400vdc distribution – deployment, components and best
TRANSCRIPT
400VDC Distribution – Deployment, Components and Best Practices for Safe Implementation
BJ Sonnenberg – Mgr Business Development Emerson Network Power David Geary – Director of Engineering Universal Electric Corp / StarLine dc Solutions Brian Davies - Director of Product Development Anderson Power Products
2
Common Perception Related to 400VDC
Perception of safety issues in higher voltage DC applications • Hazardous voltage • Arcing • No current zero crossing – difficult to break current • Grounding methods • Arc flash issue not well understood
3
Physiological Effects of DC and AC AC or DC above 30volts can be potentially dangerous and cause involuntary muscle action (tetanus)
Low frequency (50 to 60Hz) AC is 3 to 5 times more dangerous in this regard than DC of same voltage because:
• AC produces extended muscle contraction which can freeze the hand to the power source • DC produces a single contraction , which usually forces the hand away from the power source • AC can cause heart fibrillation , and once power is removed the heart is not likely to restart • DC makes heart still, once power is removed and the heart can restart
Figures are approximate and depend on individual’s body chemistry and other factors www.allaboutcircuits.com – volume1
4
Body Current/Duration Characteristics for Hand-to-Hand Pathway, IEC/TR 60479-5 - Hot Conductor to Ground
I - Normally no perception II - No dangerous physiological effect, risk of startle reactioIII - Risk of muscular reaction IV - Critical effects, risk of ventricular fibrillation
Average human body resistance =1500 ohm (200-400V)
208/230/277VAC - IV 120VAC - III
400VDC (one pole) – III
400VDC direct midpoint - III
400VDC midpoint 50kΩ - II
48VDC - II
RCD 30mA/200ms RCD –residual current device (in US and Canada also known as GFI or GFCI)
5
Safety: 400V DC Grounding High Resistance Midpoint Ground (HRMG)
• Human body current for line to ground is limited to 7.5mA (for 50kOhm resistor) IEC Zone II • No dangerous effects
• High resistance midpoint grounding (HRMG) makes 400V DC as safe as -48V DC with regard to electrical shock (line to ground)
• No arc flash to ground during single ground fault for HRMG • HRMG is widely used today in 110/220VDC networks in industrial, utility
and railway environments • Requires real-time ground fault detection
© 2011 NTT/NTT Facilities/France Telecom/Emerson Network Power Intellectual Property. All rights reserved
R=50kΩ
AC In
400V DC Power System
+200V DC
-200V DC
R
Loads
400V DC
R
200V DC
200V DC
ᴖᴖ
6
Causes of Arcing in AC and DC
Bad connection in a circuit carrying high current - AC ≈ DC (most cases) Disconnection of components and equipment in power distribution - DC is worse Unintentional short circuit of power conductor to earth or another conductor- AC=DC
Mechanism of arc ignition : If the electrical field strength created by potential difference between two separated conductors exceeds a certain threshold , the energy will be sufficient to ionize the gas in the gap. For arc ignition a potential difference as low as 30V is enough. Electric arcing occurs and is tolerated at normal load conditions in : Connectors Switches Spark gaps
7
DC arc faults were more persistent, due to the lack of a periodic zero-crossing. As such, from a local perspective, high arc currents (175A) damaged copper electrodes and support structures and may be considered a fire hazard.
AC open series faults dissipated within a few cycles of the point of discontinuity. However, fast-acting transients were observed in both the gap voltage and current waveforms. With magnitudes up to four times the bus voltage, these spikes may be cause for alarm as this would exceed voltage ratings for various passive components within system power electronics.
From the results presented herein: DC open series faults are electrically benign, but mechanically hazardous; AC open series
faults are electrically malign, but mechanically benign.
From a dc system perspective, the lack of considerable spikes in the gap voltage or current waveforms is an electrical advantage. Despite the fact open series faults persist for a much longer duration, if power electronics could effectively be utilized for fault isolation, the impact on other distribution laterals would be minimized.
Future research will explore dc arc detection, fault clearing strategies, power downstream of limiting sources, and dc arc model development. Additionally, safety considerations will remain a strong focus.
H.B. Estes, A. Kwasinski, R.E. Hebner, F.M. Uriarte, and A.L. Gattozzi Department of Electrical & Computer Engineering
The University of Texas at Austin,Center for ElectromechanicsAustin, TX 78758, USA
Open Series Fault Comparison in AC & DC Micro-grid Architectures (ref 1)
8
Elements of Safe Deployment – Designing for Safety and Reliability
• Elements of safe design • System components selection • Equipment construction –plug in approach (minimizes
installation errors ) • System architecture and best practices – hot plug-in approach • Grounding • Procedures –installation, operating, maintenance – NFPA 70E
9
Connectors for DC Powered IT Equipment
Arc breaking technologies
Saf-D-Grid connector
Other connectors
Standardization update
10
Arc Breaking Technologies 1) Fujitsu - DC circuit breaker magnetic arc quenching technology Not practical, high cost and the size are not compatible with IEC 320
2) Delta - 4th contact pair triggers “Hot Swap” secondary circuitry of the power supply to avoid breaking arc Does not support IT devices lacking “Hot Swap” capability
Cost of 4 wire cable higher than 3 wire
PDU, Cord and Power Supply must be by same manufacturer to achieve Safety Agency Listing
3) APP - Connector geometries naturally suppress arcing & contacts have sacrificial arcing area Robust contacts increase price versus IEC320 inlet
3 wire cable keeps price of power cords down
All of the above technologies allow safe disconnection of the powered load.
11
Saf-D-Grid (SDG)
2 flat surfaces have greatest resistance to arcing SDG’s flat wiping contacts dampen initiation and
continuation of arcing
Over wipe of connector housings quenches arcing Insulators eliminate line of sight between contacts upon un-
mating
Large tracking distances between contacts Prevents arcing products from developing arcing between
lines or ground
Sacrificial contact area Prevents dampened arcing damage from effecting electrical
performance
Large selection of options Flush-mount Receptacle
Mid flange Receptacle
Ultra-short Receptacle (< IEC320)
Standard Plug
Wide “T” Latch Plug
Right Angle Plug
UL, IEC, PSE or CCC approved cordage
Specialty Cords SDG to IEC320 C20
SDG to IEC320 C14
SDG to Delta (Linetek)
Approvals UL 1977 Recognized &
UL 817 Listed IEC 61984 Certified CCC Approved
12
Other Connectors Fujitsu Plug and Socket with integral
miniature DC circuit breaker Socket has switch for plug lock and
power on/off Compatible with specification in
development by IEC Socket specified for fixed installation
usage only, no portable multiple outlets or extension cords allowed
Too big for power supply connection Delta (Rong Feng, Linetek) Plug and Socket with 4th contact pair
to trigger switching off power supply 4 wire configuration not supported
by pending IEC specification or EMerge alliance standard
Rong Feng Connector
Fujitsu Connector
13
DC Connector Standards & Specifications • EMerge Alliance Data/Telecom Center Standard 1.03
• APP Saf-D-Grid approved standard connector
• UL 2695 DC Rated Attachment Plugs And Outlet Devices Intended For Use With Information Technology And Telecommunications Equipment Installed In Restricted Access Locations
• APP Saf-D-Grid internally evaluated to all specifications. APP has differed UL evaluation until UL 2695 is raised from “Investigation” to “Standard”.
• IEC TS63275 D.C. Plugs And Socket-Outlet For ICT Equipment Installed In Data Centres And Telecom Central Offices
• Draft Technical Specification covers plug and sockets for fixed installation. Fujitsu, Legrand form factor
• Work on Appliance Connector standard will begin in TC23SCG Nov 2014. Brian Davies will convene Ad Hoc committee to develop Technical Specification
14
380V DC CIRCUIT PROTECTION
Tmax Molded Case
Emax DC
380VDC FUSES 20-100 Amp, 700 V dc
22 X 58 MM
Product Highlights UL 489 Listed UL 489B Listed TUV Certified IEC/EN 60947-2 Temperature stable hydraulic/magnetic overcurrent sensing technology Optional relay trip circuit, permitting remote operator system shut down
See video: https://www.youtube.com/watch?v=6---aEbkyAE
16
380V DC CIRCUIT BREAKERS
17
SYSTEM TESTING by Emerson Network Power: System Performance under Faults and Arcing
Tests performed to evaluate short circuit performance (line to line) and impact on main bus voltage recovery time under different operating conditions Difference in circuit breaker and power distribution performance
vs. 48VDC and AC Comparison of 3 different circuit breakers Impact of cable inductance and circuit breaker rating
Arcing Understanding of risk scenario Comparison of different plugs Impact on bus voltage when disconnecting the load
18
Comparison of 63A Circuit Breaker Performance from 3 Suppliers at Short Circuit Test – Battery Source (AC UPS Battery) – No Load to Short (UL 1012 supplementary breakers ) Cable: 5m x 70mm²+0.5m x 25mm², each pole .Battery: 30x12V=360V/25Ah. Rectifiers disconnected
ABB Schneider Nader
400V
1250A 400V 1100A 400V 1350A
S282UC-K C60H-DC NDB2Z-63
Test results are comparable , Nader has lowest short circuit impedance Voltage recovery on main bus well within power supply hold-up time < 10ms
No major voltage overshoot on main bus. © 2013 Emerson Network Power Intellectual Property. All rights reserved
Voltage recovery on main bus 1.9ms ~2ms ~2ms
19
Power Plugs in 400VDC Disconnection Tests
APP Fujitsu Molex Saf-D-Grid EXTreme LPH Power
Power Modules
Signal Module
400VDC/20A
Micro switch
400VDC/10A 250VDC/30A per contact in Power Module
20
APP Saf-D-Grid plug(20A) Disconnection
380V
5A 10A
5A load, normal disconnect 10A load, normal disconnect 10A load, slow disconnect
10A
380V 380V
- The APP plug operates satisfactory up to 20A - No arcing (current transients) between the pins at distinct and ”normal” speed disconnection - No visible arcing outside the plug - Clear tendency for arcing at slow or non distinct disconnection - The plug disconnection of 5-25A loads has no impact on DC voltage on the 400V Bus
21
Conclusions from Testing on Equipment and System Level
400VDC distribution vs 48V and AC 2 – pole circuit breaker in 400VDC
The same safety requirements as for 230VAC distribution
Rectifier output capacitor is the main energy source (not the battery) for ceasing circuit breaker in hard short circuit
400VDC circuit breakers Similar and stable performance
Similar ceasing times to 48V and AC circuit breakers
400VDC plugs Commercially available today and with certifications
Safe operation with regard to arcing
22
400VDC Distribution System Design – Best Practices Summary • Safe design of conversion equipment • Flexible , plug in distribution – eliminates installation errors • Busway with pluggable interfaces • Minimize field terminal type connections • Use connectors to interconnect equipment • Use factory made distribution units – avoid field improvisation
23
• Plug-in components • Ability to service major elements without system shutdown • Shielding and protective access • Compartmentalize serviceable components
DC UPS Constructions Principles for Safe Equipment Design 120kW Example
24
Advantage of Busway Distribution
25
Adding, Servicing, Changing components in an electrical system are not always easy!
• Permissible to install on energized busway. • Grounding is established prior to voltage being applied. • Busway is “finger safe”. However, there is no reason to place hands or tools up inside the access slot. • No routine maintenance required ?
Adding, Servicing, Changing circuits using is easy and safe! THE BUSWAY ARC FLASH ADVANTAGE
Busway vs Discrete Distribution
Circuit plug in
26
Busway Layout Options
27
Rack Distribution – Power Strips
• Similar construction to AC strips • Loads can be hot plugged in or disconnected
28
Distribution Implementation Strategy – System Architecture Plug and play approach Limit personnel access to live components Allow easy and live replacement of failed components through creative distribution system architecture Maintain continuous operation under multiple
faults
29 SOURCE: EMERSON NETWORK POWER 2012
Output Connectivity Options
400VDC UPS
DistrA
DistrB
Battery
Bus duct Wire in conduit
Battery
400VDC UPS
Server Rack
Server Rack
A B
A B
Bus duct
Battery
400VDC UPS
Server Rack
A B
Bus duct
800A CB limit 230kW
Distribution options: 1.Fuses – shorter clearing time 2.Breakers – easier to operate 3.Bus duct plug-ins – space, scalability
30
Plug in Concept Benefits
Hot plug in maintenance concept
• 2N+ 1 UPS configuration • Busway with 2 End Feeds (Redundant) • Busway plug In units are added as racks are added (live) • Racks can be removed without system shutdown • During routine maintenance personnel is never exposed to live
parts : • Server level • Rack level
Hot plug –in point
Server
A side B side
Fixed structure
31
DC System Architectures Between BICSI Classes - Examples
32
Practical Implementation - Example
BICSI 002 Class F1,F2,F2+,F3 ? Equivalent
BICSI 002 Class F3, F4 Equivalent – using single or double DC busway
Single utility feed shown. For BICSI Class F3 and F4 two independent utility feeds would be employed.
33
Fault Characteristics in AC and DC Circuits
• In low voltage AC distribution ground faults are substantially more common than phase to phase faults – ref. 4 ,although statistics are difficult to come by and require substantial research. In statistics cited for circuit elements that involve cable conductors (IEEE Std 493-2007), 99% of failures due to arcing faults involved ground. Remaining 1% did not (ref. 4). It is generally acknowledged that ground faults constitute at least 80% of all electrical faults.
• It is reasonable to assume that the case would be similar for low voltage DC distribution, therefore preventing arcing faults to ground is the most effective strategy to eliminate majority of electrical faults (HRMG grounding and plug-in connections)
• NFPA 70E assumes that line to ground fault will ultimately evolve to L-L fault , but with HRMG that is not the case.
34
Grounding Basics
35
ETSI EN 301 605 (Grounding and Bonding)- Summary
• Both system earthing arrangement comply with relevant safety requirements
• IF the continuity of operation is placed in the forefront THEN the symmetrical IT system ±200 Vdc with earthed high-ohmic mid-point is the first choice. In cases where an IT system is used for reasons of continuity of supply, automatic disconnection is not usually required on the occurrence of a first fault (single fault) to an exposed-conductive-part or to earth. This is valid on condition that an Insulation Monitoring Device (IMD) indicates the first fault by an audible and/or visual signal which shall continue as long as the fault persists.
• IF similar system earthing arrangement as for today’s -48 Vdc system is requested THEN the TN-S system +400 Vdc may be chosen.
IT system with earthed high-ohmic mid-point TN-S system with earthed negative line terminal
Source - Ericsson
36
By ETSI ’rejected’ system earthing arrangement
Both system earthing arrangements below are extracted from IEC 60364-1
Asymmetrical, one power source: Normal operation: L+ = +400 Vdc, L- ≈ 0 V Disadvantage: Very hard to detect the difference of a correct L- ≈ 0 V (via high-ohmic resistance) and a real earth fault L- = 0 V due to a short-circuit between L- and earth.
Symmetrical, two power sources: Normal operation: L+ = +200 Vdc, L- = -200 Vdc Disadvantage: Series connection of two 200 V power sources L+ = +200 Vdc and L- = -200 Vdc
IT systems - asymmetrical and symmetrical
Source - Ericsson
37
Grounding Conclusions High resistance midpoint grounding (HRMG) makes ≈400VDC as
safe as 48VDC with regard to electrical shock (line to ground)
No arc flash to ground during single ground fault for HRMG
HRMG is widely used today in 110/220VDC networks in industrial, utility and railway environments
The HRMG technology is already well established and proven
No RCD required, but there is a need of ground fault monitoring in HRMG
No EMI problems reported from a dozen of POC sites
NTT, NTT-F, FT and Emerson Network Power have selected high resistance midpoint grounding for 400VDC
© 2011 NTT/NTT Facilities/France Telecom/Emerson Network Power Intellectual Property. All rights reserved
38
OSHA , NFPA70E Overview What is NFPA 70E?
"Standard for Electrical Safety in the Workplace," outlines the specific procedures and practices to be followed for (OSHA compliance and) safety when working on live equipment.
What is Covered?
Safety-related work practices associated with electrical energy during activities such as installation, inspection, operation, maintenance and demolition of electric equipment.
39
12
Qualified Person: A qualified person shall be trained and knowledgeable in the construction and operation of equipment or specific work method and be trained to recognize and avoid the electrical hazards that might be present with respect to that equipment or work method.
Such person shall also be familiar with the proper use of the special precautionary techniques; personal protective equipment including arc flash suit; insulating and shielding materials; and insulated tools and test equipment. A person can be considered qualified with respect to certain equipment and methods but still be unqualified for others.
NFPA -70E Safety Requirements
40
NFPA -70E Safety Requirements • DC requirements added in 2012
• For DC systems >100VDC NFPA 70 requires an arc flash hazard risk analysis and appropriate PPE (Personnel Protective Equipment) when working on energized systems (Art.130.5).It also sets worker protection boundary distances.
• Article 130.4 also requires a shock hazard analysis to be performed
• NFPA 70E refers to two methods to determine DC arc flash and PPE requirements(Art 130.5B) – calculation methods and table method . Calculation methods require calculating the incident energy. Table method is a simple determination of PPE requirement based on system voltage and available short circuit current . The calculation methods ,especially Ammerman method are much more accurate.
• Two calculated methods are referenced in Annex D :
• Maximum Power Method (per Doan)
• DC arc model (Ammermann)
41
NFPA 70E Tables for Determining DC Arc Flash
Look up method table Calculation method table
42
Sample Calculation for 120kW System 120kW system with 60 min battery Faults in locations 1-3 do not produce a significant hazard and are omitted in the analysis 4 cabinets =
1hr back-up
Fault #5 - single battery cabinet when serviced with battery breaker opened
43
Results per Ammerman Method
Risk Category 2 Risk Category 0
AC input not considered in this analysis
44
Strategies for Safety Enhancements in DC Distribution – On the Roadmap • Use inherent current limiting characteristics of electronic converters in
distribution system design • DC powered lighting and HVAC • Further improvement of rectifier efficiency • New topologies • New components (GaN , SIC) • Improved ground fault detection and location • Battery/energy storage advances , including storage located at or near
loads • Natural gas as primary power source • Electronic and hybrid breakers and switches
Euro-team to develop semiconductor-based DC circuit breaker david manners 1st July 2014 A publicly-funded European team lead by Infineon is to try and develop a semiconductor-based DC circuit breaker. Losses in power grids and electric devices are between 5% and 7% smaller with direct current than with alternating current. Direct current also makes it possible to more efficiently feed electric energy from regenerative sources into power grids and energy storage and to improve grid stability; with direct current it would be possible to build much more compact electric devices. Funded by the German Federal Ministry of Education and Research (BMBF), the research project called “NEST-DC” aims to investigate the foundations of a semiconductor-based and completely electronic circuit breaker for DC power grids and applications.
45
•Conclusions To assure safety in electrical distribution AC or DC : • Use proper components with ratings & listings selected for safe
operation
• Assure selectivity of protection scheme
• Use proper grounding methods in distribution
• Select system architecture allowing full isolation of distribution components for ease o maintenance
• Use plug-in concept where possible , minimize field installation work
• Adhere to and follow safety procedures
Under most operating and maintenance conditions a
400VDC system is safer than an equivalent AC system
46
To Continue Discussion Please , join us at Intelec 2014 , Vancouver , booth 201 You will see a fully assembled small demo of a 400VDC system and will have an opportunity to talk to leading industry experts.
47
References – Safety Related 1. Open Series Fault Comparison in AC&DC Microgrid Applications – H.B Estes et al. – 978-1-4577-1250-0/11/$26.00 2011 IEEE
2. A DC Arc Model for Series Faults in Low Voltage Microgrids – Fabian M. Uriarte et al.– IEEE Transactions on Smart Grid, Vol.3 , No. 4, December 2012 3. NFPA70E Standard 2012 4. Fault Characteristics in Electrical Equipment – Eaton white paper TP08700001E – September 2011
5 . http://www.interfire.org/features/electric_wiring_faults.asp
6. A Study of the Safety of the DC 400 V Distribution System – Masatoshi Noritake et al , Intelec 2010
7. Grounding Concept Considerations and Recommendations for 400VDC Distribution System - Keichi Hirose , Toshimitsu Tanaka , Sylvain Person , BJ Sonnenberg , Marek Szpek , Intelec 2011 8. Phillips, J. ,Chapter 8 , “DC Arc Calculations, in Complete Guide to Arc Flash Hazard Calculation Studies , Scottsdale AZ Brainfiller, Inc. , 2011 9. Case Study – DC Arc Flash and Safety Considerations in a 400 VDC Architecture Power System Equipped with VRLA Battery - Michael , M. Krzywosz
, Intelec 2015 (not released yet)
10. Arc Flash Calculations for Exposure to DC Systems - Doan D.R. ,Industry Applications , IEEE Transactions on Volume 46 , Issue 6, 2010 11. DC arc models and Incident Energy Calculations , - Ammerman R.F. , Industry Applications , IEEE Transactions on Volume 46 , Issue 5, 2010 12. AC&DC Power Distribution for Data Centers ,TGG Presentation At the Green Grid forum -2012
13. ANSI/BICSI 002-2011 , Data Center Design and Implementation Best Practices
14. 380VDC Architectures for the Modern Data Center White paper , EMerge Alliance 2013 15. ETSI EN300-132-3-1, ITU-T L1200 , Emerge Alliance Data/Telecom Center standard 16. ETSI EN 301 605 , Earthing and Bonding standard
17. IEEE Std 493 – 2007 (Gold Book) , Design of Reliable Industrial and Commercial Power System
48
Back-up
49
Agency Status / Standards
Standardization Work Closely Harmonized to Agree on Aligned Global Standards
• 400V system standards currently released or under development through international efforts UL (several products listed today) – cover all distribution system components ETSI EN 300 132 -3-0 – power interface standard – RELEASED ETSI EN 301605 – earthing and bonding for 400VDC systems - RELEASED ITU – (ITU-T l.1200) – adopted ETSI voltage levels - RELEASED IEC / IEEE – working group in place – new DC UPS standard
ATIS – voltage levels standard in development SCTE – committee started NEC – Current edition applies to both AC and DC : Wiring , protection , safety EMerge Alliance - Focus on site and system interfaces – RELEASED YD/T 2378-2011 (China Standard) 240VDC Direct Current Power Supply System for Telecommunications – RELEASED Planned update for 336V (380VDC) mid to late 2014 NEMA / EPRI – work in progress
• Standards also needed for and driven by renewable resource deployments
50
Understanding “Arc Flash”
Simply put, an arc flash is a phenomenon where a flashover of electric current leaves its
intended path and travels through the air from one conductor to another, or to ground.
The results are often violent and when a human is in close proximity to the arc flash, serious
injury and even death can occur.
Arc flash can be caused by many things including:
Dust
Dropping tools
Accidental touching
Condensation
Material failure
Corrosion
Faulty Installation
Three factors determine the severity of an arc flash injury:
Proximity of the worker to the hazard
Temperature
Time for circuit to break
OSHA Definition of Arc Flash
An arc flash is the light and heat produced from an electric arc supplied with sufficient electrical energy to cause substantial damage, harm, fire, or injury. Electrical arcs experience negative resistance, which causes the electrical resistance to decrease as the arc temperature increases. Therefore, as the arc develops and gets hotter the resistance drops, drawing more and more current (runaway) until some part of the system melts, trips, or evaporates, providing enough distance to break the circuit and extinguish the arc.[
OSHA definition Wikipedia definition
51
Such persons permitted to work within the limited approach boundary of exposed energized electrical conductors and circuit parts operating at 50 volts or more, shall at a minimum, be additionally trained in all of the following: Distinguish exposed live parts from other parts of electrical
equipment. Determine nominal voltage of the exposed parts. Be aware of minimum approach distances to exposed parts. Decision-making process necessary to determine the degree and
extent of the hazard and the personal protective equipment and job planning necessary to perform the task safely
NFPA 70E Article 110.2(D)(1)(b)(4)
Training requirements from OSHA and NFPA70E
11