4> - voltimum · 2013. 7. 5. · fp200 gold® bs7629-1:2008 installation fire resistant cables...

52

Upload: others

Post on 09-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,
Page 2: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Prysmian FP100® is the original fire resistant single core cable for use in metal conduits or trunking to achieve a highly robust fire resistant wiring system. It maintains circuit integrity during a fire both when tested in free air or in a metallic conduit. When burnt, it produces very low levels of smoke and virtually no (less than 0.5%) acidic gases, thus safeguarding human life and protecting equipment.

Through the use of a dual layer insulation system, FP100® offers fire resistance combined with abrasion and damage resistance, making it an excellent choice both for upgrading existing conduit based systems to current essential safety circuit standards or new installations.

Systems based upon standard pvc cables, even when protected by metal conduit, have been shown to fail within minutes in a fire. Therefore they are no longer permitted by BS5839-1 or BS5266-1 for fire alarm or emergency lighting systems, as they do not ensure prolonged operation in the event of a fire.

> Prysmian FP100® is Loss Prevention Certification Board (LPCB) listed as a fire resistant cable. The LPCB range approval is given on the basis of (i) satisfactory testing at an enhanced voltage of 600/1000V to BS6387 category CWZ when tested in steel conduit and the conduit is considered as the metallic layer required by BS6387, for those sizes capable of fitting within the test conduit, and (ii) satisfactory testing to IEC60331-21 at an enhanced temperature of 950°C for those sizes too large to fit in the test conduit.

Additional tests have demonstrated the ability of FP100® to achieve a 120 minute rating (PH120) to BS EN50200 and a 120 minute rating to BS8434-2 when tested in a steel conduit. These tests demonstrate the ability of FP100® to meet the fire resistance requirements necessary for use in "enhanced" installations in accordance with BS5839-1:2002 and "Cable systems with an inherently high resistance to attack by fire" in accordance with BS5266-1:2005.

Prysmian FP100® cables are manufactured under an ISO9001 Quality Management System certified by BASEC and LPCB.

> Prysmian FP100® may be considered as a low smoke conduit wire to BS7211 for the purposes of installation, and should be installed in accordance with BS7671/IEE Wiring Regulations, or any other appropriate national regulations. It is suitable for installation in surface mounted or embedded conduits and trunking, or other similar fixed protected installations. For surface systems, the use of a metallic conduit or trunking is recommended to ensure integrity of the system in the event of fire. For fully embedded systems protected by a non combustible layer, non metallic conduit or trunking may be used.

Temperature Range-25 to +90ºC≠

Bending Radiusup to 8mm diameter r=4D above 8mm diameter r=6D

Mechanical impactRequires protection

Fire PerformanceBSEN60332-1-2

FlexibilitySemi-flexible

Halogen FreeBSEN50267-2-1

Low Smoke EmissionsBSEN61034-2

Fire ResistantIEC 60331-21

BS6387 Category CWZ*EN50200 PH120*BS8434-2 120min*

*When tested in Steel Conduit

Certificate No 077c

Page 3: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

* Sizes 1.5 - 10mm2 are rated at 450/750V.Installation methods for current rating “Enclosed in conduit on a wall or in trunking” in accordance with BS7671/IEE Wiring Regulations. Minimum recommended installation temperature -5°C.The tabulated ratings are based upon a 30°C ambient temperature at 90°C operating temperature.For other ambient temperatures or where several circuits are grouped together, the following rating factors should be applied.

> Essential safety circuits where the cable is protected by metal conduit or trunking.

> May be used for emergency lighting, fire alarm systems not requiring a twisted cable or other essential services.

CONDUCTOR

Plain annealed copper stranded (class 2)

conductor for flexibility.

PRIMARY INSULATIONMineral ceramic (Mica/Glass) fire resistant tape.

SECONDARY INSULATION90°C high performance cross linked mineral filled insulation.

o red o brown o black o yellow o orange

o grey o blue green/yellow

Other core colours available on request

Temperature rating factors

Rating factors for groupings

Nominal cross

sectional area

mm2

Approximate cable

weight

kg/km

Maximum conductorresistance

at 20°C

ohms/km

Current rating

DC or single phase AC

Amps

Current rating Three

phase AC

Amps

Volt drop DC

mV/A/m

Approximate overall

diameter

mm

Short circuit rating(1 sec)

Amps

Volt drop Single

phase AC

mV/A/m

Volt drop Three

phase AC

mV/A/m

Single Core

1 .5* 3.5 26 12.1 215 23 20 31 31 27

2.5* 4.1 38 7.41 360 31 28 19 19 16

4* 4.6 54 4.61 570 42 37 12 12 10

6* 5.2 75 3.08 860 54 48 7.9 7.9 6.8

10* 6.6 120 1.83 1425 75 66 4.7 4.7 4

16 7.7 180 1.15 2275 100 88 2.9 2.9 2.5

25 9.0 270 0.727 3375 133 117 1.85 1.9 1.65

35 10.0 360 0.524 5000 164 144 1.35 1.35 1.15

50 11.7 490 0.387 7150 198 175 0.99 1.05 0.9

70 13.2 680 0.268 10000 253 222 0.68 0.75 0.65

95 15.3 940 0.193 13575 306 269 0.49 0.58 0.5

120 16.8 1160 0.153 17150 354 312 0.39 0.48 0.42

150 18.7 1440 0.124 21450 393 342 0.32 0.43 0.37

185 20.8 1800 0.0991 26450 449 384 0.25 0.37 0.32

240 23.5 2350 0.0754 34325 528 450 0.19 0.33 0.29

300 27.3 3000 0.0601 42925 603 514 0.155 0.31 0.27

400 32.5 3970 0.0470 57225 683 584 0.120 0.29 0.25

500 36.0 4980 0.0366 71525 783 666 0.093 0.28 0.24

630 40.0 6340 0.0283 90125 900 764 0.072 0.27 0.23

Ambient Temperature°C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Number of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Page 4: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Ref:FP1

00

/PY/0

8/0

7

UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002

Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireSO50 6YUUnited Kingdom

For further information please see our dedicated FP website:www.fpcables.co.uk

www.prysmian.co.uk

Overseas Sales enquiriesTel: +44 23 8029 5481Fax: +44 23 8029 5465

Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]

Page 5: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP200 GOLD®

FIRE RESISTANT CABLES

Page 6: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP200 GOLD® BS7629-1:2008

INSTALLATION

DATA CAPABILITY

APPROVALS

FP200 GOLD®

FIRE RESISTANT CABLES

> The original highly durable and dressable, easy to terminate and install fire resistant cable, using the unique InsuditeTM damage resistant insulation system. Approved for fire detection and fire alarm critical signal paths to BS5839-1:2002+A2:2008 and voice alarm systems to BS5839-8:2008 in ‘standard’ application areas, and emergency lighting systems to BS5266-1:2005.

The changes to cable test methods and requirements first introduced by BS5839-1:2002+A2:2008 “Fire detection and fire alarm systems for buildings - Part 1: Code of practice for system design, installation, commissioning and maintenance” mean that fire resistant cables must now be approved against new test requirements.

> In addition to approvals to BS7629-1 and BS6387 Category CWZ, FP200 Gold® has received BASEC and LPCB approval to BS5839-1:2002 for ‘standard’ applications. This includes approval to BS EN 50200 Class PH30 and the new integrated fire, shock and water test BS8434-1 for 30 minutes. FP200 Gold® is also approved to BS EN 50200 Class PH60 as required by BS5266-1:2005.

All Prysmian FP200Gold® cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

> FP200 Gold® has excellent data/signal transmission characteristics making it ideal for voice alarm, addressable and networked systems.

> In accordance with BS5839-1 and BS5266-1 requirements, cables must be supported by a fixing that can withstand the same fire conditions as the cable. To meet this requirement the use of Prysmian AP LSOH® coated metal P-clips or the new FP FirefixTM rapid fixing system is recommended.

FP200Gold should be installed in accordance with BS7671/IEE Wiring Regulations and/or any other appropriate national regulations or codes. It is suitable for indoor and outdoor installation in suitably protected environments and particularly appropriate for surface wiring, direct burial in plaster, tray or other installations requiring a dressable product.

TemperatureRange

-20 to +70˚C

Bending RadiusFixed r=6D

Mechanical ImpactMedium

Fire PerformanceBS EN 60332-1-2BS EN 50266-2-4

FlexibiltyRigid

Halogen FreeBS EN 50267-2-1

Low Smoke EmissionsBS EN 61034-2

Fire ResistanceBS6387 Category CWZ

BS EN 50200 PH30 & PH603

BS EN 50200 Annex E

Certificate No 077fCertificate No 077k

CABLE CHARACTERISTICS

Page 7: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Two core

1.03 1/1.13 8.0 78 18.1 13 15 44 AP7 251/GL2520 UFPNF02

1.5 1/1.38 8.1 93 12.1 16.5 19.5 29 AP7 251/GL2520

2.5 1/1.78 9.5 140 7.4 23 27 18 AP9 251/GL2520 -

4.0 7/0.85 11.6 195 4.6 30 36 11 AP11 252/GL2520 -

Three core

1.03 1/1.13 8.2 88 18.1 13 15 44 AP7 251/GL2520 UFPNF02

1.5 1/1.38 8.4 116 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04

2.5 1/1.78 10.4 180 7.4 23 27 18 AP10 252/GL2520 -

4.0 7/0.85 12.3 248 4.6 30 36 11 AP12 252 -

Four Core

1.03 1/1.13 8.5 107 18.1 13 15 44 AP8 251/GL2520 UFPNF04

1.5 1/1.38 10 143 12.1 16.5 19.5 29 AP9 251/GL2520 -

2.5 1/1.78 11.9 225 7.4 23 27 18 AP11 252/GL2520 -

4.0 7/0.85 13.5 310 4.6 30 36 11 AP13 254

1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative.3 BS5266-1:2005 clause 9.2.3 states a minimum cross-sectional area of conductor of 1.5mm2

FP200 Gold® is also available in multi-core versions (7,12 & 19 core) Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.

KEY APPLICATIONS > Fire detection and fire alarm systems for buildings> Voice alarm systems> Emergency lighting> Other essential service circuits

CABLE DESCRIPTION

CONDUCTORPlain annealed copper solid (1.0 - 2.5 mm2) or stranded (4.0 mm2) circular conductor complying with BS EN 60228 class 1 or class 2.

INSULATIONHigh performance damage resistant InsuditeTM.British Standard Type EI5.

CORE IDENTIFICATION HARMONISED CORE IDENTIFICATION:o o brown-blue | o o o brown-black-greyo o o o blue-brown-black-grey

NON HARMONISED CORE IDENTIFICATION:o o red-black | o o o red-yellow-blueo o o o black-red-yellow-blue

Non harmonised colours to special order.

SCREEN/CPC Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor which provides automatic screen earthing.

SHEATH Robust thermoplastic LSOH sheath; Colour - White or Red. Other colours to special order. For external exposure the use of a white sheath is recommended.

Nominal

cross

sectional

area

mm2

Conceptual

Construction

no./mm

Mean

overall

diameter

mm

Approximate

cable

weight

kg/km

Maximum

conductor

resistance

at 20°C

ohms/km

Current

rating DC or

single phase

AC

Enclosed

Amps

Current

rating DC or

single phase

AC

Clipped direct

Amps

Volt drop

DC or single

phase

AC

mV/A/m

1 LSOH®

fixing

clips

2 Nylon

LSOH®

gland

Recommended accessories

Colour - White or Red

FP FirefixTM

fixing

clips

Notes to table

FIRE RESISTANT CABLES 300/500V

Temperature ratings factor

Rating Factors for Groupings

Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Number of circuits 2 3 4 5 6 7

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

UFPNF01*UFPNF02

* Single clip

Page 8: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

UK Sales enquiries

Tel: 0845 767 8345

Fax: 023 8029 5465

UK Technical helpline

Tel: 023 8029 5222

Fax: 023 8029 5002

[email protected]

Prysmian Cables & Systems Limited

Chickenhall Lane

Eastleigh

Hampshire

SO50 6YU

United Kingdom

For further information please see

our dedicated FP website:

www.fpcables.co.uk

www.prysmian.co.uk

Overseas Sales enquiries

Tel: +44 23 8029 5481

Fax: +44 23 8029 5465

Overseas Technical helpline

Tel: +44 23 8029 5481

Fax: +44 23 8029 5002

Information hotline

Tel: +44 (0) 23 8029 5029

Fax: +44 (0) 23 8029 5437

[email protected]

Re

f:FP

20

0G

old

/06

/09

Page 9: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Mechanical Impact Medium

Temperature Range

-20 to +70°C

Fire ResistanceBS 6387 Category CWZ

BS EN 50200 PH30BS EN 50200 Annex E

Low Smoke EmissionsBS EN 61034-2

Halogen Free BS EN 50267-2-1

Flexibility Rigid

Fire Performance BS EN 60332-1-2BS EN 50266-2-4

Bending Radius Fixed r=6D

FP200 Gold® Multicore

BS7629-1:2008

>

>

>

>

FIRE RESISTANT CABLES

Plain annealed copper solid (1.0 - 1.5 mm2) or stranded

(2.5 mm2) circular conductor complying with BS EN 60228

class 1 or class 2.

High Performance damage resistant InsuditeTM.

British Standard Type EI5.

Laminated aluminium tape screen bonded to sheath and in contact with tinned annealed coppper 0.5mm2 drain wire which provides automatic screen earthing.

Conductor

Insulation

Screen

Core Identifi cation

Sheath Robust thermoplastic LSOH sheath

Colour - White or Red. Other colours to special order

For external exposure the use of a white sheath isrecommended.

>

Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465

www.fpcables.co.uk

Ref: FP200Gold_Multi/01/09

Certifi cate No 077aCertifi cate No 077b

7-12-19 cores white with printed number.

Key Applications > Fire detection and fi re alarm systems for buildings

Voice alarm systems

Emergency lighting

Other essential service circuits

Page 10: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

1 Recommended clip spacing 300 mm and 400 mm vertical. 2 Brass gland may be used as an alernative.3 This size is not included in the latest (2008) edition of BS7629-1 and is therefore manufactured to BS7629-1:1997Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.Minimum recommended installation temperature 0°C.*The tabulated rating is as a two core and may be used where its number of cores carrying current does not exceed the square root of the total number of cores.

Notes to table

Temperature rating factors

Rating Factors for Grouping

Ambient Temperature °C 25 30 35 40 45 50 55 60

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

Prysmian FP200 Gold® Multicore Cable

Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465

www.fpcables.co.uk

Ref: FP200Gold_Multi/01/09

1.0 1/1.13 12.1 196 18.1 13* 15* 44 AP12 252

1.5 1/1.38 13.3 249 12.1 16.5* 19.5* 29 AP13 252

2.5 7/0.67 16.3 387 7.4 23* 27* 18 AP16 254

Nominal cross

sectional area

mm

Conceptual construction

no./mm

Mean overalldiameter

mm

Approximatecable weight

kg/km

Maximum conductorresistance at 20°C

ohms/km

Current rating DC or single phase AC Enclosed

Amps

Current rating

DC or single phase AC

Clipped direct Amps

Recommended accessories

2Nylon LSOH Gland

Volt drop DC or single phase AC

mV/A/m

Seven core

Twelve core

1.5 1/1.38 17.5 399 12.1 16.5 19.5* 29 AP18 254

2.5 7/0.67 21.7 637 7.4 23* 27* 18 AP22 255

Nineteen core

The tabulared ratings are based upon a 30°C ambient temperature and 70°C operating temperature.For other ambient temperatures or where cables are grouped toghether, the following rating factors should be applied.

1.5 1/1.38 20.5 588 12.1 16.5 19.5* 29 AP20 255

2.53 7/0.67 25.6 949 7.4 23* 27* 18 AP25 -

Number of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

1LSOH® Fixing Clips

Page 11: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Mechanical Impact Medium

Temperature Range

-25 to + 70°C

Fire ResistanceBS 6387 Catergory CWZ

BS EN 50200 PH30

Low Smoke EmissionsBS EN 61034-2

Halogen Free BS EN 50267-2-1

Flexibility Semi Flexible

Fire Performance BS EN 60332-1-2BS EN 50266-2-4

Bending Radius Fixed r=4D

FIRE RESISTANT CABLES

>

>

>

FP200 Flex

Plain annealed copper stranded circular conductor complying

with BS EN 60228 class 2

High performance damage resistant InsditeTM

o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey

Conductor

Insulation

Core Identification

Sheath Robust thermoplastic LSOH® sheath

Colour - White or Red. Other colours to special order

For external exposure the use of white sheath is recommended

>

Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465

www.fpcables.co.uk

Ref: FP200Flex/10/09

Key Applications Fire detection and fire alarm systems for buildings, voice alarm

systems, emergency lighting systems and other essential service

circuits. In addition to approvals to BS7629-1 from BASEC and

LPCB, FP 200 FlexTM has received LPCB approval against the fire

test requirement of BS6387 Category CWZ

>

Screen > Aluminium/Polyester tape screen in contact with full size

tinned annealed copper stranded circuit protective conductor

>

>

Certificate No 077a/03

BS7629-1

British Standard Type E15.

TM

Page 12: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

1 Recommended clip spacing 300mm horizontal and 400mm vertical2 Brass glands may be used as an alternative

Minimum recommended installation temperature 0°CInstallation methods for current rating in accordance with BS7671/IEE Wiring Regulations.The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.For other ambient temperatures or where cables are grouped togethor, the appropriate rating factors should be applied.

Notes to table

Temperature Rating Factors

Rating factors for Grouping

Prysmian FP200 FLEXTM Fire Resistant Cable

Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465

www.fpcables.co.uk

Ref: FP200Flex/10/09

Two Core

1.5 7/0.53 8.2 99 12.1 16.5 19.5 29 AP7 251/GL2520

2.5 7/0.67 9.6 145 7.4 23 27 18 AP9 251/GL2520

Three Core

1.5 7/0.53 8.7 120 12.1 16.5 19.5 29 AP8 251/GL2520

2.5 7/0.67 10.2 176 7.4 23 27 18 AP10 252/GL2520

Four Core

1.5 7/0.53 9.7 149 12.1 16.5 19.5 29 AP9 251/GL2520

2.5 7/0.67 11.4 218 7.4 23 27 18 AP11 252/GL2520

Nominal cross

sectional area

mm2

Conceptual construction

no./mm

Mean overall diameter

mm

Approximatecable weight

kg/km

Maximum conductor resistance at 20°C

ohms/km

Current rating

DC or single phase ACEnclosed

Amps

Current rating

DC or single phase AC

clipped directAmps

LSOH fixing clips 1

Recommended accessories

Nylon LSOH gland 2

Volt drop DC or single phase AC

mV/A/m

Ambient Temperature °C 25 30 35 40 45 50 55 60

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

Number of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Page 13: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP PLUS™

FIRE RESISTANT CABLES

New GenerationNow with enhanced

InsuditeTM insulation

Page 14: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP PLUS™

‘ENHANCED’FIRE RESISTANT CABLES

CABLE CHARACTERISTICS

FP PLUS™ BS7629-1:2008

DATA CAPABILITY

INSTALLATION

APPROVALS In addition to approvals to BS7629-1 and BS6387 Category

CWZ, FP PLUSTM

has received BASEC and LPCB approval to

BS5839-1:2002 for enhanced applications. This includes approval

to BS EN 50200 Class PH120 and the new integrated fire, shock

and water test BS8434-2 for 120 minutes. All Prysmian FP PLUSTM

cables are manufactured under an ISO 9001 Quality System

certified by BASEC and LPCB.

FP PLUSTM

has excellent data/signal transmission characteristics

making it ideal for voice alarm, addressable and networked

systems.

In accordance with the new BS5839-1 and BS5266-1 requirements,

cables must be supported by a fixing that can withstand the same

fire conditions as the cable. To meet this requirement the use of

Prysmian AP LSOH® coated metal P-clips or the new FP FirefixTM rapid fixing system is recommended. FP PLUS

TM

should be installed

in accordance with BS7671/IEE Wiring Regulations and/or any

other appropriate national regulations or codes. It is suitable for

indoor and outdoor installation in suitably protected environments

and particularly appropriate for surface wiring, direct burial in

plaster, tray or other installations requiring a dressable product.

>

>

>

>

The new generation of FP PLUSTM

is a highly durable and dressable,

easy to terminate and install fire resistant cable, using an enhanced

variant of the unique InsuditeTM damage resistant insulation system.

It brings to the market for the first time an enhanced fire alarm

cable with the unmatched combination of rigidity and ease of

bending associated with the market leading FP200 Gold® cable.

New generation FP PLUSTM

sets previously unobtainable levels in

ease of installation for an enhanced cable whilst maintaining

full compliance with all the necessary test requirements.

Approved for fire detection and fire alarm critical signal paths to

BS5839-1:2002+A2:2008 and voice alarm systems to

BS5839-8:2008 in enhanced application areas and emergency

lighting systems to BS5266-1:2005.

Certificate No 077g/02

Mechanical Impact Medium

Fire ResistanceBS 6387 Category CWZBS EN 50200 PH120BS 8434-2 120 min

Low Smoke EmissionsBS EN 61034-2

Halogen Free BS EN 50267-2-1

Flexibility Rigid

Fire Performance BS EN 60332-1-2BS EN 50266-2-4

Bending Radius Fixed r=6D

Temperature Range

-20 to +70°C

Page 15: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FIRE RESISTANT CABLES 300/500V FP PLUS

KEY APPLICATIONS > Fire detection and fire alarm systems for buildings> Voice alarm systems> Emergency lighting> Other essential service circuits

CABLE DESCRIPTION

CONDUCTORPlain annealed copper solid circular conductor complying with BS EN 60228 class 1.

INSULATIONHigh performance damage resistant enhanced InsuditeTM.British Standard Type EI5.

CORE IDENTIFICATION HARMONISED CORE IDENTIFICATION:o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey SCREEN/CPC Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor which provides automatic screen earthing.

SHEATH Robust thermoplastic enhanced LSOH sheath; Colour - White or Red. Other colours to special order. For external exposure the use of a white sheath is recommended.

Nominal cross

sectional area

mm2

Conceptual Construction

no./mm

Mean overall

diameter

mm

Approximate cable

weight

kg/km

Maximum conductor resistance

at 20°C

ohms/km

Current rating DC or single phase

AC Enclosed

Amps

Current rating DC or single phase

AC Clipped direct

Amps

Volt drop DC or single

phase AC

mV/A/m

1 LSOH®

fixingclips

2 NylonLSOH®

gland

Recommended accessoriesColour - White or Red

FP FirefixTM

fixingclips

Two core

1.5 1/1.38 9.2 115 12.1 16.5 19.5 29 AP9 251/GL2520 UFPNF04

2.5 1/1.78 11.5 176 7.4 23 27 18 AP11 252/GL2520 -

1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative. Minimum recommended installation temperature 0°C.Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.

Notes to table

Temperature ratings factor

Rating Factors for Groupings

Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Number of circuits 2 3 4 5 6 7

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

Page 16: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP PlusTM‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)

BS7629-1:2008

> Plain annealed copper solid conductor complying with BS EN 60228

class 1.

> Cross-linked damage resistant insulation (Type EI5) over mineral

ceramic (mica/glass) tape.

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

> Robust thermoplastic LSOH® sheath

Colour - White or Red. Other colours to special order

For external exposure the use of a white sheath is recommended

Sheath

oo brown-blueooo brown-black-greyoooo blue-brown-black-grey

> Laminated copper tape screen bonded to sheath and in contact

with full size tinned annealed copper circuit protective

conductor which provides automatic screen earthing.

Ref: FPPlus/02/09

Screen

TemperatureRange

-20 to +70°C

Bending RadiusFixed r=6D

Mechanical ImpactMedium

Fire PerformanceBSEN60332-1-2BSEN50266-2-4

FlexibilityRigid

Halogen FreeBSEN50267-2-1

Low Smoke Emissions

BSEN61034-2

Fire ResistantBS6387 Category CWZ

BSEN50200 PH120BS8434-2 120 min

> Fire detection and fi re alarm systems for buildings. FP PLUSTM

is BASEC and LPCB approved in accordance with the requirements

of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re

resisting cables.

Key Applications

Certifi cate no 077g

Page 17: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Ref:FPPlus/02/09

Nominalcross

sectionalarea

mm²

Conceptual construction

no./mm

Mean overall

diameter

mm

Approximate cable weight

kg/km

Maximum conductor resistance

at 20°C

ohms/km

Current ratingDC or single

phase AC Enclosed

Amps

Current rating DC or single phase

ACClipped direct

Amps

Volt drop DC or single

phase AC

mV/A/m

RecommendedAccessories

LSOH® fi xing clips 1

Nylon LSOH® gland 2

Two Core

1.0 1/1.13 8.5 110 18.1 13 15 44 AP8 251/GL2520

Three Core

1.0 1/1.13 9.0 125 18.1 13 15 44 AP9 251/GL2520

1.5 1/1.38 10.0 150 12.1 16.5 19.5 29 AP10 251/GL2520

Four Core

1.0 1/1.13 10.3 160 18.1 13 15 44 AP10 252/GL2520

1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520

1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative

Minimum recommended installation temperature 0°C

Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations

The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.

For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.

FP PLUSTM Fire Resistant Cable

Temperature ratings factor

Correction factors for groupings

Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Number of circuits 2 3 4 5 6 7

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

Page 18: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP Plus Flex‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)

BS7629-1:2008

> Plain annealed copper solid (1.0 - 1.5mm²) or stranded (2.5 - 4.0mm²)

conductor complying with BS EN 60228 class 1 or class 2.

> Cross-linked damage resistant insulation (Type EI5) over mineral

ceramic (mica/glass) tape.

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

> Robust thermoplastic LSOH® sheath

> Colour - White or Red

> Other colours to special order

> For external exposure the use of a white sheath is recommended

Sheath

oo brown-blueooo brown-black-greyoooo blue-brown-black-grey

> Helically applied laminated copper tape screen in contact

with full size tinned annealed copper circuit protective conductor

which provides automatic screen earthing.

Ref: FPPlusFlex/01/09

Screen

TemperatureRange

-25 to +70°C

Bending RadiusFixed r=6D

Mechanical ImpactMedium

Fire PerformanceBSEN60332-1-2BSEN50266-2-4

FlexibilitySemi Flexible

Halogen FreeBSEN50267-2-1

Low Smoke Emissions

BSEN61034-2

Fire ResistantBS6387 Category CWZ

BSEN50200 PH120BS8434-2 120 min

> Fire detection and fi re alarm systems for buildings. FP PLUS Flex

is BASEC and LPCB approved in accordance with the requirements

of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re

resisting cables. Ideal for installations where a more fl exible cable

is required.

Key Applications

Certifi cate no 077h

Page 19: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Ref:FPPlusFlex/01/09

Nominalcross

sectionalarea

mm²

Conceptual construction

no./mm

Mean overall

diameter

mm

Approximate cable weight

kg/km

Maximum conductor resistance

at 20°C

ohms/km

Current ratingDC or single

phase AC Enclosed

Amps

Current rating DC or single phase

ACClipped direct

Amps

Volt drop DC or single

phase AC

mV/A/m

RecommendedAccessories

LSOH® fi xing clips 1

Nylon LSOH® gland 2

Two Core

1.0 1/1.13 8.8 110 18.1 13 15 44 AP8 251/GL2520

1.5 1/1.38 9.4 130 12.1 16.5 19.5 29 AP9 251/GL2520

2.5 7/0.67 11.2 180 7.4 23 27 18 AP11 252/GL2520

4.0 7/0.85 12.6 240 4.6 30 36 11 AP12 252

Three Core

1.0 1/1.13 9.4 130 18.1 13 15 44 AP9 251/GL2520

1.5 1/1.38 10.0 155 12.1 16.5 19.5 29 AP10 252/GL2520

2.5 7/0.67 12.0 220 7.4 23 27 18 AP11 252

4.0 7/0.85 13.4 300 4.6 30 36 11 AP13 254

Four Core

1.0 1/1.13 10.4 160 18.1 13 15 44 AP10 252/GL2520

1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520

2.5 7/0.67 13.3 280 7.4 23 27 18 AP13 254

4.0 7/0.85 15.0 390 4.6 30 36 11 AP15 254

1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative

Minimum recommended installation temperature 0°C

Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations

The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.

For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.

FP PLUS FLEX Fire Resistant Cable

Temperature ratings factor

Correction factors for groupings

Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Number of circuits 2 3 4 5 6 7

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

Page 20: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helplineTel: 023 8029 5222Fax: 023 8029 [email protected]

Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom

For further information please see our dedicated FP website:www.fpcables.co.uk www.prysmian.co.uk

Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465

Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5111

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]

Ref:FP PLUS/03/11

Page 21: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP Plus Flex‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)

BS7629-1:2008

> Plain annealed copper solid (1.0 - 1.5mm²) or stranded (2.5 - 4.0mm²)

conductor complying with BS EN 60228 class 1 or class 2.

> Cross-linked damage resistant insulation (Type EI5) over mineral

ceramic (mica/glass) tape.

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

> Robust thermoplastic LSOH® sheath

> Colour - White or Red

> Other colours to special order

> For external exposure the use of a white sheath is recommended

Sheath

oo brown-blueooo brown-black-greyoooo blue-brown-black-grey

> Helically applied laminated copper tape screen in contact

with full size tinned annealed copper circuit protective conductor

which provides automatic screen earthing.

Ref: FPPlusFlex/01/09

Screen

TemperatureRange

-25 to +70°C

Bending RadiusFixed r=6D

Mechanical ImpactMedium

Fire PerformanceBSEN60332-1-2BSEN50266-2-4

FlexibilitySemi Flexible

Halogen FreeBSEN50267-2-1

Low Smoke Emissions

BSEN61034-2

Fire ResistantBS6387 Category CWZ

BSEN50200 PH120BS8434-2 120 min

> Fire detection and fi re alarm systems for buildings. FP PLUS Flex

is BASEC and LPCB approved in accordance with the requirements

of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re

resisting cables. Ideal for installations where a more fl exible cable

is required.

Key Applications

Certifi cate no 077h

Page 22: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Ref:FPPlusFlex/01/09

Nominalcross

sectionalarea

mm²

Conceptual construction

no./mm

Mean overall

diameter

mm

Approximate cable weight

kg/km

Maximum conductor resistance

at 20°C

ohms/km

Current ratingDC or single

phase AC Enclosed

Amps

Current rating DC or single phase

ACClipped direct

Amps

Volt drop DC or single

phase AC

mV/A/m

RecommendedAccessories

LSOH® fi xing clips 1

Nylon LSOH® gland 2

Two Core

1.0 1/1.13 8.8 110 18.1 13 15 44 AP8 251/GL2520

1.5 1/1.38 9.4 130 12.1 16.5 19.5 29 AP9 251/GL2520

2.5 7/0.67 11.2 180 7.4 23 27 18 AP11 252/GL2520

4.0 7/0.85 12.6 240 4.6 30 36 11 AP12 252

Three Core

1.0 1/1.13 9.4 130 18.1 13 15 44 AP9 251/GL2520

1.5 1/1.38 10.0 155 12.1 16.5 19.5 29 AP10 252/GL2520

2.5 7/0.67 12.0 220 7.4 23 27 18 AP11 252

4.0 7/0.85 13.4 300 4.6 30 36 11 AP13 254

Four Core

1.0 1/1.13 10.4 160 18.1 13 15 44 AP10 252/GL2520

1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520

2.5 7/0.67 13.3 280 7.4 23 27 18 AP13 254

4.0 7/0.85 15.0 390 4.6 30 36 11 AP15 254

1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative

Minimum recommended installation temperature 0°C

Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations

The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.

For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.

FP PLUS FLEX Fire Resistant Cable

Temperature ratings factor

Correction factors for groupings

Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Number of circuits 2 3 4 5 6 7

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

Page 23: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,
Page 24: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Prysmian FP400® is the original fire resistant armoured cable providing an easy to install and terminate, robust fire resistant wiring system. In addition to maintaining circuit integrity during a fire, FP400® produces very low levels of smoke and virtually no (less than 0.5%) acidic gases, thus safeguarding human life and protecting equipment.

FP400® handles like a standard armoured cable and can be installed just as easily. No special tools or accessories are needed for installation or termination of FP400®, which ensures that substantial installation cost savings, compared with MICC, can be achieved through its use.

FP400® is suitable for indoor or outdoor installation requiring a robust armoured cable, including direct burial, trough, fixed direct, tray or ladder.

Prysmian FP400® complies with BS7846 Category F2 which ensures that it complies with the requirements for "protected power circuits" given in the 2000 edition of Approved Document B Fire safety of The Building Regulations 2000.

> Prysmian FP400® is British Approvals Service for Cables (BASEC) approved to BS7846 Category F2. It is also Loss Prevention Certification Board (LPCB) listed as a fire resistant cable and approved to BS6387 Category CWZ, at an enhanced voltage of 600/1000V.

Witnessed ad-hoc tests have demonstrated the ability of FP400®

to achieve fire resistant properties in excess of those required by BS6387 Category CWZ and on the basis of these tests Prysmian FP400® has been approved for many projects where previously only MICC had been approved.

Additional tests have demonstrated the ability of FP400® to achieve a 60 minute rating (PH60) to BS EN50200 and a 30 minute rating to BS8434-1. These tests demonstrate that FP400®

also meets the requirements for use in "standard" installations in accordance with BS5839-1:2002 for fire detection and alarm systems, and "Cables with inherently high resistance to attack by fire" in accordance with BS5266-1:2005 for emergency lighting.

All Prysmian FP400®cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

> Prysmian FP400® may be considered as a low smoke armoured cable to BS6724 for the purposes of installation and should be installed in accordance with BS7671/IEE Wiring Regulations or any other appropriate national regulations. Although standard armour cable fixings and glands may be used, it is important to ensure that, when the cable is required to maintain circuit integrity in a fire, any fixing used to support the cable can also withstand that fire. The use of the appropriate BICON® gland or cleat is recommended.

TemperatureRange

-25 to +90°C

Bending RadiusCircular conductor r=6DShaped conductor r=8D

Mechnical ImpactVery Good

Fire PerformanceBSEN60332-1-2BSEN50266-2-4

FlexibilityRigid

Halogen FreeBSEN50267-2-1

Low Smoke EmissionsBSEN61034-2

Fire ResistantBS6387Category

CWZ

Certificate No 077bCertificate No 517b

Page 25: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Ambient Temperature °C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

> Essential safety circuits associated with fire detection, fire alarm, emergency lighting and particularly for power supplies to building equipment used in safety systems.

CONDUCTORPlain annealed copper stranded (class 2) conductor for ease of handling.

PRIMARY INSULATIONMineral ceramic (Mica/Glass) fire resistant tape

SECONDARY INSULATION90°C cross - linked insulation

HARMONISED CORE IDENTIFICATION:o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey7-48 cores white with printed numbers

NON HARMONISED CORE IDENTIFICATION:o o red-blacko o o red-yellow-blueo o o o black-red-yellow-blueNon harmonised colours to special order.

BEDDINGExtruded LSOH bedding compound.

ARMOURSingle layer of galvanised steel wires.

SHEATHRobust LSOH sheath. Colour - black.Other colours to special order

Minimum recommended installation temperature 0°C.Suitable for indoor and outdoor installations. For external exposure the use of a Black sheath is recommended.

Should be installed in accordance with BS7671/IEE Wiring Regulations or any other appropriate national regulations.

Suitable for direct burial, trough, tray, ladder or other installations requiring a robust armoured cable.

A minimum internal radius of bend of 6 x cable diameter is recommended during installations for cables having circular conductors and 8 x cable diameter for cables having shaped conductors.

No special accessories are required for the installationof FP400®.

Standard brass armoured cable glands and cast iron cleats may be used.

When the cable is required to maintain circuit integrity in a fire, it is important that any accessory used to support the cable can also withstand that fire. The use of the appropriate BICON® gland or cleat is recommended.

CURRENT RATINGSThe tabulated ratings are based upon a 30°C ambient temperature and a 90°C operating temperature.For other ambient temperatures or where cables are grouped together, the following rating factors should be applied.

Rating factors for Ambient temperatures

* Spaced by a clearance between adjacent surfaces of at least one cable diameter.Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be appliedNote. Standard conditions of grouping as stated in BS7671 IEE Wiring Regs apply

Installation MethodNumber of circuits or multi-core cables

2 3 4 5 6 7 8 9

Single layer clipped to a non-metallic surface

Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70

Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90

Single layer multicore on a perforated metal cable tray,

vertical or horizontal

Touching 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72

Spaced* 0.91 0.89 0.88 0.87 0.87 - - -

Rating factors for grouping of cables

Page 26: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Nominalcross

sectionalareamm2

Approximateoverall

diameter

mm

Approximatediameter

underarmour

mm

Nominaldiameterof armour

wiresmm

Approximatecable

weight

kg/km

Maximumconductorresistanceat 20°Cohms/km

Short Circuitrating (1 sec)of conductor

KA

Current ratingThree

phase AC Clipped direct

Amps

Current ratingThree

phase AC Free AirAmps

Volt dropThree

phase AC

mV/A/m

Three Core

1.5 13.4 8.8 0.9 340 12.1 0.20 23 25 27

2.5 14.8 10.2 0.9 430 7.41 0.35 31 33 16

4 16.1 11.5 0.9 510 4.61 0.57 42 44 10

6 17.4 12.8 0.9 620 3.08 086 53 56 6.8

10 20.3 14.8 1.25 930 1.83 1.4 73 78 4.0

16 22.8 17.1 1.25 1210 1.15 2.2 94 99 2.5

25 27.4 20.8 1.6 1800 0.727 3.6 124 131 1.65

35 29.2 22.4 1.6 2100 0.524 5.0 154 162 1.15

50 33.0 26.2 1.6 2600 0.387 7.1 187 197 0.87

70 37.0 30.0 1.6 3400 0.268 10.0 238 251 0.60

95 40.6 32.4 2.0 4500 0.193 13.6 289 304 0.45

120 43.8 35.4 2.0 5500 0.153 17.2 335 353 0.37

150 48.0 38.4 2.5 6900 0.124 21.4 386 406 0.30

185 52.0 42.2 2.5 8200 0.0991 26.5 441 463 0.26

240 57.1 46.9 2.5 10200 0.0754 34.3 520 546 0.21

300 63.0 52.6 2.5 12200 0.0601 42.9 599 628 0.185

400 69.5 58.7 2.5 15000 0.0470 57.2 673 728 0.165

Four Core

1.5 14.3 9.7 0.9 390 12.1 0.20 23 25 27

2.5 16.0 11.4 0.9 490 7.41 0.35 31 33 16

4 17.3 12.7 0.9 590 4.61 0.57 42 44 10

6 19.6 14.1 1.25 830 3.08 0.86 53 56 6.8

10 21.8 16.3 1.25 1040 1.83 1.4 73 78 4.0

16 24.6 18.9 1.25 1370 1.15 2.2 94 99 2.5

25 29.1 22.5 1.6 2100 0.727 3.6 124 131 1.65

35 32.2 25.4 1.6 2500 0.524 5.0 154 162 1.15

50 35.0 28.0 1.6 3200 0.387 7.1 187 197 0.87

70 40.2 32.0 2.0 4500 0.268 10.0 238 251 0.60

95 44.0 35.6 2.0 5600 0.193 13.6 289 304 0.45

120 48.4 38.8 2.5 7200 0.153 17.2 335 353 0.37

150 52.5 42.7 2.5 8500 0.124 21.4 386 406 0.30

185 57.1 46.9 2.5 10300 0.0991 26.5 441 463 0.26

240 62.7 52.3 2.5 12800 0.0754 34.3 520 546 0.21

300 69.6 58.8 2.5 15600 0.0601 42.9 599 628 0.185

400 78.0 65.3 3.15 20400 0.0470 57.2 673 728 0.165

Circular conductor 1.5 - 35mm2.

Shaped conductor 50mm2 and above.Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.

Page 27: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

LOW VOLTAGE 600/1000V

Nominalcross

sectionalareamm2

Approximateoverall

diameter

mm

Approximatediameter

underarmour

mm

Nominaldiameterof armour

wiresmm

Approximatecable

weight

kg/km

Maximumconductorresistance

at 20°Cohms/km

Current ratingDC or Single

phase ACClipped direct

Amps

Current ratingDC or Single

phase ACFree Air Amps

Volt dropDC

mV/A/m

Volt dropSingle

phase AC

mV/A/m

Two Core

1.5 12.9 8.3 0.9 310 12.1 27 29 31 31

2.5 14.1 9.6 0.9 380 7.41 36 39 19 19

4 15.2 10.6 0.9 450 4.61 49 52 12 12

6 16.4 12.0 0.9 530 3.08 62 66 7.9 7.9

10 18.6 14.0 0.9 630 1.83 85 90 4.7 4.7

16 21.4 15.9 0.9 920 1.15 110 115 2.9 2.9

25 25.0 19.0 1.25 1200 0.727 146 152 1.85 1.9

35 28.0 21.0 1.6 1600 0.524 180 188 1.35 1.35

50 28.0 21.2 1.6 2000 0.387 219 228 0.98 1.00

70 31.0 24.0 1.6 2400 0.268 279 291 0.67 0.69

95 33.0 26.0 2.0 3300 0.193 338 354 0.49 0.52

120 37.0 29.0 2.0 3800 0.153 392 410 0.39 0.42

150 39.3 30.9 2.0 4400 0.124 451 472 0.31 0.35

185 44.2 34.4 2.5 5700 0.0991 515 539 0.25 0.29

240 48.0 38.0 2.5 7200 0.0754 607 636 0.195 0.24

300 54.0 44.0 2.5 8300 0.0601 698 732 0.155 0.21

400 59.0 49.0 2.5 10500 0.0470 787 847 0.120 0.19

Seven Core

1.5 16.4 11.8 0.9 500 12.1 27 * 29 * 31 31

2.5 18.3 13.7 0.9 640 7.41 36 * 39 * 19 19

4 20.8 15.3 1.25 910 4.61 49 * 52 * 12 12

Twelve Core

1.5 21.2 15.7 1.25 850 12.1 27 * 29 * 31 31

2.5 24.0 18.3 1.25 1090 7.41 36 * 39 * 19 19

4 27.3 20.9 1.6 1550 4.61 49 * 52 * 12 12

Nineteen Core

1.5 24.2 18.5 1.25 1120 12.1 27 * 29 * 31 31

2.5 28.6 22.0 1.6 1650 7.41 36 * 39 * 19 19

Twenty-seven Core

1.5 29.4 22.8 1.6 1650 12.1 27 * 29 * 31 31

2.5 33.4 26.6 1.6 2150 7.41 36 * 39 * 19 19

Thirty-seven Core

1.5 32.2 25.6 1.6 2000 12.1 27 * 29 * 31 31

2.5 36.7 29.9 1.6 2650 7.41 36 * 39 * 19 19

*The tabulated rating is as a two core cable and may be used where the number of cores carrying current does not exceed its square root of the total number of cores.

Page 28: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Ref:FP40

0/PY

/08

/07

UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helpline Tel: 0845 767 8345Fax: 023 8029 5002

Prysmian Cables & Systems Limited Chickenhall LaneEastleighHampshireSO50 6YU United Kingdom

For further information please see our dedicated FP website: www.fpcables.co.uk

www.prysmian.co.uk

Overseas Sales enquiriesTel: +44 23 8029 5481Fax: +44 23 8029 5465

Overseas Technical helpline Tel: +44 23 8029 5481Fax: +44 23 8029 5002

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 5437 [email protected]

Page 29: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

FP600S

FIRE RESISTANT CABLES

Ultimate Protection for Electrical Emergency

Systems

Page 30: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Mechanical Impact Very Good

Temperature Range

-25 to +90°C

Fire ResistanceBS 7846 120 minBS 8491 120 min

Low Smoke EmissionsBS EN 61034-2

Halogen Free BS EN 50267-2-1

Flexibility Rigid

Flame PropagationBS EN 60332-1-2BS EN 60332-3-24

Bending Radius Fixed

Circular conductor r= 6DShaped conductor r= 8D

FIRE RESISTANT CABLES

Certificate No 077nCertificate No 517c/01

FP 600SBS 7846-F120

CABLE CHARACTERISTICS

FP600S is the ultimate fire resistant armoured power cable and it’s the right choice to power life safety or fire fighting systems in large and complex buildings.

BS 8519 – Category 1, 2 and 3

BS 7846 – F120, 120 mins fire, water jet & direct impact

BS 8491 – 120 mins fire, water jet & direct impact

BASEC – approved*

LPCB – approved*

London Underground – approved*

Afumex – Reduced flame propagation, low smoke and corrosive gas emission.

Designed, manufactured and tested by Prysmian in the UK to meet the demands of clients, engineers, regulators and installers.

FP600S is easy to install, requires no special tools and can be terminated, glanded and cleated like a standard armoured cable allowing significant savings compared with MICC.

>

>

>

>

>

>

>

* see www.fpcables.co.uk for certificates

Page 31: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

4 21 15 1.25 800 4.61 0.57 42 44 10 370CG04 LSF25CW

6 23 17 1.25 950 3.08 0.86 53 56 6.8 370CG05 LSF25CW

10 24 19 1.25 1200 1.83 1.4 73 78 4.0 370CG05 LSF25CW

16 27 20 1.25 1600 1.15 2.2 94 99 2.5 370CG06 LSF25CW

25 32 24 1.6 2400 0.727 3.6 124 131 1.65 370CG07 LSF32CW

35 35 27 1.6 2800 0.524 5.0 154 162 1.15 370CG07 LSF40CW

50 36 29 1.6 3200 0.387 7.1 187 197 0.87 370CG08 LSF40CW

70 41 32 2.0 4500 0.268 10 238 251 0.64 370CG08 LSF50SCW

95 44 36 2.0 5700 0.193 13.6 289 304 0.45 370CG09 LSF50SCW

120 49 40 2.5 7300 0.153 17.2 335 353 0.37 370CG09 LSF50CW

150 55 44 2.5 8600 0.124 21.4 386 406 0.30 370CG10 LSF63CW

185 59 48 2.5 10500 0.0991 26.5 441 463 0.26 370CG11 LSF63CW

240 64 54 2.5 12900 0.0754 34.3 520 546 0.21 370CG12 LSF75CW

300 70 59 2.5 15500 0.0601 42.9 599 628 0.185 370CG13 LSF75CW

400 79 66 3.15 20100 0.0470 57.2 673 728 0.165 370CG14 CW85K

4 21 15 1.25 800 4.61 0.57 42 44 10 370CG04 LSF25CW

6 21 15 1.25 820 3.08 0.86 53 56 6.8 370CG04 LSF25CW

10 23 17 1.25 1050 1.83 1.4 73 78 4.0 370CG05 LSF25CW

16 24 19 1.25 1400 1.15 2.2 94 99 2.5 370CG06 LSF25CW

25 29 22 1.6 2000 0.727 3.6 124 131 1.65 370CG06 LSF32CW

35 31 24 1.6 2300 0.524 5.0 154 162 1.15 370CG07 LSF32CW

50 32 25 1.6 2800 0.387 7.1 187 197 0.87 370CG07 LSF40CW

70 36 29 1.6 3600 0.268 10 238 251 0.6 370CG08 LSF50SCW

95 40 32 2.0 4500 0.193 13.6 289 304 0.45 370CG08 LSF50SCW

120 43 35 2.0 5400 0.153 17.2 335 353 0.37 370CG08 LSF50SCW

150 48 39 2.5 6900 0.124 21.4 386 406 0.30 370CG09 LSF50CW

185 52 43 2.5 8200 0.0991 26.5 441 463 0.26 370CG09 LSF63CW

240 57 47 2.5 10100 0.0754 34.3 520 456 0.21 370CG09 LSF63CW

300 62 52 2.5 12200 0.0601 42.9 599 628 0.185 370CG11 LSF63CW

400 69 58 2.5 15000 0.0470 57.2 673 728 0.165 370CG12 LSF75CW

Nominal cross

sectional area

mm2

Approximateoverall

diameter

mm

Approximatediameterunderarmour

mm

Nominaldiameterof armour

wires

mm

Approximatecable weight

kg/km

Maximum conductor resistance at 20°C

ohms/km

Short circuit rating

(1sec) of conductor

kA

Current rating Three phase AC clipped

direct

AmpsClaw Cleat

Ref No.

Recommended accessoriesCurrent rating Three phase

AC Free air

Amps

Volt drop Three phase

AC

mV/A/m

Brass GlandRef No.

Three Core

Four Core

Circular conductor 4.0-35mm2

Shaped conductor 50mm2 and above

Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.

The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.

For other ambient temperatures or where cables are grouped together, the following rating factors should be applied.

FP600S FIRE RESISTANT CABLES

FP600S

Page 32: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

4 21 15 1.25 800 4.61 41 52 12 12 370CG04 LSF25CW

6 21 15 1.25 800 3.08 62 66 7.9 7.9 370CG04 LSF25CW

10 22 16 1.25 800 1.83 85 90 4.7 4.7 370CG04 LSF25CW

16 23 17 1.25 1000 1.15 110 115 2.9 2.9 370CG05 LSF25CW

25 26 20 1.25 1300 0.727 146 152 1.85 1.90 370CG06 LSF25CW

35 30 23 1.6 1800 0.524 180 188 1.35 1.35 370CG06 LSF32CW

50 31 24 1.6 2200 0.387 219 228 0.98 1.0 370CG06 LSF32CW

70 33 26 1.6 2600 0.268 279 291 0.67 0.69 370CG07 LSF32CW

95 35 27 2.0 3400 0.193 338 354 0.49 0.52 370CG07 LSF40CW

120 39 30 2.0 4100 0.153 392 410 0.39 0.42 370CG08 LSF50SCW

150 42 33 2.0 4700 0.124 451 472 0.31 0.35 370CG08 LSF50SCW

185 46 36 2.5 6100 0.0091 515 539 0.25 0.29 370CG09 LSF50CW

240 51 41 2.5 7500 0.0754 607 636 0.795 0.24 370CG09 LSF50CW

300 56 45 2.5 9000 0.0601 698 732 0.155 0.21 370CG10 LSF63CW

400 61 50 2.5 11000 0.0470 787 847 0.120 0.19 370CG11 LSF63CW

Nominal cross

sectional area

mm2

Approximateoverall

diameter

mm

Approximatediameterunderarmour

mm

Nominaldiameterof armour

wires

mm

Approximatecable weight

kg/km

Maximum conductor resistance at 20°C

ohms/km

Current Rating DC or single

phase AC Free Air

Amps

Current rating DC or single phase AC

clipped direct

AmpsClaw Cleat

Ref No.

Recommended accessoriesVoltage drop DC

mV/A/m

Volt drop single phase

AC

mV/A/m

Brass GlandRef No.

Two Core

FP600S

LOW VOLTAGE 600/1000V

Page 33: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

KEY APPLICATIONS

Electrical supplies for fire fighting, life safety and property protection systems. Active fire safety systems part of a Fire Safety Engineering solution rely on an effective electrical supply remaining operational during a fire as described in BS8519:2010.

Greater emphasis is now being given to the integrity of electrical circuits which maintain the functional safe working conditions of such equipment and systems. FP600S is a new generation fire resistant power cable designed to meet the much more onerous fire survival requirement now considered appropriate for such applications.

Examples of circuits which are required to remain operational under such conditions include:

CABLE DESCRIPTION

CONDUCTORPlain annelaed copper stranded circular (4-35 mm²) or shaped (50-400 mm²) conductor complying with BS EN 60228 Class 2.

INSULATIONPrimary Insulation:Mineral ceramic (Mica/Glass) fire resistant tape

Secondary Insulation:90°C cross - linked insulation

Ambient Temperature °C 25 30 35 40 45 50 55 60

Correction Factor 1.02 1.0 0.96 0.91 0.87 0.82 0.76 0.71

Installation MethodNumber of circuits or multi-core cables

2 3 4 5 6 7 8 9

Single layer clipped to a non-metallic surface

Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70

Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90

Single layer multicore on a perforated metal cable tray,

vertical or horizontal

Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72

Spaced* 0.91 0.89 0.88 0.87 0.87 - - -

Correction factors for Ambient temperatures

Fire-fighting lift shafts>

>

Correction factors for grouping of cables

*Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be applied. Note: Standard conditions of grouping as stated in BS791 (IEE Wiring Regs) apply.

FP600S

FP600S FIRE RESISTANT CABLES

CORE IDENTIFICATION

oo brown-blueooo brown-black-greyoooo blue-brown-black-grey

BEDDINGThermoplastic LSOH bedding compound

ARMOURSingle layer of galvanised steel wires

SHEATHRobust thermoplastic LSOH sheath. Colour - black.Other colours to speical order

INSTALLATION

Minimum recommended installation temperature 0°C.Suitable for indoor and outdoor installations. For externalexposure the use of a Black sheath is recommended.

Should be installed in accordance with BS7671/IEE WiringRegulations or any other appropriate national regulations.

Suitable for direct burial, trough, tray, ladder orother installations requiring a robust armoured cable.

BENDING RADIUS

A minimum internal radius of bend of 6 x cable diameteris recommended during installations for cables havingcircular conductors and 8 x cable diameter for cableshaving shaped conductors.

ACCESSORIESNo special accessories are required for the installationof FP600S.

Standard brass armoured cable glands and cast iron cleatsmay be used.

When the cable is required to maintain circuit integrityin a fire, it is important that any accessory used tosupport the cable can also withstand that fire. The use ofthe appropriate BICON® gland or cleat is recommended.

> Pressurization > Emergency lighting> Lift power suppliers

Fire suppression systems> Watermist> Sprinkler pumps > Hose reel

> Escape systems> Smoke and fire barriers > Smoke fans> Smoke curtains and sliding doors

BS8519 requires fire resistant power cable to meet category 1, 2 or 3 of BS8491, the integrated fire, shock and water jet test.

FP600S meets all three categories and achieves the highest 120 minute fire test rating.

Page 34: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002

Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom

For further information please see our dedicated FP website:www.fpcables.co.uk www.prysmian.co.uk

Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465

Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]

Ref:FP600S/01/11

Page 35: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Installation in surface mounted or embedded conduits, or similar closed

systems and for fi xed protected installation in or on lighting fi ttings and

inside appliances, switchgear and control gear particularly for situations

in which low emissions of smoke and acid gas is requred in case of

burning

> Green/Yellow for use as earth

LSOH Conduit Wire(HO7Z-R)

Key Applications

Ref: 6491B/06/09

LSOH Wiring CablesLow Voltage (450/750 V)

6491B

Cable Approvals Cable approved to BS7211

> Plain annealed copper stranded circular conductor complying with

BS EN 60228 Class 2

> 90°C LSOH insulation complying with BS EN 50363-5 Type El 5

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

TemperatureRange

-25 to +90°C

BendingRadius

Fixed r=6D

MechanicalImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibiltyRigid

o Redo Blacko Blueo Yellowo Browno Greyoooooooo Green/Yellow

Other core colours are available on request

Halogen freeBS EN 50267-2-2

Low smoke emissions

BS EN 61034-2

Page 36: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Ref: 6491B/06/09 Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Nominalcross

sectionalarea

mm²

Conceptualconstruction

no/mm

Approx.overall

diameter

mm

Approx.cable

weight

kg

Maximumconductorresistance

at 20°C

ohms/km

Shortcircuitrating

90-160°C(1 sec)

kA

Shortcircuitrating 90-

250°C(1 sec)

kA

Currentrating DC or single phase AC enclosed

inconduit

ortrunking

Amps

CurrentratingThree

phase AC enclosed

inconduit

ortrunking

Amps

VoltagedropDC

mV/A/m

VoltagedropDC or singlephase

AC

mV/A/m

Voltagedropthreephase

AC

mV/A/m

1.5 7/0.53 3 21 12.1 0.15 0.22 22 19 31 31 27

2.5 7/0.67 3.6 32 7.41 0.25 0.36 30 26 19 19 16

4 7/0.85 4.2 47 4.61 0.4 0.6 40 35 12 12 10

6 7/1.04 4.7 66 3.08 0.6 0.9 51 45 7.9 7.9 6.8

10 7/1.35 6.1 114 1.83 1 1.4 71 63 4.7 4.7 4

16 7/1.70 7.2 171 1.15 1.6 2.3 95 85 2.9 2.9 2.5

25 7/2.14 8.4 250 0.727 2.5 3.6 126 111 1.85 1.9 1.65

35 comp.* 9.5 350 0.524 3.5 5 156 138 1.35 1.35 1.15

50 comp.* 11.3 470 0.387 5 7.2 189 168 0.99 1.05 0.9

70 comp.* 12.6 670 0.268 7 10 240 214 0.68 0.75 0.65

95 comp.* 14.7 930 0.193 9.5 13.6 290 259 0.49 0.58 0.5

120 comp.* 16.2 1160 0.153 12 17.2 336 299 0.39 0.48 0.42

150 comp.* 18.1 1430 0.124 15 21.5 375 328 0.32 0.43 0.37

185 comp.* 20.2 1790 0.0991 18.5 26.5 426 370 0.25 0.37 0.32

240 comp.* 22.9 2350 0.0754 24 34.3 500 433 0.19 0.33 0.29

300 comp.* 27 3030 0.0601 30 42.9 573 493 0.155 0.31 0.27

400 comp.* 32 4010 0.047 40 57.2 683 584 0.12 0.29 0.25

500 comp.* 35.5 5020 0.0366 50 71.6 783 666 0.093 0.28 0.24

630 comp.* 39.5 6440 0.0283 63 90.2 900 764 0.072 0.27 0.23

Ambient Temperature °C 25 30 35 40 45 50 55 60

Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Temperature Rating Factors

Correction factors for Groupings

Number of circuits 2 3 4 5 6 7 8 9

Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

* Compressed stranded conducts

LSOH Conduit Wire(HO7Z-R)

kg/km

Page 37: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Suitable for fi xed installation in dry or damp premises on walls, boards or

trays, in channels or embedded in plaster particularly for situations in

which low emission smoke and acid gas is required in case of burning

LSOH Flat Wiring Cables with Bare CPC

Key Applications

LSOH Wiring CablesLow Voltage (300/500 V)

6242B, 6243B

Cable Approvals Cable approved to BS7211

> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 16.0mm²)

circular conductor complying with BS EN 60228 Class 1 or Class 2

> LSOH 90°C cross-linked insulation

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

TemperatureRange

-25 to +90°C

Bending RadiusFixed r=4D (minor

axis)

MechanicalImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibilityRigid

> LSOH Sheath complying with BS7655 Type LTS2

> Colour - white

o o o brown-CPC-blue

o o o o brown-black-CPC-grrey

Sheath

Ref:6242B/05/06

Low Smoke Emissions

BS EN 50268-2

Halogen FreeBS EN 50267-2-1

Page 38: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Nominalcross

sectional area

phase/ CPC

mm²

Approx.overall

diameter

mm

Approximatecable

weight

kg/km

Maximumconductorresistance

at 20°C

Ohms/km

Short circuit

rating of conductor

(1 sec)

kA

Current rating Volt drop DC or single

phase AC

mV/A/m

Volt drop three

phase AC

mV/A/m

DC or Single

phase AC clipped direct

Amps

DC or Single

phase AC enclosed

in conduit or trunking

Amps

Three phase AC clipped direct

Amps

6242B Two core + CPC

1.0 / 1.0 4.5 x 8.2 70 18.1 0.14 19 17 - 46 -1.5 / 1.0 4.7 x 8.6 82 12.1 0.22 24 22 - 31 -2.5 / 1.5 5.3 x 9.9 115 7.41 0.36 33 30 - 19 -4.0 / 1.5 6.1 x 11.4 155 4.61 0.57 45 40 - 12 -6.0 / 2.5 6.8 x 13.1 216 3.8 0.85 58 51 - 7.9 -10.0 / 4.0 8.4 x 16.8 380 1.83 1.43 80 69 - 4.7 -16.0 / 6.0 9.6 x 19.5 560 1.15 2.28 107 91 - 2.9 -

6243B Three core + CPC1.0 / 1.0 4.5 x 10.7 94 18.1 0.14 19 17 17 46 401.5 / 1.0 4.7 x 11.4 112 12.1 0.22 24 22 22 31 272.5 / 1.5 5.3 x 12.8 152 7.41 0.36 33 30 30 19 16

Ambient Temperature°C 25 30 35 40 45 50 55 60Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Temperature rating factors

Ref:6242B/05/06

Note: Where conductor operates at a temperature exceeding 70°C is shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.

LSOH Flat Wiring Cables with Bare CPC

Page 39: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

PRODUCT DATASHEET & APPLICATIONS GUIDE

KEY BENEFITS:

AFUMEX LSX

BS8436

LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES

TM

● BASEC approved for the full size range of BS8436 (1.0mm2 to 2.5mm2)

● Additionally tested for 600/1000 V rating by BASEC, certificate available uponrequest

● Suitable for use in thin walls and partitions as per clause 522.6 ofthe 17th Edition IEE Wiring Regulations (1.0mm2 to 2.5mm2)

● Independently assessed by ERA for nail penetration tests (1.0mm2 to 2.5mm2)

● Full 360° metal screen aids EMC compliance

● Low smoke emissions to BS EN 61034-2

● Acidic gas emission to BS EN 50267-2-1 (less than 0.5% acid gas)

● Reduced flame propagation to BS EN 60332-3-24

BASEC

APPROVED

Page 40: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

AFUMEX LSX with EARTHSHIELD

Safety Screen Technology

AFUMEX Wiring Cables

TemperatureRange

-20 to +90°C

Bending RadiusCircular conductor r=6D

Mechanical ImpactMedium

Fire PerformanceBS EN 60332-1-2BS EN 60332-3-24

FlexibilityRigid

Halogen FreeBS EN 50267-2-1BS EN 50267-2-3

Low Smoke Emissions

BS EN 61034-2

Core Identification

Insulation

Conductor

Robust thermoplastic LSOH sheath. Colour - White.Other colours are available to special order

Sheath

oo brown-blueooo brown-black-greyoooo blue-brown-black-grey

Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor for 2, 3 & 4 core cables

Screen

Nail PenetrationBS 8436

Afumex LSX

BS 8436

The AFUMEX LSX™ range was developed to address the specific needs of modern building services. For small power and lighting circuits, AFUMEX LSX™ has many applications, including cables installed in thin walls and partitions.

AFUMEX LSX™ is robust in design yet light in weight allowing it to be used in many instances where traditionally a bulky armoured cable would be installed, often with considerable cost savings. The dressable construction offers a combination of rigidity and ease of bending which keeps its shape during installation.

>

>

>

>

Plain annealed copper solid or stranded (class 1 or 2) conductor

90°C cross linked XLPE insulation complying with BS7655 Type GP8

> >

>

TM

Key Features Easy to strip, terminate and gland

Easy to install for surface clipped, tray and basket installations, giving reduced installation costs

A robust screen that meets the nail penetration test given in BS 8436*

70°C operating and 250°C short circuit temperature

Approvals

Specifications *AFUMEX LSX™ screened wiring cables comply with BS 8436 for 1.0mm2 to 2.5mm2 and are additionally tested for 600/1000 V rating

AFUMEX LSX™ screened wiring cables are rated at 600/1000 V. (4mm2 and 6mm2)

Cable Characteristics

complying with BS EN 60228

TM

BASEC Approved to BS 8436 (1.0mm2 to 2.5mm2)

Nail Penetration: ERA verified and tested

Additionally tested for 600/1000 V rating

All Prysmian cables are manufactured under our ISO 9001 Quality System certified by BASEC.

*

Full size CPC conductor on 2, 3 and 4 core cables

Provides excellent resistance to ignition and flame spread and produces very low levels of smoke and virtually no acidic gases when burnt, safeguarding human life and protecting equipment

Dressable - retains shape when installed

Page 41: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

AFUMEX LSXTM Screened Wiring Cables

Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.

The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.

These cables when connected to suitably rated equipment are capable of being operated at a conductor temperature of 90°C. If current ratings etc are required please contact us.

Cables installed in floors, ceilings, thin walls and partitions When BS8436 cable is used to comply with BS7671:2008 clause 522.6.5 (ii), or 522.6.6 (i), or 522.6.8 (i), not only are the requirements of BS7671 on current rating, voltage drop, grouping etc. to be met but the recommendation of BS8436 for current rating and protective devices should also be followed.

Only Type B circuit breakers conforming to BS EN 60898 or Type B RCBOs conforming to BS EN 61009-12 should be used. They shall also have a maximum let-through energy (I²t) not greater than 42000 A²s for 1.0mm² and 1.5mm² cable and 60000 A²s for 2.5mm² cables.

For 1.0mm² cable the largest rated circuit breaker that shall be used is 16 amps, and may be lower depending on how the cable is used and installed.For 1.5mm² cable the largest rated circuit breaker that shall be used is 20 amps, and may be lower depending on how the cable is used and installed.For 2.5mm² cable the largest rated circuit breaker that shall be used is 32 amps, and may be lower depending on how the cable is used and installed.

Nominal cross

sectional area

mm²

Conceptual construction

no./mm

Approx overall

diameter

mm

Approx cable

weight

kg/km

Max conductor

resistance at 20°C

ohms/km

Current rating DC or single phase AC enclosed

Amps

Current rating, DC or single phase AC clipped

direct

Amps

Current rating, DC or single phase

AC perforated tray

Amps

Current rating, three

phase AC perforated

tray

Amps

Volt drop DC or single

phase AC

mV/A/m

Volt drop three

phase AC

mV/A/m

AFUMEX LSX BS8436Two Core

1.0 1/1.13 8.0 80 18.1 13 15 17 - 44 -

1.5 7/0.53 9.5 100 12.1 16.5 19.5 22 - 29 -

2.5 7/0.67 10.5 140 7.41 23 27 30 - 18 -

Three Core

1.0 1/1.13 8.5 105 18.1 13 15 17 14.5 44 38

1.5 7/0.53 9.5 120 12.1 16.5 19.5 22 18.5 29 25

2.5 7/0.67 10.5 170 7.41 23 27 30 25 18 15

Four Core

1.0 1/1.13 9.0 125 18.1 13 15 17 14.5 44 38

1.5 7/0.53 10.5 155 12.1 16.5 19.5 22 18.5 29 25

2.5 7/0.67 11.5 200 7.41 23 27 30 25 18 15

AFUMEX LSX Two Core

4.0 7/0.85 12.0 190 4.61 30 36 40 - 11 -

6.0 7/1.04 13.0 260 3.08 38 46 51 - 7.3 -

Three Core

4.0 7/0.85 12.5 230 4.61 30 36 40 34 11 9.5

6.0 7/1.04 13.5 300 3.08 38 46 51 43 7.3 6.4

Four Core

4.0 7/0.85 13.5 280 4.61 30 36 40 34 11 9.5

6.0 7/1.04 15.5 370 3.08 38 46 51 43 7.3 6.4

Ambient Temperature °C 25 30 35 40 45 50 55 60

Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

Number of circuits 2 3 4 5 6 7 8 9

Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Temperature Rating Factors

Correction Factors for Groupings (Free Air Touching)

TM

TM

Page 42: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

AFUMEX LSXTM Applications GuideScreened Wiring Cables

● Suitable for surface wiring, direct burial in plaster, tray or other installations

AFUMEX LSX™ wiring cables are designed for power and lighting applications where a screened low smoke halogen free cable is required such as:

● IEE Wiring Regulations compliant cable for installation in thin walls and partitions (clause 522.6 of 17th Edition) (1.0mm2 to 2.5mm2)

● Lightweight replacement for armoured cable in cases where high level mechanical protection is not needed

● Fully screened cable for EMC compliance and clean power supply

● Robust alternative to surface mounted flat wiring cable

● Reduced flame propagation, low smoke halogen free fire performance for public access buildings

Key Applications

Installations ● Minimum recommended installation temperature 0°C

● Automatic earthing of the screen is achieved by termination of circuit protective conductor

● Suitable for indoor and outdoor installations in suitably protected environments

● For external exposure white sheathed cable is recommended

● Should be installed in accordance with BS7671/IEE Wiring Regulations or other appropriate national regulations

Cables Installed in Thin Walls and Partitions

AFUMEX LSX™ contains an earthed metallic screen, which is in contact with a full size, un-insulated circuit protective conductor.

This provides an earth fault path for the fault current if the cable is penetrated by a nail (or similar), and when connected to a suitably selected protective device offers electrical protection by this connection of the circuit.

This performance has been independently verified by nail penetration tests carried out by ERA.

Installation note: AFUMEX LSX™ cable combined with a suitable protective device provides a means of compliance with clause 522-6 of BS 7671:2008. AFUMEX LSX™ cable meets the

Total Installed Costs of LSX™ vs SWA Cable

AFUMEX LSX™ is lightweight and compact in design, allowing cost savings to be made by the selection of smaller, lighter fixings, supports and cable tray or basket. AFUMEX LSX™ is also quick to install and easily stripped, significantly reducing the first and second fix termination times when compared with SWA cable (Steel Wire Armoured).

Simple NYLON/LSOH glands may be used.

Installation note: A neat finish can be quickly and easily achieved. AFUMEX LSX™ is ideal for clipping direct to the metal frame structure of a pre-fabricated fast track building.

Weight & Diameter Comparison Accessory SelectionCable size

SWA is heavier by %

LSXTM is smaller by %

LSOH Cable Gland Product

Code

AP Clip Code

2x1.0 - - 251 AP7W

2x1.5 135 17 251 AP9W

2x2.5 128 19 252 AP10W

2x4 100 17 252 AP11W

2x6 109 17 254 AP12W

3x1.0 - - 251 AP8W

3x1.5 115 16 251 AP9W

3x2.5 103 19 252 AP10W

3x4 80 19 252 AP12W

3x6 80 15 254 AP13W

4x1.0 - - 251 AP9W

4x1.5 100 15 252 AP10W

4x2.5 96 21 252 AP11W

4x4 73 21 254 AP13W

4x6 50 12 254 AP15W

AFUMEX LSX™ is lighter in weight and smaller in diameter than 1 kV armoured cables

requirements of BS8436 (1.0mm2 to 2.5mm2).

Page 43: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

AFUMEX LSXTM Applications GuideScreened Wiring Cables

Small Power - Ring Main & Radial Circuits

Installation Note: XLPE 90°C rated conductor gives higher current ratings and improved design options.

Ring main or radial circuit designs utilising optimum circuit breaker range.

EMC and Clean Power Supply

AFUMEX LSX™ has a full 360° metal screen, aiding EMC compliance throughout the run of the cable. The full 360° metal screen makes AFUMEX LSX™ ideally suited for clean power supply use.

Installation note: AFUMEX LSX™ cables can be grouped with limited cross talk between cables.

Lighting - HPS, Tungsten & Fluorescent

HPS, tungsten and fluorescent lighting for office, retail and domestic applications.

Installation note: AFUMEX LSX™ can be easily refitted to accommodate merchandising floor area changes, making it suitable for HIGH CHURN environments.

Fixed Applications

Air conditioning, fans, compressors, heaters and hand dryers etc.

Installation note: All cables include an un-insulated CPC equal in size to the phase conductor and in contact with the full 360° aluminium screen, which provides automatic screen earthing.

LSOH® Standard

AFUMEX LSX™ offers a pronounced effect on safety and a dramatic reduction in risk.

Installation note: AFUMEX LSX™ is part of the most comprehensive range of Low Fire Hazard cables available and has reduced flame propagation properties and offers significant improvements over standard cables in the event of a fire, preventing the spread of flames from one area to another.

Public Access Buildings Other Applications

● Point of sales equipment ● Ring mains power ● Clean Rooms ● Compressor supplies● Stadium floodlights ● Fan motor supplies● Air conditioning ● Temporary wiring requirements● Ventilation systems ● Hospitals

Availability● AFUMEX LSX™ cables can be obtained from all reputable UK wholesalers or Prysmian agents. We also hold stocks at our factory for immediate dispatch.

● The standard colour for AFUMEX LSX™ is white. Other colours can be supplied, such as black or purple to meet specific needs. A minimum order quantity may apply.

● Cable is usually supplied in 100 metre lengths. Other lengths can be made to special order.

A fire is bad enough, don’t make it worse

Minimise the risk with AFUMEX LSX™

Page 44: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helplineTel: 023 8029 5222Fax: 023 8029 [email protected]

Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom

www.prysmian.co.uk

Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465

Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]

Ref: AFU

MEXLSX/05/10

Page 45: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

PiresafeTM FlexLSOH Flexible CablesLow Voltage (300/500 V)

> Plain annealed copper, flexible stranded circular conductor, complying

with BS EN 60228 Class 5

> LSOH insulation

Core Identification

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

> Flexible LSOH® sheath

> Colour - Normally white but other colours are available on request

Sheath

> Supply leads for medium duty domestic and office appliances, lighting

fittings and portable appliances . Used in a wide range of public access

buildings and industrial complexes where improved public safety and

environmental control are desirable

Ref: PiresafeFlex/11/09

Key Applications

oo blue-brownoo blue-brown-green/yellowooo brown-black-grey-green/yellow

TemperatureRange

-15 to +70°C

Bending RadiusFixed r=4D

Flexing r=6D

Mechanical ImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibilityFlexible

Halogen FreeBS EN 50267-2-1

Low smoke emissionsBS EN 61034-2

3182B, 3183B, 3184B

> Piresafe Flex is a flexible cable, which when burnt produces very low

quantities of smoke and virtually no acidic gases thus safeguarding

human life and protecting equipment

> All Prysmian cables are manufactured under an ISO 9001 Quality

System certified by BASEC

Key Features

oooo oooo

Page 46: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Prysmian Cables & Systems Limited, Sales Office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Cable Details

Nominalcross

sectionalarea

mm²

Conceptualconstruction

no./mm

Approximateconductordiameter

mm²

Nominaloverall

diameter

mm

Approximatecable

weight

kg/km

Minimumbendingradius

(Flexing)

mm

Maximumconductorresistance

at 20°C

ohms/km

Currentrating DC

orsingle

phase AC

Amps

Volt drop DCor single

phaseAC

mV/A/m

Currentrating threephase

AC

Amps

Volt dropthreephase

AC

mV/A/m

Two Core

0.75 24/0.20 1.14 6.2 59 40 26.0 6 62 - -

1.0 32/0.20 1.32 6.6 67 40 19.5 10 46 - -

1.5 30/0.25 1.6 7.6 90 45 13.3 16 32 - -

2.5 50/0.25 2.05 9.1 141 55 7.98 25 19 - -

Three Core

0.75 24/0.20 1.14 6.6 69 40 26.0 6 62 - -

1.0 32/0.20 1.32 7 80 45 19.5 10 46 - -

1.5 30/0.25 1.6 8.2 113 50 13.3 16 32 - -

2.5 50/0.25 2.05 9.8 176 60 7.98 25 19 - -

Four Core

0.75 24/0.20 1.14 7.0 83 45 26.0 6 62 6 54

1.0 32/0.20 1.32 7.8 101 50 19.5 10 46 10 40

1.5 30/0.25 1.6 9.2 141 55 13.3 16 32 16 27

2.5 50/0.25 2.05 10.8 214 80 7.98 25 19 20 16

Ambient Temperature °C 30 35 40 45 50 55

Rating factor 1.00 0.91 0.82 0.71 0.58 0.41

Temperature rating factors

PiresafeTM Flex

Ref: PiresafeFlex/11/09

Page 47: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Installation in surface mounted or embedded conduits or similar closed

systems and for fi xed protected installation in or on lighting fi ttings and

inside appliances, switchgear and control gear

> Green/Yellow for use as earth

PVC Conduit Wire(H07V - U, H07V - R)

Key Applications

Ref: 6491X/04/06

Standard Wiring CablesLow Voltage (450/750 V)

6491X

Cable Approvals Cable approved to BS6004

TemperatureRange

-15 to +70°C

BendingRadius

Fixed r=6D

MechanicalImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibiltyRigid

> Plain annealed copper solid or stranded circular conductor complying with

BS EN 60228 Class 1 or Class 2

o Greyo Blacko Blueo Yellowo Browno o White

Green/Yellow

> PVC Insulation complying with BS EN 50363-3 Type Tl1

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Page 48: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Ref: 6491X/04/06

Nominalcross

sectional area

mm²

Approximate overall

diameter

mm

Approximate cable weight

Kg/Km

Maximum conductor resistance at 20°C

Ohms/km

Short circuit rating (1 sec)

KA

Current rating DC or single phase AC enclosed

in conduit or

trunkingAmps

Current rating Three

phase AC enclosed

in conduit or

trunkingAmps

Voltage drop DC

mV/A/m

Voltage drop DCsingle phase

mV/A/m

Voltage drop three

phase AC

mV/A/m

H07V-U (Solid conductor)

1.5 3.0 21 12.1 0.17 17.5 15.5 29 29 25

2.5 3.6 32 7.41 0.28 24 21 18 18 15

H07V-R (Stranded conductor)

1.5 3.0 23 12.1 0.17 17.5 15.5 29 29 25

2.5 3.6 35 7.41 0.28 24 21 18 18 15

4 4.2 51 4.61 0.46 32 28 11 11 9.5

6 4.7 71 3.08 0.69 41 36 7.3 7.3 6.4

10 6.1 120 1.83 1.15 57 50 4.4 4.4 3.8

16 7.2 180 1.15 1.84 76 68 2.8 2.8 2.4

25 8.4 280 0.727 2.88 101 89 1.75 1.8 1.55

35 9.5 380 0.524 4.00 125 110 1.25 1.3 1.1

50 11.3 490 0.387 5.75 151 134 0.93 1.0 0.85

70 12.6 710 0.268 8.00 192 171 0.63 0.72 0.61

95 14.7 980 0.193 10.9 232 207 0.46 0.56 0.48

120 16.2 1210 0.153 13.8 269 239 0.36 0.47 0.41

150 18.1 1510 0.124 17.3 300 262 0.29 0.41 0.36

185 20.2 1900 0.0991 21.3 341 296 0.23 0.37 0.32

240 22.9 2490 0.0754 27.6 400 346 0.18 0.33 0.29

300 27.0 3050 0.0601 34.5 458 394 0.145 0.31 0.27

400 32.0 3900 0.047 41.1 546 467 0.105 0.29 0.25

Ambient Temperature °C 25 30 35 40 45 50 55 60 65

Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35

Temperature Rating Factors

Number of Circuits 2 3 4 5 6 7 8 9 10 12 14 16 18 20

Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38

Correction factors for Groupings

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

PVC Conduit Wire(H07V - U, H07V - R)

Page 49: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Fixed installation in dry or damp premises on walls, boards or trays, in

channels or embedded in plaster

PVC Flat Wiring Cables with Bare CPC

Key Applications

Standard Power CablesLow Voltage (300/500 V)

6241Y, 6242Y, 6243Y

Cable Approvals Cable approved to BS6004

> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 16.0mm²)

circular conductor complying with BS EN 60228 Class 1 or Class 2

> PVC Insulation complying with BS EN 50363-3 Type Tl1

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

TemperatureRange

-15 to +70°C

Bending RadiusFixed r=4D(minor axis)

MechanicalImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibilityRigid

> PVC Sheath complying with BS7655 Type 6

> Colour - grey

o o o brown-CPC-blue

o o o o brown-black-CPC-grrey

Sheath

Ref:6242Y/05/06

Page 50: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Nominalcross

sectional area/ CPC

mm²

Approx.overall

diameter

mm

Approximatecable

weight

kg/km

Maximumconductorresistance

at 20°C

Ohms/km

Short circuit

rating of conductor

(1 sec)

kA

Current rating Volt drop DC or single

phase AC

mV/A/m

Volt drop three

phase AC

mV/A/m

DC or Single

phase AC clipped direct

Amps

DC or Single phase AC enclosed

in conduit in an insulated

wallAmps

Three phase AC clipped direct

Amps

Single Core

1.0 / 1.0 4.5 x 5.6 41 18.1 0.12 16 11.5 13.5 44 381.5 / 1.0 4.7 x 5.8 49 12.1 0.17 20 14.5 17.5 29 25

Two Core1.0 / 1.0 4.5 x 8.2 68 18.1 0.12 16 11.5 - 44 -1.5 / 1.0 4.7 x 8.6 85 12.1 0.17 20 14.5 - 29 -2.5 / 1.5 5.3 x 9.9 124 7.41 0.28 27 20 - 18 -4.0 / 1.5 6.1 x 11.4 172 4.61 0.46 37 26 - 11 -6.0 / 2.5 6.8 x 13.1 238 3.08 0.69 47 32 - 7.3 -10 / 4.0 8.4 x 16.8 390 1.83 1.15 64 44 - 4.4 -16 / 6.0 9.6 x 19.5 575 1.15 1.84 85 57 - 2.8 -

Three Core1.0 / 1.0 4.5 x 10.7 95 18.1 0.12 16 11.5 13.5 44 381.5 / 1.0 4.7 x 11.7 115 12.1 0.17 20 14.5 17.5 29 252.5 / 1.5 5.3 x 12.8 170 7.41 0.28 27 20 24 18 154.0 / 1.5 6.4 x 16.0 155 4.61 0.46 37 26 32 11 9.56.0 / 2.5 7.0 x 18.1 340 3.08 0.69 47 32 41 7.3 6.410 / 4.0 8.3 x 22.5 550 1.83 1.15 64 44 57 4.4 3.816 / 6.0 9.5 x 26.3 790 1.15 1.84 85 57 76 2.8 2.4

Ambient Temperature°C 25 30 35 40 45 50 55 60Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

Temperature rating factors

Ref:6242Y/05/06

PVC Flat Wiring Cables with Bare CPC

Page 51: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

> Fixed installation in dry or damp premises on walls, boards or trays, in

channels or embedded in plaster

PVC Insulated Sheathed Single Core

Key Applications

Standard Wiring CablesLow Voltage (300/500 V)

6181Y

Cable Approvals Cable approved to BS6004

> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 35.0mm²)

circular conductor complying with BS EN 60228 Class 1 or Class 2

> PVC Insulation complying with BS EN 50363-3 Type Tl1

Core Identifi cation

Insulation

Conductor

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

TemperatureRange

-15 to +70°C

Bending RadiusFixed r=4D

MechanicalImpactMedium

Fire PerformanceBS EN 60332-1-2

FlexibilityRigid

> PVC Sheath complying with BS7655 Type 6

> Normally grey but others available on request

o redo black o blueo brown

Sheath

Ref:6181Y/05/06

Page 52: 4> - Voltimum · 2013. 7. 5. · FP200 GOLD® BS7629-1:2008 INSTALLATION FIRE RESISTANT CABLES DATA CAPABILITY APPROVALS FP200 GOLD® > The original highly durable and dressable,

Cable Details

Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK

Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465

www.prysmian.co.uk

Nominalcross

sectional area

mm²

Approx.overall

diameter

mm

Approximatecable

weight

kg/km

Maximumconductorresistance

at 20°C

Ohms/km

Short circuitrating(1 sec)

kA

Current Rating Volt drop DC or single

phase AC

mV/A/m

Volt drop three

phase AC

mV/A/m

DC or Single

phase AC enclosed

in conduit or trunking

Amps

DC or Single

phase AC clipped direct

Amps

Three phase AC clipped direct

Amps

1.0 4.2 28 18.1 0.12 13.5 15.5 14 44 381.5 4.6 36 12.1 0.17 17.5 20 18 29 252.5 5.3 50 7.41 0.28 24 27 25 18 154.0 6.1 75 4.61 0.46 32 37 33 11 9.56.0 6.7 98 3.08 0.69 41 47 43 7.3 6.410 8 155 1.83 1.15 57 65 59 4.4 3.816 9.5 232 1.15 1.84 76 87 79 2.8 2.425 11.3 338 0.727 2.88 101 114 104 1.75 1.635 12.3 442 0.524 4.00 125 141 129 1.25 1.1

Ambient Temperature °C 25 30 35 40 45 50 55 60Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

Temperature rating factors

Ref:6181Y/05/06

Number of Circuits 2 3 4 5 6 7 8 9Rating Factor 0.8 0.7 0.65 0.6 0.57 0.54 0.52 0.5

Correction Factors for Groupings

PVC Insulated Sheathed Single Core