73638665 auto transformer insulation coordination study
DESCRIPTION
auto transformer insulation coordinationTRANSCRIPT
-
Surge Transfer Study for Power Transformer Using
EMTDC/PSCAD
Veerabrahmam Bathini, Chandra Shekhar Reddy Atla, Dr. K. Balaraman and K. Parthasarathy
1Abstract- The lightning and switching surges can be transferred
from one voltage level to another through transformer couplings.
A distribution system, which may not be directly exposed to the
overvoltages of atmospheric origin, but connected to a utility
system through a transformer of high turns ratio will be exposed
to overvoltages on the secondary side due to overvoltages on the
primary windings. The resulting stresses on the distribution
system may exceed the BIL levels. This paper presents modeling
of high frequency autotransformer and frequency dependent
surge arrester models and results of simulations for lightning and
switching surges transferred through 502 MVA, 380/132/13.8 kV
autotransformer using EMTDC/PSCAD. Surge arresters are
usually provided on the high voltage side and low voltage side of
the autotransformers. The purpose of the present paper is to
analyze the surges transferred towards tertiary of
autotransformer. If these surges are to be controlled to safe levels
it may be necessary to provide the surge arresters at tertiary side
also. This aspect has been highlighted in present paper.
I. INTRODUCTION
The most common primary distribution voltage in industrial
systems is 13.8/11 kV. However, for large power demands, the
utility system voltage may be as high as 380/400 kV. The
surge transfer through the transformers depends upon the
voltage turn ratio, as well as electrostatic and electromagnetic
couplings of the windings. The lightning and steep fronted
waves are partially transferred through the electromagnetic
coupling, which is the mechanism that governs the
transformer operation at power frequencies and depends upon
the turns ratio. The magnitude of these surges transferred
through electromagnetic coupling is far less than the
magnitude of surges transferred through electrostatic coupling
hence electrostatic effects dominate the coupling of transients
from the primary to the secondary windings. For slower
switching surges, the electromagnetic coupling effect
predominates [1]. The overvoltages caused by transfer of
lightning and steep fronted waves or switching surges are
compared with BIL of the equipments on low voltage side. In
case the magnitude of transferred overvoltages exceed the
BIL levels, mitigation techniques like provision of properly
rated surge arresters (SA), surge capacitors etc., have to be
1
Veerabrahmam Bathini, Sr. Power system Engineer, is with M/s
Power research and development consultants Pvt. Ltd, Bangalore,
India. (e-mail:[email protected])
Chandra Shekhar Reddy Atla, Power system Engineer, is with M/s
Power research and development consultants Pvt. Ltd, Bangalore,
India. (e-mail:[email protected])
Dr. K Balaraman, CGM, Power System Group, is with M/s PRDC Pvt. Ltd., Bangalore. (e-mail: [email protected])
Prof. K Parthasarathy, Retired Professor from IISc, Bangalore.
employed to control these overvoltages. This paper
concentrates on mitigation technique provided by surge
arrester.
The selection of an appropriate surge arrester is an important
consideration. System overvoltages under normal and faulted
conditions, system grounding and ground fault clearance times
should be considered in selecting a surge arrester. The
selection procedure is as follows [2] [7].
Arrester rated voltage (Vn): selected based on maximum temporary overvoltages (TOV) appearing
in the power network, considering earth fault factor.
Maximum continuous operating voltage (MCOV): selected based on the maximum system steady state
operating voltage.
Energy Capability: selected based on switching and lightning overvoltage studies.
This paper presents the modeling of high frequency
autotransformer and frequency dependent surge arrester to
conduct surge transfer studies for 502 MVA, 380/132/13.8 kV
autotransformer using EMTDC/PSCAD. Considering a worst
case scenario for simulation, the lightning impulse or
switching impulse injected currents at high voltage (HV) and
low voltage (LV) terminals of the autotransformer are selected
based on the V-I characteristics of corresponding surge
arresters. The modeling methodologies, data considered for
case study and simulation results are presented in following
sections.
II. MODELING
This section presents the modeling details of 502 MVA,
380/132/13.8 kV autotransformer and surge arresters.
A. Autotransformer Model
The parameter specifications of 502 MVA, 380/132/13.8 kV
autotransformer provided by manufacturer are presented in
Table 1. TABLE 1
AUTOTRANSFORMER PARAMETERS
S.No. Parameter Value
1 Rated capacity 502 MVA
2 Rated voltages (High/medium/low) 380/132/13.8 kV
3 Lightning BIL (High/medium/low) 1300/650/95 kV
4 Switching BIL (High/medium/low) 1050/650/95 kV
5 frequency 60 Hz
6
Type of system grounding
HV Solidly
LV Solidly
TV Effectively
7 Common neutral (autotransformers) Solidly
8 Short circuit Impedances : %Z (on 500 ZHL=19.3%
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 548
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
-
S.No. Parameter Value
MVA base) ZHT=268.75%
ZLT=243.38%
9 Terminal to ground capacitances and terminal to terminal capacitances
CHG
CLG
CTG
CHL
CHT
CLT = 5033.8pF
In PSCAD/EMTDC, the built in model for
autotransformer with tertiary is not available.
modeling implementation is described in this section.
single phase three winding transformers are used to
three phase autotransformer with tertiary as shown in Fig
The leakage impedances for three single phase three winding
transformers can be determined from the leakage impedances
of the autotransformer by using the procedure
Appendix [3]. The input data required for this model can be
extracted from the data provided in Table 1. To represent high
frequency model for the autotransformer
capacitances mentioned in Table 1 are connected as shown in
Fig. 2.
Fig. 1: Autotransformer model in PSCAD/EMTDC.
B. Frequency Dependent Surge Arrester Modeling
Surge arrester dynamic characteristics are significant for
studies involving lightning and other fast transient surges. The
time to crest for surges used in lightning studies can range
from 0.5 s to several s. For a given current magnitude in an
arrester, the voltage developed across the arrester can increase
by approximately 6% as time to crest of current is decreased
from 8 s to 1.3 s. One approach for an arrester model for
lightning studies would be to use a simple non
characteristics based on 0.5 s discharge voltage. This would
give conservative results (higher voltages) for surges with
slower time to crest. The frequency dependent model will give
good results for current surges with times to crest from 0.5
to 40 s [4]. The surge arrester model proposed by Pinceti [
derived from IEEE model [4] is used in the present paper for
#2
#3
#1
#2
#3
#1
#2
#3
#1
HVa
HVb
HVc
Value
=268.75%
=243.38%
= 5854.1pF
= 8057.6 pF
= 14424.4 pF
= 3023.8 pF
= 1889 pF
= 5033.8pF
model for three phase
is not available. Hence the
modeling implementation is described in this section. Three
used to represent
as shown in Fig.1.
The leakage impedances for three single phase three winding
transformers can be determined from the leakage impedances
procedure described in
The input data required for this model can be
the data provided in Table 1. To represent high
autotransformer, terminal
connected as shown in
model in PSCAD/EMTDC.
Modeling
Surge arrester dynamic characteristics are significant for
studies involving lightning and other fast transient surges. The
time to crest for surges used in lightning studies can range
to several s. For a given current magnitude in an
arrester, the voltage developed across the arrester can increase
by approximately 6% as time to crest of current is decreased
. One approach for an arrester model for
would be to use a simple non-linear V-I
discharge voltage. This would
give conservative results (higher voltages) for surges with
slower time to crest. The frequency dependent model will give
o crest from 0.5 s
model proposed by Pinceti [5]
[4] is used in the present paper for
performing surge transfer study. The surge arrester model is
presented in Fig. 3.
Fig. 2: High frequency Autotransformer model
Fig. 3: Frequency dependent surge arrester model proposed by Pinceti
This model is composed by two sections of non
resistance usually designated by
separated by inductance L1 and L0. T
M) is added to avoid the numerical problems.
and L0 are computed based on the procedure described in
The computation procedure is described in flow chart shown
in Fig. 4. Vn is arrester rated voltage (
voltage (kV) for the discharge current of
impulse, Vr1/T2 is the residual voltage
current 10 kA, 1/T2 s steep front
can vary between 2 and 20 s. The nonlinear resistors
A1 can be modeled as a piecewise linear
characteristic of A1 arrester is selected from manufacturer data
sheet and V-I characteristic of A0 is selected based on curves
proposed by IEEE W.G.3.4.11 [4] which are shown in
Fig. 4: Flowchart to calculate elements
LVa
LVb
LVc
TVa
TVb
TVc
e1t
e1l
HV
5854.1e-6 [uF]
8057.6e-6 [uF]3023.8e-6 [uF]
1889e-6 [uF]
K=Vr1/T2/Vr8/20
K
-
The V-I characteristic of A0 and value of L1 in the model have
to be properly adjusted to match the manufacturers data with
respect to switching and lighting characteristics.
Adjustment of V-I characteristics of A0 to match switching
surge Voltages:
The V-I characteristics of A0 are adjusted in surge arrester
model to get a good match between model and manufacturers
switching surge voltages and currents.
Fig. 5: Characteristics of nonlinear elements A0 and A1
proposed by IEEE W.G. 3.4.11 [4].
Adjustment of L1 to match V8/20 voltages:
The value of L1 in model is adjusted with V-I characteristic
of A1 and modified V-I characteristics of A0 to obtain a good
match between the manufacturer data and model discharge
voltages for an 8/20 s current.
The frequency dependent surge arrester models used for the
case studies are presented Tables 2, 3 and 4 and L0 and L1
values are presented in Table 5.
TABLE 2
360 kV FREQUENCY DEPENDENT SURGE ARRESTER PARAMETERS Rated arrester voltage (kVrms) 360
MCOV- Maximum Continuous Operating
Voltage (kVrms)
289
Leakage current at MCOV (mA) 5
TOV 1 sec rating (kVrms) 410
TOV 10 sec rating (kVrms) 388
Maximum residual
voltage (kV crest) at
discharge of (kAp, kVp)
[provided by
manufacturer, A1]
30/60s switching
surge current
(0.5 , 674) , (1, 692), (2, 712),
(3, 725)
8/20s lightning surge current
(5, 761), (10, 792), (20, 856), (30, 899)
0.5 s steep front
current
(10, 856), (20, 927)
V-I characteristics of A0 (Adjusted )
(kAp, kVp)
(0.5, 721), (1, 739), (2, 764),
(3, 783), (5, 798), 10, 856),
(20, 927)
Line discharge class [Energy Absorption] 4 [ 4320 KJ]
TABLE 3
120 kV FREQUENCY DEPENDENT SURGE ARRESTER PARAMETERS Rated arrester voltage (kVrms) 120
MCOV (kVrms) 97
Leakage current at MCOV (mA) 5
TOV 1 sec rating (kVrms) 139
TOV 10 sec rating (kVrms) 132
Maximum residual
voltage (kV crest) at discharge of
(kAp, kVp)
[provided by manufacturer, A1]
30/60s switching
surge current
(0.5 , 233) , (1, 240 ), (2, 255),
(3, 258)
8/20s lightning
surge current
(5, 264), (10, 273), (20, 291)
0.5 s steep front current
(10, 335), (20, 372 )
V-I characteristics of A0 (Adjusted)
(kAp, kVp)
(0.5, 289), (1, 296), (2, 306),
(3, 314), (5, 320), 10, 335),
(20, 372)
Line discharge class [Energy Absorption] 4 [ 1440 kJ]
TABLE 4
12 kV FREQUENCY DEPENDENT SURGE ARRESTER PARAMETERS Rated arrester voltage (kVrms) 12
MCOV (kVrms) 10.2
Leakage current at MCOV (mA) 5
TOV 1 sec rating (kVrms) 14.0
TOV 10 sec rating (kVrms) 13.2
Maximum residual
voltage (kV crest) at discharge of
(kAp, kVp)
[provided by manufacturer, A1]
30/60s switching
surge current
(0.5, 25.7) , (1, 26.7)
8/20s lightning
surge current
(1.5, 27.6 ), (3, 29.1), (5, 30.2),
(10, 32.4), (20, 35.9), (40, 40.2)
0.5 s steep front current
(10, 40), (20, 44)
V-I characteristics of A0 (Adjusted )
(kAp, kVp)
(0.5, 34.3), (1, 35.2), (2, 36.3),
(3, 37.2), (5, 38), 10, 40),
(20, 44)
Line discharge class [Energy Absorption] 4 [ 90 kJ]
TABLE 5
L0 and L1 VALUES FOR 360 kV, 120 kV and 12 kV SURGE ARRESTERS Surge Arrester rating L0
[H]
L1(Adjusted)
[H]
360 kV 2.42 35.0
120 kV 1.2 3.6
12 kV 0.12 0.36
III. CASE STUDIES
Case studies have been performed for 502 MVA,
380/132/13.8 kV autotransformer in order to find the surges
transferred to tertiary voltage (TV) side with lightning or
switching or steep front impulse applied at HV or LV
terminals. The Basic Insulation Levels (BIL) for the auto-
transformer is presented in Table 1.
Considering a worst case scenario for simulation, the
lightning impulse or switching impulse injected currents at HV
or LV terminals of the autotransformer are selected based on
the V-I characteristics of corresponding surge arresters. The
generated impulse currents namely 3 kA, 30/60 s switching
impulse, 20 kA, 8/20 s lightning current impulse and 20 kA,
0.5/20 s steep front current impulse, presented in Fig. 6, 7
and 8 respectively, are used in the simulation.
Case study 1: Switching current impulse of 3kA, 30/60 s
The study results with switching current impulse of 3 kA,
30/60 s as shown in Fig. 7 at autotransformer terminals are
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 550
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
-
presented in Table 6 and the corresponding voltage waveforms
at the tertiary are shown in Figures 9 and 10.
Case study 2: Lightning current impulse of 20kA, 8/20 s
The study results with lightning current impulse of 20 kA,
8/20 s as shown in Fig. 8 at autotransformer terminals are
presented in Table 7 and the corresponding voltage waveforms
at the tertiary are shown in Figures 11 to 13.
Case study 3: Steep front current impulse of 20kA, 0.5/20 s
The study results with lightning current impulse of 20 kA,
0.5/20 s as shown in Fig. 9 at autotransformer terminals are
presented in Table 8 and the corresponding voltage waveforms
at the tertiary are shown in Figures 14 to 16.
Fig. 6: switching impulse current, 3kA, 30/60 s
Fig. 7: Lightning impulse current, 20kA, 8/20 s
Fig. 8: Steep front impulse current, 20kA, 0.5/20 s
TABLE 6
SWITCHING SURGES TRANSFERRED THROUGH TRANSFORMER Case Switching
surge
applied at transformer
terminal
[SA location]
Energy absorbed
by SA at [KJ]
Voltage at Transformer
terminal [kVp] and
Corresponding %BIL
Refer
Figures
HV side
LV side
TV side
HV LV %BIL TV %BIL
1 HV side
[HV, LV]
114.6 22.0 - - 220 34 87 93 Fig. 9
2 LV side [HV, LV]
9.0 33.3 - 612 - 58.3 63 66.3 -
3 HV side
[HV, LV,TV]
119 17.5 1.5 - 220 34 23.2 25.2 Fig. 10
4 LV side
[HV, LV,TV]
12.1 32.4 0.1 612 - 58.3 23 24.2 -
TABLE 7
LIGHTNING SURGES TRANSFERRED THROUGH TRANSFORMER Case Switching
surge
applied at transformer
terminal
[SA location]
Energy absorbed by SA at [KJ]
Voltage at Transformer terminal [kVp] and
Corresponding %BIL
Refer Figures
HV side
LV side
TV side
HV LV %BIL TV %BIL
1 HV side
[HV, LV]
339 6.8 - - 220 34 121 128 Fig. 11
2 LV side
[HV, LV]
11 116 - 610 - 47 86 91 Fig. 12
3 HV side
[HV, LV,TV]
335 7.1 5.0 - 220 34 29 30.5 -
4 LV side
[HV, LV,TV]
7.4 114 0.15 610 - 47 30 31.6 Fig. 13
TABLE 8
STEEP FRONT SURGES TRANSFERRED THROUGH TRANSFORMER Case Switching
surge
applied at
transformer terminal
[SA
location]
Energy absorbed by SA at [KJ]
Voltage at Transformer terminal [kVp] and
Corresponding %BIL
Refer Figures
HV
side
LV
side
TV
side
HV LV %BIL TV %BIL
1 HV side
[HV, LV]
433 17.7 - - 249 38.5 155 163 Fig. 14
2 LV side
[HV, LV]
22.5 142.6 - 615 - 47.3 128 135 Fig. 15
3 HV side
[HV,
LV,TV]
434 17.2 5.3 - 222 34 43 45.3 Fig. 16
4 LV side
[HV,
LV,TV]
16.6 143 0.2 615 - 47 45 47.4 -
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 551
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
-
Fig. 9: Voltage at TV side of transformer for case 1, Table 6.
Fig. 10: Voltage at TV side of transformer for case 3, Table 6.
Fig. 11: Voltage at TV side of transformer for case 1, Table 7.
Fig. 12: Voltage at TV side of transformer for case 2, Table 7.
Fig. 13: Voltage at TV side of transformer for case 4, Table 7.
Fig. 14: Voltage at TV side of transformer for case 1, Table 8.
Fig. 15: Voltage at TV side of transformer for case 2, Table 8.
Fig. 16: Voltage at TV side of transformer for case 3, Table 8.
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 552
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
-
According to IEC Standard 60099-5[6], considering a safety
factor of 1.15, the acceptable overvoltages must be within
87% of BIL values. From the case studies, it is seen that with
surge arresters at autotransformer HV and LV terminals the
overvoltages at tertiary side of the transformer are high and
beyond the recommended BIL levels. Hence in addition to
provision of surge arresters at HV and LV sides of
transformer, 12 kV surge arrester at tertiary side of transformer
is required to limit the overvoltages to safe levels. It is also
seen that the energy absorbed by the three surge arresters are
well within the allowable ratings as presented in Tables 2, 3
and 4.
IV. CONCLUSIONS
The paper presents the modeling details of high frequency
autotransformer and frequency dependent surge arrester for
surge transfer studies. The results of simulations for lightning
and switching surges transferred through 502 MVA,
380/132/13.8 kV autotransformer using EMTDC/PSCAD are
presented. Three case studies have been performed to
determine need for surge arrester at tertiary of
autotransformers. Based on these studies it is observed that in
addition to surge arresters at HV and LV side of
autotransformer, surge arrester is required at tertiary side of
the transformer to limit the overvoltages to safe levels.
REFERENCES [1] J.C. Das, Surges transferred through transformers, IEEE Conference
on pulp and Industry technical conference, 2002, pp. 139-147.
[2] IEC 60071-2, Insulation co-ordination: part 2: Application guide, third edition, 1996-12.
[3] V. Brandwajn, H.W. Dommel, I.I. Dommel, Matrix Representation of
three-phase N-winding transformers for the steady state and transient studies, IEEE Transactions on Power Apparatus and Systems, Vol.
PAS-101, No.6, June 1982, pp.1369-1378.
[4] IEEE working Group 3.4.11, Application of surge protective devices subcommittee, Surge protective Devices Committee, Modeling of
Metal Oxide Surge Arresters, IEEE Transactions on Power Delivery,
Vol. 7, no.1, January 1992, pp. 302-309. [5] Micaela Caserza, Marco Giannettoni, Paolo Pinceti, Validation of ZnO
Surge Arresters Model for Overvoltage Studies, IEEE Transactions on
Power Delivery, vol. 19, no.4, Oct. 2004, pp-1692-1695. [6] IEC 60099-5, Surge Arresters- Part 5 Selection and Application
Recommendations, edition 1.1, March 2000. [7] Andrew R. Hileman, Insulation Coordination for Power Systems,
Taylor & Francis Publications, 1999.
APPENDIX: AUTOTRANSFORMER
Fig. 17: Autotransformer with Tertiary Winding
For a accurate representation of autotransformer the high and
low voltage terminals should be represented with the actual
common winding II and series winding I, as shown in Fig. 17
[3] for autotransformer with a tertiary winding III.
This requires a re-definition of the short circuit data in terms
of windings I, II, III, with their voltage ratings
VI = VH - VL
VII = VL (1)
VIII = VT
The test between H and L is already the correct test between
I and II, since II is shorted and the voltage is applied across I
with b and c being at the same potential through the short
circuit connection. Therefore, simply change ZHL to the new
voltage base VI,
2
,. .H
I II HL
H L
VZ Z in p u
V V
=
(2)
No modifications are required for the test between II and III,
ZII,III = ZLT in p.u. (3)
For the test between H and T, the modification can best be
explained in terms of the equivalent star-circuit of Fig. 17,
with the impedances being ZI, ZII, ZIII, based on VI, VII, VIII, in
this case. With III short circuited, 1 p.u. current (based on VIII
= VT) will flow through ZIII. This current will also flow
through I and II as 1 p.u. based on VH, or converted to bases
VI, VII, II = (VH VL) / VH and III = VL / VH. With these
currents, p.u. voltages become
, . .H LI I III
H
V VV Z Z in p u
V
= + (4)
, . .LII II III
H
VV Z Z in p u
V= + (5)
Converting VI and VII to physical units by multiplying eq.(4)
with (VH VL) and eq. (5) with VL, adding them up, and
converting the sum back to a p.u. value 2 2
.H L LHT I II III
H H
V V VZ Z Z Z in p u
V V
= + +
(6)
Eqs. (2), (3) and (6) can be solved for ZI, ZII, ZIII since ZI,II =
ZI+ZII and ZII,III = ZII+ZIII,
, 2. .
( )
H V H L
I III HL HL LT
H L H LH L
V V V VZ Z Z Z in p u
V V V VV V= +
(7)
The autotransformer of Fig. 17 can therefore be treated as a
transformer with 3 windings I, II, III by simply re-defining the
short circuit input impedances with eqs. (2), (3) and (7).
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 553
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.