5-13 lab ventilation safety & energy efficiency€¦ · lab ventilation safety & energy...
TRANSCRIPT
Safe, Dependable and Energy Efficient Laboratories
5-13
Lab Ventilation Safety & Energy Efficiency
Exposure Control Technologies, Inc.
919-319-4290
Thomas C. Smith
Helping Facilities Ensure
Safe, Energy Efficient & Sustainable Laboratory Buildings
National Grid
781-907-1571
Fran Boucher
Safe, Dependable and Energy Efficient Laboratories
5-13
Agenda & Topics
Introduction
Laboratory Safety & Risks
Laboratory Hoods & Ventilation Systems
Lab Ventilation - Energy Use & Costs
2012 ANSI/AIHA Z9.5 Standard
Requirements & Recommendations
Lab Ventilation Safety & Energy Survey – A National Grid Program
Recommended for Owners, EH&S Personnel, Building Managers, Facility Engineers, and Energy Engineers associated with Laboratory Ventilation Systems in Research Laboratory Buildings.
Safe, Dependable and Energy Efficient Laboratories
5-13
• Safe
• Compliant with Codes & Standards
• Productive (Flexible)
• Energy Efficient
• Sustainable
Goal: High Performance Laboratories
Biology Labs (high containment) Chemistry Labs
Animal Vivariums
Nanotechnology Labs Cleanrooms
Radiological Labs
Safe, Dependable and Energy Efficient Laboratories
5-13
Laboratory Hazards
Risk of Adverse Health Effects
Inhalation Hazards
Airborne Materials
Toxicity
Generation Rate & Concentration
Duration of Exposure
Physical Hazards
Contact - Dermal Exposure
Fire & Explosion
Dose = Concentration x Duration
Safe, Dependable and Energy Efficient Laboratories
5-13
SAFETY
THINK
LAB OFFICE
DUCTS
FILTER
ROOF
FAN
STACK
SUPPLY
AIR
Proper Performance = Protection
Proper Performance = Compliance
Operation ≈ 60% Utility Costs
Cost = $ 3 to $ 9 per cfm-yr
Laboratory Hoods &
Ventilation Systems
Safe, Dependable and Energy Efficient Laboratories
5-13
Laboratories & Fume Hoods
Laboratories are rated one of the highest energy users by building type
Fume hoods are the primary means of protecting lab personnel
Fume hood performance can be affected by numerous factors
Average Annual Energy Cost of a Traditional Fume Hood = $5,000
– Equivalent to Three 2500 sq. ft. Houses
– Estimated lifetime cost of operation ≥ $150,000 (30 yrs)
Lights
Plug/Misc. HVAC 60%
10%
30%
Building Type Average Utility
Cost
Commercial/Office $ 1 / ft2
Hospital $ 3 / ft2
Laboratory $ 7 / ft2
Specialty Labs & Cleanrooms
≥ $ 15 / ft2
Safe, Dependable and Energy Efficient Laboratories
5-13
Evaluating Fume Hood Safety
Methods to Evaluate Containment Performance and Ensure Safe Hoods
Determine Operating Conditions
• Hood and Lab Inspection
• Face Velocity Measurements
• Cross Draft Velocity Tests
• VAV Response and Stability
• Flow Visualization Smoke Tests
• Tracer Gas Containment Tests
Determine Performance (Containment )
Tracer Gas
Ejector
Mannequin
Face Velocity Probe
Tracer Gas
Detector
Cross Draft Probe
Computer &
DAQ
ANSI/ASHRAE 110 “Method of Testing Performance of Laboratory Fume Hoods”
Safe, Dependable and Energy Efficient Laboratories
5-13
ECT, Inc. has conducted more than 30,000
ASHRAE 110 Tracer Gas Containment Tests
Test Results Demonstrate > 15% Failure
• Hood design - 20%
• Lab Design
• System Operation
• Work practices - 25%
Laboratory Hood Safety & Performance
Primary Factors Affecting Performance
Safe, Dependable and Energy Efficient Laboratories
5-13
Causes of Inadequate Performance
Improper:
• Design
• Operation
• Maintenance
• Use
Safe, Dependable and Energy Efficient Laboratories
5-13
ANSI/AIHA –Z9.5 - 2012
American National Standard for Laboratory Ventilation
Newly Revised & Published September 2012
Minimum Requirements and Best Practices
– Protect People
– Ensure Dependable Operation
– Operate Energy Efficient Labs
Recommendations & Specifications for New and
Renovated Laboratories
– Hood Design & Operation
– Laboratory Design
– Ventilation System Design
– Commissioning and Routine Testing
– Work Practices and Training
– Preventative Maintenance
Safe, Dependable and Energy Efficient Laboratories
5-13
Specifications for Safe & Energy Efficient Labs
Laboratory Hood Operation
– Construction Specs & Performance Criteria
Monitors & VAV Controls
– Types, Accuracy and Operating Modes
Laboratory Design & Operation
– ACH & Air Change Effectiveness
– Diffuser Type and Location
– Temperature & Humidity Control
Ventilation Design & Operation
– Duct Velocity & Static Pressure
– Stack Discharge
– Recirculation & Energy Recovery
Commissioning and Routine Tests
– ASHRAE/ANSI 110 “Method of Testing Performance of Laboratory Fume Hoods”
– Lab Environment Tests
– System Operating Mode Tests
Safe, Dependable and Energy Efficient Laboratories
5-13
Types of Laboratory Fume Hoods
Bench-Top
– Traditional Bypass
– Low Velocity / High Performance
– VAV – Restricted Bypass
Distillation
Floor Mounted (Walk-in)
Safe, Dependable and Energy Efficient Laboratories
5-13
Fume Hood Operation and Specifications
Sash Opening Configuration
• 100% Full Open
• Design Opening
• User Opening
Average Face Velocity
• 100 fpm (0.51 m/s) – Traditional
• 60 fpm (0.3 m/s) – High Performance
Airflow Controls
• CAV
• VAV
Exhaust Flow Supply Flow
Safe, Dependable and Energy Efficient Laboratories
5-13
• Full Open Sash
• Face Velocity: 60 - 70 fpm
• Equivalent or Better Containment than Traditional Fume Hoods @ 100 fpm
• Safe & Proven Technology
• Numerous Hood Manufacturers
– Lab Crafters
– Fisher Hamilton
– Kewaunee Scientific
– Labconco
– Air Master
– Others
• EPA Tested & Approved
High Performance Fume Hoods
Safe, Dependable and Energy Efficient Laboratories
5-13
Retrofit-Upgrade Traditional Fume Hoods
Renew/Refurbish Inefficient Hoods
Improve Safety & Containment
Reduce Flow and Energy Use
Typical Reduction = 20% to 40%
• Airfoil Sill
• Sash Handle
• Baffle
Upgrade Critical Components
Safe, Dependable and Energy Efficient Laboratories
5-13
Upgrade & Retrofit Fume Hoods
Safe & Sustainable Technology
Before After
Safe, Dependable and Energy Efficient Laboratories
5-13
Flow Monitors and VAV Controls
• Hood Monitors (Flow Measuring Device)
– Flow
– Velocity
– Pressure
• Flow Control Types
– Through the Wall Velocity
– Sash Position
– Occupancy
– Manual
VAV Modes
– Two State
– Full VAV
– VAV Hybrid
TTW
Velocity
Sensor
and
Hood
Monitor
Monitors are required on all fume hoods
Safe, Dependable and Energy Efficient Laboratories
5-13
VAV Flow Response & Stability
Good Containment
Poor Containment & Intermittent Escape
Measure
Slot Velocity
or
Exhaust Flow
Safe, Dependable and Energy Efficient Laboratories
5-13
VAV Flow Response and Stability
Sash Open
Sash Closed
VAV Terminal
Good Control & Containment
Poor Control & Containment
Safe, Dependable and Energy Efficient Laboratories
5-13
Minimum Flow for VAV Fume Hoods
1990s - EPA – 50 cfm / ft of Wh
2004 - NFPA 45
25 cfm / sq. ft. ws
2010 - Defers to ANSI Z9.5
2012 - ANSI Z9.5 (must be appropriate)
Internal ACH (150 ACH to 375 ACH)
150 ACH ~ 10 cfm / sq. ft. ws
375 ACH ~ 25 cfm / sq. ft. ws
• Containment • Dilution • Removal
Internal Conc. (Ci)
Duct Conc. (Cd)
Bench-Top
Fume Hood
Size - ft
Internal
Volume (Vh) -
ft3
Min Flow cfm
(NFPA)
ANSI Flow cfm
(375 ACH)
ANSI Flow cfm
(150 ACH)
4 29.6 180 180 70
6 48.2 300 300 120
8 66.9 410 410 160
Caution: ECT finds 150 ACH too low
Safe, Dependable and Energy Efficient Laboratories
5-13
Laboratory Airflow Specifications
Operating Mode
Min and Max Flow
Temperature Control
Dilution – ACH
Air Change Effectiveness
Room Pressure
Transfer Volume
- + Room Pressure
Qt = Qe – Qs Qt = Constant
Qe - Exhaust
Safe, Dependable and Energy Efficient Laboratories
5-13
Agency Ventilation Rate
OSHA 29 CFR Part 1910.1450 4-12 ACH
ASHRAE Lab Guides 4-12 ACH
UBC – 1997 1 cfm/ft2
IBC – 2003 1 cfm /ft2
IMC – 2003 1 cfm/ft2
U.S. EPA 4 ACH Unoccupied Lab - 8 ACH Occupied Lab
AIA 4-12 ACH
NFPA-45-2004 4 ACH Unoccupied Lab - 8 ACH Occupied Lab
NRC Prudent Practices 4-12 ACH
ACGIH 24th Edition, 2001 Ventilation depends on the generation rate and toxicity of the
contaminant and not the size of the room.
ANSI/AIHA Z9.5
Prescriptive ACH is not appropriate.
Rate shall be established by the owner.
Dilution is seldom effective – source capture preferred
Typical ACH Guidelines
Safe, Dependable and Energy Efficient Laboratories
5-13
Emissions in Labs Requiring Dilution
Escape from Lab Hoods
Improper Bench Top Procedures
Unventilated Equipment
Fugitive Emissions
– Chemical Bottles & Containers
– Gas Cylinders
Accidental Spills
Typical Generation Rates
<0.1 lpm to 10 lpm
Catastrophic Failure of a Gas Cylinder
1400 lpm
Safe, Dependable and Energy Efficient Laboratories
5-13
Specifying Airflow Rates for Labs
Air Change Rate (ACH)?
Evaluate hazardous emissions
Ensure appropriate laboratory hoods
Capture hazards at the source
Ensure air change effectiveness
Base airflow rates on:
– Hood Exhaust Requirements
– IAQ Requirements
– Comfort (Temperature)
– Pressurization/Isolation
Safe, Dependable and Energy Efficient Laboratories
5-13
Ventilation System Operating Specifications
Energy Savings Require Reducing
Total Building Flow • Max and Min Flows
• Exhaust Manifolds
─ Fan Redundancy
─ Emergency Power
• System Static Pressure
• Duct Transport Velocity
• Exhaust Stack Discharge
• VAV Control Capabilities
─ Diversity
─ Sensitivity
Safe, Dependable and Energy Efficient Laboratories
5-13
Stack Discharge and Plume Dispersion
Re-entrainment
Better Design
Stack Height ≥ 10 ft.
Stack Velocity ≈ 3000 fpm
Safe, Dependable and Energy Efficient Laboratories
5-13
Laboratory Ventilation Management Program
(LVMP)
Required By ANSI Z9.5
System Management and Sustainability Plan
– Organization and Responsibilities
– Effective Collaboration/Integration
– SOP’s for Testing and Maintenance
– Metrics and Monitoring
– BAS Utilization
Management of Change
Personnel Training
Cognizant Person
Safe, Dependable and Energy Efficient Laboratories
5-13
Critical Elements of a LVMP
• Building Information - Documentation and Specifications
• Management and Personnel (Roles and Responsibilities)
• Test and Maintenance Tasks
Schedule of Activities
Preventive & Repair Maintenance
─ AHUs /Exhaust Fans
─ Control Components (Flow Terminals, Sensors, dP Transducers)
System, Environment & Hood Performance Tests
─ System Operating Mode Tests (SOMTs)
─ Lab Environment Tests (LETs)
─ Lab Hood Tests
• BAS Utilization (Monitoring and Reports)
• Management of Change (MOC)
• Record Keeping
• Training Programs
Safe, Dependable and Energy Efficient Laboratories
5-13
Training of Personnel
Ensure Proper Work Practices
• Lab Personnel • Facility Maintenance • Building Operators
Safe, Dependable and Energy Efficient Laboratories
5-13
National Grid’s
Lab Ventilation Safety and Energy Survey
Meet With Key Stakeholders
Review Building Documentation
Survey Laboratories and Exposure Control Devices
Inventory Devices
Assess the Demand for Ventilation
Evaluate State of the Systems
Assess Conformance with ANSI/AIHA Z9.5
Identify Performance Improvement Measures
Identify Potential Energy Conservation Measures
Provide Written Report & Recommendations
Information
Collection
Expert
Analysis
High Value Report
Safe, Dependable and Energy Efficient Laboratories
5-13
Lab Ventilation Safety and Energy
Survey Report
Description of Building and Lab Ventilation Systems
Summary of Utilities
Identify Ventilation Safety Risks
Typically Recommended PIMs and ECMs
Replace or upgrade inappropriate hoods
Optimize airflow specifications (ACH)
Relocate / Replace air supply diffusers
Ensure proper space pressurization
Install monitors and upgrade/replace VAV controls
Improve exhaust configuration and optimize fan stacks
Install Variable Speed Drives
Develop a Lab Ventilation Management Plan & Train Laboratory Personnel
Safe, Dependable and Energy Efficient Laboratories
5-13
National Grid’s Laboratory Building Programs
Safe, Dependable and Energy Efficient Laboratories
5-13
National Grid’s
Lab Safety and Energy Programs
Customer Conducted
Lab Building Survey(s)
Identified/ Resolved
Safety Issues
Identified/ Reduced
Energy >15%
Developed/ Implemented
LVMP
State University in MA Private University in MA*
State University in RI* Private University in RI*
Pharmaceutical Research* Biomedical Research*
* = Projects in Progress Average Annual Energy Reduction ≥15%
Safe, Dependable and Energy Efficient Laboratories
5-13
END
QUESTIONS?
Exposure Control Technologies, Inc.
919-319-4290
Thomas C. Smith
National Grid
781-907-1571
Fran Boucher