7 Heat pumps sizing
heat pump characteristics
testing & operation conditions
balance point
storage size
hydraulics
![Page 2: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/2.jpg)
2/51
Heat pump
velk QPQ
el
k
P
QCOP
elkv PQQ
COPQQ kv
11
Qv
Qk
Pel
source side
sink side
extracted heat
rejected heat
![Page 3: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/3.jpg)
3/51
Heat pumps: ground source (borehole)
![Page 4: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/4.jpg)
4/51
Heat pumps: ground source (ground HX)
![Page 5: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/5.jpg)
5/51
Heat pumps: water source (water well)
![Page 6: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/6.jpg)
6/51
Heat pumps: air source (ambient)
![Page 7: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/7.jpg)
7/51
Types of heat pumps on the market
![Page 8: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/8.jpg)
8/51
The trend is air source
![Page 9: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/9.jpg)
9/51
... also sanitary hot water HP increase
![Page 10: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/10.jpg)
10/51
Heat pumps market in Europe
![Page 11: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/11.jpg)
11/51
Top ten countries is the market
![Page 12: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/12.jpg)
12/51
Heat pump parameters
heat output, heat capacity Qk [kW] – heat output from condenser
coefficient of performance COP [-]
- electric power Pel [kW]
- evaporator input = source output Qv [kW]
at given boundary conditions
-
and
-
tv1
tv1
tk2
tk2
![Page 13: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/13.jpg)
13/51
0
2
4
6
8
-10 -5 0 5 10
t v1 [°C]
Qk,
Pel
[kW
]
50 °C
35 °C
50 °C
35 °C
1
2
3
4
5
-10 -5 0 5 10
t v1 [°C]
et [
-]
50 °C
35 °C
Air-water heat pump characteristics
tk2
tk2
air-water air-water
CO
P [
-]
![Page 14: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/14.jpg)
14/51
Air-water heat pump characteristics
elec
tric
po
wer
, hea
tin
g c
apac
ity
[kW
] conden.output
temperature
ambient air temperature
![Page 15: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/15.jpg)
15/51
Air-water heat pump characteristics
CO
P [
-]
ambient air temperature
![Page 16: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/16.jpg)
16/51
2
3
4
5
6
-5 0 5 10 15
t v1 [°C]
et [
-]
50 °C
35 °C
0
2
4
6
8
10
12
-5 0 5 10 15
t v1 [°C]
Qk,
Pel
[kW
]
50 °C
35 °C
50 °C
35 °C
Brine-water heat pump (ground source)
tk2
tk2
brine-water brine-water
CO
P [
-]
![Page 17: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/17.jpg)
17/51
Brine-water heat pump (ground source)
source temperature
hea
tin
g c
apac
ity
[kW
]
conden.output
temperature
![Page 18: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/18.jpg)
18/51
Water-water heat pumph
eati
ng
cap
acit
y [k
W]
source temperature
conden.output
temperature
![Page 19: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/19.jpg)
19/51
Testing of heat pumps
EN 14511 - Air conditioners, liquid chilling packages and heat pumps
with electrically driven compressors for space heating and cooling.
EN 14511-1: dtto - Terms and definitions
EN 14511-2: dtto - Test conditions
EN 14511-3: dtto – Test methods
EN 14511-4: dtto - Requirements
EN 16147 – Heat pumps with electrically driven compressors.
Testing and requirements for marking of domestic hot water units
![Page 20: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/20.jpg)
20/51
Testing conditions
EN 14511: water-water W/W (W10 / W35)
nominal: 10/35 °C 10/45 °C
operation: 15/45 °C 10/55 °C
EN 14511: brine-water (ground-water) B/W (B0 / W35)
nominal: 0/35 °C 0/45 °C
operation: 5/35 °C 5/45 °C 0/55 °C
-5/45 °C
EN 14511: air-water (ambient air) A/W (A2 / W35)
nominal: 7/35 °C 7/45 °C
operation: 2/35 °C 2/45 °C 7/55 °C
-7/35 °C -7/45 °C -7/55 °C
-15/35 °C -15/45 °C
![Page 21: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/21.jpg)
21/51
21/26
Requirements on heat pump
Quality label EHPA (European Heat Pump Association)
minimum COP from testing according to EN 14511 in respected lab
brine-water B0/W35 COP > 4.3
water-water W10/W35 COP > 5.1
air-water A2/W35 COP > 3.1
declaration of sound power level
documentation: planning, service and operation guides in local language
customer service network, 24 h reaction time on customer complaints
2 years full warranty, spare parts inventory available for 10 years in stock
![Page 22: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/22.jpg)
22/51
Seasonal performance factor
totel,
hwsh,
Q
QSPF
hot water
space heating
COP
SPF
HPel,
HP
Q
QCOP
Qel,tot
Qsh,hw
heat pump
back-up
Qel,HP Qel,aux Qel,bu
QHP
![Page 23: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/23.jpg)
23/51
RES directive, minimum SPF
heat pumps consume electric energy
produced mainly from fossil fuels (primary non-renewable energysource)
he electricity production efficiency
european average 45.5 % SPF > 2.5
if SPF < 2.5 ... better to use fossil fuels directly by combustion
e
SPFh
115,1
![Page 24: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/24.jpg)
24/51
EN 15450 – Annex C (informative)
![Page 25: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/25.jpg)
25/51
Operation modes
monovalent operation
only heating device
parallel bivalent operation
under bivalent temperature
(balance point) back-up heater is
switched-on
low temperature systems
monovalent
bivalent parallel
HP
HP
BU
![Page 26: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/26.jpg)
26/51
Operation modes
alternatively bivalent operation
under bivalent temperature back-up
replaced heat pump. for high
temperature heating systems
bivalent alternative
the balance point = temperature
under which the back-up heater is required
HP
BU
![Page 27: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/27.jpg)
27/51
Operation modes
monoenergetic operation
e.g. bivalent operation of electric heat pump with electroboiler
(integrated in one device)
balance point
according to heat output (dimensioning)
acc. heating water temperature
sufficient heat output from heat pump
high temperatures of heating water needed, which couldnt be
supplied by heat pump, esp. in extreme winter
![Page 28: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/28.jpg)
28/51
Heat pump sizing
determination of heat pump type
available heat source
determination of (condenser) heat output Qk (for space heating)
building heat loss
heat output for hot water
design flow temperature
design source temperature
![Page 29: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/29.jpg)
29/51
Balance point according to temperature
0
10
20
30
40
50
60
70
80
90
100
-15 -10 -5 0 5 10 15 20
Tep
lota
pří
vod
ní
vod
y [°
C]
Venkovní teplota [°C]
90/70 °C
75/55 °C
60/45 °C
55/40 °C
45/35 °C
35/30 °C
max output temperature
outdoor temperature [°C]
flow
tem
pera
ture
[°C
]
example of air source HP
radiators
underfloor heating
![Page 30: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/30.jpg)
30/51
0
5
10
15
20
25
30
-12 -8 -4 0 4 8 12 16 20
ambient temperature t e [°C]
hea
t o
utp
ut Q
k [k
W],
hea
t lo
ad Q
l [kW
]
output temperature 35 °C
output temperature 50 °C
heat load
Balance point according to heat output
balance point
ground source HP
Qk
QL
QL, des
![Page 31: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/31.jpg)
31/51
0
5
10
15
20
25
30
-12 -8 -4 0 4 8 12 16 20
ambient temperature t e [°C]
hea
t o
utp
ut Q
k [k
W],
hea
t lo
ad Q
l [kW
]
output temperature 35 °C
output temperature 50 °C
heat load
Balance point according to heat output
balance point
air source HP
Qk
QL
QL, des
Qk,bal
![Page 32: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/32.jpg)
32/51
Balance point determination
design heat load QL,des
calculation according to EN 12 831 for design external
temperature (e.g. -12 °C, -15 °C, -18 °C in CZ )
heat output at balance point Qk = QL
e.g. from desired fraction 60 to 100 % Qk,bal / QL,des
ei
L
desei
desL
tt
Q
tt
Q
,
,
balei
balk
tt
Q
,
,
desei
desL
balkibale tt
Q
Qtt ,
,
,, if Qk = konst
if Qk = konst - graph/
0
5
10
15
20
25
30
-12 -8 -4 0 4 8 12 16 20
ambient temperature t e [°C]
hea
t o
utp
ut Q
k [k
W],
hea
t lo
ad Q
l [kW
]
output temperature 35 °C
output temperature 50 °C
heat load
![Page 33: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/33.jpg)
33/51
Example
family house
design load 15 kW for
design temperature -15 °C
heat pump (SE WPL18)
heating system 50/40 °C
determine the balance point
balance point heat output
balance point power input
balance point COP
Qk =10.5 kW
![Page 34: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/34.jpg)
34/51
20
25
30
35
40
45
50
55
-15 -10 -5 0 5 10 15 20
ambient temperature t e [°C]
flo
w t
emp
erat
ure
[°C
]Flow temperature
desei
deseewdeswdesww
tt
tttttt
,
,min,1,1,11
flow tw1
return tw2
42 °C
![Page 35: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/35.jpg)
35/51
Power input at balance point
for balance power point
tv1 = -5 °C, tk2 = 42 °C
P35 = 3.3 kW
P50 = 4.5 kW
355035
3550
1
351
PP
t
PP
w
tw
3550
3513550351
w
tw
tPPPP
balance power point
P42 = 3.9 kW
interpolation
![Page 36: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/36.jpg)
36/51
Example
COP35
COP50
3550
50 15035501
w
tw
tCOPCOPCOPCOP
![Page 37: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/37.jpg)
37/51
Example
family house
design load 15 kW for
design temperature -15 °C
heat pump (SE WPL18)
heating system 50/40 °C
determine the balance point
balance point heat output
balance point power input
balance point COP
Qk =10.5 kW
balance power point
P42 = 3.9 kW
balance point COP =
![Page 38: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/38.jpg)
38/51
Heat pump sizing – coverage of demand
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
days
ou
tdo
or
tem
per
atu
re te
[°C
]
100%
25%
50%
75%
60%
0%
![Page 39: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/39.jpg)
39/51
Heat pump sizing – coverage of demand
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
a
ar
residential sector
based on heating
demand
HP heating output / design heating load
supp
lied
ener
gy b
y H
P /
heat
ing
dem
and
![Page 40: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/40.jpg)
40/51
Heat pump sizing (ground source)
dimensioning heat output (independent on ambient conditions)
50 % heat loss - coverage 85 % heat demand
60 % heat loss – coverage 93 % heat demand
70 % heat loss - coverage 97 % heat demand
water-water
![Page 41: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/41.jpg)
41/51
Heat pump sizing (air source)
dimensioning heat output (dependent on ambient conditions)
50 % heat loss - coverage 75 % heat demand
60 % heat loss – coverage 85 % heat demand
70 % heat loss - coverage 92 % heat demand
air-water
![Page 42: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/42.jpg)
42/51
Heating capacity control
usual heat pumps
start-stop regime
cycling = reduction of durability compressor
elimination cycling
undersizing
heat storage – sizing of store for minimum operation time of heat
pump
heat pump with heating capacity control
compressor speed control
possibility for monovalent operation
![Page 43: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/43.jpg)
43/51
Heating capacity control
0
5
10
15
20
25
30
-12 -8 -4 0 4 8 12 16 20
ambient temperature t e [°C]
hea
t o
utp
ut Q
k [k
W],
hea
t lo
ad Q
l [kW
]
output temperature 35 °C
output temperature 50 °C
heat load
Without capacity control
With capacity control
100%
30%
backup
backup
part load – cycling
part load – cycling
![Page 44: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/44.jpg)
44/51
Heat storage for heat pump
oversized storage for most of operation time
balancing heat output and heat load
reduction of frequency compressor on/off (1 x 10 min)
longer durability of compressor
heat source for outdoor units (air-water)
antifreeze protection
![Page 45: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/45.jpg)
45/51
Heat storage for heat pump
hydraulic decoupling of heat pump from load circuit
hydraulic shunt
heating systems can’t influence HP circuit
providing required (higher) flowrates at condenser
heat pump storage tank
heating
system
![Page 46: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/46.jpg)
46/51
Sizing of storage tank
balance to reduce on/off frequency
minimum operation time period Dt
increase of temperature Dt in store during operation of heat pump
heat stored during operation of heat pump
tcVQQ HPstored DD t
![Page 47: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/47.jpg)
47/51
Sizing of storage tank
specific volume
Dt [s] minimum operation time: 15 min
Dt [K] increase of store temperature: 3 - 5 K
usually 15 to 30 l/kW
thermal capacity (momentum) of heating system results in lower
volume requirement
tcQ
V
HP D
D
t1000
![Page 48: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/48.jpg)
48/51
Example
calculate heat storage volume for balance point heat output 10.5 kW
minimum operation time period Dt = 15 min
increase of temperature Dt in store 3 K
tcQV HP
D
D
t1000
34187998
60151000]kW[]m[ 3
HPQV
V = 754 l
![Page 49: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/49.jpg)
49/51
Integration of store
electronically
controlled pump
heat pump
control
temperature sensor
pump
bypass valve
heating system
storage tank
![Page 50: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/50.jpg)
50/51
Hydraulics
with two stores
heating water store, hot water store
bivalent (back-up) heater inside heat pump
SH HWEL.HEATER
heating
system
HW
CW
![Page 51: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/51.jpg)
51/51
Hydraulics
with central store
hot water heated in heat exchanger immersed in heating water store
volume
bivalent (back-up) heater: immersed in store
EL.HEATER
HEAT PUMP
heating
system
HW
CW
![Page 52: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according](https://reader031.vdocuments.us/reader031/viewer/2022040513/5e689a996efc2827d6557daa/html5/thumbnails/52.jpg)
52/51
Guides for design
low temperature heating < 45 °C
floor heating, wall heating
radiators with larger surface
pool water heating
hot water
low temperature 45 °C
air-water: advantage in summer, high ambient temperatures
brine-water: reduction of borehole regeneration (!)