4-way blow ceiling-suspended type - daikin comfort

28
4-Way Blow Ceiling-Suspended Type FXUQ-PVJU EDUS391437A-F15 202010 Engineering Data 60 Hz

Upload: others

Post on 04-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

4-Way Blow Ceiling-Suspended TypeFXUQ-PVJU

EDUS391437A-F15202010

Engineering Data

60 Hz

Page 2: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort
Page 3: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

1

FXUQ-PVJU EDUS391437A-F15

Table of Contents

1. FeaturesandBenefits ................................................................................22. Specifications .............................................................................................33. Dimensions .................................................................................................54. CenterofGravity ........................................................................................65. Piping Diagrams .........................................................................................76. Wiring Diagrams .........................................................................................87. Electric Characteristics .............................................................................108. SafetyDevicesSetting ............................................................................. 119. CapacityTables ........................................................................................12

9.1 CoolingCapacityatTe:43°F(6°C) .................................................129.2 HeatingCapacity .............................................................................129.3 CorrectionFactorforCoolingCapacityatTe:48°F(9°C) ...............12

10.AirVelocityandTemperatureDistributions(ReferenceData) ..................1310.1CoolingOperation ...........................................................................1310.2HeatingOperation ...........................................................................17

11.SoundLevels(ReferenceData) ...............................................................2112.Accessories ..............................................................................................23

12.1OptionalAccessories(forUnit) .......................................................23

Page 4: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

2

FXUQ-PVJU EDUS391437A-F15

1. Features and Benefits

Theunique4-wayceiling-suspendedcassetteisanidealsolutionforroomswithoutafalseceiling,orminimalspaceaboveafalseceiling,whereadaptivecomfortcontrolispreferred.

TheoptionalSensorKit(occupancyandsurfacetemperature)togetherwithairtemperaturesensorandadvancedcontrolfunctionsenablestheunittoprovideanexceptionalcomfortlevel,energyefficiency,andflexibility.

� Verylowunitheightofunder8”makesitanidealsolutionforschool,shops,restaurantsandofficeswithnoorlowfalseceilings

� OptionalSensorKitenablesinputfromthreeroomsensorstoprovideoptimizedoccupantcomfortandefficiency

� Stylishunitblendseasilywithanyinterior,astheairlouverscloseentirelywhennotinoperation � Lowenergyconsumptionthankstoaspeciallydevelopedsmalltubeheatexchanger,DCfanmotoranddrainpump

� Individualairlouvercontrol-oneormorelouvercanbeeasilyclosedviatheremotecontrollerwhenrequired

� Idealforbothnewandexistingbuildings � Canalsobemountedpartiallyrecessedinafalseceiling � Sameappearanceandsizeforallcapacitymodels

Page 5: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

3

FXUQ-PVJU EDUS391437A-F15

2. Specifications

4-way blow ceiling-suspended type

Model FXUQ18PVJU FXUQ24PVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V

1,3Coolingcapacity Btu/h(kW) 18,000(5.3) 24,000(7.0)

2,3Heatingcapacity Btu/h(kW) 20,000(5.9) 27,000(7.9)

Casing/Color Resin/Freshwhite Resin/FreshwhiteDimensions:(H×W×D) in.(mm) 7-13/16×37-3/8×37-3/8(198×950×950) 7-13/16×37-3/8×37-3/8(198×950×950)Coil(crossfincoil)

Rows×Stages×FPI 3×10×21 3×10×21Face area ft²(m²) 3.55(0.330) 3.55(0.330)

Fan

Model QTS48D11M QTS48D11MType Turbofan TurbofanMotoroutput W 46 46

Airflowrate(H/M/L) cfm (m³/min) 795/689/565(22.5/19.5/16.0) 795/689/565(22.5/19.5/16.0)

Drive Directdrive Directdrive

Temperaturecontrol Microprocessorthermostatforcoolingandheating

Microprocessorthermostatforcoolingandheating

Soundabsorbingthermalinsulationmaterial Polyethylenefoam Polyethylenefoam4Soundpressurelevel(referencedata)(H/M/L) dBA 40/38/36 40/38/36

4Soundpowerlevel(referencedata)(H/M/L) dB 58/56/54 58/56/54

Weight lbs(kg) 58(26) 58(26)

Piping connections

Liquidpipes in.(mm) f1/4(f6.4)(flareconnection) f3/8(f9.5)(flareconnection)Gaspipes in.(mm) f1/2(f12.7)(flareconnection) f5/8(f15.9)(flareconnection)

Drain pipe in.(mm) VP20(externaldia.1(26),internaldia.13/16(20))

VP20(externaldia.1(26),internaldia.13/16(20))

Safetydevices Fuse FuseRefrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series

StandardaccessoriesOperationmanual,Installationmanual,Paper

patternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,

Clampmetal,Conduitmountingplate

Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,

Clampmetal,Conduitmountingplate

Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:

Returnairtemperature:80°FDB(26.7°CDB),67°FWB(19.4°CWB) Outdoortemperature:95°FDB(35.0°CDB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)

2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB(21.1°CDB). Outdoortemperature:47°FDB(8.3°CDB),43°FWB(6.1°CWB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)

3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,

thesevaluesmaybehigherasaresultofinstallationconditions.

C:3D090219A

Page 6: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

4

FXUQ-PVJU EDUS391437A-F15

4-way blow ceiling-suspended type

Model FXUQ30PVJU FXUQ36PVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V

1,3Coolingcapacity Btu/h(kW) 30,000(8.8) 36,000(10.6)

2,3Heatingcapacity Btu/h(kW) 34,000(10.0) 40,000(11.7)

Casing/Color Resin/Freshwhite Resin/FreshwhiteDimensions:(H×W×D) in.(mm) 7-13/16×37-3/8×37-3/8(198×950×950) 7-13/16×37-3/8×37-3/8(198×950×950)Coil(crossfincoil)

Rows×Stages×FPI 3×10×21 3×10×21Face area ft²(m²) 3.55(0.330) 3.55(0.330)

Fan

Model QTS48D11M QTS48D11MType Turbofan TurbofanMotoroutput W 106 106

Airflowrate(H/M/L) cfm (m³/min) 1,095/918/742(31.0/26.0/21.0) 1,095/918/742(31.0/26.0/21.0)

Drive Directdrive Directdrive

Temperaturecontrol Microprocessorthermostatforcoolingandheating

Microprocessorthermostatforcoolingandheating

Soundabsorbingthermalinsulationmaterial Polyethylenefoam Polyethylenefoam4Soundpressurelevel(referencedata)(H/M/L) dBA 47/44/40 47/44/40

4Soundpowerlevel(referencedata)(H/M/L) dB 65/62/58 65/62/58

Weight lbs(kg) 60(27) 60(27)

Piping connections

Liquidpipes in.(mm) f3/8(f9.5)(flareconnection) f3/8(f9.5)(flareconnection)Gaspipes in.(mm) f5/8(f15.9)(flareconnection) f5/8(f15.9)(flareconnection)

Drain pipe in.(mm) VP20(externaldia.1(26),internaldia.13/16(20))

VP20(externaldia.1(26),internaldia.13/16(20))

Safetydevices Fuse FuseRefrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series

StandardaccessoriesOperationmanual,Installationmanual,Paper

patternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,

Clampmetal,Conduitmountingplate

Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,

Clampmetal,Conduitmountingplate

Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:

Returnairtemperature:80°FDB(26.7°CDB),67°FWB(19.4°CWB) Outdoortemperature:95°FDB(35.0°CDB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)

2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB(21.1°CDB). Outdoortemperature:47°FDB(8.3°CDB),43°FWB(6.1°CWB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)

3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,

thesevaluesmaybehigherasaresultofinstallationconditions.

C:3D090219A

Page 7: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

5

FXUQ-PVJU EDUS391437A-F15

3. Dimensions

FXUQ18-36PVJU

3D09

0217

A

Page 8: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

6

FXUQ-PVJU EDUS391437A-F15

4. Center of Gravity

FXUQ18-36PVJU

4D090212

Unit: in. (mm)

Page 9: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

7

FXUQ-PVJU EDUS391437A-F15

5. Piping Diagrams

FXUQ18-36PVJU

Unit:in.(mm)Model Gas Liquid

FXUQ18PVJU f1/2(f12.7)

f1/4(f6.4)

FXUQ24PVJUFXUQ30PVJUFXUQ36PVJU

f5/8(f15.9)

f3/8(f9.5)

C: 4D034245R

Page 10: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

8

FXUQ-PVJU EDUS391437A-F15

6. Wiring Diagrams

FXUQ18-36PVJU

C: 3

D09

0218

NO

TES

1.

: T

ERM

INAL

BLO

CK

:

CO

NN

ECTO

R

:

FIEL

D W

IRIN

G2.

IN C

ASE

USI

NG

CEN

TRAL

REM

OTE

CO

NTR

OLL

ER, C

ON

NEC

T IT

TO

TH

E U

NIT

IN A

CC

OR

DAN

CE

WIT

H T

HE

ATTA

CH

ED IN

STAL

LATI

ON

MAN

UAL

.3.

IN C

ASE

OF

MAI

N/S

UB

CH

ANG

EOVE

R, S

EE T

HE

INST

ALLA

TIO

N M

ANU

AL A

TTAC

HED

TO

REM

OTE

CO

NTR

OLL

ER.

4. S

YMBO

LS S

HO

W A

S FO

LLO

WS:

BLK

: BLA

CK

RED

: RED

BLU

: BLU

E W

HT:

WH

ITE

YLW

: YEL

LOW

GR

N: G

REE

N O

RG

: OR

ANG

E B

RN

: BR

OW

N P

NK:

PIN

K.5.

WH

EN C

ON

NEC

TIN

G T

HE

INPU

T W

IRIN

G F

RO

M O

UTS

IDE,

FO

RC

ED O

FF O

R O

N/O

FF C

ON

TRO

L O

PER

ATIO

N C

AN B

E SE

LEC

TED

BY

THE

REM

OTE

C

ON

TRO

LLER

. SEE

INST

ALLA

TIO

N M

ANU

AL F

OR

MO

RE

DET

AILS

.6.

CLA

SS 2

WIR

E

Page 11: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

9

FXUQ-PVJU EDUS391437A-F15

FXUQ18-36PVJUINDOORUNITA1P PRINTEDCIRCUITBOARDC105 CAPACITOR(M1F)F1U FUSEHAP FLASHINGLAMP(SERVICEMONITORGREEN)M1F MOTOR(INDOORFAN)M1P MOTOR(DRAINPUMP)M1S·M2SM3S·M4S MOTOR(SWINGBLADE)

R1T THERMISTOR(AIR)R2T·R3T THERMISTOR(COIL)S1L FLOATSWITCHV1R DIODEBRIDGEX1M TERMINALBLOCKX2M TERMINALBLOCKY1E ELECTRONICEXPANSIONVALVEZ1F NOISEFILTERZ1C FERRITECOREPS POWERSUPPLYCIRCUITSENSORKITA3P PRINTEDCIRCUITBOARDA4P PRINTEDCIRCUITBOARDCONNECTORFOROPTIONALPARTSX35A CONNECTOR(POWERSUPPLYFORADAPTOR)X81A CONNECTOR(SENSORKIT)

C:3D090218

Page 12: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

10

FXUQ-PVJU EDUS391437A-F15

7. Electric Characteristics

FXUQ18-36PVJU

ModelPowersupply IFM Input(W)

Hz Volts Voltagerange MCA MOP kW FLA Cooling HeatingFXUQ18PVJU

60 208/230V Max.253V Min. 187 V

0.6 15 0.046 0.5 90 73FXUQ24PVJU 0.6 15 0.046 0.5 90 73FXUQ30PVJU 1.4 15 0.106 1.1 200 179FXUQ36PVJU 1.4 15 0.106 1.1 200 179

Symbol:MCA:Min.CircuitAmps(A)MOP:Max.OvercurrentProtectiveDevice(A)kW: FanMotorRatedOutput(kW)FLA: FullLoadAmps(A)IFM: IndoorFanMotor

Note:1.Voltagerange Unitsaredesignedtooperateonlyattheratedvoltageprovidedinthetableabove.

2.Maximumallowablevoltageunbalancebetweenphaseis2%.3.MCA/MOP MCA=1.25×FLA MOP≤4×FLA (Nextlowerstandardfuseraring.Min.15A)

4.SelectwiringsizebasedontheMCA.

C:4D090214A

Page 13: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

11

FXUQ-PVJU EDUS391437A-F15

8. Safety Devices Setting

Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrintedcircuitboardfuse 250V,3.15A 250V,3.15A 250V,3.15A 250V,3.15ADrainpumpthermalfuse °F(°C) – – – –Fanmotorthermalprotector °F(°C) – – – –Fanmotorthermalfuse °F(°C) – – – –

C:3D090213

Page 14: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

12

FXUQ-PVJU EDUS391437A-F15

9. Capacity Tables9.1 Cooling Capacity at Te: 43°F (6°C)

Model

Indoorairtemp.°FWB(°CWB)(Te:43°F(6°C))61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH

FXUQ18PVJU 14.2 11.8 16.1 12.9 18.0 13.7 18.4 13.6 18.6 13.0 18.9 12.8 FXUQ24PVJU 19.0 15.4 21.5 16.9 24.0 18.0 24.5 17.8 24.8 17.0 25.3 16.6 FXUQ30PVJU 23.7 18.8 26.8 20.7 30.0 22.1 30.6 21.8 31.0 20.9 31.6 20.2 FXUQ36PVJU 28.4 22.1 32.2 24.2 36.0 26.0 36.7 25.7 37.2 24.7 37.9 23.6

TC: Totalcapacity:MBHSHC:Sensibleheatcapacity:MBH

Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.

2. showsratedcondition.

9.2 Heating Capacity

Model

Indoorairtemp.°FDB(°CDB)(Tc:115°F(46°C))62(16.7) 65(18.3) 68(20.0) 70(21.1) 72(22.2) 75(23.9)

TC TC TC TC TC TCMBH MBH MBH MBH MBH MBH

FXUQ18PVJU 23.3 21.9 20.7 20.0 19.3 18.1 FXUQ24PVJU 31.5 29.5 28.0 27.0 26.0 24.5 FXUQ30PVJU 39.7 37.1 35.3 34.0 32.7 30.9 FXUQ36PVJU 46.7 43.7 41.5 40.0 38.5 36.3

TC:Totalcapacity:MBH

Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.

2. showsratedcondition.

9.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)

Refertothecorrectionfactortablebelowwhenamini-splitindoorunitisconnectedtoaVRVHeatPumpsystemusingaBranchPortbox.

ModelIndoorairtemp.°FWB(°CWB)(Te:48°F(9°C))

61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)TC SHF TC SHF TC SHF TC SHF TC SHF TC SHF

FXUQ18PVJU 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ24PVJU 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ30PVJU 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035FXUQ36PVJU 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035

TC: TotalcapacitySHF:Sensibleheatfactor

Page 15: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

13

FXUQ-PVJU EDUS391437A-F15

10. Air Velocity and Temperature Distributions (Reference Data)10.1 Cooling OperationFXUQ18PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ18PVJU (Cooling operation)Air flow direction : Horizontal

Air temperature distribution of FXUQ18PVJU (Cooling operation)Air flow direction : Horizontal

Page 16: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

14

FXUQ-PVJU EDUS391437A-F15

FXUQ24PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ24PVJU (Cooling operation)Air flow direction : Horizontal

Air temperature distribution of FXUQ24PVJU (Cooling operation)Air flow direction : Horizontal

Page 17: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

15

FXUQ-PVJU EDUS391437A-F15

FXUQ30PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ30PVJU (Cooling operation)Air flow direction : Horizontal

Air temperature distribution of FXUQ30PVJU (Cooling operation)Air flow direction : Horizontal

Page 18: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

16

FXUQ-PVJU EDUS391437A-F15

FXUQ36PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ36PVJU (Cooling operation)Air flow direction : Horizontal

Air temperature distribution of FXUQ36PVJU (Cooling operation)Air flow direction : Horizontal

Page 19: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

17

FXUQ-PVJU EDUS391437A-F15

10.2 Heating OperationFXUQ18PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ18PVJU (Heating operation)Air flow direction : Down

Air temperature distribution of FXUQ18PVJU (Heating operation)Air flow direction : Down

Page 20: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

18

FXUQ-PVJU EDUS391437A-F15

FXUQ24PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

8.9 ft(2.7 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ24PVJU (Heating operation)Air flow direction : Down

Air temperature distribution of FXUQ24PVJU (Heating operation)Air flow direction : Down

Page 21: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

19

FXUQ-PVJU EDUS391437A-F15

FXUQ30PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ30PVJU (Heating operation)Air flow direction : Down

Air temperature distribution of FXUQ30PVJU (Heating operation)Air flow direction : Down

Page 22: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

20

FXUQ-PVJU EDUS391437A-F15

FXUQ36PVJU

Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.

5.6 ft/s (1.7 m/s)

4.9 ft/s (1.5 m/s)

4.3 ft/s (1.3 m/s)

3.6 ft/s (1.1 m/s)

3.0 ft/s (0.9 m/s)

2.3 ft/s (0.7 m/s)

1.6 ft/s (0.5 m/s)

1.0 ft/s (0.3 m/s)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

80.6°F (27°C)

79°F (26°C)

77°F (25°C)

75.2°F (24°C)

73.4°F (23°C)

71.6°F (22°C)

69.8°F (21°C)

68°F (20°C)

10.5 ft(3.2 m)

0.0 ft(0.0 m)

0.0 ft(0.0 m)

26.2 ft(8.0 m)

Air velocity distribution of FXUQ36PVJU (Heating operation)Air flow direction : Down

Air temperature distribution of FXUQ36PVJU (Heating operation)Air flow direction : Down

Page 23: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

21

FXUQ-PVJU EDUS391437A-F15

11. Sound Levels (Reference Data)

FXUQ18-24PVJU

4D090216A

Page 24: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

22

FXUQ-PVJU EDUS391437A-F15

FXUQ30-36PVJU

4D090215A

Page 25: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

23

FXUQ-PVJU EDUS391437A-F15

12. Accessories12.1 Optional Accessories (for Unit)

Option Note FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUBlockingmaterialkitfor2-waydischarge KDBHP49B140Airoutletblockingdecorationpanel KDBTP49B140Replacementlonglifefilter KAF5511D160

C:3D090253A

Page 26: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort
Page 27: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort
Page 28: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any inquiries, please contact your local importer, distributor and/or retailer.

©All rights reserved 10/20 FS

●Specifications, designs and other content appearing in this brochure are current as of October 2020 but subject to change without notice.