40 ohm ground fault resistance – still applicable? · nov. 8 – 10, 2016 tom guttormson, pe...
TRANSCRIPT
![Page 1: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/1.jpg)
40OHMGROUNDFAULT RESISTANCE–STILLAPPLICABLE?
MNPowerSystems ConferenceNov.8– 10,2016
TomGuttormson,PEPrincipleTechnologyEngineer
![Page 2: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/2.jpg)
2
130Kmembercustomers1,000squaremilesterritory44substations(48transformers)12.5kV- 9,121milesofline92%residentialbycustomerSystempeakdemand550MWWholesale PowerSupplier – GreatRiverEnergy
![Page 3: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/3.jpg)
3
OUTLINE
q Definition– groundfaultresistanceq Basisforresearchq Historyofgroundfaultresistancevalueq Practicesamongutilitiesq Recenttestingandpublicationsq Conclusion
![Page 4: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/4.jpg)
4
GROUNDFAULTRESISTANCE
Resistancethroughreturnpathbetweenfaultedconductorandtransformersource
A
C
B
N
![Page 5: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/5.jpg)
5
SIMPLEDIAGRAM
ZL
ZN
ZLoadZFaultZT
IFault
ZFault IFaultBoltedFault:0Ω 3470ampsFaultimpedance:40Ω 173amps
Assume:15MVAtransformerwithZ=5.75%Line impedance ZL=1.4+j1.7Ω
1mile4/0ACSR3miles1/0ACSR
7200volts/40Ω =180amps
![Page 6: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/6.jpg)
6
BASISFORSTUDY:
2011– 2015Project–• ReplacedKSlinefusewithTfuses• Auditsystem:fix&optimizecoordination
Ongoingchallenge:• Protectingfor“minimumfault”• “Standard”hasbeen40ohms• Ifwecouldsqueezeinonemorelayeroffusesizes…
Question:dowehave touse40?Howabout30???
![Page 7: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/7.jpg)
7
40
140AGnd Trip 140AGnd Trip
400APhase Trip400APhase Trip
164min fault 164min fault
65
![Page 8: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/8.jpg)
8
DISTRIBUTIONTAPS
65A
15A
25A
40A
15A
![Page 9: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/9.jpg)
9
140Gnd Trip
400Phase Trip
164min fault
15 4025
Limitedto40ampfuse
![Page 10: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/10.jpg)
10
DISTRIBUTION– LOOPEDTAP
ILoad ILoad25amps 25amps
![Page 11: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/11.jpg)
11
Question:Isthe“40ohmrule”stillapplicable?
Goal:• Investigateopportunity toapplylowervaluetoimprovesectionalizing
coordinationConsiderations:• Continueconformancewithindustrypractices• Safetyisnotcompromised
https://www.youtube.com/watch?v=WdekH0UnWXk
![Page 12: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/12.jpg)
12
GROUNDFAULTIMPEDANCEHISTORY
• Studyandengineering report– EdisonElectric Institute(EEI)&Bell Telephonein1937
• Groundfaultimpedance testingwithstagedfaults– measured impedance inrangeof5to20ohms
• Someutilitycompaniesadopted20ohmsasstandard– oneadopted40ohms
REApublishedBulletin61-2in1953;recommended:• 40ohmsforsubstationtransformers5000kVAandless• 30ohmsofOHlines&10-20ohmsforUGlinesfortransformers>5000kVA
Manycoopsadopted40ohmsasstandard
![Page 13: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/13.jpg)
13
MORERECENTRESEARCH/PUBLICATIONS
REABulletin61-2rescindedin1992,replaceby1742E-102“GuideforSectionalizingDistributionLines”(10/23/2012)• OHline30-40ohms>5000kVAtransformer,40ohms5000kVAandless• UGline10-20ohms• “40ohmrule”was intendedtobeguild line,notcast-in-stonerule
CRNStudy1997– GroundFaultImpedanceValuesforSystemProtection• SameconclusionsasRUS bulletin(didnotconductactualtesting)• CRN&otherdocumentsstate“othervaluesandmethodsmaybeapplied”
- uptotheCoop’sengineer
![Page 14: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/14.jpg)
14
RECENTTESTING…
• IEEEandABBresearch– testingbydroppingenergizelineonvarioussurfaces
• HighimpedancefaultsR>>40ohms– cannotbedetectedbytraditionalmeans
![Page 15: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/15.jpg)
15
GROUNDCONTACTRESISTANCE
Burke, James. Hard to Find Information About Distribution Systems. 5th Edition. ABB Inc. Consulting. Raleigh, NC. August 2002
![Page 16: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/16.jpg)
16
FAULTCURRENTAMPSBASEDONRESISTANCE
Surface Current(Amps)fromFigure3
Correspondingimpedance (Ω)
Dryasphalt,concreteordrysand <5 >1400
Wetsand <20 >360
Drysod 20 360
Wetsod 40 180
Drygrass 25 288
Wetgrass 45 160
Reinforced concrete 70 103
![Page 17: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/17.jpg)
17
VALUES/METHODSUSEDACROSSUTILITIES
Ø 40ohms(acrossanycoops,basedonREA/RUSBulletins)
Ø Calculatefaultcurrentusingmultiplierofloadcurrent
Ø Applypercentageofboltedfaultcurrent
Ø Nofaultimpedance(assumeboltedfault)
![Page 18: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/18.jpg)
18
MEASUREDFAULTCURRENTS- CONNEXUS
Beganrecordingfaultcurrentvaluesin2011Findingsfromfallenlines:
• Higherfaultcurrentvalues(“low”impedance) <<30ohms
• Lowerfaultcurrentvalues(“high”impedance) >>40ohms
![Page 19: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/19.jpg)
19
CONCLUSIONS
Ø ZfaultvaluesaregenerallyNOTinthe30to40ohmrange- basedontestingbyothersand internalmeasurements
Ø “GroundFaultImpedanceisadesignnumberforpurposeofmodelingandprotection/coordinationdesign”– not intended torepresentactual impedances andcurrentvalues
Changingfrom40to30ohms:ü enablesbettersectionalizing >enhancedreliabilityü will notmeasurablycompromise publicsafetyü Stillcomplieswithacceptable industrypractices
![Page 20: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/20.jpg)
20
65
560APhase Trip560APhase Trip
200AGnd Trip 200AGnd Trip
15 25 40 65
212min fault 212min fault
![Page 21: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/21.jpg)
21
TEAM
Contributions by:DaveAndersonJeanneAdventMikeFelberJohnGasalEricJacksonWaltLepistoNickLoehleinJimPaulsonJonWahlgrenMattYsethDeniseZurn
![Page 22: 40 OHM GROUND FAULT RESISTANCE – STILL APPLICABLE? · Nov. 8 – 10, 2016 Tom Guttormson, PE Principle Technology Engineer. 2 130K member customers ... 140 A Gnd Trip 140 A Gnd](https://reader035.vdocuments.us/reader035/viewer/2022070906/5f7abad45635ba6fab453da3/html5/thumbnails/22.jpg)