51248770.pdf

Upload: tehman-alam

Post on 06-Jul-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/17/2019 51248770.pdf

    1/1

    TÜV 10 ATEX 2539 X

    Group II

    4  II (3)G

    Conditions in Hazardous Areas (ATEX 94/9/EG)

    [Ex ia] IIB T4

    1 0044

    Conditions Marking

    Equipment can beused without restriction

    Observe specialoperating conditions

    X

    Ex component withpart certificate cannotbe used alone;CE conformity is onlycertified after installationin complete equipment

    U

    Associa-tedequip-ment [ ]

    Useoutsidehazardousarea,effectivein Ex area

    EN60079-0(2006)

    [Ex ib] IIB

    EN60079-0(starting fromEdition 5.0)

    [Ex ib Ga] IIB

    Equip-ment

    Usewithinhazardousarea

    EN60079-0(2006)

    Ex ib IIB T4

    EN60079-0(starting fromEdition 5.0)

    Ex ib IIB T4 Ga

    Flamma-ble sub-stances

    Class Division Group Zone Temporary behavior ofthe flammable sub-stance in Ex area

    Gases,vapors,liquids

    Class I 1 A, B , C, D 0 or 1 Permanent ly, for longperiods, frequently

    Occasionally

    2 A, B, C, D 2 Normally not, only fora short period

    Dust Class II 1 E, F, G 20 or 21 Permanently, for longperiods, frequently

    Occasionally

    2 E, F 22 Normally not, only fora short period

    Fibers Class III 1 – 20 or 21 Constantly

    Occasionally

    2 – 22 Normally not, only fora short period

    Gas ignition temperatures

    Ammonia 630°C

    Methane 595°C

    Hydrogen 560°C

    Propane 470°C

    Ethylene 425°C

    Butane 365°C

    Acetylene 305°C

    Cyclohexane 259°C

    Diethyl ether 170°C

    Carbon disulfide 95°C

    Gas Ignition Temperatures

    Ammonia 630°C

    Methane 595°C

    Hydrogen 560°C

    Propane 470°C

    Ethylene 425°C

    Butane 365°C

    Acetylene 305°C

    Cyclohexane 259°C

    Diethyl ether 170°C

    Carbon disulfide 95°C

     Year “ATmosphère EXplosible” EC directive

    Approvalnumber

    Group A: Acetylene, B: Hydrogen, C: Ethylene, D: PropaneGroup E: Metal dust, F: Coal dust, G: Grain dust

    Gas Conditions Group I

    Methane Minessusceptibleto firedamp(coal mining)

    150°C With deposits of coal dust onthe operating equipment

    450°C Without deposits of coal duston the operating equipment

    Ex mark perDirective 94/9/EG (ATEX)

    Associa-tedequip-ment [ ]

    Use outsidehazardous area,effective in Ex area

    ANSI/ISA60079-0 [AEx ib] IIB

    Equip-ment

    Use withinhazardousarea

    ANSI/ISA60079-0 AEx ib IIB T6

    Flammablesubstances

    Temporary behavior of theflammable substance in Exareas

    Classification of thehazardous area

    Gases,vapors,liquids

    Permanently, for long periods,frequently

    Zone 0

    Occasionally Zone 1

    Normally not, only for a shortperiod

    Zone 2

    Passive Components Energy Storing Devices Energy Sources*

    Pt100 Capacitor Thermocouple

    Switch Coil Photo cells

    Distributionboxes

    *RequirementsU 1 1.5 V; I 1 100 mA; P 1 25 mW

    ResistorsValues must be exactly defined and consideredwhen determining overall system safety

    Flammablesubstances

    Temporary behavior offlammable substances

    Classification of ha-zardous areas

    Required marking for equipmentto be used per CENELEC

    IEC 600079-0(starting fromEdition 5.0)

    Device Group Category Equipm. Protect.Level (EPL)

    Gases,vapors,liquids

    Permanently, for longperiods, frequently

    Zone 0 II 1G, (1)G Ga, [Ga]

    Occasionally Zone 1 II 2G, (2)G Gb, [Gb]

    Normally not, only fora short period

    Zone 2 II 3G, (3)G Gc, [Gc]

    Dust Permanently, for longperiods, frequently

    Zone 20 II III (IEC 60079-0,startingfromEdition5.0)

    1D, (1)D Da, [Da]

    Occasionally Zone 21 II III (IEC 60079-0,startingfromEdition5.0)

    2D, (2)D Db, [Db]

    Normally not, only fora short period

    Zone 22 II III (IEC 60079-0,startingfromEdition5.0)

    3D, (3)D Dc, [Dc]

    Methane,coal dust

    Constantly Coal mining I M1 Ma

    Methane,coal dust

    Frequently Coal mining I M2 Mb

    CENELECMarking

    TypicalGas

    Ignition Energy/µJ

    III AII BII C

    MethanePropaneEthyleneHydrogen

    280> 18060 ... 180> 40

    CENELECMarking

    TypicalGas

    Ignition Energy/µJ

    III AII BII C

    MethanePropaneEthyleneHydrogen

    280> 18060 ... 180> 40

    IEC 60079-0 (starting from Edition 5.0)CENELECMarking

    Typical dusts

    III AIII BIII C

    Flammable lintNon-conducting dustConducting dust

    US marking

    Protection type for electrical equipmentin gas explosive hazardous areas

    Protection principle Zone Standard Class/Zone Application

    EN IEC UL

    o Oil encapsulation Exclusion of the Ex atmosphere 1 or 2 EN 60079-6 IEC 60079-6 UL 60079-6

    Class I, Zone 1

    Transformers, starting resistors,switching devices

    q Sand encapsulation Spark prevention 1 or 2 EN 60079-5 IEC 60079-5 UL 60079-5Transformers, relays,safety fuses, switches

    mamb

    Molded encapsulation Exclusion of the Ex atmosphere0, 1, 2

    1, 2EN 60079-18 IEC 60079-18 UL 60079-18 Relays, sensors, solenoid valves

    pxpypz

    Pressure encapsulation Exclusion of the Ex atmosphere0, 1, 2

    1, 22

    EN 60079-2 IEC 60079-2 ISA 60079-2Class I,Div. 1/2

    Switch and control cabinets

    d Pressure-tight encapsulation Propagation prevention 1 or 2 EN 60079-1 IEC 60079-1 UL 60079-1Switch and command systems,heating equipment, lights

    e Increased safety Spark prevention 1 or 2 EN 60079-7 IEC 60079-7 UL 60079-7 Class I, Zone 1 Junction and connection boxes, housings,terminal blocks

    iaibic

    Intrinsic safety Ignition energy limitation

    0, 1, 2

    1, 22

    EN 60079-11 IEC 60079-11 UL 60079-11 Class I, Div. 1Measuring and control technology, sensors,actuators

    EN 60079-25 IEC 60079-25 UL 60079-25 Intrinsically safe systems

    EN 60079-27 IEC 60079-27 UL 60079-27 Intrinsically safe fieldbus systems (FISCO)

    nA Non-sparking equipment Comparable with Ex e 2

    EN 60079-15 IEC 60079-15 UL 60079-15 Class I, Zone 2 Approved for Zone 2nC Sparking equipment Comparable with Ex d 2

    nR Vapor-proof equipment Protection by housing 2

    op isop prop sh

    Optical radiationIntrinsically safe

    ProtectedLocked

    12

    3

    EN 60079-28 IEC 60079-28 UL 60079-28 Optoelectronic devices

    Protection type for electrical equipmentin areas with flammable dust

    Protection principleZone Standard Class/Zone Application

    EN IEC UL

    tD Protection by housing Exclusion of the Ex atmosphere 21 or 22 EN 61241-1 IEC 61241-1 Class II, Div. 1 Junction and connection boxes, switchingdevices and switchgear units, lights

    iaD, ibD Intrinsic safetyEnergy limitation of sparksand temperatures

    20, 21 or 22 EN 61241-11 IEC 61241-11 UL 913 Class II, Div. 1Measuring and control technology, sensors,actuators

    pD Pressure encapsulation Exclusion of the Ex atmosphere 21 or 22 EN 61241-4 IEC 61241-4 NFPA 496Class II, Div.1/2

    Switch and control cabinets, motors

    maD, mbD Molded encapsulation Exclusion of the Ex atmosphere 20, 21 or 22 EN 61241-18 IEC 61241-18Command, signaling and display devices,sensors

    Protection Type

    Category

    1G Use in a defined area

    (1)G Use outside hazardous area,effective up to the described area

    Gas Conditions Group I

    Methane Mines susceptible tofiredamp(coal mining)

    150°C With deposits of coal dust onthe operating equipment

    450°C Without deposits of coal duston the operating equipment

    ID No. Notified Body/Official Testing Agency(Examples)

    Country

    0 04 4 TÜV Nord G erma ny

    0102 P TB Germany

    01 58 E XA M G er many

    06 37 I BE xU Ge rm any

    0 08 0 I NE RI S Fr an ce

    0081 LC IE France

    0 34 4 K EMA Nethe rlan ds

    0402 SP Sweden

    0163 LOM Spain

    0 60 0 EECS (BA SEEFA ) U K

    0518 SCS UK

    www.wago.comPlease find additional information at

    Ex Marking acc. to Standard (Example)

    Dust Group

    Gas Group / Ignition Energy Permissible Surface Temperature per IEC 505

    Protection Type

    Intrinsic Safety, Simple Electrical Equipment

    Conditions in Ex Areas Ex Marking acc. to Standard

    Gas Group / Ignition Energy

    Conditions in Hazardous Areas, USA Permissible Surface Temperature per IEC 505 / NEC 500

    Protection Type

       0   8   8   8 -   0

       1   4   5   /   0   0   0   6 -   3

       6   0   1

       E  x -   P  o  s   t

      e  r   0   4   /   2   0   1   1 -   0

       1   D   E   +   G   B

      ·   P  r   i  n   t  e   d   i  n   G  e  r  m  a  n  y

      ·   S  u   b   j   e  c   t   t  o   d  e  s   i  g  n  c   h  a  n  g  e  s

    UL/FM

    Group II

    ATEX/IEC

    Explosion Protection –

    Real Progress in Safety

    Class/Zone Categorization Class/Division Categorization

    EC Type Examination Certificate Additional Conditions

    T1=450°C

    T2=300°C

    T3=200°C

    T4=135°C

    T5=100°CT6= 85°C

    T1=450°C

    T2=300°C

    T3=200°C

    T4=135°C

    T5=100°CT6= 85°C

    T2A=280°CT2B=260°CT2C=230°CT2D=215°CT3A=180°CT3B=165°C

    T4A=120°CT3C=160°C