Electronics Manual
CoDeSys Controller
TypeCPX−CEC
CPX−CEC−C1/−M1
C PX Te r mina l
Manual5 69 1 22en 1004a[753 482]
-
8/9/2019 569122g1 Manual Codesys
2/87
-
8/9/2019 569122g1 Manual Codesys
3/87
Contents and general instructions
IF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 100 4a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Designation P.B E−CPX−CEC−EN. . . . . . . . . . . . . . . . . . . . . . . .
Orderno. 56 9 122. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
© (Festo AG & Co. KG, D73726 Esslingen, Germany, 2010)Internet:http://www.festo.comE − ma i l: s er v i c e_ i nt e rn a ti o na l @f e st o. c om
The reproduction, distribution and utilisation of this docum e nt a s w e ll a s t h e c om m un i ca t io n o f i t s c o nt e nt s t o o t he r swithout explicit authorisation is prohibited. Offenders will
be h e ld liable f o r th e p a ym e n t o f da m a ge s. A ll r igh t s r e se r v e d in t h e e v e nt o f t h e gr a n t o f a p a t en t , ut ilit y m o du leor design.
-
8/9/2019 569122g1 Manual Codesys
4/87
-
8/9/2019 569122g1 Manual Codesys
5/87
Contents and general instructions
IIIF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Contents
Designated use V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety instructions VI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Ta r ge t g r o up V I I I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ser vice VI I I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Impor tant user instructions IX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on the use of this manual XI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Sys tem s ummar y 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .1 The CoDeSys controller CPX−CE C/CPX−CEC−... 1−3. . . . . . . . . . . . . . . . . . . . . . . .
1 .2 Suppor ted motor controllers 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .3 The operating modes of the CoDeSys controllers 1−6. . . . . . . . . . . . . . . . . . . . .
1 .4 The CoDeSys provided by Festo programming environment 1−9. . . . . . . . . . . . .
1.4.1 P rogramming languages 1 −1 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2 L ibraries 1 −1 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4.3 P arameterisation 1 −1 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .5 Meaning of the LE D displays 1 −1 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.1 CP X−specific LE Ds 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Ins tallation 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .1 General installation instructions 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .2 Dismantling and fitting 2 −4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Dismantling 2 −4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2.2 Fitting 2−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .3 Connection and display elements 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .4 Setting the switches of the CoDeSys controller 2−7. . . . . . . . . . . . . . . . . . . . . . .
2.4.1 RU N/STOP rotary switch 2−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.2 DI L switches 2−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .5 Ethernet interface 2 −1 0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.1 E thernet cable 2 −1 0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .6 Communication interfaces 2 −1 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6.1 C A Nopen interface (CPX−CEC−C1/−M1) 2 −1 2. . . . . . . . . . . . . . . . . . . . . . .
2.6.2 RS2 32 interface (CPX−CEC) 2 −1 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
6/87
Contents and general instructions
IV F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
2.7 Connection of an operator unit type F E D 2 −18. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8 Connection of a handheld type CPX−MM I 2 −19. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.9 Complying with protection class I P65 /I P 67 2 −20. . . . . . . . . . . . . . . . . . . . . . . . . .
3. Commis sioning 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 P rereq uisites for commissioning 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 First steps 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Configuration of the CPX modules 3−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4 Configuration of the C A Nopen slaves 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 P arameterisation of the CPX terminal 3−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 .5.1 P arameterisation via control configuration in CoDeSys 3 −10. . . . . . . . .
3 .5.2 P arameterisation via t he handheld type CPX−MM I 3 −13. . . . . . . . . . . . .
3.6 Forcing 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Diagnosis 4−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 G eneral error response of the CoDeSys controller 4−3. . . . . . . . . . . . . . . . . . . . .4.2 Diagnosis via controller LE Ds 4−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Fur ther diagnostic options 4−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Technical append ix A−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical data A−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Index B−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
7/87
Contents and general instructions
VF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
D e si g nate d u se
Th e t y p e C P X − C E C/ C P X −C E C − . .. CoDeSys controller documented in this manual is intended exclusively for use in FestoCPX terminals for installation in a machine or an automationcontrol system.
I n c o m bin at io n w it h a C P X t e r m in a l, t h e C P X − C EC / C P X −C E C − .. .i s u se d fo r
controlling pneumatic and electric actuators (valves, outp u t m o du les a n d m o t o r c o n t r o lle r s v ia C A N o p e n )
interrogating electric sensor signals through the inputmodules
communication via Ethernet.
Th e C P X t e r min a l w it h t he C P X − C EC / C P X −C E C − .. . m a y o n ly beu se d a s f o llo ws:
as designated in industrial applications
without any modifications by the user. Only the conversions or modifications described in the documentationsupplied with the product are permitted
in faultless technical condition
only in combination with approved components
(e. g.valves, drive/displacement encoder combinations).
The limit values specified for pressures, temperatures, electric a l da t a , t o rq u e s e t c . sh ou ld be o bse r v e d.
P le a se c om p ly w it h th e r e g ula t io ns o f t h e w o r k er s’ c o m pensation insurance association, the German Technical Cont r o l B o ar d ( TÜ V ) a n d t he e le c t ric a l r e q uir e m en t s o f t h e V D E o rthe corresponding national and local safety regulations.
-
8/9/2019 569122g1 Manual Codesys
8/87
Contents and general instructions
VI F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Safety instructions
Protection against dangerous movements
Warning H ig h a c c e ler a t ion f o r ce s a t t h e c o n n ec t e d ac t u a to r s! U nde sired movements can cause collisions and severe injuries.
Dangerous movements can occur through faulty controllin g o f c o n n ec t e d a c t u at o r s, e . g . v ia :
unsafe or faulty circuitry or cabling,
faulty operation of the components,
errors in the measured value and signal generators,
defects or non−EMC−compliant components,
errors in the higher−order control system,
programming errors in user programs and projects.
Simply switching off the compressed air supply or loadv o lt ag e is n o t su ita ble f o r lo c kin g p r o c edu r e s. I n t h e e v e n to f a f a u lt, t h is co u ld lea d t o un in t en t io n al m o ve m e n t o f t h edrive.
· Before doing mounting, installation and service work,bring the system into a safe condition (e.g. by bringingthe drive into a safe position and deactivating thecontroller).Always make sure that the compressed air supply andpower supply are switched off and locked when workingin the machine area.
· Make sure that no persons are in the operating range of the drives or any other connected actuators.
· Do not switch on the compressed air supply until thesystem is correctly installed and parameterised.
-
8/9/2019 569122g1 Manual Codesys
9/87
Contents and general instructions
VIIF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
· Brakes controlled by the drive controller are alone notsuitable to ensure personal protection!Secure vertical axes from falling or sliding down whenthe compressed air and load voltages are switched off,a s f o ll o ws :
mechanical locking of the vertical axis, external braking/safety catch/clamping device or sufficient counterbalance of the axis.
· Additional measures are required for use in safety−related applications; in Europe, for example, the standardslist e d un de r th e E C M a c h ine r y D ir e c t iv e m u st be o bserved. Without additional measures in accordance withstatutory minimum requirements, the product is notsuitable for use in safety−related sections of controlsystems.
Protection from pressurised tubing
CautionD a n g er o f in j u ry t h r o u gh in a p p r op r ia te h a n dlin g o f p r e ssurised tubing!
U n de sir e d m o ve m e n ts o f t h e c o n n ec t e d a c tu a t o rs a n duncontrolled movements of loose tubing can cause injuryto human beings or damage to property.
· Do not connect, disconnect or open pressurised tubing.
· The tubing must always be vented before removal(release compressed air).
· Use suitable protective equipment (e.g. safety goggles,safety shoes, etc.).
-
8/9/2019 569122g1 Manual Codesys
10/87
Contents and general instructions
V I I I F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Target group
Th is m a n u al is in t e n de d e x c lu siv e ly f o r t e c hn ic ia ns t r a in e d incontrol and automation technology, who have experience ininstalling, commissioning, programming and diagnosingpositioning systems.
S e r v i c e
Please consult your local Festo Service if you have any technical problems.
-
8/9/2019 569122g1 Manual Codesys
11/87
Contents and general instructions
IXF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Important user instructions
Danger categories
Th is m a n u al c o n t a in s in str u c t io n s o n t h e p o ssible da n g e r sw h ic h ca n o c cu r if t h e p r o duc t is n o t use d c o rr e c t ly. Th eseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a
pictogram.A distinction is made between the following danger warnings:
Warning ... means that failure to observe this instruction may resultin serious personal injury or property damage.
Caution... means that failure to observe this instruction may resultin personal injury or property damage.
Note... means that failure to observe this instruction may resultin damage to property.
The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitivecomponents:
Electrostatically sensitive devices: Improper handling canresult in damage to components.
-
8/9/2019 569122g1 Manual Codesys
12/87
Contents and general instructions
X F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Identifying special information
Th e f o llow in g p ic to g r a ms m a r k p a ssa g e s in t h e t e x t w h ichcontain special information.
Pictograms
Information:Recommendations, tips and cross−references to other information sources.
Accessories:Information on necessary or useful accessories for the Festoproduct.
Environment:I n f o rm a t ion o n t h e e n v iro n m e nt a lly f r ien dly u se o f F e st o
products.
Text markings
· The bullet indicates activities which may be carried out inany order.
1 . N u me r al s d en o te a c ti v it i es w h ic h m us t b e c a rr i ed o u t i nthe numerical order specified.
Hyphens designate general lists.
Brackets designate menu entries.Example: [Scan module configuration].
Arrow brackets mark placeholders for designations. Example:"Status of ".
Quotation marks designate names of windows, dialogues andbuttons. Example: "Control configuration".
-
8/9/2019 569122g1 Manual Codesys
13/87
-
8/9/2019 569122g1 Manual Codesys
14/87
Contents and general instructions
XII F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
The following product−specific terms and abbreviations areused in this manual:
Term/abbreviation Meaning
0 signal 0 V applied at inpu t, or output supplies 0 V
1 signal 24 V applied at input, or output supplies 24 V
0 x0 1 ( A0h ) Hexadecimal numbers are marked by a prefixed "0x" or by a subscript"h"
C A Nopen Fieldbus p rotocol b ased on C A N, which i s s tandardised a s a Europeanstandard
C o D eS y s p r ov i d e d b y F e st o( = C oD e Sy s p b F)
C o D eS y s = C o n tr o l le r D e v e l o pm e n t S y st e mC o D eS y s p r ov i d e d b y F e s t o p e rm i t s c o n f ig u r a ti o n , c o m mi s s i on i n g a n dp r o g ra m m i ng o f v a ri o u s c o m p on e n t s a n d d e v i ce s b y F e s t o. I n t h i sd o c u me n t at i o n, c a l le d " C o D e Sy s p b F " f o r s h o r t
CPX t erminal Complete s ystem consisting o f C PX m odules w ith o r without
pneumatics
CPX m odules Common term for the v arious modules which c an be i ntegrated in a CPXterminal
D H CP ( D yn a mi c H o stConfiguration Protocol)
D y na m ic p r ot o co l f o r a u to m at i c a s si g nm e nt o f I P a d dr e ss e s
DI L switch Du al−in−line s witches c onsist o f s everal switch e lements w ith w hichs e tt i ng s c a n be m a de
I/O modules Collective term for the CPX modules which prov ide d igital inputs a nd
outputs
I/Os Digital inputs and outputs
EasyI P Protocol f or f ast e xchange o f o perands b etween F esto controllers
EDS f ile Electronic d ata s heet, which d escribes t he f unction a nd characteristicso f a C A N o pe n d ev i ce i n s ta n da r di s ed f o rm ( e .g . n u mb e r of I / Os ,n u m b er o f d i a gn o s i s b y t e s , et c . ) .
Ethernet Phy sical p rotocol a nd network f or connecting variou s d evices
Fieldbus n ode Provides the connection to specific f ieldbuses. Transmits controls i g n al s t o t h e c o n ne c t e d m o d ul e s a n d m on i t or s t h e ir a b i li t y t o f u n c ti o n
-
8/9/2019 569122g1 Manual Codesys
15/87
Contents and general instructions
X I I IF e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Term/abbreviation Meaning
F H P P ( F e st o H a n d li n g a n dPositioningProfile)
U n i f or m f i el d b u s d a t a p r o f il e f o r p os i t i on i n g c o n tr o l le r s f r o m F e s t o
F TP ( Fi le Tr an sf er P ro to co l) P ro to co l f or f il e t ra ns fe r v ia TC P/ IP
H an dh el d t y pe C PX −M MI H an dh el d t er mi na l f or c om mi ss io ni ng a nd s er v ic e p ur po se s
H T T P ( H y p er Te x t Tr a n sf e rProtocol)
P r ot o co l f o r da t a t r an s fe r v i a T CP / I P
I P (Internet Protocol) Protocol for addressing and delivering data
Login/Logout Programming s ystem is l ogged out/logged o ut
M AC a d dr e ss ( M ed i aA c c e s s C o n tr o l a d d r e s s )
F i x ed a s si g n ed a d d r es s f o r E t h e rn e t d e v i ce
Modbus/TCP Communication s tandard v ia T CP/I P in automation t echnology
N ode I D Provides u niqu e i dentif ication o f a b us s lave o n the C A Nopen fieldbus
OLE Object Linking and E mbedding
OPC OLE f or Process C ontrol; s tandardised s oftware interface that p ermitsa c ce s s t o p ro c es s d a ta
PLC/I PC Programmable logic controller/industrial PC
Pneu matic interface Interface between the modular electric peripherals and the pneumatics
SoftMotion Motion f unctionality i ntegrated i n the C oDeSys p bF p rogramming a ndr u n − ti m e s y s t em . T h e f o l l ow i n g m o t io n c o n tr o l m o d el s a r e o f f e re d a smodules:
Single/multi−axis positioning movements with PLCopen Motionmodules
2.5D CNC control
TCP/I P Combination o f t he p rotocols TCP a nd I P, the m ost−widely u sed protocoli n c o m m un i c at i o n v i a E t h e rn e t
T F T P ( Tr i v i al F i l e Tr a n s f erProtocol)
P r ot o co l f o r f il e t r an s fe r v i a T CP / I P
TSP
( Ta r g e t S u p p or t P a c k ag e )
A t a rg e t s u p p or t p a c k ag e c o m bi n e s a l l c o n f ig u r a ti o n a n d e x p a ns i o n
f i le s t h at a r e n e ed e d t o m a ke a s p ec i fi c c o nt r ol l er ( t ar g et ) u s ab l e f o rt h e p r o gr a m m in g e n v i ro n m en t ( C o De Sy s p r ov i d e d b y F e s t o)
-
8/9/2019 569122g1 Manual Codesys
16/87
Contents and general instructions
XIV F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Term/abbreviation Meaning
U D P ( U s e r D a t ag r a mProtocol)
A m i ni m al , c o nn e ct i on l es s n e tw o rk p r ot o co l t h at h a s a l o we r p r o t oc o lo ve r he a d c o mp a re d t o T CP. T hi s h a s t h e a d va n ta g e o f a f a st e re x ch a ng e o f d a ta . D u e t o t h e l a ck o f a r e pl y, t h e c o rr e ct t r an s mi s si o nm u st b e e n su r ed , e . g. b y m e an s o f a u s er p r og r am
User data Telegram d ata w ithout p rotocol f rame d ata. T he l ength o f t he u ser datai s d e fi n ed i n t h e c o nf i gu r at i on o f t h e f i el d bu s s l av e
www World Wide Web
Ta b. 0/ 2 : P ro du ct −s pe ci fi c t er ms an d a bb re vi at io ns
-
8/9/2019 569122g1 Manual Codesys
17/87
System summary
1−1F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Chapter 1
-
8/9/2019 569122g1 Manual Codesys
18/87
1 . S y ste m su m m ar y
1−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Contents
1. System summar y 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 The CoDeSys controller CPX−CEC/CPX−CEC−... 1−3. . . . . . . . . . . . . . . . . . . . . . . .
1.2 S uppor ted motor controllers 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 The operating modes of the CoDeSys controllers 1−6. . . . . . . . . . . . . . . . . . . . .
1.4 The CoDeSys provided by Festo programming e nvironment 1−9. . . . . . . . . . . . .
1 .4.1 P rogramming languages 1 −11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .4.2 L ibraries 1 −12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .4.3 P arameterisation 1 −12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 M eaning of the LE D displays 1 −13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 .5.1 CPX−specific LE Ds 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
19/87
-
8/9/2019 569122g1 Manual Codesys
20/87
1 . S y ste m su m m ar y
1−4 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
CPX−CEC−C1 offers...
A CANopen interface to which up to 31 CANopen slavesc a n b e c o nn e ct e d
CPX−CEC−M1 offers...
The CoDeSys software package SoftMotion forcoordinated multi−axis movements.
CPX−CEC−M1 can alternatively also be operated as aCANopen master. The SoftMotion functions are then notavailable.
CPX−CEC offers...
An RS232 interface (Sub−D, 9−pin) for connecting a typeF E D operator unit or for operating external devices.With external devices, data communication must beprogrammed by the user.
-
8/9/2019 569122g1 Manual Codesys
21/87
1 . S y ste m su m m ar y
1−5F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1.2 Su ppor ted mot or cont rollers
The CoDeSys controllers CPX−CEC−C1/−M1 as CANopenmasters support all motor controllers from Festo.
CPX−CEC−M1 with SoftMotion functions supports thefollowing motor controllers:
Motor controller Required firmware1 fr om Ve r s i on . . .
CMM P−A S 3.5.1501.2.1
CMMS−A S 1.3.0.1.11
CMMS−ST 1.3.0.1.7( t he v e rs i on s 1 . 3. 0 .1 . 10 a n d 1 . 3. 0 .1 . 12 a r en o t s u pp o r te d )
SFC−L AC 1.0.5
SFC−L ACI 1.0CMM D 1.4
1 ) S e e r at i ng p l at e f o r F C T p l ug − in o f t h e m o to r c o nt r ol l er
Ta b. 1/ 2 : S up po r te d mo to r c on tr ol le rs w it h CP X −C EC −M 1(date: June 2010)
C P X − CE C − C 1/ − M 1 su pp o r t u p t o 3 1 a x es. W e r e c om m e n d
o p e ra t in g th e C P X − CE C − M 1 w ith a m a x im um o f e ig h t ax e s.
-
8/9/2019 569122g1 Manual Codesys
22/87
1 . S y ste m su m m ar y
1−6 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1 .3 T he o pe ra ti ng mo de s o f t he Co De Sy s c on tro ll er
The CoDeSys controllers can be operated in various operatingm o de s, dep e n ding o n t h e de m a nd:
Stand Alone
Remote Controller Ethernet
Remote Controller Fieldbus (fieldbus node required)
The individual operating modes are briefly presented in thefollowing:
Stand Alone operating mode
1 2
1 CPX−CEC/CPX−CEC−...
2 CPX terminal controlled by the CPX−CEC/CPX−CEC−...
F ig . 1 /1 : S ta nd A lo ne op er at in g mo de
-
8/9/2019 569122g1 Manual Codesys
23/87
1 . S y ste m su m m ar y
1−7F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Remote Controller Ethernet operating mode
Ethernet
1 2
1 CPX−CEC/CPX−CEC−... connected to an Ethernet network
for communication
2 CPX terminal controlled by the CPX−CEC/CPX−CEC−...
F i g. 1 /2 : R em o te C o nt ro l le r E th e rn e t o p er at i ng m od e
-
8/9/2019 569122g1 Manual Codesys
24/87
1 . S y ste m su m m ar y
1−8 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Remote Controller Fieldbus operating mode
21 3
1 CPX−CEC/CPX−CEC−... connected to the fieldbus forcommunication over the fieldbus node
2 C P X f ie ldbus n o de , h e r e: C P X − F B1 3
3 CPX terminal controlled by the CPX−CEC/CPX−CEC−...
F i g. 1 /3 : R e mo t e Co n tr ol l er F i el d b us o p er at i ng m od e(fieldbus node required)
-
8/9/2019 569122g1 Manual Codesys
25/87
1 . S y ste m su m m ar y
1−9F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1 .4 T he C oD eS ys pr ov id ed by Fe st o p ro gr am mi n g e nv i ro nm en t
Use CoDeSys provided by Festo to commission and programthe CoDeSys controller. CoDeSys provided by Festo offers aconvenient user interface with the following functions:
Configuration and parameterisation of the CPX−CEC/CPX−CEC−... with control configuration
Programming as per IEC 61131−3 Integrated module libraries
Library administrator to integrate additional libraries
Simulation mode, permits testing of projects on the PC,without PLC
Visualisation with the integrated visualisation editor
Documentation with the integrated projectdocumentation
Debugging functions: testing program sequence,observing and changing variables, error search
CPX−CEC−M1: SoftMotion programming editors areintegrated.
To be a ble t o u se a c o n t ro lle r ( t a rg e t ) u n de r C o D e Sy sp r ov ide d by F e sto , a so − c alle d Ta r g et S u p p or t P a c k a g e isneeded for the corresponding target. This permits access tot h e syst e m f un c t ion s o f t h e t a r ge t a n d c on t a inscorresponding information in the form of online help. TheTarget Support Package makes CoDeSys functions usable fort h e r e sp e c t iv e de v ic e o r lim it s t h e m , if n e c e ssa r y.
W it h t h e Ta r g et S u p po r t P ac k a g e, C o D e Sy s c a n su p p or t a llthese characteristics and functions of these devices.And so CoDeSys provided by Festo contains many functions
that are available only on certain devices.
-
8/9/2019 569122g1 Manual Codesys
26/87
1 . S y ste m su m m ar y
1−10 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
CoDeSys provided by Festo is supplied with the TargetSupport Package for the CoDeSys controller. It also containsadditional functions that are specially adapted to theCoDeSys controller.
Information about which functions of CoDeSys provided byFesto are supported by the CoDeSys controller and whicha ddit io n a l fu n c t io n s a re a v aila ble c a n be f o u n d in t he o n lin ehelp (key word"Functional Overview").
-
8/9/2019 569122g1 Manual Codesys
27/87
-
8/9/2019 569122g1 Manual Codesys
28/87
1 . S y ste m su m m ar y
1−12 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1.4.2 Libraries
To make programming easier, CoDeSys provided by Festomakes it possible to organise into libraries objects that areu sa ble inde p e nde n t ly o f p r oj e c t s, su c h a s m o du les, de c la r ations and visualisations. A library administrator, with whichyou can integrate and view libraries, is available for thispurpose.
Detailed descriptions on the libraries and programming canbe f o u nd in t h e o n line h e lp.
1.4.3 Parame terisation
I n f o rm a t ion o n pa r am e t e risa t ion o f t h e en t ire sy st em v ia t h e
CoDeSys controller can be found in the online help.
-
8/9/2019 569122g1 Manual Codesys
29/87
1 . S y ste m su m m ar y
1−13F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1.5 Mean in g of th e LEDdi spla ys
The LEDs on the cover indicate the operating status of thedevice and are arranged in two groups.
1 Controller LEDs(see section 4.2)
RUNSTOP
E R R O RTP
2 CPX−specific LEDsPSPLSFM
1 2
F ig . 1 /4 : L ED di s pl ay s o f t he d ev ic e ( he re C PX −C EC −C 1/ −M 1 as a n e xa mp le )
-
8/9/2019 569122g1 Manual Codesys
30/87
1 . S y ste m su m m ar y
1−14 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1.5.1 CPX −specific LE Ds
Th e disp la y s o f t h e C P X − spe c if ic L E D s a r e de sc ribe d in t h efollowing. Information on the controller LEDs can be found insection 4.2.
P S ( P ow e r Sy s te m ) s u ppl y t o t h e el e c t ro n i c s
LED (green) Seq uence Meaning Err or treatment
L E D l ig h ts u p
ON
OFF
N o e rr o r. O p e r at i n g v o l ta g e / se n s or s u p p ly a p p l ie d
L E D f l as h es
ON
OFF
Operating voltage/sensors u p p l y o u t s id e t h e t o l er a n ce r a ng e
E l i m in a t e u n d e r vo l t ag e
ON
OFFI n t e rn a l f u se f o r t h eoperating voltage/sensor
s u p p l y ha s r e s p on d e d
1 . E l im i na t e s h or t c i rc u it / ov e rl o ad o nm od u le s i de
2 . D ep e nd s o n t h e p a ra m et e ri s at i ono f t h e m od u le ( m od u le p a ra m et e r) :· T h e s e n s or s u p pl y v ol t a ge w i l l
b e s w it c he d o n ag a in automatically w h en t h e s h or t c i rc u it h a sbeen eliminated (default)
· P o we r O F F / O N i s n e c e ss a r y
L ED i s o ff
ON
OFFT h e o p e ra t i ng v o l ta g e /s e n s or s u p p ly i s n o tapplied
C h e ck th e o p e ra t i ng v o lt a g ec o nn e ct i on o f t h e e l ec t ro n ic s
Tab. 1 /4: Displays of PS LE D
-
8/9/2019 569122g1 Manual Codesys
31/87
1 . S y ste m su m m ar y
1−15F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
P L ( P ow e r Lo a d) l o a d s u ppl y ( o u tpu t s / va l v es )
LED (green) Sequence Meaning Er ror treatment
L E D l ig h ts u p
ON
OFF
No error. Load voltageapplied
LED flashes
ON
OFFL oa d v ol ta ge a t t he s ys te ms u p p ly o r a d d it i o na l s u p p l yo u ts i de t h e t o le ra n ce r a ng e
E l i m in a t e u n d e r vo l t ag e
Tab. 1/5 : Displays of PL LE D
SF ( Sy s t e m Fa i l ur e ) Sy s te m e r ro r
LED (red) Sequence 1 ) Meaning Er ror treatment
L ED i s o ff
ON
OFFNo error
LED flashes
ON
OFFSimple error/information( e r ro r cl a s s 1 )
S e e d e sc r ip t io n o f e r ro r n u mb e rs i nt h e C P X s y st e m ma n ua l
LED flashes
ON
OFF
E r r or ( e r r or c l a s s 2 )
LED flashes
ON
OFFS e r io u s e r r or( e r ro r cl a s s 3 )
1 ) T he s y st e m e r ro r LE D f la s he s d e pe n di n g o n th e c l as s o f e r ro r wh ic h h as o c cu r re d .E rr or c la ss 1 ( mi no r e rr or ): f la sh o nc e, p au seError class 2 (error): f lash twice, pauseE rr or c la ss 3 ( se ri ou s e rr or ): f la sh t hr ee t im es , p au se
Tab. 1/6 : Displays of SF LE D
-
8/9/2019 569122g1 Manual Codesys
32/87
1 . S y ste m su m m ar y
1−16 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
M ( M o d i fy ) M o d i fy / fo rc e a c t i ve
LED (yellow) Seq uence Meaning Err or treatment
L ED i s o ff
ON
OFFForce is not active
LED flashes
ON
OFFForce is active The Force f unction is e nabled
( s ee C P X s y st e m m a nu a l, s y st e m
p a r am e t er F o rc e m o d e ;f u nc t io n n o. 4 4 02 ) .
Tab. 1 /7: Displays of M LE D
Information on the controller LEDs can be found insection 4.2.
-
8/9/2019 569122g1 Manual Codesys
33/87
Installation
2−1F e st o P. B E− C PX − CE C −E N e n 1 0 04 a
Chapter 2
-
8/9/2019 569122g1 Manual Codesys
34/87
2 . I n st a ll a ti o n
2−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Contents
2. Installation 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 G eneral installation instructions 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Dismantling and fitting 2 −4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .2.1 Dismantling 2 −4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .2.2 Fitting 2−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Connection and display elements 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 S etting the switches of the CoDeSys controller 2−7. . . . . . . . . . . . . . . . . . . . . . .
2 .4.1 RU N/STOP rotary switch 2−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .4.2 DI L sw itches 2−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 E thernet interface 2 −10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .5.1 E thernet cable 2 −10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Communic ation interfaces 2 −12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 .6.1 C A Nopen interface (CPX−CE C−C1/−M1) 2 −12. . . . . . . . . . . . . . . . . . . . . . .
2 .6.2 RS2 32 interface ( CPX−CEC) 2 −17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.7 Connection of an operator unit type F E D 2 −18. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8 Connection of a handheld type CPX−MM I 2 −19. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.9 Complying w ith protection class I P65 /I P 67 2 −20. . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
35/87
2 . I n st a ll a ti o n
2−3F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2. 1 G en era l in st al la ti on i ns tru ct ion s
Warning Danger of injury from electric shock.
· A lw a y s swit c h o f f t h e p ow e r su pp ly be f or e f it t ing o rremoving CPX modules.
CautionThe CoDeSys controller contains electrostatically sensitivecomponents.
· Therefore, do not touch any contacts.
· Observe the handling specifications for electrostaticallysensitive devices.
NoteC h e c k w ith in t h e f r a me w o r k o f y o u r E M E R G E N C Y S TO Pconcept to ascertain the measures necessary for puttingy ou r m ac h in e /s y st e m i nt o a s a fe s t at e i n th e e ve n t o f a nE M E R G E N C Y S TO P ( e . g. sw it c h in g o f f p o we r so u r c es,load voltage supply, compressed air, etc.).
Information on fitting the CPX terminal can be found in theCPX system manual type P.BE−CPX−SYS−... .
-
8/9/2019 569122g1 Manual Codesys
36/87
2 . I n st a ll a ti o n
2−4 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2.2 Dismantli ng and fitting
Th e c on t r olle r is f it t ed in an in te r lin kin g blo c k o f t h e C P Xterminal (see Fig. 2/1).
2.2.1 Dismantling
D ism a nt le t h e c o n t r o lle r a s f o llow s:
1 . L oo se n t he f ou r s cr ew s o f t he c on tr ol l er w i th a TO R Xs c re w dr i ve r s i ze T 1 0 .
2 . P u ll t h e co n tr ol l er c a re f ul l y an d w i th o ut t i lt i ng a w ay f r omt h e c o nt a ct r a il s o f t h e i nt e rl i nk i ng b l o ck .
1 CPX−CEC/CPX−CEC−...
2 Interlinking block
3 Contact rails
4 Screws
3
4
1
2
F i g. 2 / 1: D i sm a nt l in g /f i tt i ng o f t h e c o nt ro l le r ( h er e C P X− C EC − C1 / −M 1 a s a n e x am p le )
-
8/9/2019 569122g1 Manual Codesys
37/87
2 . I n st a ll a ti o n
2−5F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2.2.2 Fitting
NoteF it t h e c on t ro lle r t o th e le f t en d p o sitio n o f t h e C P Xterminal (position 0).
F i t t h e c on t ro l le r a s f o ll o ws :
1 . C h ec k t h e s e al a nd s ea l s u rf a ce s .
2 . I n se r t t h e c o nt ro l l er i n t h e i n te r li n ki n g b l o ck . M a ke s ur ethat the grooves with the power contact terminals on thebo t t om o f t h e c o n tr o ller lie a bo ve t h e c o n ta c t r ails.
3 . P u sh t h e c o nt ro l le r ca re f ul l y a n d w i th o ut t il t in g as f a r a spossible into the interlinking block.
4. P la c e t h e scr e w s so t ha t t he se lf− c u tt in g th r e ads c a n be
u se d. Tig ht e n t h e sc re w s by h a n d.
5 . T ig ht en t he s cre ws w it h a TO RX s cre wd ri ve r s iz e T 10 w it ht or qu e 0 . 9 .. . 1 . 1 Nm .
-
8/9/2019 569122g1 Manual Codesys
38/87
2 . I n st a ll a ti o n
2−6 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2 .3 C on nec ti on an d di sp la y e lem en ts
2
34
6
7
5
1
1 Status LEDs
2 R U N / S TO P r o t ar y sw itc h
3 Ethernet interface(10/100BaseT, RJ45)
4 CPX−CEC−C1/−M1:CANopen interface (plug, 9−pin, Sub−D )CPX−CEC:RS232 interface(socket, 9−pin, Sub−D)
5 DIL switch 1
6 DIL switch 2
7 C o n n ec t io n f o r a h a n dh eld of t y p eC P X − M M I
F i g. 2 /2 : C o nn e ct i on a n d di s pl a y el e me n ts ( h er e f o r C P X− C EC − C1 / −M 1 a s a n ex a mp l e)
-
8/9/2019 569122g1 Manual Codesys
39/87
2 . I n st a ll a ti o n
2−7F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2 .4 S et ti ng t he sw it ch es of th e C oD eS ys co nt ro ll er
2. 4. 1 R UN /STO P ro ta ry s wi tch
NoteL ea v e t h e R U N / S TO P r o ta r y sw it c h a t p o sitio n " 0 " ( S TOP )during installation.
Th e sw it c h se t t in g of t h e R U N / S TO P r o t ar y sw it c h w it hfour internal digital inputs is passed on to the controller andc a n be e v alu a t ed t h e r e .
Rotar y switch Setting Meaning
0 STOP
CoDeSys controller stoppedT he S TO P L ED l i gh ts u p y el low
1 ... F RU NCoDeSys controller startedT h e R U N L E D l i gh t s u p g r ee n
Ta b. 2/ 1: S wi tc h s et ti ng s o f t he RU N /S TO P ro ta ry s wi tc h
-
8/9/2019 569122g1 Manual Codesys
40/87
2 . I n st a ll a ti o n
2−8 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2.4.2 DI L switches
The DIL switches must be accessible in order to makesettings:
· R e m ov e , if a p p lic a ble , th e c o ve r o r an I P 6 5 / I P 6 7 p lugfrom the Sub−D interface.
DIL switch 1D I L s wi t ch 1 i s r es e r ve d . L ea v e t h e t w o sw i tc h e le m en t s of D I L sw i tc h 1 a t O F F.
CPX−CEC/CPX−CEC−. .. DIL switch 1
Reserved D I L 1 . 1: O F FD I L 1 . 2: O F F
Tab. 2 /2 : S et ti ng the DI L s wi tc h 1
-
8/9/2019 569122g1 Manual Codesys
41/87
2 . I n st a ll a ti o n
2−9F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
DIL switch 2
For CPX−CEC−C1/−M1, you can switch the CAN bus termination( 1 2 0 ) o n o r o f f.
CPX−CEC−C1/−M1 DIL switch 2
Te r m i na t i on s w i tc h e d o f f D I L 2 . 1: O F FD I L 2 . 2: O F F
Te r m i na t i on s w i tc h e d o n D I L 2 . 1: O ND I L 2 . 2: O F F
A l l f ur t h er s w it c h s e tt i ng s a re r e se r ve d .
Th e D I L sw it c h 2 o n t h e C P X −C E C h a s n o f u n ct io n .
Ta b. 2 /3 : S et ti ng the DI L s wi tc h 2
-
8/9/2019 569122g1 Manual Codesys
42/87
2 . I n st a ll a ti o n
2−10 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2.5 Ethernet interface
Th e E t h e r ne t in t e r fa c e p e r m it s c o n n e c tio n o f a p r o gr a m m in gdevice, PC or type FED operator unit to the CoDeSyscontroller.
Th e E t he r n e t in t e rf a c e is de sig ne d a s a n R J 45 soc k e t.
Socket Pin Signal E xplanation
12
34
56
78
12345678Housing
TD+TDRD+n.c.n.c.RDn.c.n.c.Shield
Tr a n sm i t te d d a t a +Transmitted dataR e c ei v ed d a t a +n o t c o n ne c t edn o t c o n ne c t edR e c ei v ed d a t a n o t c o n ne c t edn o t c o n ne c t edScreening
Ta b. 2 /4 : P in a ss ig nm en t of t he Et he rn et i nt er fa ce
I f t h e Et h er n et i n t er f ac e i s n o t us e d , c lo s e i t w i th t h e A K −R J 45cover. In this way you will comply with protection classI P 6 5 / I P 6 7 .
2.5.1 Ethernet cable
U se a s c o n n ec t in g c a ble :
Cab le speci fi cation Screened flexib le Ethernet round cab le of category 5M ax. out er di am ete r: 5 .4 mmCore diameter: 0 .89 ... 1 .0 mm AWG24−26Ready made: Crimping pliers on RJ45
-
8/9/2019 569122g1 Manual Codesys
43/87
2 . I n st a ll a ti o n
2−11F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
NoteI f th e CP X te r m ina l is f it t ed o nt o a m o vin g p a r t o f amachine, the Ethernet cable on the moving part must beprovided with strain relief.
Ne tw or k c on nec ti on In o rd er to c on nec t yo ur Co De Sy s c on trol le r t o a n et wor k o rP C , y o u w ill re q u ire a p a t ch o r c r o ssov e r c a ble. Th e in t e r f ac e
automatically recognises which cable is connected anda u t om a t ica lly c o n v e r t s t h e sig n a ls.
NoteUse the RJ−45 plug from Festo in order to comply with theprotection class IP65/IP67:
Type FBS−RJ45−8−GS
Observe the fitting instructions for the plug.
F ig . 2/ 3: R J− 45 p lu g ty pe F BS −R J4 5 −8 −G S
-
8/9/2019 569122g1 Manual Codesys
44/87
2 . I n st a ll a ti o n
2−12 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2.6 Commun icat ion i nterfaces
2 .6 .1 C A No pe n i nt er fa ce (C PX −C EC −C 1/ −M 1)
O n th e CP X − C E C− C 1 / −M 1 , th e re is a C A N o p e n in t e rf a c e f o rc o n n ec t io n of C A N bu s sla ve s.
Th e C A N o p e n in t e rf a c e is de sig ne d as a 9 − p in S u b− D p lu g .
Plug Pin Signal Internalcontacts
Explanation
5
1
9
6
12345
6789Housing(plug)
n.c.C A N _ LCAN_GNDn.c.CAN_SHLD
CAN_GNDC A N _ Hn.c.n.c.
FE
n o t c o n n ec t e dC A N l owC A N g ro un dn o t c o n n ec t e dC o nn e ct i on t o f u nc t io n al e a r th ( F E) 2 )
C A N g r ou n d ( o pt i on al )1 )
C A N h ig hn o t c o n n ec t e dn o t c o n n ec t e dT he p lu g h ou si ng m us t b e c on ne ct edto FE 2 ).
1 ) I f a m ot o r c on t ro ll e r w it h e x te r na l v ol t ag e s u pp l y i s c o nn e ct e d,C A N g r ou n d (o p ti o na l ), p i n 6 c a nn o t b e u s ed o n t h e C P X− C EC − C1 / −M 1 .
2 ) F E : F u n ct i o na l e a r t h i n g
Ta b. 2/ 5: P in as si gn me nt fo r t he C A No pe n in te rf ac e
Th e c o n n ec t e d C A N bu s sla ve s a r e n o t su pp lie d w ith p o w erover the CANopen interface.
-
8/9/2019 569122g1 Manual Codesys
45/87
2 . I n st a ll a ti o n
2−13F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Connecting the CAN bus
CAN bus line
NoteFaulty installation or high transmission rates may caused a ta t ra n sm i ss i o n e r ro r s a s a r es u lt o f s i g na l re f le c ti o nsand attenuations.
Tr a n sm issio n e r r or s c a n be c a u sed by : missing or incorrect terminating resistor
incorrect screened connection
branches
large distances
unsuitable cables.
U s e a t w is t ed , s cr ee n ed 4 − c or e c a bl e as a C A N b us l i ne . Th e
CoDeSys controller communicates with the drive controllersv i a t h e C A N bu s l i ne .
I f t he Fe st o CA N bu s pl ug i s u se d, a c ab l e d i am et er o f 5 . .. 8o r 7 . .. 1 0 m m i s p er mi tt ed .
NoteI f t h e CP X t e rm in a l is f it t ed o n to t h e m o v in g p ar t o f amachine, the CAN bus line on the moving part must beprovided with strain relief. Also observe the relevantregulations in EN60204 part 1.
-
8/9/2019 569122g1 Manual Codesys
46/87
2 . I n st a ll a ti o n
2−14 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
C o n n ec t i o n w i th F e st o C A N b u s pl u g
Note· Use protective caps or blanking plugs to seal unused
connections.
You will then comply with protection class IP65/I P67.
· Note the fitting instructions for the CAN bus plug. Tighten
t h e t w o fa st e nin g scr e w s a t f ir st by ha n d an d t he n w ithmax. 0.4 Nm.
You can connect the CPX−CEC−C1 easily to the CAN buswith the CAN bus plug from Festo,type FBS−SUB−9−BU−2x5POL−B. You can disconnectt h e p lu g f ro m t h e n o de w it ho u t in t er r u p tin g t h e bu s lin e(T−Tap function).
NoteTh e c la mp st r ap in t h e Fe st o C A N bu s plu g is c o n n ec t e donly capacitively internally with the metal housing of thesub−D socket. This prevents equalising currents fromf l ow i ng v i a t h e s c re e ni n g o f t h e C A N b u s l i n e (Fig. 2/4).
· Clamp the screening of the CAN bus line under the clampst r a p in t h e C A N bu s plu g .
-
8/9/2019 569122g1 Manual Codesys
47/87
2 . I n st a ll a ti o n
2−15F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
1 Folding coverwith inspectionwindow
2 Clamp strapfor screenedconnection 1)
3 Protective cap if
c o nn e ct i on i s n o tused
4 C A N bu soutgoing (OUT)
5 C A N bu sincoming (IN)
6 SUB−D plug 1)
1) connectedcapacitively
V +
G N D H L
S L D
V +
G N D H L
S L D
21 3
456
F i g. 2 / 4: C A N b u s pl u g fr o m F es t o, t y pe F B S −S U B − 9− B U −2 x 5 PO L −B
-
8/9/2019 569122g1 Manual Codesys
48/87
2 . I n st a ll a ti o n
2−16 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Further connection possibilities for the CAN buswith adapters
Caution· M a k e su r e o f t h e c o r re c t p o la rit y wh e n yo u c on n e c t t h e
C A N b u s i n te r fa c e.
· Connect the screen.
T h er e a re f u r th e r w a ys o f c o nn e ct i ng t he C A N b us w i tha da p te r s, wh ic h ca n be o r der e d se p a ra t e ly f ro m Fe st o . Th e seadapters and additional accessories can be found under:
è www.festo.com/catalogue
M12 adapter 5−pin (protection class IP65),type FBA−2−M12−5POL
Screw terminal adapter 5−pin (protection class IP20),
type FBA−1−SL−5POL
-
8/9/2019 569122g1 Manual Codesys
49/87
2 . I n st a ll a ti o n
2−17F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2 .6 .2 R S2 32 in te rf ac e ( CP X− CE C)
The RS232 interface enables a type FED operator unit ore x t er n a l dev ic e s to be c o n n ec t e d to t h e C P X − C EC .
When using external devices, data communication must beprogrammed by the user.
Socket Pin Signal E xplanation
12345678
9Screen
n.c.RxDTxDn.c.GNDn.c.n.c.n.c.
n.c.Screen
n o t c o n ne c t e dR e c ei v e d d a t aTr a n sm i t te d d a t an o t c o n ne c t e dD a t a r e f er e nc e p o t e nt i a ln o t c o n ne c t e dn o t c o n ne c t e dn o t c o n ne c t e d
n o t c o n ne c t e dC on n ec t io n t o f u nc t io n al e a r th ( F E )
Ta b. 2/ 6: P in as si gn me nt of t he R S2 32 i nt er fa ce (C PX −C EC )
-
8/9/2019 569122g1 Manual Codesys
50/87
-
8/9/2019 569122g1 Manual Codesys
51/87
2 . I n st a ll a ti o n
2−19F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2. 8 C on nec ti on of a h an dh eld ty pe CPX− MM I
The 5−pin M12 socket serves to connect a CPX−MMI for fastpreliminary commissioning, diagnosis or parameterising.
F i g. 2/ 6 : C P X t e rm i na l wi t h h a nd h el d ty p e C P X− M M I
The connection with the CPX−MMI is interrupted during ap r o gr a m dow n lo ad if p a ra m e te r s h a ve be e n c h a n ge d v ia t h eCoDeSys provided by Festo software. This guarantees thec o n sist e n c y o f t h e disp la y e d da t a.
Use only the following original cables( è www.festo.com/catalogue) for connecting the CPX−MMI:
Type Cable length in [m]
KV−M12−M12−3,5 3.5
KV−M12−M12−1,5 1.5
Ta b. 2/ 7 : C on ne ct io n c ab l e f or ha nd he ld ty pe CP X− MM I
Further information on parameterisation via CPX−MMI can befound in the section 3.5.2.G e n er a l in f o rm a t ion o n t h e C PX − M M I c a n be f o u n d in t h emanual P.BE−CPX−MMI−1−...
-
8/9/2019 569122g1 Manual Codesys
52/87
2 . I n st a ll a ti o n
2−20 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
2 .9 C om pl yi ng w it h pro te ct io n cl as s IP 65 /I P67
In order to comply with protection class IP 65/IP67, seal unused sockets and the switch with the appropriate covers.
Connection/switch
ConnectionIP65/IP67
Cover 1)
IP65/IP67
E thernet, RJ 45 Plugt y p e F B S − RJ 4 5 − 8 −G S
Cover2 )
t y pe A K −R J 45
Sub−D (CANopen/R S 23 2 ) a n dDIL switch
P lu g t yp e F BS −SUB−9−BU−2X5POL−B
Transparent cover2 )
t y p e A K − S U B −9 / 1 5 −B
S e r v i ce i n t er f a c e,M12
C on n ec t in g c a bl e a n dp lu g o f t he C PX −M MI
P r o te c t iv e c a p2 )
t y pe I S K− M 12
Rotary switch Cover2 )
t y pe A K −R J 45
1 ) I f c on ne ct io n i s n ot u se d2 ) I n cl u de d i n s c op e o f d e li ve r y
Ta b. 2 /8 : C on ne ct io ns a nd c ov er s fo r p ro te ct io n cl as sI P 6 5 / I P 6 7
-
8/9/2019 569122g1 Manual Codesys
53/87
-
8/9/2019 569122g1 Manual Codesys
54/87
3 . C o mm i s si o ni n g
3−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Contents
3. Commis sioning 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 P rereq uisites for commissioning 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 First steps 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Configuration of the CPX modules 3−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Configuration of C A Nopen slaves 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 P arameterisation of the CPX terminal 3−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 .5.1 P arametrisation via control configuration in CoDeSys 3 −10. . . . . . . . . .
3 .5.2 P arametrisation via the handheld type CPX−MM I 3 −13. . . . . . . . . . . . . .
3.6 Forcing 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
55/87
3 . C o mm i ss i o ni n g
3−3F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
3. 1 P re re qu is it es for com mi ss ion in g
CautionD a n ge r o f in j u ry du e t o u nde sire d m o ve m e nt s o f t h econnected actuators.
· Test projects and programs at first without activeactuators and without compressed air.
1 . I n st all t he p ro g r am e n vir o nm e n t Co D e Sy s pr ov ide d byF e sto o n a P C o n w h ich y o u c ar r y o ut c o m m issio n ing ,configuration and programming.
Detailed installation instructions can be found on theaccompanying CD−ROM. Observe the instructions on thec o ve r o f t h e C D− R O M .
2 . C o nn e ct th e P C t o t h e C o De Sy s co n tr ol l er.
3.2 Fi rst steps
The commissioning procedure described in the followingse c t io n s u se s t he e x a m ple o f t h e C P X − CE C − C 1 o r CP X − C EC − M 1a s a C A N o p e n m a st er. F u r t h e r in fo r m a tio n o n c o m m ission in gthe variants CPX−CEC−M1 with SoftMotion and CPX−CEC canbe f o u n d in th e o n line h e lp.
1 . S ta r t C oD eS ys pr ov id ed by Fe st o.
2 . C rea te a n ew pro je ct.
1 . S el ec t t he ta rg et s ys te m.
2 . I f n e ce s sa r y, ch a ng e t h e s e tt i ng s f o r t h e t a rg e tsystem.
3 . C r ea t e th e p ro g ra m m od u le " P LC _ PR G ".
· S e le c t t h e la n g ua g e of t h e m odu le , e. g . S TL .
-
8/9/2019 569122g1 Manual Codesys
56/87
3 . C o mm i s si o ni n g
3−4 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
4 . I n t he " O bj e ct O rg a ni z er " , c h an g e to " Re s ou r ce s ".
5 . O p en th e " P LC Co n fi g ur at i on " .
6 . S el ec t th e Ro ot n od e, i f a pp li ca bl e.
7 . O p en t h e "N e tw o rk c o nf i gu ra t io n " ta b.
8 . C a rr y o ut t h e "S e ar ch n e tw o rk " f un c ti o n.
9 . S e le c t th e d es i re d C oD e Sy s c on t ro l l er.1 0 . C a r r y o u t t h e " S e t a s a c t ive P LC " fu n c tio n .
1 1 . S a ve t h e p ro j ec t . You can now log in to the controller, if necessary.
F i g. 3 /1 : N e tw o rk c o nf i gu ra t io n us i n g t h e e x am p le o f t h e C P X− C EC − C1
-
8/9/2019 569122g1 Manual Codesys
57/87
3 . C o mm i ss i o ni n g
3−5F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
3. 3 C on fi gu ra ti on of th e C PX mod ul es
Detailed information on configuration of the CPX modulesc a n be f o u n d in th e o n line h e lp.
A f t er yo u h a v e c r e at e d a n e w p r oj e c t in se c t ion 3. 2 a ndselected the desired CoDeSys controller, now continuec o m m issio n ing w it h c o nf ig u ra t io n of t h e C P X m o dule s.
1 . C lic k in t he w in do w "P LC C o nf ig u ra t io n" o n t h e n o de s t ot he l ef t of t he C PX −C EC −. ..
2 . C l ic k w i th t h e ri g ht m o us e b ut t on o n t he e l em e nt"IOModules[FIX]".
F ig . 3 /2 : C on fi gu ra ti on o f t he CP X mo du le s
Now you can perform module configuration automaticallyor manually.
-
8/9/2019 569122g1 Manual Codesys
58/87
3 . C o mm i s si o ni n g
3−6 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Automatic module configuration
· Perform the [Scan module configuration] function if youwant to perform module configuration automatically.
T h e I/ O m od u le s o f a C P I m o du l e ar e n o t in c l ud e d in a u to matic module configuration. In this case, carry out a manualmodule configuration (see next section) or perform the"Scan" function in the "CP Modules" tab.
F ig . 3 /3 : " CP M od ul es " t ab
-
8/9/2019 569122g1 Manual Codesys
59/87
3 . C o mm i ss i o ni n g
3−7F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
Manual module configuration
· Select [Append Subelement] if you want to performmodule configuration manually.
Attach the CPX modules from left to right in the physicalsequence on the CPX terminal. The modules are added at thebottom in the tree structure. The CoDeSys controller sits inthe CPX terminal to the far left at position 0.
· F r om t he list o f t h e C P X mo du les, se le c t t h e C P X mo du let o th e r i gh t of C P X− C EC − .. .
· Repeat [Append Subelement] until you have selected allCPX modules.
Addressing of inputs and outputs takes place automatically( p r ese t in t h e de live r y c on dit ion o f t h e de v ic e) . F or e a c h mo du le , a t le a st 4 by te s o f in p u ts o r o u t pu t s ar e r e ser v e d.
The rotary switch of the CPX−CEC−C1, for example, occupieso n ly 4 bit s o f in p u ts, bu t 4 by t e s a re r e ser v e d.Alternatively, you can also manually address the inputsand outputs. Information can be found in the online help.
3. Save the project.
-
8/9/2019 569122g1 Manual Codesys
60/87
-
8/9/2019 569122g1 Manual Codesys
61/87
3 . C o mm i s si o ni n g
3−9F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
3 .5 P ar am et er is at ion o f th e C PX t er mi na l
Th e C P X te r m in al is su p p lie d fr o m th e f a c t or y wit h pr e se tp a ra m et e rs . If r e qu i re d , y o u c a n s e t t h e r e ac t io n of t h e C P Xt e r m in a l as w e ll as t h e r e a c tio n of in div idu a l mo du les a n dchannels by parameterising.A dist in c t io n is m a de be t w ee n t h e f o llo win g p a r a me t e risa tions:
system parameters, e.g.: switching off fault messages,setting reaction times, etc.
module parameters (module and channel−specific), e.g.:monitoring, settings in the event of faults, settings forforcing
diagnostic memory parameters.
Detailed specifications on the parameters and data as well as
ba sic in f o rm a t ion o n p a r a m e t er isa t io n o f t h e C P X t e r m ina lcan be found in the CPX system manual type P.BE−CPX−SYS−....
Detailed information on the module parameters can be foundin the user documentation of the respective modules.
The following parameterisation options are available:
Parameterisation via ... Des cription Proper ties
C o n tr o l c o n f ig u r a ti o n i nC o D eS y s: l o g ou t
A c c e s s t o a l l p a r a me t e rs o f t h e C P X t e rm i na l
Convenient parameterisation via a PC Parameterisation is stored in the
p r o je c t , i . e . t h e p a r a me t e rs r e m a inafter Power OFF/ON
Handheld type CPX−MM I Parameterisation is carriedo u t v i a m e nu − li s te d e n tr i esw i th t h e h a nd h el d
Parameterisation is saved only locallyi n t he C PX t er mi na l a nd i s l os t w it hPower OFF/ON
Ta b. 3 /1 : P ara me te ri sa ti on op ti on s
-
8/9/2019 569122g1 Manual Codesys
62/87
3 . C o mm i s si o ni n g
3−10 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
3 . 5. 1 P a ra m et e ri s at i on v i a c o nt r ol co n fi g ur a ti o n i n C o De Sy s
D e t aile d in f o rm a t ion o n p a r a m e t er isa t io n c a n be f o u n d in t h eonline help.
You can easily parameterise the CPX terminal with the controlconfiguration. Parameterisation can be undertaken for:
the setpoint configuration (logout): parameters aret r a n sf e r r ed w h e n t h e p r o j ec t is lo a de d.
When the relevant dialogue has been opened, you can viewand modify the individual parameters.
Parameters cannot be changed in the online mode.
I n t h e f o llo win g , p a ra m e t er isa tio n is de sc r ibe d u sin g t h ee x a m ple o f t h e R o ot n o de :
· Click in "PLC Configuration" on the symbol for theCPX−CEC.
Settings
· Set the following parameters in the "Settings" tab,i f n e ce s sa r y:
F ig . 3/ 4: " Set ti ngs " t ab
-
8/9/2019 569122g1 Manual Codesys
63/87
3 . C o mm i s si o ni n g
3−11F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
M o d u l e # 0
In the "Module #0" tab, you receive the following informationon the CoDeSys controller:
F ig . 3 /5 : " Mo dul e # 0" ta b
Network configuration (logout)
· Look for the controller for which you want to prepare thenew CoDeSys project in the "Network configuration" tab:
F ig . 3 /6 : " Ne tw or k co nf ig ur at io n" ta b
-
8/9/2019 569122g1 Manual Codesys
64/87
3 . C o mm i s si o ni n g
3−12 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
S ys t e m p a ra m et e rs
· Set the system parameters in the "System Parameters"tab:
F ig . 3 /7 : " Sy st em Pa ra me te rs " t ab
Trace parameters
· Set the following parameters in the "Trace Parameters"tab:
F ig . 3 /8 : " Tr ac e P ar am et er s" ta b
-
8/9/2019 569122g1 Manual Codesys
65/87
3 . C o mm i s si o ni n g
3−13F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
3 .5 .2 P ar am et er is a ti on v i a th e h an dh el d ty pe C PX −M M I
T h e p a ra m et e rs o f t h e C P X t er m in a l c an b e r e ad a n d m od i fi e dv i a a c o nn e ct e d ha n dh e ld .
Transfer of the parameterisation to the CPX modules
Note· Parameterisations via the handheld are saved onlylocally in the CPX terminal and are lost with PowerOFF/ON.
· Th e c on n e c tio n w ith t h e C P X − M M I is in t e rr u p te d du r in g aprogram download if parameters have been changed viathe CoDeSys provided by Festo software.
· Parameters changed by the CPX−MMI and Festo_CPX.liba r e o n ly t h en o v er w r it te n du r in g t he p r o je c t do w n loa d if parameter changes have also been made in the CoDeSysproject.
Further information on parameterisation via CPX−MMI can befound in the manual P.BE−CPX−MMI−1−...
-
8/9/2019 569122g1 Manual Codesys
66/87
3 . C o mm i s si o ni n g
3−14 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
3.6 Forcing
Through forcing, you can compel input and output signals.Actual input signals or status changes by program areignored and replaced by the force values.
Warning High acceleration forces at the connected actuators!
U n de sir e d m ov e m e nt s o f t h e a c t ua t o r s c an c a u secollisions and severe injuries.
· Be very careful when forcing in order to avoid undesiredm o ve m e n ts o f t h e a c t ua t o r s.
· Make sure that no persons are in the operating range of the drives or any other connected actuators.
F o rc in g o f in p u ts w it h
handheld type CPX−MMI
Forcing an input does not modify the input signal itself and
cannot be o bse r v e d a t t h e r e le va n t st a t us LE D . Th e lo g ic alstatus of the input changes internally and in some cases hasan effect on the program. The forced input status is transf e r r ed t o t h e im ag e t a ble of t h e in p u ts. Th e o n line disp lay inCoDeSys provided by Festo therefore shows the forced inputsignal.
F o rc in g o f o u t pu t s w it hhandheld type CPX−MMI
Forcing an output does modify the actual output signal andc a n be o bse r v ed a t t h e r e le va n t st a t us L E D. H o w ev e r, t h eforced output signal is not t r a n sf er r e d t o t h e im a g e t able o f the outputs. The online display in CoDeSys provided byFesto does not show the forced, physical output signal,but the status from the image table.
-
8/9/2019 569122g1 Manual Codesys
67/87
3 . C o mm i s si o ni n g
3−15F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
NoteThe online display in CoDeSys provided by Festo alwaysshows the signal status valid in the process diagram. Whenforcing with the handheld type CPX−MMI, observe thefollowing:
Forced input states are transferred to the image tableand therefore recognised by the controller. They arevisible in the online display.
Forced output states are not t r a n sfe r r ed t o t h e im a g etable and are therefore not recognised by the controller.They are not therefore represented in the online display.
You have various ways of temporarily influencing input oroutput signals, e.g. for test purposes:
Forcing via the handheld type CPX−MMI
Forcing with the online display in CoDeSys provided by
Festo.
F u r t h e r inf o r m at io n o n fo r c in g ca n be f o u n d in th e C P Xsystem manual type P.BE−CPX−SYS−... and in the online help.
I f se v e ra l f u n c t ion s a r e a c t iv e a t t h e sa m e t ime , t h e f o llow in gapplies:
Force signals have the highest priority
Forcing via the handheld has higher priority than forcingwith the online display.
-
8/9/2019 569122g1 Manual Codesys
68/87
-
8/9/2019 569122g1 Manual Codesys
69/87
Diagnosis
4−1F e st o P. B E− C PX − CE C −E N e n 1 0 04 a
Chapter 4
-
8/9/2019 569122g1 Manual Codesys
70/87
4 . D i ag n os i s
4−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Contents
4. Diagnosis 4−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 G eneral error response of the CoDeSys controller 4−3. . . . . . . . . . . . . . . . . . . . .
4.2 Diagnosis via controller LE Ds 4−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Fur ther diagnostic options 4−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
71/87
4 . D i ag n os i s
4−3F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
4 .1 G en er al er ro r r es po ns e o f t he Co De Sy s c on t ro ll er
Warning
If an error occurs, the controller does not stop butcontinues with the program processing. Undesiredmovements of the actuators can cause collisions andsevere injuries.
· Include error handling mechanisms for all errorcategories in the user program.
· M a k e sur e t h a t no p e rso n s a re in t h e o p e ra t in g r a ng e o f the drives or any other connected actuators.
The CoDeSys controller makes available the following errorhandling mechanisms in user programs:
System event CPX_system_fault
Channel/module diagnosis in the flag words
Module support in the Festo_CPX.lib
Detailed information on error handling in user programs canbe found in the online help.
-
8/9/2019 569122g1 Manual Codesys
72/87
4 . D i ag n os i s
4−4 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
For the CoDeSys controller, the following diagnostics optionsa r e a va i l ab l e:
Diagnos is via ... Advantages Des cription
Status LE Ds Fast on−the−spotr e co gn i ti o n o f f a ul t s
Controller LEDs, see section 4.2 CPX−specific LEDs, see section 1.5.
H and he ld ty pe C PX −M MI Fas t on −t he− sp ot
r e co gn i ti o n o f f a ul t s
S e e C P X s y st e m ma n ua l
Control configuration Online diagnosis withoutprogramming
S ee o nl in e h el p
User program Detailed diagnosticevaluation:
System eventCPX_system_fault
Channel/module diagn os is i n th e f la g w or ds
Module support in theFesto_CPX.lib
S ee o nl in e h el p
Ta b. 4 / 1: D ia gn os ti c o pt io ns o f t he C oD eS ys c on tr ol l er
-
8/9/2019 569122g1 Manual Codesys
73/87
4 . D i ag n os i s
4−5F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
4. 2 D ia gn os is vi a c on tro lle r LED s
Th e c o n tr o ller L E D s h av e t h e f o llow in g m ea n in g :
R UN P LC s t at u s: s t ar t e d
LED (green) Sequence Status Error number Error handling
L E D l ig h ts u p
ON
OFFP LC p r o gr a m s t a r t ed( RU N /S TO P s wi tc h i s i n
p os it io n " 1 . .. F ")
L E D i s o f f
ON
OFFP LC p r o gr a m s t o p p ed( RU N /S TO P s wi tc h i s i np o s i ti o n " 0 " )
· S e t R U N / S TO Ps w i t ch t o p o s it i o n"1 ... F"
Tab. 4/2 : Displays of RU N LE D
S TO P P LC s t at u s s to p pe d
LED (yellow) Sequence Status Error number Error handling
L E D l ig h ts u p
ON
OFFP LC p r o gr a m s t o p p ed( RU N /S TO P s wi tc h i s i np o s i ti o n " 0 " )
L E D i s o f f
ON
OFFP LC p r o gr a m s t a r t ed( RU N /S TO P s wi tc h i s i np os it io n " 1 . .. F ")
· S e t R U N / S TO Ps w i t ch t o p o s it i o n"0"
Tab. 4/3 : Displays of STOP LE D
-
8/9/2019 569122g1 Manual Codesys
74/87
4 . D i ag n os i s
4−6 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
E R RO R P LC r u n− t im e e r ro r
LED (red) Seq uence S tatus Er ror number Err or handling
L E D l ig h ts u p
ON
OFFPLC program error CPX error · R ea d o ut e rr or
c o de o ve rh a nd h el d o rC o De Sy s p b F
L ED i s o ff
ON
OFF
No error
Tab. 4/4: Displays of E RRO R LE D
TP Ethernet connection: link/traffic
LED (green) Seq uence S tatus Err or number Error handling
L E D l ig h ts u p
ON
OFF
E thernet connection OK
LED flashes
ON
OFF
D a t a t r a ns f e r a c t i ve( L E D f l a s h e s i r r eg u l a rl y )
L E D i s o f f
ON
OFFE t h e rn e t c o n n ec t i on t o t h ep a ra m et e ri s at i on P C n o t O K
· Check the connection the IP address
Tab. 4/5: Displays of TP LE D
-
8/9/2019 569122g1 Manual Codesys
75/87
4 . D i ag n os i s
4−7F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
4.3 Fur th er dia gn ost ics opt ions
F u r t he r in f o r m at io n o n dia g n osis v ia t h e c o n t ro l c o n f ig ur a t io nin CoDeSys provided by Festo and via user programs can befound in the online help.
Further information on diagnostics with SoftMotion( C P X −C E C − M 1) c a n be f o u n d in t h e o n lin e h e lp.
-
8/9/2019 569122g1 Manual Codesys
76/87
4 . D i ag n os i s
4−8 F e s t o P. B E − C PX − C E C− E N e n 1 0 0 4 a
-
8/9/2019 569122g1 Manual Codesys
77/87
Technical appendix
A−1F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
Appendix A
-
8/9/2019 569122g1 Manual Codesys
78/87
A . Te c h n ic a l a p p en dix
A−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
Contents
A. Technical append ix A−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Technical data A−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
79/87
A . Te c h n ic a l a p p en dix
A−3F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
A.1 Technical data
CPX−CEC/CPX−CEC−...
General technical data f or t he CPX terminal See CPX system m anual: Manual P.BE−CPX−SYS−...
Total number of axes CPX−CEC−C1 CPX−CEC−M1
313 1 ( r ec o mm e nd e d: m a x. 8 )
CPU data Processor 400 M Hz, 32 M B RAM, 32 M B f lash
Configuration suppor t CoDeSys
Parameterisation CoDeSys
Programming sof tware CoDeSys provided by Festo
Programming language As per I EC 61131−3LDR, STL, ST, FUN, SFC, also CFC
Program memory 4 M B user program
Protocol CoDeSys Level 2, EasyI P, Modbus TCP, TCP/I P
Dev ice−specific diagnostics Channel and module−oriented diagnostics Undervoltage/short circuit of modules Diagnostic memory
Additional functions CPX−CEC/CPX−CEC−... CPX−CEC−C1
CPX−CEC−M1 CPX−CEC
Diagnostic functionsM o t io n f u n c t i on s f o r e l e c tr i c d r i v es
S o f tM o t io n f u n c ti o n s f o r e l e c tr i c d r i v esR S 2 3 2 c o m mu n i c at i o n f u n c ti o n
Baud rate 10/100 bit/s as per I E E E802.3 (10BaseT)or 802.3u (100BaseTx)
Processing time Approx. 200 ìs/1k instructions
LED display (bus−specific) TP: Ethernet connection: link/traf fic
-
8/9/2019 569122g1 Manual Codesys
80/87
-
8/9/2019 569122g1 Manual Codesys
81/87
A. Technical appendix
A−5F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
CPX−CEC/CPX−CEC−...
Power failure bridging 10 ms
Storage temperature 20 ... +70 °C
A mbient temperature 5 ... +50 °C
R elative air humidity 95%, non−condensing
Product weight 155 g
Dimensions W x L x H 50 mm x 107 mm x 55 mm
-
8/9/2019 569122g1 Manual Codesys
82/87
A. Technical appendix
A−6 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
-
8/9/2019 569122g1 Manual Codesys
83/87
Index
B−1F e st o P. B E− C PX − CE C −E N e n 1 0 04 a
Appendix B
-
8/9/2019 569122g1 Manual Codesys
84/87
B . I nd ex
B−2 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
-
8/9/2019 569122g1 Manual Codesys
85/87
B . I nd ex
B−3F e s t o P. B E − CP X − C EC − E N e n 1 0 0 4 a
A
Abbreviations XII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories 2−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C
CableEthernet 2−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Handheld type CPX−MMI 2−19. . . . . . . . . . . . . . . . . . . . . . .
C A N bu sConnecting 2−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Connection 2−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Line 2−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Termination 2−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CoDeSys provided by Festo XI I , 1−9. . . . . . . . . . . . . . . . . . . .
Commissioning 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Configuration
C A Nopen slaves 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CPX modules 3−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection and display elements 2−6. . . . . . . . . . . . . . . . . . .
CPX−M M I 2−19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D
Designated use V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosis 4−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dismantling 2−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F
Firmware XI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting 2−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Forc ing 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front end display (F E D) 2−18. . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
86/87
B . I nd ex
B−4 F e s t o P .B E − C PX − C E C− E N e n 1 0 0 4 a
H
Handheld type CP X−MM I 2−19. . . . . . . . . . . . . . . . . . . . . . . . .
I
Installation 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interfaces
C A Nopen 2−12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Ethernet 2−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS23 2 2−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L
LEDsController LEDs 4−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CPX−specific 1−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M
Motor controllers, suppor ted 1−5. . . . . . . . . . . . . . . . . . . . . .
O
Operating modes 1−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator unit type F E D 2−18. . . . . . . . . . . . . . . . . . . . . . . . . .
P
ParameterisationVia control configuration 3−10. . . . . . . . . . . . . . . . . . . . . . .Via handheld type CPX−MM I 3−13. . . . . . . . . . . . . . . . . . . .
Parameterisation of the CPX terminal 3−9. . . . . . . . . . . . . . . .
Pin assignmentC A Nopen interface 2−12. . . . . . . . . . . . . . . . . . . . . . . . . . . .Ethernet interface 2−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS23 2 interface 2−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
8/9/2019 569122g1 Manual Codesys
87/87
B . I nd ex
Protection class I P6 5/I P67 2−20. . . . . . . . . . . . . . . . . . . . . . .
S
Ser vice V I I I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SoftMotion 1−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Commissioning 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Diagnosis 4−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Meaning X I I I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Strain relief 2−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SwitchDI L sw itch 2 −8 , 2−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RU N/STOP rotary switch 2−7. . . . . . . . . . . . . . . . . . . . . . . .
System parameters 3−12. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TTarget group V I I I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical data A−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
U
User instructions IX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .