    BUILDINGS MUST BREATHE!

    CONTINUOUS VENTILATORS

    Standard Size9" throat and 12" throat 10 foot sections. Other sizesavailable upon request. Low profile design can be used forsingle unit or continuous run installation with no disassem-bly.

    Integral DampersEasy-moving damper opens to any degree from fully opento completely closed.

    DesignAerodynamically proportioned to exclude weather pro-tects air passages and full outlet area.

    Bird ScreenFully protected by 4 x 4 mesh galvanized hardware cloth.

    ConstructionDurable 26 gauge exterior combined with internal compo-nents of 24, 20 and 18 gauge die formed sheet metal andmachined parts for long service life.

    FinishPre-painted or galvalume is standard. Other materials and

    finishes available upon request.Drainage AreaContinuous slot bottom of both sides of windbands.

    used on metal roofing systems roofs conform to MPs high standards and specifications which have been

    developed, tested and proven over many years. They provide an excellent value for the user.

  • 8/13/2019 4.4Continuous Vents

    2/16

    DIMENSIONS AND TECHNICAL DATAB

    A

    C

    D

    E

    THROAT

    BIRD SCREEN

    DIE-FORMED BAFFLE

    RAIN SHIELD

    DAMPER

    LIFTER ARM

    SADDLE STRAP

    SIDE SKIRT

    END CAP OF VENT END CAP OF VENT

    DRAIN AT MULTI-UNIT SPLICE

    ROOF PANEL MAJOR RIBNOTE:BREAK DRAIN ASSEMBLY TOFOLLOW EXACT ROOF SLOPE.

    END CAP OF VENT

    DRAIN AT CAPOF END VENT

    ROOF PANEL MAJOR RIB

    POP RIVET ENDCAP TO DRAINASSEMBLY

    PULL BAR CONNECTION:Install turnbuckles betweenadjacent pull bars. With thedampers in the closed position,adjust turnbuckles starting atone end of the run.

    PULL BARTURNBUCKLE

    STOVE BOLT

    DIMENSIONS (In Inches)

    Throat* A B C D E

    9 13 211

    4 141

    2 18 281

    4*12 17 2812 18 22 33

    SHIPPING WEIGHTS

    StandardSize Boxed Pkg. Size

    Crated

    9" 124 lbs 209 lbs 12412" X 1912" X 3012"

    12" 148 lbs 218 lbs 12412" X 23" X 35"

    * Other sizes available upon request.

    Chain-operated damper utilizes a rugged sash chain through chain locking device. Damper is spring-loaded to open and canbe adjusted to any opening from fully open to fully closed. Optional operator packages for multiple units or wall operation areavailable. (See below.)

    RAIN SHIELDDAMPEREND CAP

    LIFTER ARMGUIDE RODSPRING

    PIVOT BRACKET & SADDLE STRAPPULL BAR

    PULLEY AT FRAME OR WALL

    PULL BAR IN CLOSED POSITION

    TO CLOSE DAMPER, PULL CABLE

    2" TRAVEL

    STANDARD CABLE OPERATION

    RAIN SHIELDDAMPEREND CAP

    LIFTER ARMGUIDE RODSPRING

    CHAIN CATCH (OPT.)CHAIN WITH HANDLE

    PIVOT BRACKET &SADDLE STRAP

    PULL BAR

    OPTIONAL PULL CHAIN OPERATION(SINGLE UNITS ONLY)

    PULL CHAIN MUST BEREMOVED FOR CONTINUOUSRUN OPERATION

  • 8/13/2019 4.4Continuous Vents

    3/16

    L o u v e r s V e n t i l a t o r s T r i m R o o f C u r b s S p e c i a l t y I t e m s

    9" CONTINUOUS VENTILATOR SPECIFICATIONSVentilators are of low profile design to provide gravity type ventilation.

    Birdscreen is provided to prevent nesting and each unit contains flashing for eithersingle unit or continuous-run installation.

    Each unit is 9" x 10' with a base ventilating capacity of 2700 CFM at 20

    temperature differential with a 25' stack height.

    Exterior parts are 26GA. G90 galvanized, painted galvanized or galvalume.ASTMA446.

    Interior parts are all of G90 galvanized steel.

    Substructure consists of 10GA. saddle straps with interior baffles of 24GA.

    Pull bars and pivot brackets are of 20GA. Lifter arms and damper slides are of18GA.

    Manual operation is through activation of pull bar, which is attached to bell-cranked type lifter arms connected to damper with teflon coated pins throughdamper slides.

    Dampers are spring loaded to remain in open position until pull bar isoperated and locked in the closed position. Dampers operate in vertical manor.

    Birdscreen is 4x4 mesh galvanized hardware cloth.

  • 8/13/2019 4.4Continuous Vents

    4/16

    B

    A

    C

    D

    E

    THROAT

    DIMENSIONS (In Inches)

    Throat A B C D E4 614 1212 9 10 18

    9 13 2114 1412 18 2814

    12 17 2812 18 22 33

    18 2634 4558 3058 30 49

    24 3312 57 3838 3618 5818

    36 4712 8114 5358 55 8312

    SHIPPING WEIGHTS

    Size Boxed Standard Crated Pkg. Size

    9" 124 lbs 209 lbs 12412" X 1912" X 3012"

    12" 148 lbs 218 lbs 12412" X 23" X 35"

  • 8/13/2019 4.4Continuous Vents

    5/16

    WELDED FRAME VENTILATOR DIMENSIONS

    A A/2 B C D E F G H J K L M N P WT.

    15 712 39 2612 8 2234 1138 1138 978 5 612 712 1678 8 25

    18 9 4558 3058 1058 2634 1338 1338 11 578 814 9 1858 912 30 275#

    20 10 49 3258 1014 2834 1438 1438 1138 8 918 10 1734 9 33

    24 12 57 3838 1178 3312 1634 1634 1358 818 914 12 2112 11 3618 324#

    30 15 7018 45916 1438 41 2012 2012 14 912 1158 16 2658 1138 4914

    BE

    M

    A (THROAT)

    P

    H

    G L

    J

    F

    D

    C

    N

    BIRD SCREEN

    EXTERIOR FRAME

    RAIN SHIELD

    INTERIOR FRAME

    SADDLE STRAP

    SIDE

    SKIRT

    K

    WELDED FRAME RIDGE VENTILATORS

    NOTE: EXTERIOR AND INTERIOR FRAME MADE OF 18" X 1 12" X 1 12" ANGLE HOT-DIPPED GALVANIZED AFTER

    WELDING. ALL OTHER PARTS MADE OF 22 GA. SHEET METAL, STANDARD WHITE OR GALVALUME.

  • 8/13/2019 4.4Continuous Vents

    6/16

    Table of Capacities for Continuous Ventilators

    CAPACITY:

    To determine capacity per unit, multiply Base Rating by Temperature-Height Factor: CFM = Base x

    Temperature-Height Factor

    Based on fresh air intake area 11/2times ventilator throat area. Assumes 5 mph wind speed.

    Temperature-Height FactorsTemperature Difference Base Ratings

    Height 5 10 15 20 25 30 35 40 45 Size C.F.M.

    10' .37 .49 .58 .64 .70 .76 .81 .86 .95 4" 1200

    15' .42 .60 .71 .80 .86 .92 .99 1.05 1.09 9" 270020' .53 .70 .81 .92 .99 1.07 1.14 1.22 1.26 12" 3600

    25' .58 .77 .89 1.00 1.08 1.18 1.25 1.33 1.39 15" 4500

    30' .63 .83 .97 1.08 1.17 1.28 1.36 1.45 1.50 18" 5400

    35' .66 .87 1.02 1.14 1.24 1.35 1.44 1.51 1.58 24" 7200

    40' .70 .93 1.08 1.22 1.30 1.41 1.50 1.61 1.68 30" 9000

    45' 74 96 1 12 1 28 1 38 1 48 1 59 1 68 1 75 36" 10800

    MP

    L o u v e r s V e n t i l a t o r s T r i m R o o f C u r b s S p e c i a l t y I t e m s

  • 8/13/2019 4.4Continuous Vents

    7/16

    L o u v e r s V e n t i l a t o r s T r i m R o o f C u r b s S p e c i a l t y I t e m s

    METALLIC PRODUCTS CONTINUOUS VENTILATORDESIGN EVALUATION AND CERTIFICATION

    This is to certify that the construction of the Metallic Products 10ft. sections of ridge ventilators with 10ga. Base Straps, 24 ga. Baffles, and 26 ga. Sides, Ends, Skirts and Dampers will withstand wind loadsof 100 MPH when adequately supported by the roof panel to which it is attached. Minimum requiredattachment is No. 14 self tapping screw to the top of each major roof panel rib.

    Wind load is determined in accordance with the MBMA Design Manual procedure. The following analysis

    could be construed as Parts and Portions of the building structure, such as load supporting systems ofstructural roof panels, purlins, bracing, and framing.

    The typical installation procedure for vents is to fasten each side skirt to the roof panel with a minimumof 1-#14 STS @ 12" o.c. (2 fasteners per linear foot of vent). Various Manufacturers test data has indicatedthat the resistance of these fasteners exceeds the design values used by Metallic Products by a factorin excess of 2 1/2 to 1. This design value is 50 lbs. pull out and 100 lbs. shear per fastener when installedin 26 ga. galvanized panels of 50,000 psi minimum yield stress.

    The probable extreme standard condition would be a roof with mean height of 60 ft. and a slope between10 and 30 degrees (4/12 included).

    1. Assume the clear distance at the ventilator between roof sheets to be 24" max. (This is probablygreater than would occur for a 12" throat vent.)

    2. Assume total vent is in Z edge strip. Building would have to be at least 100 ft.wide and 25 ft.high at the eave.

    3. Velocity Pressure q = 30.4 PSF (100 MPH) (Table 5.2b in the MBMA Low Rise Building SystemsManual)

  • 8/13/2019 4.4Continuous Vents

    8/16

    Page 2

    METALLIC PRODUCTS CONTINUOUS VENTILATORDESIGN EVALUATION AND CERTIFICATION

    12" Standard Throat Ventilator: The 24 inch ridge opening results in 2 x 47.88 = 95.76 lbs. per ft. uplift onventilator or 47.88 lbs per fastener which is less than the 50 lbs. per fastener design stress. The ventilatoris less than 2 ft. high resulting in a shear stress of less than 50 lbs./fastener from an equal horizontal windload.

    The building design used to create this wind loading exceeds the dimensional parameters of moststandard buildings offered by Metal Building Manufacturers. The location of the vent at the very end of

    the building ridge (within the Z edge strip) is not unusual when continuous vents are used for the fullbuilding length. However, a more common arrangement is to place the vents, one in the center of eachbay or to begin the continous run, one ventilator back from the end wall peak.

    Evaluation conducted by:_______________________________ May 7, 1997John M. Reynolds, P.E.

  • 8/13/2019 4.4Continuous Vents

    9/16

    DATE:

    TITLE:

    PART:3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    1/4/99FLASHING

    WITHOUT DIE-FORMEDSKIRTS

    CONTINUOUS VENT

    DRAWING #2CV-01.6/ Rev. 03/00

    END CAP OF VENT

    DRAIN AT END OF VENT

    CAULK HERE

    POP RIVET END CAP TODRAIN ASSEMBLY

    ROOF PANEL MAJOR RIB

    END CAP OF VENT

    DRAIN AT MULTI-UNITSPLICE (WEEP)

    CAULK HERE

    ROOF PANEL MAJOR RIB

    NOTE:BREAK DRAIN ASSEMBLY TO FOLLOWEXACT SLOPE OF ROOF

    END VIEW

    SIDE

    SKIRT

    FASTENER

    CLOSURE WITH SEALANT T&B

    NOTES:BE SURE WEEPS ARE LEFT OPENFOR 5:12 AND UP ROOF PITCHES,THE TWO BOTTOM RIVETS MUST BEREMOVED BEFORE END SKIRT MAYBE PLACED ON VENT. REPLACE

    RIVET WITH SCREW.

    RIDGE VENT FLASHINGWITHOUT DIE-FORMED SKIRTS

  • 8/13/2019 4.4Continuous Vents

    10/16

    DATE:

    TITLE:

    PART:3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    END OF VENT DETAIL

    CONTINUOUS VENTILATOR

    DIE-FORMED SKIRT

    END SKIRT DETAIL ANDCONTINUOUS VENT SPLICE

    END CAP OF VENT

    CV-01.7 / Rev. 03/00

    END CAP OF VENT

    CHANNEL

    GUTTERTAPE SEAL

    ROOF PANEL

    GUTTER SUPPORT

    CHANNEL SUPPORT

    4/22/97

    DIE-FORMEDSKIRT APPLICATION

    CONTINUOUS VENT

    VFSS-1

  • 8/13/2019 4.4Continuous Vents

    11/16

    4/22/97

    FLAT SKIRTAPPLICATION

    CONTINUSOUS VENT

    DATE:

    TITLE:

    PART:3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    END OF VENT DETAIL

    CLOSURE (Not by MP)

    CONTINUOUS VENTILATOR

    FLAT SKIRT

    END SKIRT DETAIL ANDCONTINUOUS VENT SPLICE

    CLOSURE (Not by MP)

    END CAP OF VENT

    DRAIN AT END OF VENT

    CAULK HERE ROOF PANELMAJOR RIB

    POP RIVET ENDCAP TO DRAINASSEMBLY

    END CAP OF VENT

    CAULK HERE

    DRAIN AT MULTI-UNIT SPLICE

    CV-01.8 / Rev. 03/00

    ROOF PANELMAJOR RIB

  • 8/13/2019 4.4Continuous Vents

    12/16

    DATE:

    TITLE:

    PART:3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    1/04/99

    INSTALLATION

    DETAILS

    FLAT SKIRT

    CONTINUOUS VENT

    CV-01.9 / Rev. 03/00

    BIRD SCREEN

    DAMPER GUIDE RODBAFFLE

    RAIN SHIELDDAMPER

    DAMPER SLIDELIFTER ARMSADDLE STRAPPIVOT BRACKET

    SKIRTOPERATOR BAR

    THROAT

    END CAP

    PUNCH MARKS

    FIELD CUT

    6:12

    5:12

    4:12

    3:12

    2:12

    END CAP DETAILNOTE: DOTTED LINE INDICATES

    FIELD CUT FOR 6:12 ROOFSLOPE. OTHER SLOPES

    AS NOTED.

    BLIND RIVETS (2) REQD

    FOAM CLOSURE

    END SKIRT

    PEAK PANEL

    ROOF PITCH LESS THAN 1:12 INSTALLATION:INSTALL END SKIRT FOR 1:12 ROOF SLOPE AND FOAM CLOSURE WITHTAPE SEALER TOP AND BOTTOM.

    ROOF PITCH GREATER THAN 5:12 INSTALLATION:REMOVE TWO BOTTOM RIVETS BEFORE INSTALLING END SKIRT.REPLACE THE RIVETS WITH SHEETING SCREWS ONCE END SKIRT ISIN PLACE.

    PULL BAR CONNECTION

    DETAIL

    RAIN SHIELDDAMPEREND CAP

    LIFTER ARMGUIDE RODSPRING

    PIVOT BRACKET & SADDLE STRAPPULL BAR

    PULLEY AT FRAME OR END WALL

    PULL BAR IN CLOSED POSITION

    TO CLOSE DAMPER, PULL CABLE

    2" TRAVEL

    RAIN SHIELDDAMPER

    END CAP

    LIFTER ARMGUIDE RODSPRING

    CHAIN CATCH (OPT.)

    CHAIN WITH HANDLE

    PIVOT BRACKET &SADDLE STRAP

    PULL BAR

    STANDARD CABLE OPERATION

    OPTIONAL PULL CHAIN OPERATION(SINGLE UNITS ONLY)

    PULL CHAIN MUST BEREMOVED FOR CONTINUOUSRUN OPERATION

    L o u v e r s V e n t i l a t o r s T r i m R o o f C u r b s S p e c i a l t y I t e m s

  • 8/13/2019 4.4Continuous Vents

    13/16

    CONTINUOUS VENT OPERATORSDRAWING VEW-1

    DETAIL 3 - TYPE AOPERATOR #624 - HAND PULL-CABLE

    35 ft. Plastic Coated Cable2 Cable ClampsI Chain Catch2 Pulleys

    DETAIL 3 - TYPE BOPERATOR #634 - HAND PULL-CHAIN

    35 ft. Chain2 PulleysI Chain Catch

    DETAIL 3 - TYPE COPERATOR #618 - LEVER TYPE

    40 ft. Cable2 Pulleys2 Cable ClampsI Lever HandleMounting & Installation Hardware

    DETAIL 3 - TYPE DOPERATOR #632 - BOAT WINCH TYPE

    60 ft. Cable2 Pulleys

    OPERATOR #6161 Lever Handle Mounting Hardware

    OPERATOR #619 - EXT.50 ft. Cable3 Eye Bolts

    2 Cable Clamps

    OPERATOR #634A10 ft. ChainI PulleyI Chain Catch

    OPERATOR #634B4 ft. ChainI PulleyI Chain Hook

    SINGLE UNIT OPERATOR FORMONOVENT

    10 ft. Chain Installed

  • 8/13/2019 4.4Continuous Vents

    14/16

    3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    DATE:

    TITLE:

    PART:

    OCT. 1, 1983

    END WALL

    INSTALLATION

    CONTINUOUS VENT

    VEW-1

    OPERATOR A: 3/16" UNCOATED AIRCRAFT CABLE WITH CABLE KEEPER 3 UNITS MAX.

    OPERATOR B: NO. 35 ZINC COATED SASH CHAIN WITH CHAIN KEEPER 3 UNITS MAX.OPERATOR C: HAND LEVER TYPE 6 UNITS MAX.

    OPERATOR D: BOAT WINCH TYPE 12 UNITS MAX.

    CV-01.11 / Rev. 10/83

  • 8/13/2019 4.4Continuous Vents

    15/16

    OCT. 1, 1983

    SIDE WALL

    INSTALLATION

    CONTINUOUS VENT

    VSW-1

    3306 Ella Blvd.

    Houston, TX 77018(713) 688-6624 1-800-356-7746

    E-mail: [email protected]

    DATE:

    TITLE:

    PART:

    OPERATOR A: 3/16" UNCOATED AIRCRAFT CABLE WITH CABLE KEEPER 2 UNITS MAX.

    OPERATOR B: NO. 35 ZINC COATED SASH CHAIN WITH CHAIN KEEPER 2 UNITS MAX.

    OPERATOR C: HAND LEVER TYPE 5 UNITS MAX.

    OPERATOR D: BOAT WINCH TYPE 10 UNITS MAX.

    CV-01.12 / Rev. 10/83