    QUICK START GUIDEQUICK START GUIDE

    Whats in the delivery?

    Getting started

    The first steps

    PC utility software

    Document no.: 4189340603A

    SW version 3.0X.X or later

    Generator Paralleling Controller, GPC-3Generator Protection Unit, GPU-3/GPU-3 Hydro

    Paralleling and Protection Unit, PPU-3

  • 8/2/2019 5CE23d01

    2/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 2 of 23

    Table of contents

    1. ABOUT THIS DOCUMENT .................................................................................................... 3GENERAL PURPOSE ...................................................................................................................... 3INTENDED USERS.......................................................................................................................... 3CONTENTS/OVERALL STRUCTURE.................................................................................................. 3

    2. WARNINGS AND LEGAL INFORMATION ........................................................................... 4LEGAL INFORMATION AND RESPONSIBILITY..................................................................................... 4ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4SAFETY ISSUES ............................................................................................................................ 4DEFINITIONS ................................................................................................................................ 4

    3. WHATS IN THE DELIVERY? ............................................................................................... 5STANDARD DELIVERY.................................................................................................................... 5OPTIONAL DELIVERY ..................................................................................................................... 6

    4. GETTING STARTED .............................................................................................................. 8CONNECTING THE DEVICES ........................................................................................................... 8BASIC WIRING FOR GPU-3 AND GPU-3HYDRO ........................................................................... 10BASIC WIRING FOR GPC-3 AND PPU-3 ....................................................................................... 12

    5. THE FIRST STEPS .............................................................................................................. 14BASIC AC VALUES ...................................................................................................................... 14

    6. PC UTILITY SOFTWARE .................................................................................................... 17INSTALLATION............................................................................................................................. 17GETTING CONNECTED WITH THE UNIT .......................................................................................... 18READ PARAMETERS FROM THE DEVICE ........................................................................................ 19BASIC CONFIGURATION OF A DEVICE USING THE UTILITY SOFTWARE.............................................. 20

    7. CONFIGURING THE SPEED GOVERNOR AND AVR OUTPUTS ..................................... 21

  • 8/2/2019 5CE23d01

    3/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 3 of 23

    1. About this documentGeneral purpose

    This document is the Quick Start Guide for the Multi-line 2 GPC (Generator ParallelingController), GPU (Generator Protection Unit) and PPU (Paralleling and Protection Unit). Thedocument mainly includes general product information, mounting instructions and wiringdescriptions.

    The general purpose of this Quick Start Guide is to help the user with the first steps of installingand using the unit.

    Intended users

    This Quick Start Guide is mainly intended for the panel builder in charge. On the basis of thisdocument, the panel builder designer will give the electrician the information he needs in order toget started to install the unit. For detailed electrical drawings, the Installation Instructions mustbe used.

    Contents/overall structure

    This document is divided into chapters, and in order to make the structure simple and easy touse, each chapter will begin from the top of a new page.

    Please make sure that you also read the Installation Instructions beforestarting to work with the Multi-line 2 controller and the gen-set to becontrolled. Failure to do this could result in human injury or damage to theequipment.

  • 8/2/2019 5CE23d01

    4/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 4 of 23

    2. Warnings and legal information

    This chapter includes important information about general legal issues relevant in the handlingof DEIF products. Furthermore, some overall safety precautions will be introduced andrecommended. Finally, the highlighted notes and warnings, which will be used throughout thisdocument, are presented.

    Legal information and responsibility

    DEIF takes no responsibility for installation or operation of the generator set. If there is any doubtabout how to install or operate the generator controlled by the unit, the company responsible forthe installation or the operation of the set must be contacted.

    Electrostatic discharge awareness

    Sufficient care must be taken to protect the terminals against static discharges during theinstallation. Once the unit is installed and connected, these precautions are no longer necessary.

    Safety issues

    Installing the unit implies work with dangerous currents and voltages. Therefore, the installationof the unit should only be carried out by authorised personnel who understand the risks involvedin the working with live electrical equipment.

    Definitions

    Throughout this document a number of notes with helpful user information will be presented. Toensure that these are noticed, they will be highlighted in order to separate them from the generaltext.

    Note symbol

    Warnings

    Be aware of the hazardous live currents and voltages. Do not touch any ACmeasurement inputs as this could lead to injury or death.

    The notes provide general information which will be helpful for the reader to

    bear in mind.

    The warnings indicate a potentially dangerous situation which could result indeath, personal injury or damaged equipment if certain guidelines are notfollowed.

    The units are not to be opened by unauthorised personnel. If opened anyway, thewarranty will be lost.

  • 8/2/2019 5CE23d01

    5/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 5 of 23

    3. Whats in the delivery?

    Standard delivery

    The main unit

    Standard display unit, DU-2

    Layout is option dependent.

    Display cable, 3m Installation Instructions

  • 8/2/2019 5CE23d01

    6/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 6 of 23

    Optional delivery

    Display cable with plugs, 6m (option J2)

    PC cable for option N programming - Ethernet cable crossed (option J4)

    Display cable with plugs, 1m (option J6)

    PC cable for utility software (option J7)

  • 8/2/2019 5CE23d01

    7/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 7 of 23

    Additional standard display, DU-2 (option X2)

    Display unit, DU-2 DC/DC converter 2 x CANbus cable 3m

    Layout is option dependent.

    Additional operator panel, AOP-1 (option X3)

    AOP-1 0.5m cable

    Additional operator panel, AOP-2 (option X4)

    AOP-2 DC/DC converter 2 x CANbus cable 3m

  • 8/2/2019 5CE23d01

    8/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 8 of 23

    4. Getting started

    Connecting the devices

    Connecting the display with the main unit

    Connect the SUB-D display cable to the main unit and the display unit as shown in the belowpicture.

    Connecting the power supply to the main unit

    Terminal 1: +24V DC

    Terminal 2: 0V DC

    787776757473 96 979594929190 938988878586838482818079

    7271697068676566626359 60 6 15856575553 54 645251504947464443 45 4841403837 39 42

    Service port DisplayPMS CAN

    Engine CAN

    Power

    Self check ok

    Alarm inhibit

    Option M4

    Terminal 98: +24V DC

    Terminal 99: 0V DC

  • 8/2/2019 5CE23d01

    9/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 9 of 23

    Connecting the additional operator panel, AOP-1 (optional)

    Connecting the additional operator panel, AOP-2 (optional)

    The CAN cable for the CANbus communication between the display unit of main unit no.1 and theAOP-2 has to be connected to the CAN port (CAN 2) of the display unit (DU-2) and the CAN port(CAN 1) of the AOP-2 as shown in the below drawing.

    The AOP-2 can be placed up to 200m from the main display. The AOP-2 requires a separatepower supply unit, while the display receives the power supply through the display cable from themain unit.

    For further information about the installation of multiple displays and AOP-2s,please refer to the document Description of Option X.

    AOP-1 cable0.5m

    Display unit,DU-2

    AOP-1

  • 8/2/2019 5CE23d01

    10/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 10 of 23

    Basic wiring for GPU-3 and GPU-3 Hydro

    AC wiring

  • 8/2/2019 5CE23d01

    11/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 11 of 23

    DC wiring

  • 8/2/2019 5CE23d01

    12/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 12 of 23

    Basic wiring for GPC-3 and PPU-3

    AC wiring

    For further information, please refer to the document Installation Instructions.

  • 8/2/2019 5CE23d01

    13/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 13 of 23

    DC wiring

  • 8/2/2019 5CE23d01

    14/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 14 of 23

    5. The first steps

    Basic AC values

    This chapter guides you through the most essential parameters which have to be adjustedbefore you can start using the unit.

    The setpoints can either be adjusted from the display unit or by using the DEIF utility software.The following examples will show how to adjust the parameters from the display unit.

    All settings are reached by placing the cursor under SETUP (in the main page) and pressingENTER.

    Place the cursor under SYST and press ENTER.

  • 8/2/2019 5CE23d01

    15/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 15 of 23

    Place the cursor under GEN and press ENTER.

    Place the cursor under the setting you require and press ENTER.

  • 8/2/2019 5CE23d01

    16/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 16 of 23

    Generator nominal settings 1

    No. Setting Min.

    Max.

    Factory

    setting

    Notes Ref. Description

    6000 Nominal settings 1

    6001 Nom. settings 1 Frequency 48.0Hz62.0Hz

    50.0Hz DesignersReference

    Handbook

    The selection ofnominal settings to be

    used is set in 6006. A

    binary input or selection

    in M-logic can also be

    used.

    The range of nom.

    voltage and nom.

    power depends on the

    selected range in 9030

    Scaling.

    6002 Nom. settings 1 Power10kW

    20000kW480kW

    6003 Nom. settings 1 Current0A

    9000A867A

    6004 Nom. settings 1 Voltage100V

    25000V400V

    6005 Nom. settings 1 RPM100 RPM

    4000 RPM1500 RPM

    6006 Nom. settings 1 Set1

    41

    To adjust the transformer settings, use the or push-button to get to the transformerpage.

    VT and CT settings

    No. Setting Min.

    Max.

    Factory

    setting

    Notes Ref. Description

    6040 G transformer

    6041 G transformer U primary100V

    25000V400V

    Designers

    Reference

    Handbook

    If no voltage

    transformer is present,

    the primary and

    secondary side values

    are set to generatornominal value.

    6042 G transformer U secondary100V

    690V

    400V

    6043 G transformer I primary5A

    9000A1000A

    6044 G transformer I secondary1A

    5A5A

    6050 Busbar settings

    6051 BB settings U primary100V

    25000V400V

    Designers

    Reference

    Handbook

    If no voltage

    transformer is present,

    the primary and

    secondary side values

    are set to generator

    nominal value.

    6052 BB settings U secondary100V

    690V400V

    6053 BB settings U BB nom.100V

    25000V400V

  • 8/2/2019 5CE23d01

    17/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 17 of 23

    6. PC utility software

    Installation

    1. Go to www.deif.com2. Select Download centre3. Select Software download4. Select Multi-line 2 utility software V.3.X in the dropdown menu5. Fill in your e-mail address and click Submit.

    Subsequently you will receive an e-mail containing a link. Click the link and follow theinstructions.

    The USW is now installed on your computer.

    Installation of USB drivers

    On Windows Vista machines, the USB drivers are installed automatically.

    This is the procedure on Windows XP machines:

    When you connect the DEIF product, Windows XP will launch two Hardware Wizards. Twodrivers are installed, so please let Windows execute both Found new Hardware Wizard.

    We recommend letting the Hardware Wizard install the software automatically by choosing theRecommended option. If the Advanced option is chosen, the needed files are available fromthe USW3 installation folder (default: C:\Program Files\DEIF\USW3\) in the USB driverfiles/source PreInstaller folder.

    Please select Continue Anyway if a Hardware Installation warning (see figure below) appearsduring the installation.

  • 8/2/2019 5CE23d01

    18/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 18 of 23

    Getting connected with the unit

    Connect the service port to the USB on the computer (option J7 or option J3).

    Click the Utility Software 3 icon on the desktop or in the Windows Start menu.

    Desktop icon: Quick launch and Start menu icon:

    Utility Software 3.lnk

    The below window appears.

    Open Windows devicemanager.

    Check the COM portused for communi-cation, and make surethe settings corres-

    pond to the applicationsettings.

    Open the applicationsettings by clicking thisicon.

    Click the Connect icon.

  • 8/2/2019 5CE23d01

    19/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 19 of 23

    Read parameters from the device

    After retrieving all the parameters, the device is ready to be configured.

    Open the Parameterslist.

    Click the Readparametersicon.

  • 8/2/2019 5CE23d01

    20/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 20 of 23

    Basic configuration of a device using the utility software

    When the parameters have been uploaded, the below options will be available.

    The parameters can be configured as follows.

    Click a parameter, and the below dialogue box will appear.

    The parameter setpoint has now been changed and downloaded to the device.

    For further information, please refer to the document General Guidelines forCommissioning.

    Click this or use thebar to adjust thesetpoint, and thenclick Write and OK.

    Click the Gentab.

  • 8/2/2019 5CE23d01

    21/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 21 of 23

    7. Configuring the speed governor and AVR outputs

    Dependent on the hardware configuration, relays or analogue outputs can be used for speedgovernor and AVR control.

    The settings used for this are the following:

    No. Setting Min.

    Max.

    Factory

    setting

    Notes Ref. Description

    2600 Relay control

    2601 Relay control GOV ON time10 ms

    6500 ms500 ms

    Designers

    Reference

    Handbook

    GPU:

    Option G2

    This menu is only

    available if Relay

    is selected in

    menu 2781.

    2602 Relay control GOV periodtime

    50 ms32500 ms

    2500 ms Normally used:Relay 65 for

    increase and relay

    67 for decrease.2603 Relay control Increase relayNot used

    Option dep.Relay 65

    2604 Relay control Decrease relayNot used

    Option dep.Relay 67

    2720 Relay control (AVR)

    2721 Relay control AVR ON time10 ms

    3000 ms100 ms

    Option:

    AVR control

    (D1)

    Relay outputs for

    voltage/VAr/power

    factor control.

    This menu is only

    available if Relay

    is selected in

    menu 2782.

    Normally used:

    Relay 69 for

    increase and relay

    71 for decrease.

    2722 Relay control AVR per time50 ms

    1500 ms500 ms

    2723 Relay control U increaseNot used

    Option dep.Relay 69

    2724 Relay control U decreaseNot used

    Option dep.Relay 71

    2780 Regulator output

    2781 Reg. output GOVRelay

    EICRelay

    Designers

    Reference

    Handbook

    GPU:

    Option G2

    Selection of the

    speed output:

    Relay, analogue

    or engine

    interface

    communication.

    Analogue and EIC

    are optiondependent.

    2782 Reg. output AVRRelay

    AnalogueRelay

    Option:

    AVR control

    (D1)

    Generator voltage

    control based on

    relay or analogue

    output signals.

    Analogue

    selection is only

    available if option

    E1, E2, EF2, EF4

    or F2 is present.

  • 8/2/2019 5CE23d01

    22/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 22 of 23

    No. Setting Min.

    Max.

    Factory setting Notes Ref. Description

    5980 Governor output

    5981 Governor output Output A

    Disabled

    AO66AO71 Disabled

    Option E

    and F

    Normally used:

    Analogue output66

    5990 AVR output

    5991 AVR output Output A

    Disabled

    AO66

    AO71

    Disabled

    Option D Normally used:

    Analogue output

    71

    AVR control requires option D1.

    Analogue outputs require option E1, E2, EF2, EF4 or EF5.

    For further information, please refer to the document General Guidelines forCommissioning.

  • 8/2/2019 5CE23d01

    23/23

    GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Quick Start Guide

    DEIF A/S Page 23 of 23

    For further information, please check the following documents: