DEVAR Inc. 706 Bostwick Avenue, Bridgeport, CT 06605 TEL: 203-368-6751 FAX: 203-368-3747 1-800-566-6822 www.devarinc.com
Model 332
ALARM / CONTROLLER
INDUSTRIAL CONTROL EQUIPMENT MANUAL NO. 990620A
TABLE OF CONTENTS Section Title Page No. I General Description …………………………… 1 II Specifications ………………………………….. 3 III Installation ……………………………………... 5 IV Operation ………………………………………. 7 V Recalibration …………………………………… 9 VI Power Supply Options ……………………….… 12 VII Troubleshooting ………………………………... 13 VIII Parts List ……………………………………….. 18 Addendum A Model 332-AP Pump Controller
TABLES AND ILLUSTRATIONS Figure Title Page No.
3.1 General Dimensions 332W ……………………… 5 3.2 General Dimensions 332P ………………..……… 6 3.3 Field Wiring ……………………………………... 6 4.1 Dip Switch Setting Table ……………………...… 8 5.1 Input Range Calibration Table ............................... 10 5.2 Display Recalibration Procedure ............................ 11 5.3 Decimal Point Location .......................................... 11 6.1 Modification for 24 VDC Power ............................ 12 7.1 Schematic ................................................................ 14 7.2 Component Location, Display Board ..................... 15 7.3 Component Location, Circuit Board ....................... 16 7.4 Component Location, Power Supply ...................... 17
Page 1
SECTION I GENERAL DESCRIPTION
1.1 General
The Devar Model 332 Alarm/Controller is a high accuracy multipurpose instrument, providing process indication, two separate alarm channels, independently adjustable set and reset points, substantial relay contact rating and simplicity of adjustment, with set and reset points read directly from the digital display.
1.2 Theory of Operation
Used as a simple alarm, the 332 monitors a single voltage or current input signal and compares it to the trip point setting. When the input signal reaches the trip point setting an alarm is initiated and the internal relay, which is normally energized for fail-safe operation, will de-energize.
1.3 Dual Channel Operation
The 332 monitors a single voltage or current input and provides two output channels with independent trip point adjustments and environmentally sealed, 10 amp, SPDT relays. Each channel can be set to alarm on an increasing or decreasing input signal by means of an internal DIP switch setting. A red LED turns on indicating which channel has alarmed and the bright red backlit display begins flashing on and off, alerting an observer to the alarm condition. The flashing display option can be disabled if desired.
990620
Page 2 1.4 Set Point and Reset Point
A special feature of the 332 is the ability to set not only the alarm trip point, but also the reset point (e.g. the alarm could be set to trip if the input were to go above 75%, but not to reset until the input fell below 50%). Both set and reset points can be adjusted anywhere between -5% and +105% of the input range. This feature makes the 332 ideal as a simple on/off controller. A typical application could be level control in a tank. If the desired level was at 50%, a pump could be turned on when the level fell below 50% and turned off once the level rose above some pre-specified value. Should the level continue to drop (e.g. below 40%) a second pump could be activated until the level was corrected.
1.5 Display
The 332 provides a large 3-1/2 digit display with bright red backlit digits, which can be easily seen in bright ambient light or in total darkness. This display is used to monitor the input signal as well as to set the alarm trip and reset points. The display is calibrated to read in percent, however, it can be factory calibrated to read directly in engineering units such as °F, °C, PSI, GPM, etc.
1.6 Packaging and Shielding
The 332 is housed in a rugged steel enclosure and is available in either panel mounted or wall mounted versions. The internal relays are epoxy encapsulated in a separate steel box mounted inside of the larger enclosure. This method of assembly provides environmental isolation for the relays as well as electrical shielding for the electronic circuitry. In addition, all lines going to the electronic circuitry have been RFI filtered.
1.7 Power
The 332 is powered from 115 VAC, however, 230 VAC and 24 VDC operations are also available. When AC powered, The 332 provides a 24 VDC output which can used to power an external two wire transmitter.
990620
Page 3
SECTION II SPECIFICATIONS
2.1 General a. Repeatability ........................................................................ 0.1 % of span b. Resolution Trip Adjust ........................................................ 0.1 % of span c. Display Accuracy ...................................................... Reading ± 2 Counts d. Indication ................................................. Input, Set Points, Reset Points; Scale 0 to 100% Standard (Non-standard Ranges Between ± 1999 Counts) e. Set Point (dual) .................................................................... -5% to +105% f. Reset Point (dual) ................................................................. -5% to +105% g. Operating Temp. Alarm ....................................................... -10 to +70° C h. Operating Temp. Display ........................................................ 0 to +60° C i. Storage Temperature ............................................................. -20 to +80° C j. Temperature Effect .......................................................... 0.018%/°C, max. k. Display …………………………………… 1/2 inch High, 3.5 Digit LCD Backlit, Red Digits on Black l. Power ..................................................................... 115 V, 50/60 Hz, 6 VA Option E71: 230 V, 50/60 Hz, 6 VA Option E92: 24/28 VDC, 90 mA (Non-isolated) 2.2 Inputs a. Standard Ranges ………………………………. 332-1 0/5 mA, Ri = 200 Ohms -2 1/5 mA, Ri = 200 Ohms -3 4/20 mA, Ri = 50 Ohms -4 10/50 mA, Ri = 20 Ohms -5 0/10 mA, Ri > 10 meg -6 0/5 V, Ri > 10 meg -7 0/1 mA, Ri = 1K Ohms -8 0/1 V, Ri > 10 meg -9 1/5 V, Ri > 10 meg -X Non-standard, Specify 990620
Page 4 2.3 Alarm Contacts a. Relays .............................................................. (2) SPDT,
Epoxy Encapsulated b. Mechanical Life……………………………… 20 Million Operations c. Electrical Life……………………………...… 100,000 Operations at 8 Amps, 240 VAC, 24 VDC, Resistive 50,000 Operations at 10 Amps (N.O. contact) 5 Amps (N.C. contact) 120 VAC, Resistive 30,000 Operations at 7.2 Motor Run Amps, 45 Lock Rotor Amps, 120 VAC 10,000 Operations at 5 Motor Run Amps, 30 Lock Rotor Amps, 240 VAC d. Maximum Switched Power………………….. 200 W DC, 2000 VA AC e. VDE Contact Rating…………………………. 8 Amps, 250 VAC f. UL Contact Rating…………….........………... 10 Amps, 240 VAC, Resistive, 8 Amps, 24 VDC, Resistive 1 /3 HP, 120 VAC 1 /2 HP, 240 VAC 2.4 Housing
a. Indoor Type………………………………….. Panel or Wall Mounted, Gray Baked Enamel Over Zinc Plated Steel b. Weight ............................................................. 2.3 lbs.
990620
Page 5
SECTION III INSTALLATION
3.1 Mounting
The 332 Alarm/Controller is available, either as a wall mounted (332W) or as a panel mounted (332P) unit. The wall mounted unit is attached to the wall by means of two #6 or #8 screws (see fig. 3.1). The panel mounted unit is inserted through the front of the panel then locked in place by a U-shaped bracket, which is screwed to the rear of the housing using two #6 screws (see fig. 3.2).
3.2 Field Wiring
Field wiring connections are made to a 12 point, compression type terminal block, which can accept up to 14 AWG wire (see fig. 3.3).
Figure 3.1 – General Dimensions 332W 990620
DEVAR INC.
4.38"(111 mm)
4.00"(101.6 mm)
2.68"(68 mm) 4.72"
(120 mm)
INPUTSET SET
RESET RESET
Model 332W
+ – 24V
GN
D
AC
AC
BA
MOUNTING HOLES0.169 DIA, 4 IN. ON CENTER
Page 6
Figure 3.2 – General Dimensions 332P
Figure 3.3 – Field Wiring 990620
4.60"(117 mm)
3.90"(99 mm)
INPUTSETSET
RESET RESET
A B
2.95"(75 mm)
PANEL CUTOUT3.67" (93.2 mm) × 2.71" (68.8 mm)TOLERANCE ±0.015 (±0.38 mm)
MODEL 332PALARM CONTROLLER
DEVAR Inc.
CASE
AC ACGN
DG
ND
+24 VDC
CO
MM
ON
+ INPU
T
ALARMB
117 VAC(OPTION E71, 220 VAC)
ALARMA
4 WIRETRANSMITTERPOWER
+
+
-
-2 WIRETRANSMITTER
-++24 VDC(OPTION -E92)
OR
Page 7
SECTION IV OPERATION
4.1 High-Low Selection
Each channel of the 332 Alarm/Controller can be independently configured for high alarm or low alarm operation by setting the internal dip switches. To do this remove the cover from the top of the 332 and set the dip switches to the proper positions as specified in figure 4.1.
4.2 Alarm Indication
The 332 has been factory configured so that if either channel goes into alarm the display will begin to flash. The display will continue to flash as long as one of the channels remains in the alarm condition. If this feature is not desired it can be disabled by removing diodes D3 and D4 from the PC board. See figure 7.3 for the location of diodes D3 and D4. An alarm condition is also indicated by two red LEDs, one for channel A and one for channel B. These LEDs will light on alarm. The operation of the LEDs is not affected by disabling the flashing display.
4.3 Trip Point Selection
To set the trip point turn the selector knob to the Set position then adjust the trip point pot until the desired trip point appears on the display. To set the reset point, turn the selector knob to the Reset position, then adjust the reset pot until the desired reset point appears on the display. For a high alarm, the reset point should be set at least 0.1% below the trip point, and for a low alarm, at least 0.1 % above the trip point, this is to prevent relay chattering when the input is exactly at the trip point. However, we recommend a dead band setting of 1% or more, in order to exceed the noise normally found on the input signal, in factory environments. Once the trip and reset points are set for both channels, turn the selector knob to Input (the center position). The input will now be displayed.
4.4 Trip Point Monitor
The set and reset points can be set whenever power is applied to the unit. An input signal is not required. The set and reset points can also be monitored at any time, while the unit is in operation. Turning the selector switch to display the trip or reset point has no effect on the operation of the unit.
990620
Page 8
ALARM ACTION ON POSITIONS OFF POSITIONS
HI 1, 2 3, 4 A
LOW 3, 4 1, 2
HI 5, 6 7, 8 B
LOW 7, 8 5, 6
Figure 4.1 – Dip Switch Setting Table 990620
1 2 3 4 5 6 7 8
SPAN ZERO OFF
ON
TOP VIEW OF CIRCUIT BOARD SIDE VIEWOF SWITCH
Page 9
SECTION V RECALIBRATION
5.1 Standard Input Calibration
The 332 Alarm/Controller is calibrated to display 00.0 to 100.0 for any standard input range. To change the input from one standard range to another standard range, the proper values for resistors R107, R109 and R110 must be selected. The value of these resistors, for standard input ranges, is listed in figure 5.1. The location of these resistors can be found in figure 7.3.
5.2 Span and Zero Adjustment
Once the proper calibrating resistors have been installed, turn the selector switch to the Input position and apply an input signal to the unit. Adjust the span and zero pots (see fig. 7.3) until the display is calibrated to read 00.0 to 100.0.
5.3 Nonstandard Input Calibration
The 332 Alarm/Controller can also be calibrated for nonstandard input ranges. To do this the values of resistors R107, R109, and R110 must be calculated so that the new input range will produce an output voltage of 0 to 4.75 V at pin 14 of amplifier U2. See figure 7.1 for the circuit schematic and figure 7.3 for the location of amplifier U2. Once the resistors have been installed, an input signal must be applied and the span and zero pots adjusted, as described in paragraph 5.2.
5.4 Engineering Units
The display of the 332 Alarm/Controller can also be calibrated to read directly in engineering units. To do this requires the removal of jumper J2, the selection of resistors R28 and R29, and the positioning of jumper J1, for decimal point selection. These components are located on turret terminals on the PC board, behind the display (see fig. 7.2).
990620
Page 10 5.5 Display Recalibration To recalibrate the display, the value of resistors R28 and R29 can be calculated by following the steps outlined in figure 5.2. See figure 5.3 for decimal point selection. Once these resistors and jumpers have been installed the unit must be calibrated. To do this, apply a signal to the input terminals of the 332. Input the bottom of the range and adjust the zero pot for the proper display reading, then input the top of the range and adjust the span pot. Repeat this procedure until the display is calibrated. See figure 7.3 for the location of the span and zero pots.
R109 R110 R107
Input Range Ohms Part No. Ohms Part No. Ohms Part No.
0/1 mA 1,000 223737-0021 84,500 223737-0036 243,000 223737-0131
0/5 mA 200 514490-2000 84,500 223737-0036 243,000 223737-0131
1/5 mA 200 514490-2000 82,500 223737-0076
4/20 mA 49.9 514490-0499 82,500 223737-0076
10/50 mA 20 223737-0181 82,500 223737-0076
1/5 V 4,320 223737-0026 82,500 223737-0076
0/1 V 84,500 223737-0036 243,000 223737-0131
0/5 V 3,320 223737-0138 243,000 223737-0131
0/10 V 1,500 223737-0059 243,000 223737-0131
Figure 5.1 – Input Range Calibration Table 990620
Page 11
To Recalibrate Display Example
1. Specify New Range -45.0 to 150.0 °F
2. Calculate Span Counts (Ignore decimal point)
1500 -(-) 450 1950 counts
3. Note offset counts -450 counts
4. Calculate Scaling Factor a = (span) × 4.2283 × 10-5 (1950) × 4.2283 × 10-5 = 0.08245
5. Calculate Resistor R19 45300 × a 1-a
45300 × 0.08245 1- 0.08245
6. Select Closest Standard 1% Resistor, 50 PPM/°C or better
R19 = 4020 Ohms
7. Calculate millivolt Offset V = (± Offset) × 2 × 10-4 (-450) × 2 × 10-4 = -0.09 Volts
8. Calculate Offset Resistors
Using R28 = 20,000
9. Select Closest Standard 1% Resistor, 50 PPM/°C or better
R28 = 20K R29 = 4.53K
Figure 5.2 – Display Recalibration Procedure
Figure 5.3 – Decimal Point Location 990620
D3
D3
D2 D2J1
J1
J1
J1
D1
D1
R19 = = 4070.6
6.2355 + 0.09
-1 × 20,000 = 4499R29R28
6.2355 -V= -1
Page 12
SECTION VI POWER SUPPLY OPTIONS
6.1 Conversion to 230 VAC Power
To change the power supply operation from 115 to 230 VAC, a jumper "J3" must be added on the power supply board and the track must be cut in two places. Reference figure 7.1 for the circuit schematic and figure 7.4 for the location of the jumper and the cut tracks.
6.2 Conversion to 24/28 VDC Power
For 24 to 28 VDC operation, remove transformer "TI" and diode bridge "DB1" from the power supply board, add diode IN4002 (380666-01) and jumpers "J4" and "J5". Reference figures 6.1, 7.1, and 7.4.
Figure 6.1 – Modification for 24 VDC Power 990620
Page 13
SECTION VII TROUBLESHOOTING
7.1 Check Points
If the 332 Alarm/Controller is not operating properly, check the following: a. That the unit is receiving power. b. That all terminals are wired correctly and that terminal screws are tight. c. That the reset point is below the set point for a high alarm. d. That the reset point is above the set point for a low alarm.
7.2 Troubleshooting
If the cause of the problem is not found, disconnect all connections, except power, from the terminal block. Make the following tests to determine in, which part of the circuit the problem lies.
a. Check for +24 volts between field terminals 3(+) and 2(-). b. Turn the selector switch to the set and reset positions and check to see that the display responds to adjustment of set and reset pots. c. Short input terminals 1 and 2, and turn the selector switch to the input position. For a 0 to 100% display, the reading should be 00.0, if the unit has been calibrated for a zero based input such as 0 to 10 volts. The display should read -25.0 if the unit has been calibrated for an input with a 25% offset such as 4 to 20 mA. d. To troubleshoot the circuit, refer to the schematic, figure 7.1 and component location drawings, figures 7.2, 7.3, and 7.4.
7.3 Replacement Parts
Replacement parts may be ordered, by their part number from Devar Inc. Most capacitors, diodes and resistors are readily obtainable from local electronics distributors. Reference Section VIII for a complete list of parts used in the 332.
990620
Page 14
Figure 7.1 - Schematic 990620
+2
BRN
RED
1
D
R23
12MC
120.
1uF
LED
2
C18
0.04
7uF
R11
24.3
K
0/4.
75V
AL1
56
4
YEL
OR
N
D
K1
11
C19
0.04
7uF
S1
K2
16
+28V
+28V
K1
R20
8.06
KLE
D1
K2
R21
8.06
K
BLU
D1
+
R11
0U2
C10 1uF
P2 10K
AL2
CO
MPA
RAT
OR
R33 1K
S1
R32 1K
AL1
CO
MPA
RAT
OR
U1
R30
40.2
K
OSC
ILLA
TOR
A
48
LO
18
10
14
1314
2 3 4LOH
IH
I
HI
HI
LO LO
6 7 85
SHEE
T
DW
G N
O.
SH
REV
DES
CR
IPTI
ON
AR
ELEA
SE E
CN
302
0B
TER
MIN
AL S
CR
EW
TUR
RET
TER
MIN
AL
RIB
BON
CAB
LE C
ON
NEC
TOR
FEED
TH
RO
UG
H C
APAC
ITO
R
FER
RIT
E BE
AD
TRAC
E C
UT
S S
Q1
5
C7
0.04
7uF C
30.
047
uF
U2
R3
16.5
K
R2
16.5
K
U1
R31
40.2
K
R4
16.5
KU
2
R5
16.5
KU
1
C9
0.04
7uF
A
C6
0.04
7uF
21
4
76
7 123 11+1
5V
103
1 O
F 1
SIZE
SCAL
EW
T
DR
AWIN
G N
O.
NO
NE
PREP
ARED
CH
ECKE
D
MEC
H
ELEC
DES
IGN
APPR
OVE
D
APPR
OVE
D
CO
NTR
ACT
NO
.
RN
T
FIN
ISH
MAT
ERIA
L
NEX
TAS
S'Y
NO
.
R29
1.2M
R28
1.2M
13
A
6
R22
49.9
K
D3 D4
D6D5
D
1312
R10
16.5
K
-1.2
V
A
U1
U2
9 1011
REL
EASE
EC
N 3
020B
, CH
ANG
E R
20 &
R21
,C
HAN
GE
LED
1 &
2, A
DD
R28
, R29
, D3,
D6
C DAD
D R
30 &
R31
, EC
N 3
136
E FAD
D C
200,
EC
N 3
253
GAD
D R
34, E
CN
327
8H
ADD
C10
0, E
CN
322
3
C1
0.04
7 uFC
R1
13V
R1
16.5
K
R6
40.2
K
R10
9C
111u
F
C8
0.04
7uF
5 3
R7
40.2
K
A
CH
ANG
E R
26 &
R27
, AD
D C
18, C
19,
R30
, 31,
32,
33,
EC
N 3
020C
9
C2
0.04
7uF
R10
7
20
3
AC12
AC11
+24V
CU
T FO
R22
0 VA
C
GR
N
6 7 8
3 4 1 2
+28V
INU
3
OU
TU
5
U4
42
3
58
C15
10uF
C17
10uF
A D
16
C16
10uF
+5V
-5V
CR
32.
5V
CR
22.
5V
R27
1.21
K
C10
00.
1µF
A
A
C20
010
µF
C14 330 uF
BLK
BLK
14
CR
41.
2V
R26
806
OU
T
Q10
Q8
Q7
Q9
R34
100K
C13
0.1u
F
S
S
1717
1818
5
7
4 8
92
SSQ
3
-1.2
V
Q5
S SQ
6
19
C20
0.00
1uF
C19
0.00
1uF
L2L1
11 12
-1.2
V
+15V
+–
DB1
T15
D2
20
Q5
Q612
AR
930
.1K
P1 10K
R8
7.87
K
+5V
+15V
14
C5
0.04
7uF
ZER
O
A
C4
0.04
7 uF
111-1
.2V
GN
D10
89
7
SPAN
A
A
A
+15V
A
A+1
5V
D
131
J3
220
VAC
09/1
2/05
AL2
INPU
T–
+15V
+28V
BDE
VA
R In
c.
UN
SPEC
IFIE
D D
IMEN
SIO
N T
OLE
RAN
CE
D
ECIM
AL
+/-
0.00
5"
FRAC
TIO
N
+/-
1/64
"
ANG
LE
+
/- 1/
2 D
EGR
EE
BM 5
1540
7
This
Dra
win
g is
the
sole
pro
perty
of
DEV
AR In
c.,
and
is s
ubm
itted
on
the
unde
rsta
ndin
g th
at th
e co
nten
ts h
ereo
f are
not
pu
blis
hed
and
are
not
to b
e di
sclo
sed.
to th
ird p
erso
ns w
ithou
tpr
ior p
erm
issi
on.
IN
+ -
- +
Q4
- +- ++-
Q2
-+
+-
R25
1.2M Q11
R24
12M
-
-N/A
-
-N/A
-
151
5436
332
ALAR
M/C
ON
TRO
LER
SCH
EMAT
IC
RED
RAW
N, E
CN
331
1
706
Bost
wic
k Av
enue
, Brid
gepo
rt, C
onn.
066
05TE
L: (2
03) 3
68-6
751
FAX:
(203
) 368
-374
7
5154
36
0.8V
V≅
∆
2P3 20
K
3P4 20
KP5 20
K
R14
3.57
K
P6 20K
109
J2
+5V
R13
3.57
K
-5V
J1
DIS
PLAY
-1.2
V
R18
45.3
K
R29
R17
1.07
KTR
IP1
RES
ET2
RES
ET1
TRIP
2
R28
RFLRFH
D3D2D1
IN LO
NC
+V
13
1+5
V
-1.2
V
R16
25.5
K
–
R15
3.57
KR
123.
57K
12
11
ROH
IN HI
COMTST
-V
A
+
19
R30
100
R31
100
20
POW
ER S
UPP
LY B
OAR
D
CIR
CU
IT B
OAR
D
S223
54 1
RES
ET1
4TR
IP1
5IN
PUT
TRIP
2R
ESET
28 7 6
CIR
CU
IT B
OAR
D
DIS
PLAY
BO
ARD
6
FILT
ER B
OX
APPR
OVE
D
AGAG AG AGAGAG AG AG
DAT
E
10-2
0-93
03-2
4-92
01-0
5-94
04-1
6-97
04-2
0-00
04-3
0-01
06-1
4-01
1-19
-06
REV
R19 2K
H
Page 15 PAGE 16 FIGURE 7.3
Figure 7.2 - Component Location, Display Board 990620
Page 16
Figure 7.3 - Component Location, Circuit Board 990620A
Page 17
Figure 7.4 - Component Location, Power Supply 990620
Page 18
SECTION VII PARTS LIST
7.1 Parts relating to calibration can be found in Fig. 5.1, The Input Range Calibration Table. To order spare or replacement parts, contact your local Devar Inc. representative. Whenever possible, specify items by description and part number. 7.2 Resistors, 1% Metal film Part Number
R1,2,3,4,5,10 16.5K 223737-0099 R6,7,30,31 40.2K 223737-0048 R8 7.87K 223737-0042 R9 30.1K 223737-0009 R11 24.3K 223737-0137 R23,24 12M (5%) 221862-0024 R25,28,29 1.2M (5%) 222087-0015 R12,13,14,15 3.57K 223737-0063 R16 25.5K 223737-0008 R17 1.07K 223737-0053 R18 45.3K 223737-0085 R19,20,21,27 2K 223737-0058 R26 1.5K 223737-0059 R32,33 1K 223737-0021
7.3 Potentiometers
P1,2 10K, 3006Y 381098-0010 P3,4,5,6 20K, 3299W 381355-0011
7.4 Capacitors
C1 thru C9,18,19 0.047µF, 50WV, Ceramic 382473-0001 C10,11,15,16,17 10µF, 20WV, Tantalum 380767-0001 C12,13 0.1µF, 50WV, Ceramic 382473-0001 C14 330µF,50WV, Electrolytic 514491-0001
990620
Page 19 7.5 Semiconductors
Q1 thru Q11 N Channel, V-MOS 514404-0001 D1,2,3,4,5,6 Diode, IN4153 222095-0001 CR1 Zener, 13V, IN5243B 381071-0005 LED1,2 LED, HLMP-4700 514472-0002 DB1 Diode Bridge, PF10 380766-0002
7.6 Integrated Circuits
U1,2 Op-Amp, Quad, TLC27L4IN 514841-0001 U3 Regulator, 15V, LM340T-15 381584-0001 U4 DC to DC Converter, TSC7660 514735-0001 U5 Regulator, 24V, MC7824CT 513410-0001 CR2,3 Reference, 2.5V, LM385B-2.5 382209-0003 CR4 Reference, 1.2V, LM385B-1.2 382209-0001
7.7 Switches
S1 Switch, DIP 513655-0002 S2 Switch, Rotary 515416-0001
7.8 Transformer
T1 Power Transformer 514797-0004 7.9 Display 515413-0001 7.10 Cable Assembly BM 515433-0001 7.11 Filter Box Assembly BM 515412-0001 Includes: Relays, Terminal Block and EMI Filters, Epoxy Encapsulated 990620
Model 332-AP
Alternating Duplex Pump Controller The specifications for the Model 332 Alarm/Controller and the Model 332-AP Duplex pump controller are exactly the same except for the action of the relays. The Model 332-AP is specifically designed for pump control applications. The 332-AP has two channels, one for each pump. Each channel provides independently adjustable trip (pump-on) and reset (pump-off) set points. As with the standard 332, the alarm action (high or low) must be preset for each of the two channels. For pump-up applications, the alarm action for both channels is set to low. For pump-down applications the alarm action for both channels is set to high. Note that with the 332-AP the alarm action for both channels will always be the same. Note also that for pump-up applications the reset (pump-off) point must be set above the set (pump-on) point and for pump down applications the reset (pump-off) point must be set below the set (pump-on) point. When the input level crosses the first trip point one of the two output relays will energize and the normally open contact will close, turning the pump on. Output relays alternate each time the trip point is crossed. This allows the work load to be shared between the two pumps, with only one pump working at a time. Should the input level cross the second trip point, then the pump that is not operating will also turn on and both pumps will run simultaneously until the first reset point is reached. Unlike the standard 332 the relay coils are energized while in the tripped (pump-on) state, therefore if power is removed from the 332-AP the relay contacts will go into the pump-off position. Manual 990620A Addendum A