Section Three Low Voltage Cables
Section 3, Page 36
THREE CORE CU XLPE NEUTRAL SCREEN CABLES Circular construction Copper conductor XLPE insulation Copper neutral screen PVC sheath Current ratings (A) and voltage drops (mV/A.m)
Product Sheet No. 081-03 B Conductor
Size
(mm2) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) 16 91 2.55 97 2.55 118 2.55 87 2.55
25 122 1.61 131 1.61 153 1.61 114 1.61
35 151 1.17 162 1.17 184 1.17 139 1.17
50 185 0.868 198 0.868 218 0.868 166 0.868
70 234 0.609 252 0.609 269 0.609 207 0.609
95 289 0.450 311 0.450 323 0.450 249 0.450
Issue: January 2012
0.6/1 kV. Made to AS/NZS 4961
Note: Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under Copyright Licence 000926. Please see the Standard for full details. The values in this table are for typical New Zealand installation conditions of:- Ambient Air Temperature 30°C Soil Temperature 15°C Soil Thermal Resistivity 1.2 K.m/W Depth of Burial 0.5 m