CablesELECTRICALE L E C T R I C A L
April 24, 2007
CONDUMEX INCORPORATED
WIRE & CABLE PRODUCT INDEX
!
!
!
MTW/THHN/THWN 600 VOLTS COPPER 14 AWG SOLID 750 MCMSTRANDED UL 83XHHW-2 600 VOLTS COPPER 14 AWG 1000 MCM STRANDED UL 44RHH-RHW-USE 600 VOLTS COPPER (XLP) 6 AWG 1000 MCM STRANDED UL 44
BUILDING WIRE
!
!
TYPE TC/THHN 600 VOLTS COPPER 14 AWG STRANDED 750 MCMSTRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BAREGROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTORFOR SIZES 14, 12 AND 10 AWG UL 1277TYPE TC/XHHW-2 600 VOLTS COPPER 14 AWG STRANDED 750 MCMSTRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BAREGROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTORFOR SIZES 14, 12 AND 10 AWG UL 1277
TRAY CABLE
POWER CABLE
!
!
!
!
!
PRIMARY URD CABLES, 15 KV 35 KV, 100% & 133% INSULATIONLEVELS, COPPER OR ALUMINUM CONDUCTOR, EPR OR TR-XLPINSULATION, CONCENTRIC COPPER WIRE NEUTRAL, WITH OR WITHOUTENCAPSULATING JACKET OVERALLSPECIFICATIONS: ICEA S-94-649 & AEIC CS8TYPE MV-90 & MV-105 (EPR INSULATION ONLY FOR MV-105) POWER CABLE, 5 KV - 35KV, 100% & 133% INSULATION LEVELS, COPPER CONDUCTOR, EPR OR XLPINSULATION, COPPER DRAIN WIRE OR COPPER TAPE METALLIC SHIELD, BLACK PVCSUNLIGHT RESISTANT JACKET. SINGLE CONDUCTOR CONSTRUCTION.LISTED UL 1072; SPECIFICATIONS: ICEA S-93-639 & AEIC CS8TYPE MC ARMORED CABLES, 600 VOLTS, 5 KV - 15 KV, MULTI-CONDUCTORSTRANDED COPPER, EPR OR XLP INSULATION, ALUMINUM OR GALVANIZED STEELINTERLOCKED ARMOR, PVC SUNLIGHT RESISTANT JACKET OVERALL. UL 1569HIGH VOLTAGE POWER CABLES UP TO 138 KV, COPPER OR ALIMINUM CONDUCTOR,XLP UNSULATION, METALLIC SHIELD,PVC JACKET.SPECIFICATION: AEIC Cs7BARE OVERHEAD CONDUCTORS, TYPES AAC AND ACSR, PER ASTM B230 & B232
SPECIAL PURPOSE CABLES
! TYPE RHH-RHW 2000 VOLTS, (DLO), SINGLE CONDUCTOR TINNED COPPER, ROPE-LAYSTRANDED, EPR INSULATION, SEPARATOR, BLACK CSPE JACKET. CONDUCTOR SIZES4 AWG 1 AWG UL LISTED AS VW-1; SIZES 1/0 AWG 929.2 MCM UL LISTED FOR “CTUSE”, CSA LISTED AS FT4. SIZE 1111 MCM IS PER ICEA S-68-516.
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947302-06
TYPE THHN OR THWN 600 VOLTS
1) Annealed bare solid (14-10 AWG),
annealed bare stranded class C
concentric round (14-2 AWG),
DESCRIPTION
compressed stranding class B
(1 AWG - 1000 MCM) copper conductor.
2) Polyvinyl chloride (PVC insulation)
3) Nylon overall protective jacket.
123
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
14
12
10
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000
1 Solid
1 Solid
1 Solid
19
19
19
19
19
19
19
19
19
19
19
19
19
37
37
37
37
37
61
61
61
4.1
6.5
10.3
4.1
6.5
10.3
16.5
26.2
41.7
52.6
66.3
83.7
106
133
168
211
0.06
0.08
0.10
0.07
0.09
0.11
0.15
0.18
0.23
0.26
0.29
0.32
0.37
0.41
0.47
0.52
0.57
0.62
0.67
0.72
0.80
0.88
0.98
1.14
15
15
20
15
15
20
30
30
40
40
40
50
50
50
50
50
60
60
60
60
60
70
70
70
5
5
5
5
5
5
5
6
6
7
7
7
8
8
8
8
9
9
9
9
9
10
10
10
0.10
0.12
0.15
0.12
0.14
0.17
0.23
0.26
0.34
0.36
0.39
0.45
0.50
0.54
0.59
0.65
0.72
0.78
0.83
0.87
0.96
1.06
1.15
1.27
16
23
37
17
26
40
65
99
157
197
241
306
380
472
587
729
870
1033
1196
1359
1685
2023
2454
3347
SizeAWG/kcmil
Numberof
Strands
ConductorAreakcmil
ConductorDiameter
mils
InsulationThickness
mils
JacketThickness
mils
OverallDiameter
inch
NetWeightlb/mft
manufacturing tolerances.
VINANEL Nylon, solid or stranded type®
General use in commercial and industrial
SPECIFICATIONS
construction, and installations where
resistance against oils and gasoline is
APPLICATION
75° CIn oil (Oil resistant II)
6) Superior abrasion and mechanical
properties.
7) Sizes 1/0 and larger are marked "For
CT use", and are approved for installation
overload exists.
in cable trays. Sunlight resistant in
Accordance with NEC Article 318.
manufacturing process.
4) Flame retardant, UL listed as VW-1.
5) Smooth nylon jacket aids in easier
pulling.
1) Good resistance to moisture, heat, oil,
gasoline, chemicals and grease.
2) Suitable for installation where thermal
3) Strict quality control during
FEATURES
MAXIMUM CONDUCTOR TEMPERATURE
Dry locations (THHN)
Dry and wet locations (THWN)
90° C
75° C
MAXIMUM OPERATING VOLTAGE
600 volts
required. May be used for power and
gases, gasoline and chemicals. Also
suitable as machine tool and switchboard
control circuits in recognized raceways, in
wet or dry locations, and in presence of
wiring.
UL-83
HOW TO ORDER
NATIONAL ELECTRICAL CODE REFERENCE
Ampacities
Switchboard wiring
Conduit fill tables
Article 3 10-15
Article 384
Chapter 9
THHN or THWN, 600 volts, size, color and length
11
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947303-06
THHN/THWN 600 VOLTS
POWER CABLE TYPE TC
DESCRIPTION
2) Polyvinyl Chloride (PVC) thermoplastic
insulation.
1) Annealed bare Class C concentric
strand copper conductors.
3) Nylon protective covering.
4) Binder tape over core.
5) Overall flame retardant PVC jacket.
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
Size
AWG
Numberof
Strands
Numberof
Conductors
JacketThickness
mils
OverallDiameterinches
NetWeightlb/Mft
14
12
10
19
19
19
2
3
4
5
7
9
12
16
2
3
4
5
7
9
12
16
2
3
4
5
7
9
12
45
45
45
45
45
60
60
60
45
45
45
45
60
60
60
60
45
45
60
60
60
60
80
0.34
0.36
0.40
0.43
0.46
0.56
0.63
0.67
0.38
0.40
0.43
0.46
0.55
0.64
0.71
0.76
0.45
0.47
0.55
0.60
0.65
0.75
0.89
68
87
109
130
167
234
285
335
90
119
154
173
247
326
400
485
139
180
247
178
367
480
637
manufacturing tolerances.
FEATURES
Wet or DryDry
75° C90° C
APPLICATION
Electrical Code
Condumex Type TC cable may be used for power,
messenger. Type TC cable may be used in wet or
dry locations and in the presence of oil and most
lighting, control, signal and communcation circuits,
in raceways, direct burial in earth, or in
SPECIFICATIONS
S-73-532 (table E-2 or Method S/B 4.)
7) Circuit identification; color coded per ICEA
UL 1277 and UL 83
HOW TO ORDER
chemicals in accordance with the National
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
Condumex Tray Cable Type TC/THHN,
600 volts, number and size of conductors.
1) UL listed for direct burial.
2) Flame retardant, (passes UL 1277, 70,000
BTU flame test.3) Sunlight resistant; can be installed outdoors.
4) UL listed as Type TC for power and control
Electrical Code.
tray cable used in accordance with the National
Resistant I.
5) PVC jacket is UL rated 90 C and listed OilO
required metallic sheathed cables.
substantial cost savings over the previously
Location Applications. Type TX offers
6) Acceptable for Class I, Division 2, Hazardous
7a) Other color coding methods are available,
based on ICEA S-73-532
2
245 13
5) Binder tape over core
750 kcmil) copper conductors.
6) Overall flame retardant PVC jacket.
DESCRIPTION
3) Nylon protective covering.4) Fillers
1) Annealed bare Class C (8-2 AWG)compressed stranded Class B (1/0 AWG-
2) Polyvinyl Chloride thermoplastic insulation
36 145 2
POWER CABLE TYPE TC
THHN/THWN 600 VOLTS
Size
AWG/kcmil
Numberof
Conductors
GroundConductor
AWG
InsulationThickness
mils
JacketThickness
mils
OverallDiameter
inch
NetWeightlb/Mft
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1/0
2/0
4/0
350
500
750
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
10
8
6
6
6
6
4
4
4
3
2
1
6
6
4
3
2
1
30/5
30/5
40/7
40/7
50/8
50/8
50/8
50/8
60/9
60/9
60/9
70/10
50/8
50/8
50/8
60/9
60/9
70/10
60
60
80
80
80
80
80
80
80
110
110
110
80
80
110
110
110
140
0.638
0.698
0.884
1.015
1.223
1.320
1.428
1.549
1.760
1.980
2.260
2.967
1.350
1.457
1.773
2.188
2.502
3.057
338
448
693
1012
1495
1858
2297
2791
3374
4526
6230
8845
1913
2311
3597
5754
8018
11716
Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.
MAXIMUM OPERATING VOLTAGE
UL 1277 and UL 83
7) Circuit identification; color coded per ICEA
MAXIMUM CONDUCTOR TEMPERATURE
Wet or DryDry
75° C90° C
required metallic sheathed cables.
3) Sunlight resistant; can be installed outdoors.
tray cable use in accordance with the National
Electrical Code.
APPLICATION
in accordance with the National Electrical Code.
6) Acceptable for Class I, Division 2, Hazardous
4) UL listed as Type TC for power and control
600 volts
5) PVC jacket is UL rated 90° C and listed Oil
Resistant I.
1) UL listed for direct burial.
2) Flame retardant, (passes UL 1277, 70,000
BTU flame test.)
FEATURES
Condumex Type TC cable may be used for
cable may be used in wet or dry locationsand in the presence of oil and most chemicals
power, lighting, control, signal andcommunication circuits, in raceways, direct
HOW TO ORDER
600 volts, number and size of conductors.Condumex Tray Cable Type TC/THHN,
SPECIFICATIONS
S-73-532 (table E-2 or Method S/B 4.)
Location Applications. Type TC offers
substantial cost savings over the previously
7a) Other color coding methods are available,
based on ICEA S-73-532
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947303-06
3
1) Annealed bare stranded class B compact
copper conductor.
DESCRIPTION
3) Ethylene propylene (EPR) or cross-linked
polyethylene (XLPE) insulation.
4) Polyvinyl chloride (PVC) protective jacket.
2) Extruded semiconducting strand shield.
VULCANEL®
MEDIUM VOLTAGE
WET OR DRY POWER CABLE 5 KV
XLPE OR EPR NON-SHIELDED
24 13
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
SizeAWG/kcmil
Numberof
Strands
ConductorDiameter
inch
InsulationThickness
inch
InsulationDiameter
inch
JacketThickness
mils
OverallDiameter
Inch XLPE EPR
Net WeightLb/Mft
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
manufacturing tolerances.
5kV 133% Insulation Level, 115 mils Insulation Thickness
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
cable, voltage and insulation level, conductor
Ampacities
Cable Trays
Type MV
ICEA S-66-524, AEIC CS-S (XLP)
extrusion) results in a virtually perfect
cable core.
- Very low dielectric loss
Normal Operation 105° C130° CEmergency Overload
VULCANEL® 5kv Non-shielded power cables
adequate for proper termination of the shielding.
1) Simultaneous extrusion of strand shield,
250° CShort Circuit
UL 1072
326
318
310-15
National Electrical Code References:
VULCANEL®EPR/XLPE Non-Shielded power
size and type, length and reel dimensions.
SPECIFICATIONS
are ideally suited for use in industrial and
utility applications where shields cannot be
APPLICATION
abrasion, ozone and moisture.
- Electrical stability under stress
- Low dielectric loss- Chemical resistance
FEATURES
3) Easy-stripping insulation shield4) The external PVC jacket is resistant to
EPR insulation offers:- Excellent heat, moisture and corona
2) XLPE insulation offers:- Low moisture absorption.
- Good resistance to chemicals.
insulation and insulation shield (triple
accordance with the National ElectricalCode.
5) UL listed as MV-105, sunlight resistant,direct burial. Optional marking "For CTuse" available on single conductor in
HOW TO ORDER
resistance.
MAXIMUM CONDUCTOR TEMPERATURE
Page 1 of 2
ICEA S-68-516, AEIC CS-6-87 (EPR)
4
VULCANEL®
MEDIUM VOLTAGE
WET OR DRY POWER CABLE 5 KV
XLPE OR EPR NON-SHIELDED
Page 2 of 2
SizeAWG/kcmil
Numberof
Strands
ConductorDiameter
inch
InsulationThickness
inch
InsulationDiameter
inch
JacketThickness
mils
OverallDiameter
Inch XLPE EPR
Net Weightlb/Mft
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
25kV 100% Insulation Level, 260 mils Insulation Thickness
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
35kV 100% Insulation Level, 345 mils Insulation Thickness
Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
15kV 133% Insulation Level, 220 mils Insulation Thickness
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
15
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
VULCANEL®
MEDIUM VOLTAGE EPR
SHIELDED POWER CABLES 5, 15, 25, 35 KV
346 125
DESCRIPTION
1) Annealed bare stranded class B compactcopper conductor.
2) Extruded semiconducting strand shield.3) Ethylene propylene rubber (EPR) insulation.4) Extruded semiconducting insulation shield.5) Annealed copper tape shield (25% overlap
6) Polyvinyl chloride (PVC) protective jacket.minimum).
Three-phase electrical distribution systems.
trays.
Suitable for use in overhead installations,recognized raceways, direct burial or cable
APPLICATION
voltage and insulation level, conductor
Ampacities
Cable TraysType MV
- Chemical resistance
5) The external PVC jacket is resistant to
- Electrical stability under stress
MAXIMUM CONDUCTOR TEMPERATURE
SPECIFICATIONS
use" available on single conductor in
accordance with the National Electrical
Code.
abrasion, ozone and moisture.
6) UL listed as MV-105, sunlight resistant,
direct burial. Optional marking "For CT
3) Easy-stripping insulation shield
4) Tape shield provides high short circuit
capabilities and uniform shield impedance.
- Low dielectric loss
UL 1072
size and type, length and reel dimensions.
ICEA S-68-516, AEIC CS6-87
326
318
310-15National Electrical Code References:
VULCANEL® EPR shielded power cable,
2) EPR insulation offers:
- Excellent heat, moisture and corona
resistance.
insulation and insulation shield (triple
extrusion) results in a virtually perfect
cable core.
250 °CShort Circuit
1) Simultaneous extrusion of strand shield,
Normal Operation 105 °C130 °CEmergency Overload
FEATURES
SPECIFICATIONS
HOW TO ORDER
Page 1 of 2
Size
AWG/kcmil
Numberof
Strands
ConductorDiameter
Inch
InsulationThickness
inch
Insul. Shld.Diameter
inch
JacketThickness
mils
OverallDiameter
Inch
NetWeightlb/Mft
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
19
19
19
19
37
37
37
61
61
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.11
0.45
0.49
0.55
0.62
0.66
0.71
0.76
0.81
0.91
1.03
1.21
1.36
0.53
0.57
0.63
0.70
0.74
0.79
0.84
0.90
0.99
1.13
1.32
1.46
60
60
60
80
80
80
80
80
80
80
80
80
0.67
0.71
0.74
0.85
0.92
0.97
1.02
1.07
1.17
1.32
1.50
1.64
290
357
478
668
775
933
1071
1226
1560
2150
3027
3845
5kV 133% Insulation Level, 115 mils Insulation Thickness
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
19
19
19
19
37
37
37
61
61
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.11
0.67
0.74
0.78
0.83
0.88
0.94
1.03
1.16
1.34
1.36
0.75
0.82
0.86
0.91
0.96
1.02
1.14
1.26
1.44
1.59
80
80
80
80
80
80
80
80
80
110
0.93
1.00
1.04
1.09
1.14
1.20
1.32
1.44
1.62
1.83
570
736
849
1010
1190
1330
1753
2280
3142
5794
5kV 100% Insulation Level, 175 mils Insulation Thickness
Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.
6
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
Page 2 of 2
VULCANEL®
MEDIUM VOLTAGE EPR
SHIELDED POWER CABLES 5, 15, 25, 35 KV
Size
AWG/kcmil
Numberof
Strands
ConductorDiameter
Inch
InsulationThickness
inch
Insul. Shld.Diameter
inch
JacketThickness
mils
OverallDiameter
Inch
NetWeightlb/Mft
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
19
19
19
19
37
37
37
61
61
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.11
0.45
0.49
0.55
0.62
0.66
0.71
0.76
0.81
0.91
1.03
1.21
1.36
0.53
0.57
0.63
0.70
0.74
0.79
0.84
0.90
0.99
1.13
1.32
1.46
60
60
60
80
80
80
80
80
80
80
80
80
0.67
0.71
0.74
0.85
0.92
0.97
1.02
1.07
1.17
1.32
1.50
1.64
290
357
478
668
775
933
1071
1226
1560
2150
3027
3845
15kV 133% Insulation Level, 220 mils Insulation Thickness
1/0
2/0
3/0
4/0
250
350
500
750
1000
19
19
19
19
37
37
37
61
61
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.11
0.92
0.96
1.00
1.06
1.11
1.21
1.33
1.51
1.66
1.00
1.04
1.11
1.16
1.22
1.31
1.43
1.61
1.80
80
80
80
80
80
80
80
110
110
1.18
1.22
1.29
1.34
1.40
1.49
1.61
1.85
2.04
894
1009
1181
1394
1537
1936
2516
3620
4543
25kV 100% Insulation Level, 260 mils Insulation Thickness
1/0
2/0
3/0
4/0
250
350
500
750
1000
19
19
19
19
37
37
37
61
61
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.11
1.09
113
1.18
1.23
1.29
1.38
1.50
1.68
1.83
1.19
1.23
1.28
1.33
1.39
1.49
1.61
1.83
1.97
80
80
80
80
80
80
110
110
110
1.37
1.41
1.46
1.51
1.57
1.67
1.85
2.07
2.21
1041
1226
1380
1569
1750
2163
2893
3900
4807
35kV 100% Insulation Level, 345 mils Insulation Thickness
manufacturing tolerances.Dimension and weights shown are nominal, unless otherwise indicated, and subject to
17
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-94735-05
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
ICEA-S-68-516
SPECIFICATIONS
three conductor cable, voltage size andlength.
Condumex Mining Cable EPR type SHD-GC
HOW TO ORDER
MINING CABLE EPR TYPE SHD-GC
THREE CONDUCTOR 5000 VOLTS
18.SHD-GC.01
with a nylon webbing, provides a tough, defense
round configuration.
and Health Administration Approval No. P-218-1-MSHA
by the Pennsylvania Department of Environmental
Resources. Meets MSHA flame test requirements.
6) Acceptance No. P-218-1-MSHA by Mines Safety
5) PLCV-Cured extra-heavy-duty CSPE, reinforced
4) Prevulcanized thermosetting non-wicking fillers
mechanical resistant jacket.
resistance, outstanding corona resistance,
high dielectric strength and chemical resistance.
designed for flexibility and resistance to
FEATURES
2) Ground check conductor facilitates fail-safe
3) EPR insulation offers excellent heat and moisture
are used if necessary to obtain a substantially
1) Special tinned copper stranded conductors
fatigue resulting from bending and flexing.
ground monitoring for maximum safety.
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
6
4
2
1
1/0
2/0
3/0
4/0
300
350
7x30/29
7x47/29
7x74/29
7x37/25
7x47/25
7x60/25
7x75/25
19x35/25
19x49/25
19x58/25
0.20
0.25
0.31
0.35
0.39
0.45
0.50
0.59
0.69
0.76
110
110
110
110
110
110
110
110
120
120
10
8
6
5
4
3
2
1
1/0
2/0
8
8
8
8
8
8
8
8
8
8
1.56
1.68
1.87
1.95
2.08
2.20
2.36
2.50
2.81
2.95
1675
1888
2322
2653
3068
3504
4206
5023
6371
7654
SizeAWG/kcmil
Number ofStrands/AWG
ConductorDiameter
inch
InsulationThickness
mils
GroundSizeAWG
GroundCheck Size
AWG
OverallDiameter
inch
NetWeightlb/mft
manufacturing tolerances.
MAXIMUM CONDUCTOR TEMPERATURE
Normal continuous 90° C
130° COverload
250° CShort circuit
MAXIMUM OPERATING VOLTAGE
5,000 volts
Trailing cable on ac mining equipment
where service conditions are severe and
maximum safety is mandatory, such as
APPLICATION
power shovels and draglines in open-pit
mines, quarries, gantry cranes and slag
reclaiming. Also used for medium voltage
distribution in underground mines where
frequent relocation is necessary.
DESCRIPTION
1) Three flexible annealed tinned copperrope-lay stranded conductors.
2) Extruded semi-conducting conductor shieldand ethylene propylene rubber (EPR) insulation.
3) Color coded cotton/copper braid shieldapplied over semi-conducting tape.
4) Two annealed tinned copper rope-lay strandedgrounding conductors.
5) Annealed tinned copper rope-lay stranded
and covered with a yellow cotton braid.
chlorosulfonated polyethylene (CSPE) jacket.
6) Rubberized cotton binder tape.7) Nylon web reinforced extra-heavy-duty
ground check conductor, yellow EPR insulation
346 2 157
18
5) Overall flame retardant PVC jacket.
DESCRIPTION
XLPW insulation.
3) Fillers (if required)
4) Binder tape over core.
2) Cross-Linked polyethylene, thermosetting
1) Annealed bare stranded compressed
Class B copper conductors.
without grounding conductor.Volts number and size of conductors, with or
Condumex Type TC cable may be used for power,
messenger. Type TC cable may be used in wet
lighting, control, signal and communication circuits,in cable trays, raceways, direct burial, or on
HOW TO ORDER
Condumex Tray Cable Type TC/XHHW, 600
SPECIFICATIONS
UL 1277
APPLICATION
most chemicals in accordance with the
MAXIMUM OPERATING VOLTAGE
National Electrical Code.
or dry locations and in the presence of oil and
6) Acceptable for Class 1, Division 2, HazardousLocations applications.
5) PVC jacket is UL rated 90O
C and listed OilResistant I.
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
90 CO
130 CO
FEATURES
OverloadNormal
1) UL listed for direct burial.2) Flame retardant, (passes UL 1277 70,000
National Electrical Code.
BTU flame test.)3) Sunlight resistant; can be installed outdoors.4) UL listed as Type TC for power and control
tray cable, use in accordance with the
3 145 2
POWER CABLE TYPE TC
XHHW 600 VOLTS
Size
AWG/kcmil
Numberof
Conductors
GroundConductor
AWG
InsulationThickness
mils
JacketThickness
mils
OverallDiameter
inch
NetWeightlb/Mft
Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
8
6
4
2
1/0
350
500
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
10
8
8
6
6
4
4
4
4
3
2
10
8
8
6
6
3
2
45
45
45
45
55
55
55
55
65
65
65
45
45
45
45
55
65
65
60
60
80
80
80
80
80
80
110
110
110
60
80
80
80
80
110
110
0.66
0.74
0.88
1.03
1.21
1.31
1.42
1.54
1.75
1.96
2.25
0.73
0.87
0.97
1.12
1.34
2.17
2.49
336
474
691
1015
1501
1861
2255
2735
3298
4437
6120
418
630
867
1276
1900
5681
7870
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
19
DESCRIPTION
copper conductor.
2) Cross-linked polyethylene (XLPE)
insulation.
compressed (6 AWG-1000 MCM)
1) Annealed bare stranded class B
concentric round (14-8 AWG)
APPLICATION
Power or control circuits in recognized
switchboard wiring.
Dry locations 90° C
presence of oil. Also suitable as
designs.
temperatures.
4) Suitable for installation in sub-zero
pulling and greater conduit fill.
5) Optical "For CT use" marking, for use in
cable trays. Sunlight resistant in
FEATURES
2) Good moisture resistance.
raceways, in wet or dry location and in
75° CWet locationsOverload 130° CShort Circuit
MAXIMUM OPERATING VOLTAGE
3) Good resistance to most oils and
chemicals.
MAXIMUM CONDUCTOR TEMPERATURE
600 volts
accordance with NEC Article 318.6) Available in VW-1 and non VW-1
UL-44
SPECIFICATIONS
Chapter 9
250° C
1) Smaller overall diameter for easier
HOW TO ORDER
National Electrical Code References:
Article 310
VULCANEL®
XLPE cable, type XHHW-2,600 volts, size and length.
Ampacities
Switchboard wiring
Conduit fill tables
* Dupont trade mark
Article 384
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
VULCANEL
TYPE XHHW-2 600 VOLTS
®XLPE CABLE
2 1
Size
AWG/kcmil
Numberof
Strands
ConductorAreakcmil
ConductorDiameter
inch
InsulationsThickness
Mils
OverallDiameter
inch
NetWeightlb/Mft
manufacturing tolerances.
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000
7
7
7
7
7
7
7
19
19
19
19
37
37
37
37
37
61
61
61
4.1
6.5
10.3
16.5
26.2
41.7
66.3
106.0
133.0
168.0
211.0
0.07
0.09
0.11
0.15
0.18
0.23
0.29
0.37
0.41
0.47
0.52
0.57
0.62
0.67
0.72
0.80
0.88
0.98
1.14
30
30
30
45
45
45
45
55
55
55
55
65
65
65
65
65
80
80
80
0.13
0.15
0.17
0.24
0.27
0.32
0.38
0.48
0.52
0.58
0.63
0.70
0.75
0.80
0.85
0.93
1.04
1.15
1.30
19
48
42
71
98
153
241
378
446
556
697
851
997
1180
1306
1662
1974
2450
3240
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
10
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
National Electrical Code References:
Product Article 310, Table 310-13
Ampacities Article 310-15
HOW TO ORDER
CONDUMEX type RHH-RHW-USE-2
XLPE 600 volts, size, length, quantity,
packaging.
DESCRIPTION
polyethylene (XLPE) insualtion.
1) Annealed bare stranded class B
conductor
2) Flame-retardant cross-linked
TYPE RHH-RHW-USE-2
COPPER XLPE 600 VOLTS
APPLICATION
May be installed in free air, all raceways or
underground service entrance cable.
Type RHH 90° C Dry and
temperatures.
6) Stable electrical propoerties.
UL-44 Standard for Rubber-Insulated
use in direct burial in industrial and
commercial application. May be used as
7) Extremely tough.
SPECIFICATIONS
4) Good resistance to most oils and
3) UL approved as VW-1 (RHH or RHW)
chemicals.
5) Suitable for installation in sub-zero
2) UL listed as types RHH or RHW or USE for
resistant insulation.
damp locations
ICEA S-66-524 Standard for Cross-Linked
Type RHW or 75° C Dry and
use in accordance with the National
Electrical Code.
MAXIMUM CONDUCTOR TEMPERATURE
600 volts
MAXIMUM OPERATING VOLTAGE
USE wet locatinons
1) Flame retardant, moisture and heat
FEATURES
Wires and Cables.
Polyethylene Insualted Wire and Cable.
Size
AWG/kcmil
Numberof
Strands
ConductorAreakcmil
ConductorDiameter
inch
InsulationsThickness
mils
OverallDiameter
inch
NetWeightlb/Mft
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000
7
7
7
7
19
19
19
19
37
37
37
37
37
61
61
61
16.5
26.2
41.7
66.3
106
133
168
211
0.15
0.18
0.22
0.28
0.36
0.41
0.46
0.51
0.56
0.61
0.66
0.71
0.79
0.87
0.97
1.12
60
60
60
60
80
80
80
80
95
95
95
95
95
110
110
110
0.27
0.31
0.35
0.41
0.53
0.58
0.63
0.69
0.76
0.82
0.87
0.92
0.99
1.11
1.20
1.36
73
108
161
245
392
485
600
746
887
1052
1216
1380
1708
2055
2542
3353
Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.
11 111
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04
CODE SIZE STRAND OVERALL DIAMETER NET WEIGHT RUPTURE STRENGTH
Turkey
Swan
Swallow
Sparrow
Robin
Raven
Quail
Pigeon
Penguin
Partridge
Linnet
Oriole
Ibis
Lark
Hawk
Hen
Heron
Dove
Eagle
Duck
Grosbeak
Starling
Crow
Drake
Condor
Canary
Rail
Bluejay
6
4
3
2
1
1/0
2/0
3/0
4/0
266.8
336.4
336.4
397.5
397.5
477.0
477.0
500.0
556.5
556.5
605.0
636.0
715.5
715.5
795.0
795.0
900.0
954.0
1113.0
6/1
6/1
6/1
6/1
6/1
6/1
6/1
6/1
6/1
26/7
26/7
30/7
26/7
30/7
26/7
30/7
30/7
26/7
30/7
54/7
26/7
26/7
54/7
26/7
54/7
54/7
45/7
45/7
0.198
0.250
0.281
0.316
0.355
0.398
0.447
0.502
0.563
0.642
0.721
0.741
0.783
0.806
0.858
0.883
0.904
0.927
0.953
0.953
0.990
1.051
1.035
1.108
1.093
1.162
1.165
1.259
5.03
6.35
7.14
8.03
9.02
10.11
11.35
12.75
14.30
16.31
18.31
18.82
19.89
20.47
21.79
22.43
22.96
23.55
24.21
24.21
25.15
26.70
26.29
28.14
27.76
29.51
29.59
31.98
36
58
73
91
115
145
183
231
291
366
162
525
545
619
654
743
781
765
869
779
872
986
918
1095
1021
1160
1076
1256
54
86
108
136
171
216
273
344
433
544
688
782
811
921
973
1106
1162
1138
1293
1159
1298
1467
1366
1629
1520
1726
1601
1869
1,190.3
1,860.8
2,304.0
2,857.5
3,555.0
4,387.5
5,310.0
6,682.5
8,430.8
11,317.5
14,107.5
17,325.0
16,312.5
20,317.5
19,507.5
23,850.0
24,750.0
22,725.0
27,900.0
23,400.0
25,200.0
28,350.0
26,100.0
31,500.0
28,125.0
32,337.0
25,875.0
30,987.0
WORD AWG or MCM AL/Steel Inch mm Lbs./mft kg/km lbs
manufacturing tolerances.Dimension and weights shown are nominal, unless otherwise indicated, and subject to
BARE ACSR CABLE
ALUMINUM CONDUCTOR STEEL REINFORCED
26.ACSR.01
DESCRIPTION
CONDUCTORS
Aluminum 1350 wire concentrically laid overa solid or stranded galvanized steel core.
Mechanical design requirements.
5) Good corrosion resistance.
3) High resistance to mechanical strength.
4) Wide variety of sizes available in long
lengths to suit both electrical and
fewer towers required.
strength to permit the longest possible
spans.
2) Minimum sag between supports with
1) Ideal combination of conductivity and
FEATURES
Code Word, quantity required in weight.
ACSR cable, size, Aluminum Association
HOW TO ORDER
Overhead transmission, subtransmission
overhead electrical cables. Messenger and
overhead lines. Messenger cables to support
APPLICATION
and distribution systems. Static wires to protect
power support conductor in catenary systems
for railroad electrification.
SPECIFICATIONS
ASTM B498 Galvanized steel class A
ASTM B232 Conductor overall
SPECIFICATIONS
ASTM B230 Aluminum wires
MAXIMUM CONDUCTOR TEMPERATURE
Normal Operation 75 °C
112
NOTES:
Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-94735-05