 amps RMS available.

August, 1985

RHFN-362 WHFN-362

Catalog

30-150

Page 7

Heavy Duty Safety Switches Fusible and Non-Fusible

JHFN-362

240, 480, 600 VOLTS Ac, 250, 600 VOLTS De, FUSIBLECfi AND NON-FUSIBLE NEMA 1, 3R, 4 AND 12 ENCLOSURES Fusible,® 600 Volts Ac

NEMA1 @ NEMA3 R POLES AMPS INDOOR RAI NPROOF

CAT. NO. CAT. NO.

3·Pole 30 4.Wire SN 60 r-·- ! """"�" 100 switch es from switch es from

���< 200 page 10 and page10 and 400 select neutral select neutral 600 ki tfrom ki tfrom 800 page9 page9 1200

Fusible, 600 Volts Ac

4·Pole 30 I HFN-461

4-Wire 60 HFN-462

���{ 100 HFN-463 200 HFN-464 400 HFN-465 600 HFN-466

Non· Fusible. 240 Volts Ac

2-Pole(j) 30 ! ! 2-Wire 60

n 100 Use3 Pole Use3 Pole 200 below below 400 600

Non-Fusible, 240 Volts, Ac

5-����G) 30 HUN-321 RHUN-321 60 HUN-322 RHUN-322

rn 100 HUN-323 RHU�·323 200 HUN-324 RHUN-324 400 HUN-325 RHUN-325 600 HUN-326 RHUN-326

Non· Fusible, 600 Volts Ac, 600 Volts De

�:����G) 30 HUN-261 RHUN-261 60 HUN-262 RHUN-262 100 HUN-263 RHUN-263

n 200 HUN-264 RHUN-264 400 HUN-265 RHUN-265 600 HUN-266 RHUN-266 800� HUN-267 RHUN-267 1200 HUN-268 RHUN-268

Non-Fusible, 600 Volts Ac

3-Pole G) 30 HUN-361 RHUN-361 3.Wire 60 HUN-362 RHUN-362 100 HUN-363 RHUN-363

nr 200 HUN-364 RHUN-364 400 HUN-365 RHUN-365 600 HUN-366 RHUN-366 800� HUN-367 RHUN-367 1200 6 HUN-368 RHUN-368

Non-Fusible, 600 Volts Ac, 250 Volts De /4-Pole 30 HUN-461 4-Wire 60 HUN-462

nn 100 HUN-463 200 HUN-464 400 HUN-465 600 HUN-466

CD For neutral kits refer to page 9. (2)30-600 amp switches are available w1th provision for Class J

fuses. To order, add suffix J to catalog number. @BOO and 1200 ampere switches have provis1on tor Class L

fuses (1 fuse per pole). @NEMA 12 (30 to 200 Amp.) enclosures are ava1lable w1th

knockouts. To order, add suffix 0 to catalog number.

For new NEC terminal data see page 9. For price information see Bryant Price List BPL 30-125

HORSEPOWER RATING VOL TS NEMA4

NEMA12 @@ AcSTD. MAXIMUM De STLS. STEEL

CAT. NO. CAT. NO. 480V 600V 480� 600V 250V 600V 3<1> 3<1> 3<1> 3<1>

5 7V2 15 20 �-·- � Order 3 Pole 15 15 30 50 �:�t;�g��3" switch es fr«?n 25 30 60 75

page 10 and 50 60 125 150 select neutral select neutral 100 125 250 350 kit from kit from 150 200 400 500 page9 page9

480V 600V 480V 600V 2<1> 2<1> 3<1> 3<1>

25 15 20 50 30 50 50 60 75 125 150 250 350 400 500 480V 600V 480V 600V

2<1> 2<!> 2<1> 2<1> ! I Use3 Pole Use3 Pole below below

240V 240V 480V 600V 1<1> 3<1> 1<1> 3<1>

WHUN-321 JHUN-321 3 71/2. WHUN-322 JHUN-322 10 15 WHUN-323 JHUN-323 15 30 WHUN-324 JHUN-324 15 60 WHUN-325 JHUN-325 100 WHUN-326 JHUN-326 200

240V 240V 480V 6��v 1m 1<1> 1d>

WHUN-261 JHUN-261 7112 10 15 WHUN-262 JHUN-262 20 25 30 WHUN-263 JHUN-263 30 40 50 WHUN-264 JHUN-264 50 50 50 WHUN-265 JHUN-265 WHUN-266 JHUN-266 ... .. . .. ... . .... .. .... ..

240V 240V 480V 600V 1d> 1d> 3<1> 3d>

WHUN-361 JHUN-361 15 20 WHUN-362 JHUN-362 30 50 WHUN-363 JHUN-363 60 75 WHUN-364 JHUN-364 125 150 WHUN-365 JHUN-365 250 350 50 WHUN-366 JHUN-366 400 500 . .. ..

· · · · · · . . .... 240V 600V 480V 600V

2<1> 2d> 3<1> 3d>

JHUN-461 10 25 20 30 5 JHUN-462 20 50 50 60 10 JHUN-463 30 50 60 75 20 JHUN-464 50 50 125 150 250 350

400 500 @SwitChes are available w1th proviSion for tang term1nals To

order, add suff1x A to catalog numt'er. @Ac rated only ® For Class R fuse k1ts. refer to page 14. @These are 2-phase rat1ngs www .

Elec

tricalP

artM

anua

ls . c

om

Catalog

30-150

PageS

Heavy Duty Safety Switches Dimensional Data NEMA 1 INDOOR

�c=:J

T)�\ r41

1�� B -----1 D � For 30 Ampere Switch es

For 60 th rough 1200 Ampere Switch es

(j)250 Volt units only

NEMA 3R RAINPROO F

r---u /JLQ I-- B -----, D�

pO For 30 Ampere Switch es

\V v 'v -o l

For 60 th roug h 1200 Ampere Switch es (j)250 Volt umts only

DIMENSIONS - INCHES POLES AMPS

A

2501600 Volt HFN Fusible Switch es

2, 3® 30 99/32 2, 3 30 1815/16 2, 3(j) 60 167116 2, 3 60 1815/16 2,3 100 287116 2, 3 200 375/a 2, 3 400 5915/32 2, 3 600 66':a 2, 3 800 6531132 2, 3 1200 735/32

2501600 Volt HUN Non - F usible Switch es

2, 3(j) 30 99/32 2, 3 30 167116 2, 3 60 167116 2, 3 100 287116 2, 3 200 375/a 2, 3 400 501/a 2, 3 600 545/a 2, 3 800 60 2, 3 1200 6429/32

2501600 Volt RHFN Fusible Switch es

2, 3(j) 30 2, 3 30 2, 3 60 2, 3 100 2, 3 200 2, 3 400 2,3 600 2, 3 800 2, 3 1200

103116 1815116 1815,16 287-'16 375 8 5915132 661·8 6531 32 755132

77116 8718 87's

1013/16 1313116 235132 235132 3911 '16 4211116

B

71/z 9 9 9

1013/16 1313/16 235/32 235/32 3911/16 4211116

71/z 9 9

1013/16 1313/16 235/32 235132 3911/16 4211/16

413/16 517/32 517/32 77116 821/32

12318 123/8 129/32 129/32

2501600 Volt RHUN Non - Fusible Switch es

2, 3(j) 30 103/16 77116 413'16 2, 3 30 1815116 87/a 517/32 2, 3 60 1815116 871a 517/32 2, 3 100 287'16 1013/16 77/16 2, 3 200 37518 1313/16 821132 2, 3 400 501;8 235/32 123/8 2, 3 600 545/8 235132 123/a 2c 3 800 60 3911116 129/32 2, 3 1200 6429132 4211'16 129132

c 413/32 517/32 517/32 517132 77!16 821/32

1211/32 1211/32 121/4 121/4

413/32 517/32 517/32 77116 821/32

1211/32 1211/32 121/4 12114

75132 93/s 93/8

10314 131/2 1521/32 1521/32 1525/32 1525/32

75/32 93/8 93/a

103/4 13112 1521/32 1521/32 1525/32 1525/32

CONDUIT D SIZES, INCHES

627/32 1/2,3/4, 1 97/a 112,3/4, 1, 1'/4, 1112,2.2112 97/a 1/2, 3/4, 1' 11/4, 11/2, 2, 21/2 97/a 112,3/4, 1, 11/4, 1112, 2, 2112

121/16 112,3/4, 1, 1114, 11/z, 2 1313/32 lfz, 3/4, 11/z, 2, 2'12, 3 1521/32 31/2,4 1521/32 3112,4 1525/32 1525/32

627/32 1/2, 3/4, 1 97/a 1/z,3/4,1, 11/4, 11/2, 2, 21/2 97/a 1/z, 3/4, 1, 11/4, 1112, 2, 2112

121/16 1/2,3/4, 11/4, 11/2,2 1313/32 1/2,3/4,11/2,2,21/2, 3 1521/32 3112, 4 ' 1521/32 31/2,4 ! 1525/32

I 1525/32

CONDUIT SIZES, INCHES

1/2,3/4, 1' 1114, 1112,2 3/4, 1, 11/4, 11/2,2 1/2, 3/4, 1' 11/4, 11/2,2 3/4,1, 1114, 11/2,2 1/2, 3/4, 1, 11/4, 11/2, 2 3/4, 1, 11/4, 11/2,2 112, 3(4, 1' 11/4, 11/2,2 314, 1' 1114, 11/2,2 112, 3/4, 11/2, 2, 21/2, 3 2, 21/2, 3

1/2,314, 1, 11/4,11/2,2 3/4, 1' 1114, 1112, 2 112,3/4, 1, 11/4,1112,2 3/4, 1, 11/4,1112,2 112,314,1, 11/4,1112, 2 3/4, 1, 1114,11/2,2 1/2,3/4, 1, 11/4,11/2, 2 3/4, 1, 11/4, 11'2,2 112, 314,1112,2, 21/2,3 2, 2112, 3

NEMA 4 WATERTIGHT STAINLESS STEEL, NEMA 12 DUST-TIGHT & OIL-TIGHT INDUSTRIAL

r B ' _j '---c l Tl � I A D ' I=

.P ,-v- v v

1--- D _______,

For 30 th rough 200 Ampere Switch es

rr {'\

D I A

I � I J h�B�·

�c-----1 r--p

!fJ l � 0 1 For 400 th rough 600 Ampere Switch es

t�

rc -1

:� Jfc=J � D __,

For 30 Ampere, 250 Volts Switch es

(j) 250 Volt units only

FA

DIMENSIONS - INCHES

POLES AMPS B c D

2501600 Volt WHFN Fusible Switch es

�.3® 30 1011 16 77'16 421/32 615116 2,3 30 1815116 9t,a 517.'32 93/a 2,3 60 1815'16 9118 517132 93/a 2,3 100 287'16 1015116 77/16 103/4 2,3 200 375/a 1315/16 821132 131/2 2,3 400 6117/32 235!32 1213/32 177/16 2,3 600 683 16 235/32 1213/32 177116

2501600 Volt WHUN Non- Fusible Switch es

2,3® 30 1011'16 77116 421132 615116 2,3 30 1815116 91/8 517132 9318 2,3 60 1815116 9118 517132 93/8 2,3 100 287.16 1015116 77ft6 103/4 2,3 200 37518 1315Jt6 821/32 131/2 2,3 400 523/16 235/32 1213/32 177116 2,3 600 5611116 235132 1213/32 177116

2501600 Volt JHFN Fusible Switch es

2,3(j) 30 1311116 719/32 421/32 615/16 2,3 30 1815/16 8?13 517/32 93/s 2,3 60 1815116 8?13 517/32 93/a 2,3 100 287'16 1011116 77116 103/4 2,3 200 37518 1311/16 821/32 131/2 2,3 400 6117'32 235!32 1213/32 177116 2,3 600 683/16 235/32 1213/32 177116

2501600 Volt JHUN Non - F usible Switch es

2,3<D 30 1311/t6 719/32 421/32 615/16 2,3 30 1815/16 87/a 517/32 93/a 2,3 60 1815116 87/a 517132 93/a 2,3 100 287116 1011116 77/16 103/4 2,3 200 37518 1311/16 821/32 131/2 2,3 400 523/16 235/32 1213/32 177116 2,3 600 5611116 235/32 1213/32 177/16

All products in this catalog meet the new wire bending space requirements as identified in 1981 NEC Section 373-6 (b). August, 1985

�"c

www . El

ectric

alPar

tMan

uals

. com

NK-400

GNK

EK-1

� "�

RFK-1

--� .: t/ RFK-2 �/ r-�. RFK-4 8 1 t ... '· •• -� ._ , ., '� RFK-3

\ RFK-5

R1H-200

ST-4

ST-6

August, 1985

Catalog

30-150

Page 9

General and Heavy Duty Safety Switches Modifications and Accessories

TERMINAL D.ATA FOR SWITCHES THAT COMPLY WITH 1981 NEC SECT. 373-6 (b)

AMPS

30 60

100 200 400

or 600

PLUG- GENERAL DUTY

No. ofw1res

MIN.

WIRE

SIZE

#14 #14 #14 #4

250 MCM 3 0 1 0

MAX.

WIRE SIZE

#8 #3 1'0

200 MCM 750 MCM 300 MCM 750 MCM

TYPE AMPS

Cu Cu AI Cu AI Cu AI

Cu Cu

Cu,AI

30(j) 30 @ 60 100 200

400 or

600 800

1200

HEAVY DUTY

No. : of wires :

MIN.

WIRE

SIZE

#14 #14 #14 #14 #6

250 MCM 3 0 1 0 1 0 1 0

MAX.

WIRE SIZE

#8 #3 #3 1•0

250MCM 750 MCM 300 MCM

, 750MCM : 750 MCM

750 MCM

ELECTRICAL INTERLOCK KITS

TYPE i

Cu AI Cu1AI Cu1AI Cu·AI Cu•AI

Cu Cu

Cu. AI Cu,AI Cu·AI

DOUBLE THROW

MIN. MAX.

WIRE SIZE I WIRE SIZE

AMPS· ...... -1------ .. i of ���es j SIZE ! of ��;es SIZE

l • . 30 . 1 #14 1 60@ . 1 #14 1 60@ 1 #12 1

100@ 1 #12 1 100@ 1 #12 1 200 1 #6 1 400 2 1 0 2

or 1 600 1 0 2

#6 #4 1 0 1 0

1 1 0

I ggg �g� ! 750 MCM ! 350 MCM

TYPE

Cu Cu AI CuAI

Cu CuAI CuAI CuAI CuAI i

Cu

r-·

DESCRIPTION AMPS CAT. NO.

i Electrical interlock kits are available for H-600 30 Amps, 250 Volts® EK-1® I type heavy duty safety switches. The kit con- 30, 60 Amps, 600 Volts, I ! tains a contact block having 1 NO and 1 NC con- 60 Amps, 250 Volts® EK-2 i tact rated 10 amps resistive and 6 amps in- All 100 and 200 Amp I ductive, mounted on a steel bracket with a con- Switches® EK-3

trol arm. The control arm is actuated by the All400 and 600 Amp switch mechanism and breaks the control cir- Switches® EK-5

I switch Not cuit before the safety opens. All BOO thru 1200 Amp l available for motor circuit switch. Switches EK-4®®

I

i I i i

!

NEUTRAL KITS FIELD INSTALLED IN NON-FUSIBLE AND FUSIBLE HEAVY DUTY SWITChES GROUNDING KITS

AMPS

30 60

100 200

400 600 800

1200

CATALOG NUMBER

NEMA 1 NEMA 3R, 4, 12 N- K-30 @ ----L-�N""'Kcc30cc-@"g�---NK60 NK60 NK100 NK100 NK200 NK200 NK400 NK400 NK600 NK600 NKBOO NKBOO NK1200 NK1200

CLASS R FUSE CLIP KITS®®

DESCRIPTION

For use with heavy duty safety switches only. Kit will reject all fuses except class R. Only one kit required for a three pole switch.

INTERCHANGEABLE RAIN PROOF HUBS

DESCRIPTION

CATALOG NUMBER MAX. RATING

GNK-6 --+----6""'0-�A------i GNK-20 200A GNK-60 600A

- --·------ .. ---�------�

AMPS CAT. NO

30A, 250V RFK-1 30A, 600V/60A, 250V RFK-2 60A, 600V RFK-3 1 00/200A, 250/600V RFK-4 400/600A, 250/600V RFK-5

HUB DIA. SWITCH CAT. NO. i--- INCHES SIZE

I All rainproof switches except 400 and 600 % 30 l amperes are shipped with cutout covered by a 1 thru i plate. Figure 1 shows a hub mounted in posi- 1114 100 I I lion. Hubs smaller than 2" can be used on 200 11/z Amps

ampere switches by ordering an adapter plate 2 R 1HA. 2 200

i 2112 Amps ! 3 Adapter Plate '---

r I ' '

i

i

MYERS-TYPE HUBS HUB DIA. ZINC DESCRIPTION INCHES CAT. NO.

All 400 and 600 ampere rainproof switches are 1/z shipped with plain tops, no cutouts. Order zinc % or chrome Myers-type hubs from the �able 1 below; hubs are shipped separately. 1114

11/z Rainproof switches 30 through 200 amperes 2 with plain tops for use with Myers-type hubs, are 2V2 available in minimum ordering quantities of 100 3 units. (Mixed 30, 60, 100 and 200 amperes.) 31/z

4 .

(j) 250V Sw1tch @ 600V Switch @ NEMA 1

@ Cannot be installed when conduit entrance is at top right. ® Excepl four blade, four pole and double throw switches. @ This unit is only factory mounted.

@ NEMA3R @ For factory installation add suffix A

to catalog number to specify.

® For 250V applicalion only. Use NK60 for 600V.

For price information see Bryant Price List BPL 30-125

ST-1 ST-2 ST-3 ST-4 ST-5 ST-6 ST-7 ST-8 ST-9 ST-10

ROH-075 ROH-100 ROH-125 ROH-150 ROH-200 R1H-200 R1H·250 R1H-300 R1HA

CHROME CAT. NO.

CST-1 CST-2 CST-3 CST-4 CST-5 CST-6 CST-7 CST-8 CST-9 CST-10

www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page 1 0

Double Throw Switches Motor Circuit Switches

XUN-321

Features-Specifications DOUBLE THROW SWITCHES • Cover interlock (through 600A

prevents door from opening when switch is energized

• Positive-make, quick-break operating mechanism

• Handle may be padlocked in top ON, neutral, or bottom ON positions

• All switches except 600 Amps are UL Listed

Application Data • Double throw switches are designed for

use as transfer switches when load is

XUN-321 SDSN6030 SDSN6030

DOUBLE THROW NEMA 1, 3R, 250, 600 V.A.C. FUSIBLE AND NON-FUSIBLE Fusible, 240 Volts Ac Fusible, 600 Volts Ac

SHIP POLES AMPS CAT. NO. WT. POLES AMPS CAT. NO.

NEMA1 NEMA3R LBS. NEMA1 NEMA3R

2-Pole 30 r- t"' 18 2-Wire 60 3Pole 3Pole 1 24

ii 100 3 Wire 3 Wire 61 200 Switch Switch 125

SS Below Below

3-Pole 30 XFN- 361 3-Wire 60 XFN- 362

sss 100 XFN-363 200 XFN- 364 """""" 400 XFN-365 ))) I

3-Pole 30 XFN-321 20 3-Wire 60 XFN-322 RXFN- 322' 31

i'i'i 100 XFN-323 RXFN-323 85 200 XFN- 324 RXFN- 324 160

sss 400 XFN-325 250 600@ XFN- 326 310

i i I

SHIP W T .

LBS.

53 54 87

170 260

I supplied from two sources. Switch Non-Fusi ble, 240 Volts Ac Non-Fusible, 600 Volts Ac

opens one circuit and closes another simultaneously, or isolates both circuits.

Features-Specifications MOTOR CIRCUIT SWITCHES • Insulated shield prevents accidental

contact with line terminals • Blades visible in open or closed

position • Cover interlock prevents cover from

opening when switch is energized. Interlock release permits cover to be opened for switch inspection.

• Trunk-type latches keep cover tightly closed; provides an effective dust-resisting seal.

• Over-center quick-make, quick-break switching mechanism prevents teasing of contacts

• Large wiring gutters facilitate wiring and provide easy access to terminals

• Handle can be padlocked in OFF position by up to three padlocks

• Cover can be padlocked in closed position

• Neoprene gasket seals out moisture and dust from switch assembly

• 6 Pole switches are listed under UL E-5189

Application Data • Designed to meet the demands of heavy

industry for a compact, non-fusible switch with visible contact disconnect.

2-Pole 30 ! o,,., I 15 2-Wire 60 3Pole,

II 100 3 Wire """" 200 Switch 84 II 400 Below 130

2-Pole 60 !0''" �0- 22 2-Wire 100 3Pole, 3Pole, 39

II 200 3 Wire 3 Wire 100 """" 400 Switch Switch 135 II 600@ Below Below 215 �Pole 30 XUN-321 I l) ,------.;?- 3-Pole 60 XUN- 362 RXUN- 362 31

3-Wire 60 XUN- 322 I 20

I! I 100 XUN-323 I 39 200 XUN-324 106 """""" 400 XUN-325 163 Ill 600<D XUN- 326 I 224 _J

4-Pole 60 XUN-422 32 4-Wire 100 XUN-423 i 46 II II 200 I XUN-424 I 127 -<-<.c:< II II

<D Ac ratmg only.

MOTOR CIRCUIT SWITCHES 6 Pole Non-Fused Complete

CATALOG NUMBER AMPS

NEMA 1 NEMA 3R NEMA 12

30 SDSN6 030 RDSN6030 JDSN6030 60 SDSN606 0 RDSN606 0 JDSN6060

100 SDSN6100 RDSN6100 JDSN6100 200 SDSN6200 RDSN6200 JDSN6200

,-TERMINALS ARE SUITABLE FOR EITHER COPPER OR ALUMINUM CABLE

SWITCH WIRE RANGE RATING

COPPER ALUMINUM

30 #14·#2 #12-#2 60 #14·#2 #12·#2

100 #14-1/0 #12·1/0 200 #4-300MCM #4·300MCM �-

ELECTRICAL INTERLOCK KIT Double Throw Switches

DESCRIPTION

XLK111 Universal Type

3-Wire 100 XUN-363 RXUN-363 50

Ill 200 XUN-364 RXUN- 364 110 4ll0 XUN-365 RXUN-365 191 """""" 600G) XUN- 366 RXUN-366 256 Ill

4-Pole 60 I XUN-462 �-

33 4-Wire 100 XUN-463 46

Ill\ i <-<-<< II II

MAXIMUM H.P. RATINGS 600 VAC 250 VDC

AMPS 120 VAC 240VAC 480VAC 600VAC 250VDC

30 5 10 20 25 71/2 60 10 20 40 60 15

100 15 30 75 75 25 200 60 100 100 40

Accessories Aux. Switch Kits*

AMP RATING CONTACT SWITCH USED ARRANGEMENT KIT STYLE NO. WITH

30,60,100 1A, 1B 178C265G05 200 1A, 1B 178C619G01 200 2A's, 2B's 178C619G02

Permtts fteld mounttng of an auxthary swttch for separate control ctrcutt applica­tions. Each switch includes three soldered, identified leads.

NEUTRAL KITS

CAT. NO. l

__ J XNK-2 I XNK-4 I XNK-6

AMPS -----r-------E CAT. NO.

------�------ ---�-� L 200 400 600 -�-_L_ _j

For price information see Bryant Price List BPL 30-125 August, 1985

www . El

ectric

alPar

tMan

uals

. com

NEMA 1 INDOOR DOUBLE THROW SWITCHES

For 30 t h rough 600 Ampere Switch es

Fusible Switches

! DIMENSIONS -INCHES CONDUIT CAT. NO. SIZES ,

i A I B c INCHES

XFN-3 21 I 151/s 101/4 33/4 1/2, 3/4, 1' 11/4 XFN-3 22 225/s 121/2 61/2 3/4,1 ' 11/4, 11/2, 2 XFN-3 23 345!32 131/2 61/2 11/2,2,21/2 XFN-3 24 I 5 13/64 I 173132 103/32 2, 21/2 XFN-3 25 6519/64 205!32 1 15f32 21/2,3 XFN-3 26 7019/64 225f32 135f32 3, 31/2

XFN-3 61 I 345!32 131/2 61/2 1/2, 3/4, 1' 11/4 XFN-3 62 I 345!32 131/2 61/2 3/4,1 ' 11/4, 11/2, 2 XFN-3 63 385!32 1415/32 613f16 11/2,2 XFN-3 64 5 1%4 175!32 103132 2, 21/2, 11/2 XFN-3 65 651%4 205f32 1 15/32 21/2,3

Not to be used tor construction purposes unless approved.

NEMA JR, OUTDOOR DOUBLE THROW SWITCHES

MOTOR CIRCUIT SWITCHES

[lo A'

I I LL �---

ON OFF

6 Pole Un its- 30, 60, 100 AMPERES 6 Pole Un its- 200 AMPERES

Non-Fusible Switches

CAT. NO. A

XUN-3 21 151/s

XUN-3 22 225/s

XUN-3 23 211/s

XUN-3 24 3151/64

XUN-3 25 4 11%4

XUN-3 26 4919/64

XUN-422 2 11/s

XUN-423 2 11/s

XUN-424 3151/64

XUN-262 225/s XUN-263 2 11/s

XUN-264 3151/64

XUN-265 4119(64

XUN-266 491%4

XUN-3 62 225/s XUN-3 63 211/s

XUN-3 64 3 151/64

XUN-3 65 4 11%4

XUN-3 66 491%4

XUN-462 2 15/32

XUN-463 215132 --

Fusible Switches

I CAT. NO.

A

RXFN-3 22 23 RXFN-3 23 341/2

RXFN-3 24 4327/64

Non-Fusible Switches

RXUN-3 62 151/2 RXUN-3 63 2 1 '12 RXUN-3 64 3151/64 RXUN-3 65 4119/64 RXUN-3 66 4919/64

Catalog

30-150

Page 1 1

Double Throw Switches Motor Circuit Switches

Dimensional Data

DIMENSIONS -INCHES CONDUIT

B

I 101/4

121/2

131/2

175/32

205132

225132

175/32

175/32

2113/32

121/2

131/2

175132

205/32

225132

121/2

131/2

175132

205/32

225132

175/32

175132

DIMENSIONS -INCHES

B 1415/16

1415/16

175f32

1415116 1415116 175132 205/32 225/32

c 33/4 61/2

61/2

103132

1 15132 135132

61/2

61/2

103132

61/2

61/2

103/32

115/32

135/32

61/2

61/2

103132

1 15132

135/32

61/2 61/2

c 7 7

103132

7 7

103132 115132 135!32

SIZES, INCHES

1/2, 3/4, 1, 11/4 3f4, 1' 11/4, 11/2, 2

11/4, 11/2,2

11/2,2,21/2

21/2, 3

3. 31/2

3f4, 1' 11/4, 11/2, 2 11/4, 11/2,2

11/2,2,21/2

3/4, 1' 11/4, 11/2, 2 11/4, 11/2,2

11/2, 2,21/2 21/2,3

3, 31/2

3/4, 1' 11/4, 11/2, 2 11/4, 11/2,2

11/2, 2, 21/2

21/2,3

3, 31/2

3/4, 1' 11/4, 11/2, 2 11/4, 11/2,2

CONDUIT SIZES , INCHES

3/4, 1' 11/4, 11/2, 2

11/4, 11/2, 2

11/2,2,21/2

3/4, 1' 11/4, 11/2, 2 11/4, 11/2, 2 1112,2,21/2 21/2,3 3, 31/6

6 Pole Units- 30, 60, 100 AMPERES

ENCLOSURE DIMENSIONS -INCHES AND MM

TYPE A B c IN. MM IN. MM IN. MM

NEMA1 183/4 476 181/2 470 815116 227

NEMA3R 183/4 476 181/2 470 815116 227

NEMA 12 183/4 476 181/2 470 815/16 227

6 Pole Units- 200 AMPERES

NEMA 1 3FI16 799 217116 545 93/4 248

NEMA3R 317116 799 217116 545 93/4 248

NEMA 1 2 3Fi16 799 2 17116 545 93/4 248

All products in this catalog meet the new wire bending space requirements as identified in 1981 NEC Section 373-6 (b).

August, 1985

www . El

ectric

alPar

tMan

uals

. com

Catalog

30-150

Page 1 2

Westinghouse Electric Corporation Bryant E lectric, Circuit Protective Devices Bridgeport, Connecticut 06606

August, 1985 www . El

ectric

alPar

tMan

uals

. com

\,

October 1 991 Supersedes Catalog 30-1 50, pages 1 - 1 2, dated March, 1 989 For standard terms of sale, refer to Sel l ing Pol icy 25-000 Mai led to: E, D, C/30-1 00A

Westinghouse Electric Corporation Distri bution and Control Business U n it Standard Distri bution Products Division Pittsburgh, Pennsylvan ia , U . S.A. 1 5220

Safety Switches • General Duty • Heavy Duty • Double Throw • Motor Circuit Switches

Cata log 30-150

Page 1

www . El

ectric

alPar

tMan

uals

. com

Catalog 30-150

Page 2

Heavy Duty Safety Switches Features

Instruction l abel for

Underwriters Laboratory Label

Star mounting holes at top and bottom for easy 2, 3 or 4 point mounting.

De-ion a rc chute interrupts and cools a rcs for longer switch l i fe

Unbreaka ble steel cross arm controls contacts; provides positive

Diamond poi nted jaws prevent burning and pitting of cu rrent-carrying su rfaces

Door latch securely holds door closed ; permits padlocking in position

b lade a l ignment

lv-'""'P<:c:ible fuse cl ips are spring rei nforced for lower operating temperatu res and long-l ife performance

Door interlock prevents cover from being opened when switch is energ ized

Insu lated shield prevents accidental contact with l i ne terminals . The unique design a l l ows the

.-----l i ne conductors to be instal led by simply loosening two screws and sl id ing the line shield downward.

B lades a re visible in open or closed posit ion

ass J Fuse Provisions are provided in 600V, 30-600A switches. When J fuses a re required, the l oad blocks can easily be moved to these pre-dri l led and tapped mounting provisions, el iminating the need to order specia l switches from the factory.

Front-operated handle with h igh-vis ib i l ity red vi nyl sleeve

Quick-make, quick-break mechan ism prevents contact teasing

Ample knockouts on a l l fou r sides and at rear of enclosu re

Pressure-type a l uminum l i ne and load terminals can be used with 60 or 75°C copper or a l uminum wire

Line and load bases constructed of h ig h-impact phenol ic

October 1991

0

www . El

ectric

alPar

tMan

uals

. com

@ Westinghouse

'Heavy Duty Safety Switcf. �

October 1991

Rating Identification: Embossed nameplate enhances appearance and permanently identifies Westing house name, catalog numbers, volts ampere and horsepower rat ings. No need to open door to obtai n data

Durable Finish: Entire enclosure is bonderized i nside and out and coated with baked on enamel for maximum durab i l ity and resistance to rust. Scratches cannot spread even though they extend through to the bare metal . All outdoor enclosu res are fabricated from galvanized steel .

Front Operated Handle: An i ntegral part of switch mech­an ism, the easi ly accessib le handle permanently controls contacts, permits close ganging, does not discon nect when door is opened. Red v iny l sleeve pro­vides h igh vis ibi l ity; indicates handle positio n (down for OFF; up for ON). The handle is pro­vided with a V2' Dia. hole for hook stick operation. The vinyl boot can either be dr i l led or removed when hook stick opera­tion is required.

Padlocking: Operating handle can be pad­locked i n OFF position by three padlocks with %" hasps. Pre­vents closing of contacts - an essentia l requi rement for heavy­duty i ndustr ia l appl ications. Handle can be padlocked i n ON position by d ri l l i ng hole in han­d le at position marked "X".

Removable Interior Parts: Al l i nterior parts a re easi ly removable from the front if replacement is necessa ry. (See Price List 30- 1 90)

Cata log 30-150

Page 3

Heavy Duty Safety Switches Features

Dual Purpose Interlock: Prevents switch from bei n g thrown O N with cover open; prevents cover from bei ng opened u nless switch is O FF. Authorized person nel can bypass both conditions by rotat­ing the i nterlock lock defeater screw located a bove the handle.

Teaseproof Switch Mechanism: Over-center design with positive d rive spring action maximizes strength of qu ick-make, qu ick­break switch mechanism. Pre­vents contact teasing. The mechanism a lso provides a di rect mechanical drive for "fail safe" operation in the u n l i kely event of spring fa i l u re.

Steel Cross Arm and Vokes: Steel yokes in an impact-resis­tant g lass polyester i nsulating block firmly engage steel cross­arm that d rives the moving b lades and provides positive b lade a l ig nment.

Diamond-Pointed Break-Jaws: Movi ng contacts extend beyond the break-jaws, permitt ing the breaking a rc to travel along the outside non current-carrying edges of jaws and blades. Pre­vents burn ing and pitt ing of cur­rent-ca rryi ng su rfaces.

De-lon Arc Chute: Prevents a rc damage by i nter­rupt ing and coo l ing hot a rcs. Molded materia l of ch ute is car­boniz ing and track resistant. Pro­longs switch l ife; a l lows maximum horsepower ratings permitted by UL. www .

Elec

tricalP

artM

anua

ls . c

om

Catalog 30-150

Page 4

General Duty Safety Switches Plug Fuse, Fusible and Non-Fusible

. I /

PF3 1 1 N RGFN32 1 N GFN32 1 N

Features-Specifications NEMA 1 Plug Fuse Indoor, NEMA 3R Plug Fuse Rainproof • Embossed metal nameplate permanently With Neutra l , 1 20 Volts Ac (1 B lade, 1 Fuse)

identifies cat. no., amps. hp rat ings Fusible Amps N E MA 1 Indoor N E MA 3R Rainproof • Front-operated handle permits close Systems

ganging. Handle is i nteg ral part of switch- Cat. No. Approx. Std. Cat. No. Approx. i ng mechanism; provides permanent con- Wt. Pkg. Wt. trol of contacts; can be padlocked in OFF Lbs. Ea. Lbs. Ea. or ON position 1 -Pole

• Red vi nyl cover instantly identifies han- 2-Wire S N 30 PF2 1 1 N 3 1 0 RPF2 1 1 N 4 die; i ndicates position I I

• Blades visible in open or closed position With Neutra l , 1 20/240 Volts Ac (2 B lades, 2 Fuses)

• Twin rei nforced blades provide maximum 2-Pole surface contact 3-Wire SN 30 PF31 1 N 3 1 0 RPF3 1 1 N 4

• Quick-make, qu ick-break, tease-proof i l l switch ing mechanism Fusible, 240 Volts Ac - NEMA 1 and 3R Enclosures

• Diamond-poi nted brea k jaws pro long Poles blade l ife ; keep si lver-plated contact a rea

Amps NEMA 1 Indoor N E MA 3R Rainproof

free of pitting and burni ng Cat. No. Approx. Std. Cat. No. Approx. • Tin p lated current carrying pa rts provide Wt. Pkg. Wt.

an excel lent beari ng su rface for moving Lbs. Lbs. parts 2-Pole 30 GFN221 ® 5 1 0 RGFN221 ® 6

• Easi ly accessib le fuse holders suitable for 2-Wire 60 { u� a w;,., r� · w;ffl

standard and time delay fuses at maxi- �� 1 00 2 Pole Solid 2 Pole Solid

mum HP rat ings 200 Neutral Neutral 400 Listings Listings

• Ample knockouts a nd wiring room 600 Below Below • Line and load termi nals su ita ble for cop- 2-Pole 30 GFN321N 5 1 0 RGFN321 N 6

per or aluminum wire 3-Wire S N CD 60 GFN322N 1 2 RGFN322N 1 4 • Door latch securely ho lds door closed;

� � � 1 00 GFN323N 27 RGFN323N 27

permits padlocki ng 200 GFN324N 40 RGFN324N 42 • Sing le cover i nterlock prevents door from 400 GFN325N 1 63 RGFN325N 1 63

600 GFN326N 1 73 RGFN326N 1 7 5 opening when switch is energ ized on a l l

3-Pole 30 { "" . w;,. l "" • w;,., but 30A outdoor switches. 60-600A switches a re provided with a dua l cover 3-Wire 60 3 Pole Solid 3 Pole Solid

1 00 Neutral Neutral i nterlock which a lso prevents the switch ��� 200 Listings Listings from being tu rned on when the cover is Below Below open. 400 GFN325@ 1 60 RGFN325@ 1 62

• Star mou nting feet assure easy mounting 600 Use 3P, 4W RGFN326@ 1 7 2 • UL Listed F i le E51 89 Switch

• Meets NEMA Spec. KS 1 - 1 990 3·Pole 30 GFN42 1 N 5 1 0 RGFN42 1 N 6 • Meets Federa l Spec. WS-865c 4-Wire S N CD 60 GFN422N 1 3 1 RGFN422N 1 5

Type LD-30A outdoor and p lug fuse

I <�� 1 00 GFN423N 27 1 RGFN423N 27

Type ND-30-600A i ndoor and 60-600A 200 GFN424N 42 1 RGFN424N 45 outdoor 400 GFN425N 1 63 1 RGFN425N 1 63

• Rated 1 00K Amp RMS. When used with 600 GFN426N 1 7 3 1 RGFN426N 1 75 Class R fuses. See Table page 5® Non-Fusible, 240 Volts Ac - NEMA 1 and 3R Enclosures

2-Pole 30 RGUN221 6 Application Data 2-Wire 60

r

� { ���N222 1 2 • For use on commercia l , residential and

n 1 00 3 Pole

l ight industr ia l appl ications. 200 Listings 3 Pole

• Al l switches a re U n derwriters' Laborato- 400 Below Listings

ries l isted and suitable for use as Service 600 Below

E ntrance Equi pment when neutral is pro- 3-Pole 30 GUN321 5 1 0 RGUN321 6 vided or grou nding kit is employed. 3-Wire 60 GU N322 1 2 1 RGU N322 1 3

1 00 GU N323 24 1 RGU N323 27 For price information see Price List 30-125. nr 200 GU N324 42 1 RGU N324 45 For renewal parts data see Price List 30-190. 400 GUN325@ 1 36 1 RGUN325@ 1 36 CD The neutral is included when last digit is "N". 600 GUN326@ 1 46 1 RGUN326@ 1 48 ® Not approved for service entrance. 3 ri l fi I i lied nP.LJtrrd kit

GFN422N

Horsepower Rati ngs

Std. 120 v 240 v Pkg . Max. Std. Max. Std.

5 2 v, . .

5 2 v, 3 1 V2

�'10�

Horsepower Ratings 240 VAC

Std. Ac Std. Max. Pkg. 1 !11 3!11 1 !11 3!11

5 1 V2 3

5 1 V2 3 3 7 112 3 7V, 1 0 1 5 7 V, 1 5 1 5 30

1 5 2 5 50 50 1 00 75 1 00

50 1 00 75 1 00

5 3 7 V, 1 7% . . 1 5 1 1 5 30 1 25 50 1 50 1 00

75 1 00

5 3 1 1 0 � .

5 7 V, 1 1 5 1 30 1 50 1 1 00 1 1 00

n,..+nh.o.. 1 QQ1

www . El

ectric

alPar

tMan

uals

. com

NEMA 1 Plug Fuse Indoor, NEMA 3R Fuse Rainproof

0

0 NEMA 1 Indoor NEMA 3R Rainproof

NEMA 1 General Duty Indoor

..,_--- 8 --- :c-- o --- �

D

c - � 0

rF:B

�:)

A D A

E

For 30 Ampere Switches Only For 60-600 Ampere Switches

NEMA 3R General Duty Rainproof(])

A

j_

For 30 Ampere Switches Only For 60 thru 600 Ampere Switches

Note: Mou nting hole dimensions for NEMA 1 and 3R Switches a re as fo l lows :

30 and 60A - %2' Dia. 1 00 and 200A - 1 %2 ' D ia . 400 and 600A - 17/32' Dia .

Externa l mounting fla nges a re not provided

Cata log 30-150

Page 5

General Duty Safety Switches Di mensional Data, N E MA 1 , N E MA 3R

PF Plug Fuse Switches, RPF Plug Fuse Switches

Poles Amps Dimensions - I nches A B c D

1 , 2 30 61V16 4% 35fs 61116 N EMA 1

1, 2 30 73/32 415/16 4 9% NEMA 3R

GFN Fusible Switches, GUN Non-Fusible Switches

Poles Amps Dimensions - Inches A B c D E F

2, 3 30 71 3/16 7V32 4111 6 515/1 6 ·��--"

2, 3 60 1 6 1/2 8% 55fs 87/s 1 51/s 5 2, 3 1 00 2215116 1 0'/s 71/2 1 27/16 2 P/16 6 - ----2, 3 200 3 1 '132 1 3'/s 82V32 1 321132 291'132 8% 2, 3 Fus 56'132 23112 1 21 1/32 1 73/4 4629/32 1 7

400 & 600 2, 3 Non-Fus 441%2 23V2 1 21 V32 1 7% 3713/32 1 7

400 & 600

RGFN Fusible Switches, RGUN Non-Fusible Switches

Poles Amps Dimensions - Inches A 8 c D E F ---

2, 3 30 9 1 V32 7 41/s 6 2, 3 60 1 67116 97132 55fs 8112 1 5'/s 5 2, 3 1 00 2215/16 1 1 1/s 77/16 1 27116 2 1 '132 6 2, 3 200 3 1 "132 1 43116 821/32 1 321132 2917132 83/s ---- ---2, 3 Fus 400 561/s 231/2 1 2'/s 1 73/4 4629132 1 7

& 600 2, 3 Non-Fus 445fs 23V2 1 2% 1 7 % 371 3/32 1 7

400 & 600

UL Listed Short-Circuit-Current Ratings General Duty Switches

Switch Ampere Short-Circuit Type Rating Rating Plug-Fuse 30 1 0,000A Fusible 30-600A 1 0,000A with H or K Fuses Fusible 30-600A 1 OO,OOOA with R Fuses Non-Fusible 30-600A 1 0,000A withstand rating

on 400 and 600A switches. These switches CD 30-200A outdoor switches have a provision for a rain-have (4) i nternal mou nt ing holes. tight hub in the top end.

October 1991

All products in this catalog meet the wire bending space requirements as identified in 1 990 NEC Section 373-6 (b). www .

Elec

tricalP

artM

anua

ls . c

om

Cata log 30-150

Page 6

Heavy Duty Safety Switches Fu sibl e and Non-Fu sible

Features-Specifications • Bonderized UL Listed organic finish

resists rust

• Dual cover interlock prevents accidenta l operation ; door cannot be opened when switch is ON; contacts can not close with door open. Both functions are defeatible by authorized person nel

• Line termi na l sh ield prevents accidental contact with l i ne termi na ls

• De-ion arc chute i nterrupts and cools hot a rcs; prevents arc damage

• Embossed metal nameplate permanently identifies cata log n umber, amperes and horsepower rat ing

• Front-operated hand le permits close gang ing . Handle is integ ral part of switch­ing mechanism; provides permanent con­trol of contacts; can be padlocked in OFF or ON position

• Red vinyl cover i n stantly identifies han­dle, ind icates position (down for "OFF," up for "ON").

• Blades visible i n open or c losed position

• Quick-make, qu ick-break, tease-proof switch ing mechanism

• Diamond-poi nted brea k jaws prolong b lade life; keep contact a rea free of pit­ting and burn ing

• Tin-plated current-carryi ng pa rts have l u bricated moving pa rts for ease of operation

• Easi ly accessible fuse ho lders su itable for standard, t ime delay and Type J fuses (Type J for 30-600A, 600V switches)

• Ample knockouts and wir ing room

• Line and load termi nals su itable for cop­per or a l uminum wi re

For NEC terminal data see page 9. For price information see Price List 30-125. For renewal parts data see Price List 30-1 90.

- J' ,.. . I

-240 Volts Ac, 250 Volts De, FusibleCD NEMA 1 , 3R, 4/4X and 12 Enclosures FusibleCD, 240 Volts Ac or 250 Volts De Poles Amps N E MA 1 :IJ

Indoor Cat. No.

NEMA 3R<?; Rain proof Cat. No.

N E MA 4 4X Stls. Steel Cat. No.

N E MA 1 2 (31 Cat. No.

Horsepower Rating

2-Pole 2-Wire

2-PoleC�) 3-Wire SN

30 60

1 00 200 400 600 800@

1 200@

HFN221 HFN222 HFN223 HFN224 HFN225 HFN226

RHFN221 RHFN222 RHFN223 RHFN224 RHFN225 RHFN226

Order 3 Pole switch below

WHFN221 WHFN222 WHFN223

JHFN221 JHFN222 JHFN223 JHFN224

Order 3 Pole switch below

30 } Order 2 Pole !Order 2 Pole }Order 2 Pole l Order 2 Pole

1 gg switch from switch from switch from switch from

200 above above above above

400 { Select neutral Select neutral t Select neutral Select neutral kit from kit from kit from kit from �gg neutral table neutral table neutral table neutral table

1 200 on page 9 on page 9 on page 9 on page 9 -- -- -- - -- -- --· --

Fusible CD , 240 Volts Ac 3-Pole 3-Wire

��� 3-PoleC�) 4-Wire SN

k�<

-- --30 HFN321 60 HFN322

1 00 HFN323 200 HFN324 400 HFN325 600 HFN326 800 (<) HFN327

1 200(<) HFN328

--- -- --RHFN321 WHFN321 RHFN322 WHFN322 RHFN323 WHFN323 RHFN324 WHFN324 RHFN325 WHFN325 RHFN326 WHFN326 RHFN327 RHFN328

-- --· ---JHFN321 JHFN322 JHFN323 JHFN324 JHFN325 JHFN326 -- --· .-- --· .-- -- -- -- ·--

30 60

1 00 200 400 600 800

1 200

r" .. , .,,. f"" , .,,. J � .. , .,,. !""·· ,,. switch from switch from switch from switch from above above above above l Select neutral Select neutral t Select neutral Select neutral kit from kit from kit from kit from neutral table neutral table neutral table neutral table on page 9 on page 9 on page 9 on page 9 --- -------- --- ·----- -- --

4-Pole 30 HFN421 JHFN421 4-Wire 60 HFN422 JHFN422

����

240 Volts

Ac Std.®

1 0 30

1 112 3 71/2

1 5

3 71f2

1 5 25 50 75

3 7lf2

1 5 25 50 75

3 7112 --- --· -- --- --- --·

Maximum(!:)

1 0 30

3 1 0 1 5

3 1 0 1 5 --

7112 1 5 30 60

1 25 200

7112 1 5 30 60

1 2 5 200

-- --7112

1 5

250 Volts De

5 1 0 20 40 50

5 1 0 20 40 --50

50

-- ·-- --600 Volts Ac, 600 Volts De, FusibleCD NEMA 1, 3R, 4/4X and 12 Enclosures Fusib leCD , 600 Volts Ac, 600 Volts De ----

NEMA 4/4X NEMA 1 2 Poles Amps NEMA 1 ® NEMA 3R Horsepower Rating Volts Indoor Rain proof Stls. Steel Cat. No. --- ---- De Cat. No. Cat. No. Cat. No. Ac Std . ® Maximum (f)

480V 600V 480V 600V 250 600

------2-Pole 30 HFN261 RHFN261 WHFN261 JHFN261 2-Wire 60 HFN262 RHFN262 WHFN262 JHFN262

1 00 HFN263 RHFN263 WHFN263 JHFN263 200 HFN264 RHFN264 400 600

1 0 1 0 ---·-3 3 5 1 0

1 0 1 5 25 30

1 0 1 0 -- ----7'12 1 0 1 0

20 25 25 30 40 40 50 50 50 �� 800®

Order 3 Pole switch below 1 200®

Fusible CD, 600 Volts, Ac ® 3-Pole 30 HFN361 RHFN361 3-Wire 60 HFN362 RHFN362

��� 1 00 HFN363 RHFN363 200 HFN364 RHFN364 400 HFN365 RHFN365 600 HFN366 RHFN366 800® HFN367 RHFN367

1 200® HFN368 RHFN368

CD For Class R fuse kits, refer to page 9 to order. ® 800 and 1 200 ampere switches have provision for

Class L fuses.

- --- --480V 600V 480V 600V 30 30 30 30 ·------- -- - -----

WHFN361 JHFN361 5 7112 1 5 20 WHFN362 JHFN362 1 5 1 5 30 50 WHFN363 JHFN363 25 30 60 75 WHFN364 JHFN364 50 60 1 25 1 50 WHFN365 JHFN365 1 00 1 2 5 250 350 WHFN366 JHFN366 1 50 200 400 500

@ For all neutral kits refer to page 9 to order. @ Applies when standard, Class H fuses are used. 0 Applies when time delay fuses are used.

50

1 0 2 5 40 60

0 Switches are available with provision for tang terminals. ® These 800 and 1 200A switches are rated 250V De max. (9) 30-400A switches are also rated 600V De. To order, add suffix A to catalog number.

@ Ac rated only.

October 1991

www . El

ectric

alPar

tMan

uals

. com

Features-Specifications • Door latch securely holds door closed;

permits padlocking

• Door i nterlock prevents door from open­ing when switch is energ ized

• Star mounting feet assure easy mounting

• UL Listed Fi le E5 1 89 and complies with UL Standard UL98

• CSA Certified Fi le (400-1 200 amps) LR-281 1 5

• Meets NEMA Spec. KS 1 - 1 990

• Meets Federal Spec. WS-865c, Type H D

Application Data • Provide dependable conti nuous service

on the most rugged industria l appl ications.

• Al l switches a re U nderwriters' Laborato­ries l isted and su itable for use as Service Entrance Equipment when neutral is pro­vided or g rou nding kit is employed .

• All Heavy Duty Safety Switches, when used with Cl ass R or J fuses, a re rated for 1 00,000 amps RMS ava i l able.

• l't ratings assure that the let-through peak currents will a lways be with i n the switches i nterrupti ng capa bi l ity. When used with Class R or J fuses, these with­stand ratings a re as fol lows :

Switch Ampere Rati ng

30 60

1 00 200 400 600

I P ( Pea k Amperes)

1 1 ,000 2 1 ,000 25,000 40,000 60,000 80,000

For NEC terminal data see page 9.

l' t (Amps' Seconds)

50,000 200,000 500,000

1 ,600,000 5,000,000

1 0,000,000

For price information see Price List 30-125. For renewal parts data see Price List 30-190.

October 1991

Cata log 30-150

Page 7

Heavy Duty Safety Switches Fu sible and Non -Fu sible

240, 480, 600 Volts Ac, 250, 600 Volts De, FusibleG:l and Non-Fusible NEMA 1, 3R, 4/4X and 12 Enclosures Fusible G), 600 Volts Ac --- ---Poles Amps NEMA 1 @ NEMA 3R0 NEMA 414X NEMA 1 2 �J Horsepower Rating Volts

Indoor Rainproof Stls. Steel Cat. No. Ae Std . ® Maxi mum(Z) De

Cat. No. Cat. No. Cat. No. 48DV 600V 48DV 600V 250V 600V

3-Pole 30 4-Wire S N ® 60

1 00

I <<< 200 400 600 800

1 200

30

5 J o .... , ..,. r ..... · .. ,. r··· , ..,. r··· , ..,. , swi tch es f rom swi tch es f rom sw itch es f rom swi tch es f r om 25 pag e 6 and pag e 6 and pag e 6 and pag e 6 and 50 � s el ect neutral s el ect n eut ral s el ect neutral s el ec t neut ral 1 DO kit f rom kit f rom ki t f rom kit f r om 1 50 pag e 9 pag e 9 pag e 9 pag e 9

30 30 30

71/2 1 5 20 1 5 30 50 30 60 75 60 1 25 1 50

1 25 250 350 200 400 500

Fusible, 600 Volts Ac 480V 600V 480V 600V 20 20 30 30

4-Pole 4-Wire

�<<� 30 HFN461 60 HFN462

Non-Fusible, 240 Volts Ac 2-Pole@ 2-Wire

I ( --:-----

1�g {us e 3 Pol e { Us e 3 Pole 200 below below 400 600

{Us e 3 Pole bel ow

------

Non-Fusib le, 240 Volts Ac 3-Pole 30 HUN321 RHUN321 WHUN321 3-Wire 60 HUN322 RHUN322 WHUN322

rn 1 00 HUN323 RHUN323 WHUN323 200 HUN324 RHUN324 400 HUN325 RHUN325 600 HUN326 RHUN326

Non-Fusible, 600 Volts Ac, 600 Volts De

{Us e 3 Pole bel ow

JHUN321 JHUN322 JHUN323

25 1 5 20 50 30 50

480V 600V 480V 600V 20 20 20 20

240V 1 0

3 1 0 1 5 1 5

240V 1 0

240V 480V 30 1 0

7'12 1 5 30 60

1 00 200

240V 480V 1 0 1 0

600V 30

6DOV 1 0

2-Pole 30 HUN261 RHUN261 WHUN261 JHUN261 ----==----=1-=-o ---

1 5 7112 2-Wire 60 HUN262 RHUN262

1 00 200

WHUN262 JHUN262 20 25 30

n 400 O rder 3 Pole sw itch bel ow 600 800

1 200

Non-Fusib le, 600 Volts Ac ® 3-Pole 30 HUN361 RHUN361 3-Wire 60 HUN362 RHUN362

1 00 HUN363 RHUN363

( ( ( 200 HUN364 RHUN364 400 HUN365 RHUN365 600® HUN366 RHUN366 800® HUN367 RHUN367

1 200® HUN368 RHUN368

Non-Fusib le, 600 Volts Ac, 250 Volts De 4-Pole 30 HUN461 4-Wire 60 HUN462

nn 1 00 HUN463 200

(1) For Class R fuse kits, refer to page 9 to order. @ 800 and 1 200 ampere switches have provision for

Class L fuses.

WHUN361 WHUN362 WHUN363 WHUN364 WHUN365 WHUN366

(3'; Switches are available with provis-Ion for tang terminals. To order, add suffix A to catalog number.

240V 240V 480V 60DV 1 0 1 0 30 30

JHUN361 20 20 1 5 JHUN362 50 50 30 JHUN363 75 75 50 JHUN364 1 25 1 50 50 JHUN365 250 350 50 JHUN366 400 500

--- ---240V 600V 48DV 600V 20 20 30 30

JHUN461 1 0 25 20 30 JHUN462 20 50 50 60

30 50 60 75

----- --- -

For a l l neutral kits refer to page 9 to order. @l Rated 250V De max.

5 1 0 20

,:6l Applies when standard, Class H fuses are used. 0 Applies when time delay fuses are used. �� 30-400A switches are also rated 600V De www .

Elec

tricalP

artM

anua

ls . c

om

Catalog 30-150

Page 8

Heavy Duty Safety Switches Dimensional Data

NEMA 1 Indoor

For 30A, 600V and 60 through 1 200 Ampere Switches

NEMA 3R Rainproof

For 30 Ampere, 250V Switches

-r I

A

For 30A, 600V and 60 through 1 200 Ampere Switches

For 30 Ampere, 250V Switches

NEMA 4/4X Watertight Stainless Steel. NEMA 12 Dust-Tight and Oil-Tight Industrial

For 30A, 600V and 60 through 200 Ampere Switches

Note: Mtg. hole sizes for NEMA 1 , 3R, 4/4X a n d 1 2 switches are a s follows:

30 & 60 A - 9/32'' Dia. 1 00 & 200A - 1 1/32" Dia. 400- 1 200A - 17/32"Dia.

400-1 200A NEMA 1 & 3R switches have internal mounting holes (mount­ing feet not provided).

For 30 Ampere, 250V Switches

All products in this catalog meet the new wire bending space requirements as identified in 1990 NEC Section 373-6 (b).

Poles Amps Dimensions - Inches Conduit Approx.

A 8 c D Sizes, Inches Weight

Lbs.

250/600 Volt HFN Fusib le Switches 2, 3(]) 30 99!32 7112 4131.32 627!32 33/4 631!J2 1J2, 3f4, 1 8 2, 3 30 1 9 9 511f1 6 9'Al 5 175AJ 112, 3!4, 1 ' 1 '14, 1 112, 2, 2112 1 5 2, 3(]) 60 1 67/16 9 511f16 9'AJ 5 1 51Al 112, 3!4, 1 , 1 '14, 1 112, 2, 2112 14 2, 3 60 1 9 9 511f16 9'AJ 5 1]5AJ 112, 3;4, 1' 1 1/4, 1 112, 2, 2112 1 7 2, 3 100 287/16 1Q13f16 7112 1 2'14 6 23"!32 112, 3;4, 1 , 1 114, 1 112, 2 38 2, 3 200 375AJ 1313f16 B21!J2 13"!32 B3AJ 357Al 112, 314, 1 112, 2, 2112, 3 61 2, 3 400 563!32 23112 12, ,1.32 1 77/16 1 7 4629!J2 2112, 3, 3112, 4 163 2, 3 600 563!32 23112 1 2 1 11.32 177/16 1 7 4629!J2 2112, 3, 3112, 4 173 2, 3 BOO 663/4 403AJ 12'14 1 7112 3 1 112 561 1!32 510 2, 3 1200 7J15f16 433AJ 12'14 17112 34112 6317!32 570

250/600 Volt H U N Non-Fusible Switches 2, 3(]) 30 99!32 7112 4131.32 6"!32 3'14 631132 1f.2, 3J4, 1 7 2, 3 30 1 6112 9 51 1/16 9'AJ 5 1 51AJ 112, 3;4, 1 ' 1 '14, 1 112, 2, 2112 14 2, 3 60 1 6112 9 51 1f16 97Al 5 151AJ 112, 3;4, 1' 1 '14, 1 112, 2, 2112 14 2, 3 100 287/16 1013/16 7112 12'14 6 23"!32 1f.2, 3f4, 1 1f4, 1 112, 2 34 2, 3 200 375AJ 1313/16 821;32 13"!32 83Al 357Al 112, 3/4, 1 112, 2, 2112, 3 58 2, 3 400 4419132 23112 12 , ,132 177116 17 3713)32 2112, 3, 3112, 4 1 36 2, 3 600 44191.32 23112 12 1 1)32 177/16 1 7 37131.32 2112, 3, 3112, 4 146 2, 3 BOO 6Q29J.32 403AJ 12,/4 17112 3 1 112 50112 466 2, 3 1 200 6511116 433AJ 1 21/4 17112 34112 559!32 517

Poles Amps Dimensions - Inches Conduit Hub Sizes Approx.

A 8 c D Sizes, Inches )nches Weight

Lbs.

250/600 Volt RHFN Fusi ble Switches 2, 3Ci) 30 103/16 7112 413f1 6 75/16 33/4 6112 112, 314. 1 ' 1 '14, 1 112, 2 3f4, 1, 1 1!4, 1 1/2, 2 1 0 2 , 3 30 19 g1;4 55AJ 9112 5 1]5AJ 112, 314. 1 ' 1 '14, 1 112, 2 3f4, 1, 1 1!4, 1 112, 2 1 8 2, 3 60 1 9 g1;4 55AJ 9112 5 175AJ 112, 3/4, 1 , 1 '14, 1 112, 2 3f4, 1' 1 1/4, 1 112, 2 1 9 2, 3 100 287/16 1 1 3/16 7112 12'14 6 26"!32 112, 3/4, 1' 1 '14, 1 112, 2 3f4, 1, 1 1f4, 1 112, 2 39 2, 3 200 37% 143/16 83/4 1 3112 B3AJ 3529!J2 112, 3/4, 1 112, 2, 2112, 3 2, 2112, 3 63 2, 3 400 561AJ 23112 1 23AJ 17112 1 7 4629!J2 2112, 3, 3112, 4 163 2, 3 600 561AJ 23112 123AJ 17112 1 7 4629!J2 2112, 3, 3112, 4 173 2, 3 BOO 663/4 403AJ 129132 17112 31 112 561 1!32 485 2, 3 1200 7315/16 433AJ 129!32 17112 34112 6317!32 590

250/600 Volt R H U N Non-Fusible Switches 2, 3Q) 30 103/1 6 7112 413f1 6 75/16 33/4 6112 112, 3f4, 1' 1 1f4, 1 112, 2 3f4, 1, 1 1!4, 1 112, 2 1 0 2 , 3 30 19 9'14 55AJ 9112 5 1]5AJ 112, 3;4, 1, 1 1f4, 1 112, 2 3;4, 1' 1 '14, 1 11.>, 2 1 7 2, 3 60 19 9'14 55AJ 9112 5 1]5AJ 112, 3/4, 1 , 1 '14, 1 112, 2 3;4, 1, 1 1f4, 1 112, 2 1 7 2, 3 100 287/16 1 1 3/16 7112 12'14 6 26"!32 112, 314. 1' 1 '14, 1 112, 2 3f4, 1, 1 1!4, 1 112, 2 39 2, 3 200 375AJ 143/16 83/4 1 3112 83AJ 3529!J2 112, 314. 1 112, 2, 2112, 3 2, 2112, 3 60 2, 3 400 445AJ 23112 123AJ 17112 17 37"!32 2112, 3, 3112, 4 136 2, 3 600 445AJ 23112 1 23AJ 17112 17 37"!32 2112, 3, 3112, 4 146 2, 3 BOO 6029!J2 403AJ 1 29!32 17112 3 1 112 50112 480 2, 3 1200 6511f16 433)8 1 29!32 17112 34112 559!32 580

- ----Poles Amps Dimensions - Inches Approx. --- ------ Weight

A 8 c D E F Lbs.

250/600 Volt WHFN Fusible Switches 2, 3Ql 30 1( ) 1 1/16 J15J16 421i:32 73/16 4 1 01J16 9 2, 3 30 1 9 971:32 517132 99/16 5 1 7 5fs 1 9 2 , 3 60 1 9 9'132 517132 99/16 5 1 7518 1 9 2 , 3 1 00 287/16 1 1 '/16 7 1/2 1 2 '14 6 26"132 37 2, 3 200 375/s 1 43/1 6 83/4 13112 8% 3529/32 64 2, 3 400 583/16 231/2 1 21/4 1 7 5/s 1 8 573/1 6 1 63 2, 3 600 583/16 231/2 1 21/4 1 7 5fs 1 8 573/16 1 7 3 -------- -250/600 Volt WHUN Non-Fusible Switches 2, 3 G:: 30 1 01 1/16 715/16 4211:32 73/1 6 4 1 01/16 9 2, 3 30 1 9 9'132 517132 99/1 6 5 1 7 5/s 1 7 3 60 1 9 97/32 517/32 99/16 5 175/s 1 8 3 1 00 287/16 1 1 '11 6 7112 1 2 '14 6 2623/32 36 3 200 375/s 1 4'116 83/4 1 3 112 8318 3529/32 56 3 400 4611/16 231/2 1 21/4 175/s 1 8 4511/16 1 36 3 600 46 1 1/16 231/2 1 21/4 1 7 5fs 1 8 4511/16 1 45 -----250/600 Volt JHFN Fusible Switches 2, 3CD 30 1 31 1/16 729!32 4211:32 -]i;, 4 1 31/16 1 0 2 , 3 30 1 9 9'132 517132 9'116 5 1 7 5/s 1 8 2 , 3 60 1 9 971:32 517/32 99/16 5 175/s 1 8 2 , 3 1 00 287/16 1 1 '11 6 7112 1 2 '14 6 2623132 40 2 , 3 200 375fs 1 43/1 6 83/4 1 3 112 83/s 3529/32 62 2 , 3 400 583/16 23112 1 21/4 1 7 5fs 1 8 57'116 1 63 2, 3 600 583/16 231/2 1 21/4 1 7 5/s 1 8 573/16 1 73

250/600 Volt J H U N Non-Fusible Switches ------421/32 71/s 1 31/1 6 2, 3 Q; 30 1 3 1 1/16 7 29!32 4 1 0

2, 3 30 1 9 97/32 517132 99/16 5 1 7 5fs 1 7 3 60 1 9 97/32 517132 99/1 6 5 1 7 5fs 1 8 3 1 00 287/16 1 1 3/1 6 7 '12 1 21/4 6 26"132 39 3 200 37518 1 43/16 83/4 1 3 112 8% 3529132 60 3 400 4611/1 6 231/2 1 21/4 1 7 5/s 1 8 451 1/16 1 36 3 600 4611/16 23112 1 2 '14 1 7 5fs 1 8 451 1/16 1 45

(!) 250 Volts only

October 1991

www . El

ectric

alPar

tMan

uals

. com

EK5

GNK6

GNK20

���� ft'c RFK2

RFK5

II 0 R 1 HA

ROH100

ST2

October 1991

NK600

� �� " \r RFK1

RFK3

R1 H200

Catalog 30-150

Page 9

General and Heavy Duty Safety Switches Modifications and Accessories

Terminal Data For Switches That Comply With 1990 NEC Sect. 373-6 (b) Plug - General Duty Heavy Duty Double Throw

Amps No. Min . Max. Type Amps No. Min . Max. Type Amps No. Min. Max. Type of Wire Wire 60!75°C of Wire Wire 60/75°C of Wire Wire Size 60/75°C wires Size Size wires Size Size wires Size

30 1 # 1 4 #8 Cu 30CD 1 # 1 4 #8 Cui AI 30 1 # 1 4 #6 Cui AI 60 1 # 1 4 #3 Cui AI 30® 1 # 1 4 #3 Cui AI 60 1 # 1 4 # 2 Cui AI

1 00 1 # 1 4 110 Cui AI 60 1 # 1 4 #3 Cui AI 1 00 1 # 1 2 110 Cui AI 200 1 #4 250 MCM Cui AI 1 00 1 # 1 4 110 Cui AI 200 1 #6 250 MCM Cui AI 400 1 250 MCM 750 MCM Cu 200 1 #6 250 MCM Cui AI 400 2 110 300 MCM Cui AI

or 2 310 300 MCM Cu 400 1 250 MCM 750 MCM Cui AI or 1 #2 750 MCM Cui AI 600 2 110 500 MCM Cui AI or 2 3/0 300 MCM Cui AI 600 2 110 350 MCM Cui AI

600 2 1/0 500 MCM Cu/AI 800 3 250 MCM 500 MCM Cui AI 800 3 110 750 MCM Cui AI

1 200 4 110 750 MCM Cui AI

Electrical Interlock Kits for 2 and 3 Pole Heavy Duty Safety Switches

E lectrical interlock kits a re ava i lab le for 2 and 3 pole Heavy Duty Safety Switches. Al l a re Field insta l lab le in N E MA 1 , 3R, 4/4X and 1 2 switches and provide 2 NO and 2 NC contacts. They a re mou nted on a steel bracket and are actuated by the switch mechanism. All con­trol contacts operate before the safety switch b lades open or close.

Safety Switch Kit Kit Ampere Ratings Kit Horsepower Ratings Rating Catalog 1 20VAC 240VAC 480VAC 1 25VDC 250VDC 1 20VAC 240VAC 1 25VDC 250VDC

Number

30A-240V EK-1 1 0 1 0 .3 . 1 5 30A-600V, 60A-240 & 600V EK-2 1 5 1 5 1 5 .5 .25 ''" '14 1 00A EK-31 1 5 1 5 1 5 . 5 .25 ''" '14 200A EK-32 1 5 1 5 1 5 .5 .25 ''" '14 800 & 1 200A EK-4 20 20 20 .5 .25 1 2 '12 '14 400 & 600A EK-5 20 20 20 .5 .25 1 2 '12 '14

Neutral Kits - Field Installed Equipment Grounding Kits General Duty and 2 and 3 Pole Heavy Duty

Switch Ampere Rating

Switch Type and Neutral Kit Cat. No. and Wire Range

For General Duty and 2 and 3 Pole Heavy Duty Switches

General 2 and 3 Neutral Kit Wire Duty Pole Range

Heavy Duty 60175°C Cu/AI 30A, 250V -30A, 600V ­and 60A

N K30 ( 1 ) # 1 4-6 NK60 ( 1 ) # 1 4-2

1 00 200 400

600 800

1 200

N K 1 00 NK200

N K400 N K400

N K600 NK600 NK800 N K 1 200

Class R Fuse Clip Kits Description

( 1 ) # 1 4- 1 /0 ( 1 ) #6-250 MCM ( 1 ) #4-750 MCM or

2 1 /0-250 MCM (2) #4-500 MCM (3) 1 /0-750 MCM (4) 1 /0-750 MCM

Max. Sw. Rating

60A 200A 600A

For use with Genera l and 2 and 3 pole Heavy Duty safety switches only. Kit wi l l reject a l l fuses except class R. Only one kit req u i red for a three pole switch.

Interchangeable Rainproof Hubs

Catalog Wire Range Number 60/75°C Cu/AI G N K6 # 1 4-6 G N K20 # 1 4-2 G N K60 #6- 1 /0

Amps Cat. No. 30A, 250V 30A, 600V/60A, 250V 60A, 600V

RFK1 RFK2 RFK3 RFK4 RFK5

1 00/200A, 250/600V 400/600A, 250/600V

For use with N E MA 3R General Duty, Heavy Duty, Double Throw and 6 Pole Motor Circuit Switches Description

All rain proof switches 30-200 a mperes are shipped with cutout covered by a plate. H u bs smaller than 2" can be used on 200 a mpere switches by ordering an adapter plate R 1 HA.

All 400 and larger rainproof switches are shipped with plain tops, no cutouts.

Myers-Type Hubs@ Description

For use in special applications.

CD 250V Switch @ 600V Switch

H u b Dia. Inches

% 1 1 V. 1 V2 2 2 2112 3 Adapt� Plate

Hub Dia. Inches

%

Switch Cat. No. Size

30 ROH075 thru ROH100 1 00 ROH125 Amps ROH150

ROH200

200 R1 H200 Amps R1 H250

R1 H300 R1HA

Zinc Std. Cat. Pkg. No. Oty. ST2 25

0 Mi nimum order; 1 Std. Pkg. or contact local distributor. For price informetion see Price List 30-125. www . El

ectric

alPar

tMan

uals

. com

Catalog 30-150

Page 1 0

Double Throw Switches

XUK362

Double Throw Switches Features - Specifications

NEMA 1 30, 60, 100 Ampere Switch

• Cover i nterlock prevents door from open­ing when switch is energ ized

• Quick-make, qu ick-break operating mechanism

• Handle may be padlocked i n top ON, neu­tra l , or bottom ON positions

• All switches a re U L Listed under File No. E5239 and a re su itable for use as service entrance equi pment.

• All comply with Federal specifications W-S-865c Type NDD

Application Data • Double th row switches a re suppl ied from

the factory to switch from a normal to an alternate power source. They can be field converted to switch from a normal to an a lternate load from a s ing le power source.

NEMA 3R Fusible o 6 61

ON � OFF

Yo N

NEMA 1 Non-Fusible

Typical Schematic "Double Th row" Motor Circuit Switches Features - Specifications • Insu lated shie ld prevents accidental con­

tact with l i ne termina ls • Blades v is ib le i n open or c losed position • Cover interlock prevents cover from open­

ing when switch is energized. Interlock release permits cover to be opened for switch inspection.

• Trunk-type latches keep cover tig htly closed; provides an effective dust-resist­ing seal

• Over-center quick-make, qu ick-break switching mechanism prevents teasing of contacts

• Large wir ing g utters faci l itate wir ing and provide easy access to termina ls

• Handle can be padlocked in OFF position by up to th ree padlocks

• Cover can be padlocked in closed position • Neoprene gasket sea ls out moisture and

dust from switch assembly • 6 Pole switches a re l i sted under U L

E-5 1 89 • Fusi ble u n its not ava i lab le

Application Data • Desig ned to meet the demands of heavy

industry for a compact, non-fus ible switch with visible contact d isconnect. Provides an i n-sight d isco n nect for two speed, 3!21 motors which a re remote from their motor control devices.

Motor Circuit Switches

SDSN6030

Double Throw Safety Switches - 240V AC - 250V DC 'o'" I ,.,. ;;·��0; I """' �c· Fusible - 3 Pole (use 3 pole for 2 pole appl ications) 3-Pole 3-Wire

��� sss

30 60

1 00 200 400 600

XFK321 ® XFK322® XFK323® XFK324® XFK325® XFK326®

RXFK321 ® 45 RXFK322® 45 RXFK323® 47 RXFK324® 1 1 0 - 230 - 325

Non-Fusib le - 3 Pole (use 3 pole for 2 pole appl ications)@ 3-Pole 3·Wire

I ! I """""" Ill

30 60

1 00 200 400 600 800

XUK321 XUK322 XUK323 Use XUK324 600V XUK325 Switch XUK326 XUK327

Double Throw Safety Switches - 600V AC

33 33 33 74

1 28 1 7 5 1 7 5

Horsepower Rating

240V AC

Std. Max.

1 0 30 1 0

II 1 112 3 3 3 7112 1 0 7112 1 5 1 5 I � 25 -

50 -1 - 75 -

- - 3 - - 1 0 - - -- - 1 5 - - -- - -- - -

Poles Cat. No. Horsepower Ratings

30

7112 1 5 30 60

1 2 5 -

1 0 20 40 -

1 25 1 25 1 25

250 Volts DC

5 1 0 20 40 50 50

5 1 0 20 40 50 50 50

I Amps

NEMA 1 NEMA 3R

Approx. Wt. Lbs. AC Std. AC Max.

Fusi ble - 3 Pole 3-Pole 3-Wire

I I

30 60

1 00

XFK361 ® - 44 XFK362® - 46 XFK363® - 46

240V 480V 600V 31'! 30 30

3 5 7112 7112 1 5 1 5

1 5 25 30

240V 30

7112 1 5 30

480V 31'!

1 5 30 60

600V 30

20 50 75 sss sss I 200 XFK364® - 1 05 25 50 60 60 1 25 1 50 1 4oo XFK365@ - 230 50 1 00 1 25 1 25(]) 250Ql 350Ql

Non-Fusi b le - 3 Pole@ 3-Pole 3-Wire

I l l

30 60

1 00 200

XUK361 XUK362 XUK363 XUK364

RXUK361 RXUK362 RXUK363 RXUK364

33 - - - 1 0 20 30 34 - - - 20 50 60 34 - - - 40 75 1 00 78 - - - 60 1 25 1 50 """"""

I l l 400 XUK365 RXUK365 140 - - - 1 25 250 350 600 XUK366 RXUK366 1 75 - - - 1 25 250 350 800 XUK367 RXUK367 1 75 - - - 1 25 250 350

CD These rati ngs apply only when J fuse kit catalog num­ber DJ400JK is used.

® Rated 1 0,000 AIC max with Class H fuses or 1 00,000 AIC with Class R fuses and rejector kit.

GJ Accepts 600V Class T fuses as standard and Class J fuses when used with kit no. DT400JK. Rated 1 00,000 AIC max.

Rejector Kits Use with Double Throw Switches Only Kits reject a l l fuses except Class R; one kit requ i red per 3 pole switch. C lass R fuses wi l l fit in switch without using an "R" fuse kit. Description I Catalog -,-A-m_p_e_.re-s------,-Vcc-o-lts--------1 Nu mber

30 240 30 600 60 240 60 600

1 00 240/600 200 240/600

DS12FK DS16FK DS16FK DS26FK DS36FK DS46FK

"J" fuse kit (for Cat. No. XFK365 on ly) DT400J K

For Price Information see Price List 30-125

@) Rated 1 0 ,000 AIC max when protected by Class H fuses or 1 00,000 AIC max when protected by Class R, J or T fuses. Fuse ampere rating must not exceed switch ampere rati ng.

® Accepts 300V Class T fuses only. Rated 1 00,000 AIC max.

Electrical Interlock Kits for 4 Pole Heavy Duty and Double Throw Switches Switch Type I Contacts and Rati ng Double Throw only 30-SOOA Double Throw 30-SOOA a n d 30-200A 4 Pole

1 NO (Control Pole)

1 NO 1 NC 2 NO 2 NC

Kit Catalog N u mber DS16P

DS200EK1 DS200EK2

Or.tnh�>r H l!l1

www . El

ectric

alPar

tMan

uals

. com

Catalog 30-150

Page 1 1

Double Throw Switches Motor Circuit Switches

Dimensional Data

Double Throw Neutral Kits Switch Type and Ampere Rating 30-100 Amps 200A 400 & 600A Fusible CD400A Non-Fusible 600A Non-Fusible 800A Non-Fusible

30-100 Amps 200 Amps 400-800 Amps

Neutral Kit Cat. No. DT100NK DT200NK DSBOONK DT400NK

DT600NK -

Neutral Kit Wire Range 60/75'C Cu/AI ( 1 ) # 1 4- 1 /0 ( 1 ) #6-250 MCM (2) #3/0-750 MCM (2) #6-250 MCM

(2) 250-500 MCM -

CD DT600NK may also be used in 400A Non-Fusible switches when wire size exceeds 250 MCM.

Motor Circuit Switches 6 Pole Non-Fused Disconnect Complete

Amps '

Catalog Number Approx.

NEMA 1 NEMA 3R NEMA 1 2 Weight Lbs.

30 SDSN6030 RDSN6030 JDSN6030 28 60 SDSN6060 RDSN6060 JDSN6060 30

1 00 SDSN6100 RDSN6100 JDSN6100 32 200 SDSN6200 RDSN6200 JDSN6200 49

Maximum H P Ratings 600 VAC 250 VDC

Amps 1 20 VAC I 240 VAC 480 VAC 600 VAC I 250 VDC

30 5 1 1 0 20 25 I 7112 60 1 0 I 20 40 60 1 5

1 00 1

1 5 ' 30 75 75 . 25

' I 6o 1 00 1 00 1 4o 200

® Permits field mounting of an auxiliary switch for sepa­rate control circuit applications. Each switch includes three soldered, identified leads.

Double Throw Safety Switches - N EMA 1 Indoor, N E MA 3R Outdoor

Motor Circuit Switches Terminals are Suitable for Either Copper or Aluminum Cable Switch Wire Range Rating Copper

30 # 1 4-#2 60 # 1 4-#2

1 00 # 1 4- 1 /0 200 #4-300 MCM Auxiliary Switch Kits@

Amp Rating Switch Used With 30, 60, 1 00 200 200

Contact Arrangement

1 A, 1 B 1 A, 1 B 2A's, 2B's

Aluminum # 1 2-#2 # 1 2-#2 # 1 2-1/0 #4-300 MCM

Kit Style No.

1 78C265G05 178C619G01 178C619G02

Not to be used for construction purposes unless approved. For additional d imensions, refer to the Distribution Service Center.

Fusible Switches Non-Fusible Switches

ON OFF I

O N

··) -- ._,

r- E --I Note: (3) V4' Dia. mounting holes are provided on

30-1 OOA switches and (4) 9/15" Dia. mounting holes are provided on 200-800A switches.

Catalog Dimensions Number A B C D

XFK321 XFK322 XFK323 XFK324 XFK325 XFK326

XFK361 XFK362 XFK363 XFK364 XFK365

37 1 1 1 '11 6 97/s 33112 9'14 37 1 1 15f16 9718 33112 9'14 37 1 1 15f16 9718 33112 9'14 5 1 318 1 99/1 6 1 1 '14 47 1 6 743f4 25'18 141/s 69112 20'14 861/s 277/16 1 41/a 803/4 22'14

37 1 1 15/1 6 97/s 33'12 91/4 37 1 1 15/16 97/s 331/2 9'14 37 1 1 15f16 97/s 33112 9'14 5 1 '18 1 99/1 6 1 1 '14 47 1 6 74% 253/s 141/s 691/2 20'14

Conduit Sizes, Inches

1f2, %, 1, 1 114, 1 1/2, 2 112, 3f4, 1 ' 1 '14, 1 112, 2 112. %, 1, 1 '14, 1 112, 2 1 112, 2, 2112 No Knockouts No Knockouts

112, 314, 1' 1 '14, 1 112, 2 112, %, 1 ' 1 '14, 1 112, 2 1f2, %, 1, 1 '14, 1 1/2, 2 1 1/2, 2, 21/2 No Knockouts

RXFK321 37 1 1 1 '116 911s 33112 9'14 112, 314, 1, 1 '14, 1 112, 2 RXFK322 37 1 1 1 '11 6 97/s 331/2 9'14 112, %, 1, 1 '/4, 1 112, 2 RXFK323 37 1 1 1 '116 9718 331/2 9'14 112, %, 1 , 1 1/4, 1 1/2, 2 RXFK324 5 1 3/s 1 99/16 1 1 '14 47 16 1 112, 2, 21/2

Motor Circuit Switches - 6 Pole N on-Fused Discon nect Complete

Catalog Number

XUK321 XUK322 XUK323 XUK324 XUK325 XUK326 XUK327

XUK361 XUK362 XUK363 XUK364 XUK365 XUK366 XUK367

RXUK361 RXUK362 RXUK363 RXUK364 RXL!K365 RXUK366 RXUK367

6 Pole U n its - 30, 60, 6 Pole U n its - 200 amperes 6 Pole Units - 30, 60, 1 00 Amperes

Dimensions

A B C D E

25 1 1 15f16 9718 2 1 1/2 9'14 25 1 1 15f1 6 97/s 21 1/2 9'14 25 1 1 1 5f1 6 9718 2 1 112 9'14 377/s 1 99/16 1 1 '14 33112 16 54'14 231/s 1 2112 49 1 8 63% 24118 1 4118 58112 1 9 63% 241/s 14118 58112 1 9

2 5 1 1 15f16 97/s 2 1 112 9'14 25 1 1 15!16 97/s 21 1/2 9'14 25 1 1 1 5f16 9718 2 1 1/2 9'14 377/s 199/16 1 1 '14 331/2 1 6 54'14 231/a 1 2 112 49 1 8 63% 241/a 1411s 58112 19 63% 241/s 141/s 58112 19

25 1 1 15f16 97/s 2 1 1/2 9'14 25 1 1 15f16 9718 21 1/2 9'14 25 1 1 1 '116 9718 2 1 1/2 9'14 377/s 1 99/16 1 1 1/4 331/2 1 6 54'14 23118 12112 4 9 1 8 6 4 241/s 1 4'18 58112 1 9 6 4 241/s 1 41/s 581/2 1 9

1 00 amperes Enclosure Dimensions - Inches and M M

w -n � A O N �� � OF� � 0 • • •

T[/!> I

A I

��-

lL =,

J

g] .

1T - � B

Type A B

r c ... l n . M M l n .

[ lr NEMA 1 1 8% 476 1 8'12 NEMA 3R 1 8% 476 1 8'12 NEMA 1 2 1 8% 476 1 8'12 6 Pole Units - 200 Amperes

NEMA 1 3 1 7/16 799 2 1 7/1 6 NEMA 3R 3 1 7/16 799 2 1 7/16 NEMA 1 2 3 1 7/16 799 2 1 7116

1

All products in this catalog meet the new wire bending space requirements as identified in 1 990 NEC Section 373-6 (b).

October 1991

M M 470 470 470

545 545 545

Conduit Sizes, Inches

1f2, 314, 1, 1 '14, 1 112. 2 112, %, 1' 1 '14, 1 112, 2 112, %, 1' 1 '14, 1 112, 2 1 112. 2, 21/2 No Knockouts No Knockouts No Knockouts

112, %, 1' 1 '14, 1 '12, 2 112, %, 1 , 1 '14, 1 1/2, 2 112, %, 1' 1 '14, 1 112, 2 1 '12, 2, 2112 No Knockouts No Knockouts No Knockouts

112, 314, 1' 1 '14, 1 112, 2 112, %, 1' 1 '14, 1 112, 2 112, 314, 1' 1 '14, 1 112, 2 1 112, 2, 21/2 No Knockouts No Knockouts No Knockouts

c l n . 815116 815/16 815/16

9% 9% 9%

M M 227 227 227

248 248 248

www . El

ectric

alPar

tMan

uals

. com

Catalog 30-150

Page 1 2

Safety Switches Motor Circuit Switches

Safety Switch Catalog Number Interpretation Data : 1 st 2nd 3rd

Enclosure Type Protection N E MA 1 Plug Fuse p Non-Fused u

4th I � 6th 7th

Wires Voltage Current Options CD 2 Wire 2 250V 2 Neutral +

N E MA 3R R Gen. Duty G Fused N E MA 4/4X w Heavy Duty H

F 3 Wire 3 600V 4 Wire 4

6

30A - 1

60A - 2

1 00A - 3

200A - 4

400A - 5 600A - 6 800A - 7

Tang Term inal provisions (30-200A) Copper Term inals (30-200A)

N

A

c N E MA 1 2 J Double Throw X

1 200A - 8

CD Factory assembled options are available on special order with List Price Adder. Options marked with ( + ) are available as field installed accessory kits.

N EMA 3R Enclosure

NEMA ENCLOSURE

TYPE

Heavy Duty

1 st 2nd 3rd 4th 5th 6th 7th

N * 3 6 4 C

Fused 3 Wire 600 Volt

* "N" or "K" in this position (precedi n g numbers) indicates compliance with 1 990 NEC Section 373-6 (b) for wire bending space.

DEFINITIONS NEMA Standard 1 - 1 0-1979

200 Amp With Copper

Terminal Option.

1 Type 1 enclosures are i ntended for indoor use primarily to provide a deg ree of protection against contact with the enclosed equipment.

3R Type 3R enclosures are intended for outdoor use pri mari ly to provide a degree of protection against fa l l ing rain, sleet, and externa l ice formation.

12 Type 12 enclosu res are intended for indoor use primarily to provide a degree of protection against dust, fa l l ing d i rt, and dripping noncorrosive l iquids.

4 Type 4 enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, and hose-di rected water.

4X Type 4X enclosures - same as Type 4 except they also provide a degree of protection against corro-sion and must have enclosures fabricated from stain less steel, polymerics or equivalent materia l .

Note: Above information i s for identification purposes only. Do not use to con­struct catalog numbers not l isted in this catalog.

Westi ng house E lectric Corporation Distribution and Control Business U nit Standard Distribution Products Division Pittsburgh, Pennsylvania, U .S.A. 1 5220

Printed in U.S.A.

October 1991 www . El

ectric

alPar

tMan

uals

. com