Alfred Kuhse GmbH, 21423 Winsen/Luhe, An der Kleinbahn 39, Germany Telephone +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http://www.kuhse.de The KEA 211-NC3-1-8 automatic system replaces the NC3-1-8 automatic system distributed by SEG. All functions of the replaced automatic system are fulfilled. In addition, there are other useful functions. The contact loads of the output relays correspond with those of the replaced automatic system or can support higher loads. All functions and settings can be parametrised using the Kuhse PARAWIN software. All func- tions allocated to the genset are included for sprinkler operation (according to VDS 2100-22). The automatic system is delivered with a standard parametrisation for the replacement of an NC3-1-8. The installation and warning information must be observed. Additional functions are: 17 relays, 14 of them can be parametrised on many functions. Speed measurement via pick-up (no longer possible via speedometer generator) with thresholds for start- ing, ignition, nominal and overspeed, 10 alarms, parametrisable for operating current and standby current contacts, warning and stopping, switching off generator or not All LEDs of the alarms can be used as operating displays if they are not used for alarm generation. Alarms 9 and 10 can also be delayed by the contacting and are also active in the OFF position (e.g. as a leakage warning system). The alarms are labelled by easily replaceable paper strips. The voltages and frequencies are monitored for underscoring and exceeding. In the event of an error, alarm messages can be displayed in this context. In addition, the rotating field of the mains voltage can be monitored. Enhanced functions for the control of circuit-breakers and operation with transfer synchronisation. The operation of the automatic system is simple and uncomplicated, as it is carried out directly via the usual keys for all KUHSE automatic systems. Deviating functions are marked in blue. Subject to technical change without notice. 2A211NC3-1-8UK 08/28/2017 Replacement for: 02/11/2014 OPERATING MANUAL Replacement automatic system for NC3-1-8 controller KEA 211 NC3-1-8

Upload: others

Post on 10-May-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

Alfred Kuhse GmbH, 21423 Winsen/Luhe, An der Kleinbahn 39, Germany

Telephone +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http://www.kuhse.de

The KEA 211-NC3-1-8 automatic system replaces the NC3-1-8 automatic system distributed by SEG. All

functions of the replaced automatic system are fulfilled. In addition, there are other useful functions. The

contact loads of the output relays correspond with those of the replaced automatic system or can support

higher loads. All functions and settings can be parametrised using the Kuhse PARAWIN software. All func-

tions allocated to the genset are included for sprinkler operation (according to VDS 2100-22). The automatic

system is delivered with a standard parametrisation for the replacement of an NC3-1-8. The installation and

warning information must be observed.

Additional functions are:

17 relays, 14 of them can be parametrised on many functions.

Speed measurement via pick-up (no longer possible via speedometer generator) with thresholds for start-

ing, ignition, nominal and overspeed,

10 alarms, parametrisable for operating current and standby current contacts, warning and stopping,

switching off generator or not

All LEDs of the alarms can be used as operating displays if they are not used for alarm generation.

Alarms 9 and 10 can also be delayed by the contacting and are also active in the OFF position (e.g. as a

leakage warning system).

The alarms are labelled by easily replaceable paper strips.

The voltages and frequencies are monitored for underscoring and exceeding. In the event of an error,

alarm messages can be displayed in this context. In addition, the rotating field of the mains voltage can

be monitored.

Enhanced functions for the control of circuit-breakers and operation with transfer synchronisation.

The operation of the automatic system is simple and uncomplicated, as it is carried out directly via the usual

keys for all KUHSE automatic systems. Deviating functions are marked in blue.

Subject to technical change without notice.

2A211NC3-1-8UK

08/28/2017

Replacement for: 02/11/2014

OPERATING MANUAL Replacement automatic system

for NC3-1-8 controller

KEA 211 NC3-1-8

Page 2: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 2 / 21 - 08/28/17

INSTALLATION AND WARNING INFORMATION

All information in this manual must be observed.

The connection of the unit must be carried out carefully, as a wrong connection could lead to the

destruction of the unit. The connection regulations must be observed.

The PE(N) must be connected to the point marked with the earthing symbol.

The installation and commissioning must only be carried out by sufficiently qualified personnel.

Applicable regulations, especially those of the VDE must be observed.

The parametrisation of the unit must be carried out in such a way that endangerment of persons

and property is excluded.

If the battery has to be disconnected, the charging unit must be switched off.

The battery negative potential must be earthed at the input terminal on the switchboard. The

minimum cross-section is 10 mm2.

The supply voltage (12 or 24 V DC) is selected using a switch located on the circuit board under

the hood.

If the supply voltage of the automatic system was switched off, it must only be switched on again

after approx. 20 seconds.

All the coils must be provided with a freewheeling diode (for DC voltage) or with a quench circuit

matching the inductance of the coil. This also applies for all relays and inductances that are used

differently in the switchgear or are externally controlled.

CONTENT

Not implemented or modified functions ............................................................................................................ 4 Displays and keys .............................................................................................................................................. 4

Functions of the keys ..................................................................................................................................... 4 Selection of the operating mode ................................................................................................................. 4 START key .................................................................................................................................................. 4 LED TEST key ............................................................................................................................................ 4 ALARM OFF key ......................................................................................................................................... 4

General displays ............................................................................................................................................. 5 Monitoring on ............................................................................................................................................. 5 Automatic system locked ........................................................................................................................... 5 Start control ................................................................................................................................................ 5 False start / Motor malfunctions ................................................................................................................. 5 Mimic diagram / Voltage monitor .............................................................................................................. 6

Functions ........................................................................................................................................................... 6 Start release / Start inhibitor........................................................................................................................... 6

Start release ................................................................................................................................................ 6 Start release / Start inhibitor for sprinkler operation .................................................................................. 6

Remote selection of the operating mode ........................................................................................................ 6 Acknowledging external error and horn off ................................................................................................... 6 Transfer synchronisation ................................................................................................................................ 7

Operating modes ................................................................................................................................................ 7 Off operating mode ........................................................................................................................................ 7 Manual operating mode ................................................................................................................................. 7

Start and stop .............................................................................................................................................. 7 Heat treatment ............................................................................................................................................ 7 Switching mains/Generator ........................................................................................................................ 7

Auto operating mode ...................................................................................................................................... 8 Start with generator loading ....................................................................................................................... 8 Start without generator loading .................................................................................................................. 8 Mains circuit breaker tripping .................................................................................................................... 8

Test operating mode ....................................................................................................................................... 9

Page 3: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 3 / 21 - 08/28/17

Sprinkler operation ............................................................................................................................................. 9 Error messages / Programmable operation displays ........................................................................................... 9

Use as an operation display ............................................................................................................................ 9 Use as an error message .................................................................................................................................. 9

Function and operation .............................................................................................................................. 10 Alarms 9 and 10 ........................................................................................................................................ 10

Internal error messages ................................................................................................................................. 10 Error messages of the voltage monitor ...................................................................................................... 10 Overspeed.................................................................................................................................................. 10 False start .................................................................................................................................................. 11 Speed measurement failed......................................................................................................................... 11 Generator failed ......................................................................................................................................... 11 Motor does not switch off ......................................................................................................................... 11 Synchronisation fault ................................................................................................................................ 11

Monitoring of mains and generator switches ................................................................................................ 11 Summary of the error function for the control of a joint alarm or a signal relay. ..................................... 11 Mains circuit breaker tripping ................................................................................................................... 12 Switching off mains hindered ................................................................................................................... 12 Generator circuit breaker tripped .............................................................................................................. 12 Switching off generator hindered .............................................................................................................. 12

Emergency Stop / Emergency Off (external) ................................................................................................... 12 Start program .................................................................................................................................................... 12

Start process, diesel engine ....................................................................................................................... 12 Start process, gas engine ........................................................................................................................... 13

Technical data .................................................................................................................................................. 14 Design ....................................................................................................................................................... 14 Auxiliary voltage ....................................................................................................................................... 14 Analogue inputs ........................................................................................................................................ 14 Digital inputs and outputs ......................................................................................................................... 14 Serial interface .......................................................................................................................................... 14

Change history TA211NC3-1-8 UK ................................................................................................................ 14 Wiring list for the replacement of a NC3-1-8 with a KEA 211 NC3-1-8 ........................................................ 15 Parametrisation ................................................................................................................................................. 17

Remote start / Start by internal mains monitor ............................................................................................. 17 Alarms and operation displays ...................................................................................................................... 17

Alarms 9 and 10 ........................................................................................................................................ 18 Error messages of the voltage monitor ...................................................................................................... 18

Sprinkler operation ....................................................................................................................................... 18 Further relay functions .................................................................................................................................. 19

Flag for operation displays, relay and error message inputs ............................................................................ 19 Circuit diagram of the relay board with standard parametrisation NC3-1-8 .................................................... 20 Terminal and voltage selector position plan of the basic unit .......................................................................... 21

Page 4: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 4 / 21 - 08/28/17

NOT IMPLEMENTED OR MODIFIED FUNCTIONS The optional connection of a tachometer generator is omitted, instead the input for a pick-up with an evalua-

tion of the ignition, starting, nominal and overspeed is intended as standard.

The START INHIBITOR input is only effective prior to a start and releases it as soon as a signal is no longer

pending. If the signal ceases during the operation, a running genset is not switched off.

The remote control of all operating buttons is reduced to the operating mode selection and the functions

HORN OFF and ALARM OFF.

The EMERGENCY START is omitted.

DISPLAYS AND KEYS

Functions of the keys

Selection of the operating mode

The operating modes are selected by four keys. The selected operating mode is displayed by LEDs. The keys

can be locked via an input (e.g. via connection of an external key-operated control switch), so that the unau-

thorised or random change of a defined operating mode is prevented. The operating modes described below

can be selected using the keys.

START key

The motor can be started in the MANUAL operating mode by actuating this button. If the motor needs to be

preheated, press the MANUAL and START keys at the same time. Actuating this key is ineffective when the

machine is running or also in any other selected operating mode.

LED TEST key

The functioning of all LEDs of the automatic system can be tested by this key. To control other signal lights

of the switchgear during the lamp test, a relay can be parametrised to this function.

ALARM OFF key

Due to an actuation impulse of this key, the acoustic signal issued by this alarm is deleted, the message

continues to flash. After a second confirmation, it changes over to continuous lighting. After the cause of the

error has been eliminated, the LED display is deleted by actuating the button again.

Page 5: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 5 / 21 - 08/28/17

General displays

The two upper rows of the LEDs provide important information on the operating processes and error mes-

sages. The displays described below are intended as standard.

Monitoring on

Using this green LED (after the genset start-up), the release of the operating-dependent delayed alarms is

signalled. As soon as the motor has started up, this LED flashes until the monitoring is released. The moni-

toring is switched off if there is a total failure of all "running" criteria, the automatic system is locked.

The display goes out at the beginning of the shut-down process.

Automatic system locked

This LED indicates that the automatic system is locked for further start attempts and thus genset operation is

inhibited. The automatic system is unlocked by selecting the OFF operating mode (after eliminating the cause

of the error). To do so, any actuated external Emergency OFF buttons must also be unlocked. The display is

switched on in continuous light operation by a signal on the Quick Stop input (Emergency Stop), or together

with such alarms that lead to the shut-down of the genset.

Start control

The LED start control indicates a pending start. The function

is similar to the charging check of a car. Furthermore, it shows if the

start prerequisites have been fulfilled. It is switched on for an automatic start,

or for selection of the MANUAL operating mode (in expectation of a manual

start). Any auxiliary drives and the start prerequisites

are switched on, the display flashes in the normal mode.

As soon as the auxiliary drives or the starting conditions release the start via the

START INHIBITOR input, the display changes over to steady light,

as long as either the generator or a Pick-up indicates that the

genset has started up.

The display goes out as soon as the genset exceeds the ignition speed during start-up

(detected by the D+ signal of the generator

or by the revolution transmitter signal according to the parametrisation). It continues

as a steady light again if the pending signals fail during the operation.

The display flashes in quick succession if the time for the start release

has expired without the start being released.

False start / Motor malfunctions

This alarm is controlled by three criteria. That's why this message has expired needs to be interpreted. The

message is controlled

FALSE START. If the genset has not started at the end of the starting program,

the alarm is issued. It is displayed with a steady light (without flashing),

the automatic system is locked.

MONITORING FAILED. If all signals for the

speed measurement (generator voltage, generator or Pick-up) fail during operation,

this alarm is issued. It is displayed with two short flashing impulses,

the automatic system is locked.

MOTOR DOES NOT SWITCH OFF If the genset still runs after the stop time has expired,

this alarm is issued. It is displayed by normal flashing,

the automatic system is not locked.

BELT RIP. This alarm can be released or deactivated. If

the generator does not supply voltage with an available generator voltage,

this alarm is issued. The display flashes in quick succession. It can be parametrised

if stopping is carried out immediately or if the

automatic system is to be locked only after a normal stop.

Page 6: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 6 / 21 - 08/28/17

Mimic diagram / Voltage monitor

The mimic diagram displays the mains infeed, the generator, the mains and generator circuit breakers and the

busbar. Green LEDs below the mains or generator symbol indicate if the respective voltage is within the

limits. These LEDs flash as soon as the voltages are within their limits, but the release time has not yet

expired.

The positions and any messages of the mains and generator switch are displayed by green LEDs below the

OFF keys (O). They indicate the following conditions:

In the event of a BREAKER TRIPPING SIGNAL (if parametrised), the respective LED

flashes like a normal alarm (slow flashing with equally long light and dark phases).

The LED briefly flashes once during the synchronisation of the switch.

If the SYNCHRONISATION DISRUPTED alarm (if parametrised) is pending,

the LED briefly flashes twice. However, it is overridden by the MAINS IS ON

or GENERATOR IS ON signal.

If the SWITCHING OFF IS HINDERED, it flashes with short pulses.

If the mains or the generator is switched on, the LEDs show

the position of the switch with a continuous light. Thus, it overrides the above

messages, as the switch was finally able to switch on.

FUNCTIONS

Start release / Start inhibitor

The auxiliary drives (e.g. space fan, shutters) and the start preconditions, which are only required for the start

phase (e.g. prelubrification pump), are immediately switched on in the MANUAL and TEST operating modes,

and switched on in AUTO with a start command. The switch-on duration of the start preconditions (para-

metrisable) is time-limited. They are switched off after start-up of the genset, the auxiliary drives remain

switched on during the operation and a parametrisable idle time. The functions can be parametrised to output

relays. If all required criteria are fulfilled, the START INHIBITOR signal is taken away and thus the START

RELEASE is given.

Attention: The function, which shuts down a running genset by taking away the signal during operation, is

not implemented.

Start release

After switching on the start preconditions and auxiliary drives, the START CONTROL display flashes as long

as no start release is required. The start is inhibited as long as the L- signal is available on the START

INHIBITOR input.

Start release / Start inhibitor for sprinkler operation

For the start requirement for sprinkler operation, the start is released immediately or, if important precondi-

tions are necessary, after a (short) parametrised time, independent of the signal to the START INHIBITOR

connection. The external input signal is ignored.

Remote selection of the operating mode

The operating modes OFF, MANUAL, AUTO and TEST can be selected via three contacts if the operation

selection on site (connection C22 or terminal 29) is locked by L-. The MANUAL remote selection is selected

by simultaneous signal transmission to F9 and F5 (terminals X2/4 and X2/6). In order to select a new operat-

ing mode, all inputs must first be released and the new function must then be specified.

Acknowledging external error and horn off

These two orders are summarised into a REMOTE ACKNOWLEDGEMENT. A steady signal only gives an order

so that L- must be applied several times for switching off the horn and deleting the alarms.

The first impulse (L-) to connection F8 (terminal 32) switches the horn off. A new alarm would switch it on

again.

A second impulse deletes the alarms if they are released by the parametrisation for this (e.g. smoke detectors,

etc. should not be remotely acknowledgeable). The MAINS and GENERATOR CIRCUIT BREAKER TRIPPED, and

MAINS and GENERATOR OFF HINDERED and BELT RIP are also deleted.

Page 7: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 7 / 21 - 08/28/17

If the alarm contact is still pending, remote acknowledgement of this alarm is not possible. If the automatic

system is inhibited by the QUICK STOP input, it cannot be unlocked by the remote acknowledgement as long

as the signal is pending, but only on site by release of the input signal.

Transfer synchronisation

The transfer synchronisation (if the additional units necessary for frequency adjustment, possibly voltage

adjustment and switch-on command for synchronism are available) is carried out, deviating from the original

wiring of the NC3. Thus, the procedure is clearer and the controller safer. A signal is issued to switch on the

synchronisation system. Furthermore, contactor and circuit breaker must be switched on via the switch-on

pulses issued by the automatic system.

The synchronisation duration (parametrisable) is monitored. If no synchronisation has been carried out, it is

possible to select whether a switch should be carried out with an interruption or whether the synchronisation

attempt should be continued. The D1 connection (terminal 33) can be used to select whether a switch should

be carried out with or without an interruption.

The transfer synchronisation is only released if the mains and generator voltage monitors do not show any

false voltages.

Attention: This function assumes a wiring change of the mains and generator circuit contactor or switch. The

procedure is thus clearer and the controller safer.

OPERATING MODES Off operating mode

The OFF position is automatically selected (reset function) during the application of battery voltage in order

to prevent the triggering of an unintentional start-up. When switching to OFF FROM ANOTHER OPERATING

MODE:

– A genset operation is immediately ended

– Previously displayed error messages, except the fault messages 9 and 10, are deleted as long as their

alarm contact is still active

– The automatic system is unlocked. However, if the QUICK STOP INPUT (EMERGENCY STOP) is still active,

unlocking is not possible; the AUTOMATIC SYSTEM LOCKED message remains.

Manual operating mode

Start and stop

The auxiliary drives and start preconditions are immediately switched on. After the start release, the genset

can be started up via the START button. In order to switch off the genset, the OFF or (in the event of missing

start with load) AUTOMATIC operating mode must be selected.

Using the MAINS OFF (O) key, the mains can also be switched off when the genset is at a standstill, the

MAINS ON (I) key is used to switch it on again for error-free mains voltage. The motor can be started using

the START key.

Attention: A button for manual stopping is not intended.

Heat treatment

By pressing the MANUAL and START buttons at the same time, the starter is not actuated, but the heat treat-

ment is switched on. If the MANUAL button is then released or only the START button is pressed, the starter is

switched on. For the AUTO and Test operating modes, the start delay is used for the heat treatment.

Switching mains/Generator

If the generator voltage with its voltage and frequency values is within the value limits, the generator can be

switched on. The switching between mains and generator operation and vice versa is always carried out with

the parametrised switching breaks if the GEN-ON or MAINS ON key is used.

It is also possible to first switch off the mains or the generator with the respective OFF key and then switch

on the generator or the mains with the respective ON key. Thus, it is possible to disconnect the busbar from

the power supply. The actuation of the ON keys remains ineffective if the voltage of the selected system

(mains or generator) does not lie within the specified limits.

Page 8: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 8 / 21 - 08/28/17

All switching processes are only carried out manually and not automatically. Even a remote start command

does not lead to automatic switch-on of the generator. Also, the mains is not automatically switched on if an

error message occurs during generator operation (e.g. GENERATOR OVERCURRENT), which switches off the

generator.

Auto operating mode

Start with generator loading

The automatic start can be carried out by four parametrisable functional types. Thus, all possibilities of the

NC3-1-8 are enabled in a simple manner.

(1) Start only via the internal mains voltage monitor.

(2) Start only by the external start command with load.

(3) Start only if the internal mains voltage monitor and simultaneously the external start command with

load command issued.

(4) Start only if the internal mains voltage monitor or the external start command with load issues the

command.

Attention: For start triggering (3), the start is carried out when the internal voltage monitor indicates a power

failure and the remote start is also issued. If only the remote start is removed, but the power has failed, the

genset is switched off, however it is not switched back to the failed mains. The switching-on of the mains is

carried out at the end of the power failure.

In the event of a missing start command (see start triggering (1) to (4)), genset is in standby mode. If the

entered limit values (according to the parametrisation) are no longer observed for the voltage or frequency of

the internal voltage monitor, the power delay is recognised with a delay. The green LED below the mains

symbol after expiry of this parametrised delay time. The external voltage monitor input has no influence on

the green voltage display.

The genset is started according to the required start function. The FALSE START/MOTOR ERROR message is

issued and the automatic system is inhibited if the genset has not started at the end of the start program.

After the start-up of the genset, the mains is switched off and the generator is switched on as soon as the

nominal generator voltage and frequency are reached after a switching break (parametrisable). If the mains is

defective, with respective parametrisation the switching-off can already be carried out prior to the start in

order to protect the consumer.

After normalisation of the mains voltage and release of the external input (according to the required function

type), a delay time (switch-back delay) elapses before the generator is switched off and switched on again

after a switching break.

In order to prevent heat congestion, if it was loaded the genset continues to run unloaded for the adjusted idle

run time and then is shut down.

For the operating modes (2) and (4), the generator operation is switched over without interruption for intact

mains voltage and released transfer synchronisation.

Attention: If an alarm occurs that switches off the generator while the idle time is not acknowledged, the

automatic system is locked as an automatic emergency power operation is no longer possible.

Start without generator loading

If no start with load is pending, the genset can be started by

the sprinkler requirements or

the start without generator loading input.

A switchover to generator operation is only carried out with a simultaneous start command with load or

power failure. If these start commands are issued alone, the genset runs unloaded. A mains parallel operation

such as for the NC3-1-8 is not possible, as a power, a cos-phi controller and a power cut protection are

necessary for this. Here, the Kuhse KEA 201 SPL automatic system should be used, which fulfils all func-

tions (power failure protection, synchronising unit, synchronising locking unit, power and cos phi controller)

according to the VDE regulation AR-N 4105.

Mains circuit breaker tripping

The automatic system can be parametrised in such a way that the start and the switching to generator opera-

tion can also be carried out if the mains switch fails due to an error. In this case, the genset runs automatical-

ly and takes over the substitute power supply. The green MAINS IS ON LED flashes for the display of this

error.

Page 9: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 9 / 21 - 08/28/17

For switching back to the mains, the MAINS CIRCUIT BREAKER TRIPPING message must be deleted (ALARM

OFF button). For problem-free mains voltage, the automatic system switches back to mains operation after

expiry of the switching-back time.

Test operating mode

After button selection to the TEST position, the start program is triggered. If the generator voltage with its

voltage and frequency values lies within the parametrised value limits, the mains can be switched off and the

generator can be switched on with the GEN-ON (I) or MAINS OFF (O), or the generator can be switched off

and the mains can be switched on with MAINS ON (I) or GEN-OFF (O). If the transfer synchronisation func-

tion (L- to connection C20, or terminal 33) is selected, switching over to this operating mode is carried out

without interruption.

If a start command with load or MAINS CIRCUIT BREAKER TRIPPING (if parametrised) during test operation,

operation is switched over to generator operation. Then, it is not possible to manually switch off the genera-

tor circuit breaker. Manual operation of the switch is only possible after removal of the start command (pos-

sibly also deletion of the MAINS CIRCUIT BREAKER TRIPPING alarm) and expiration of the switching-back

time.

In order to switch off the genset, the OFF or AUTO operating mode must be selected (in the event of missing

start with load command).

SPRINKLER OPERATION A L- signal on the C19 input (terminal 31) triggers a start without load, in order to supply an electrical sprin-

kler pump. The following functions are intended for the operation of an electrical sprinkler pump:

Switching of all switching-off alarms (overspeed alarm remains switched off for electronic speed sensor,

demand VDS 2100-22) to warning

Optionally, the inhibition of the generator switching-off function for GENERATOR OVERCURRENT, for

example

Start program to 6 (parametrisable) start attempts

For ending the sprinkler requirement: Cancellation of sprinkler operation after the SPRINKLER IDLE TIME

or only manual shutdown (demand VDS 2100-22)

For the duration of the acceleration time of the sprinkler pump: Switching off the emergency power

consumers or no interruption of the emergency power supply.

The supply of the sprinkler pumps is usually taken care of directly by the generator and thus prior to the

switch to the emergency power consumers. In the event of the emergency power failure, the consumers can

be switched off for a parametrisable period of time in order for enough energy to be available for the acceler-

ation time of the sprinkler pump. Furthermore, it is possible to parametrise that the consumer switches re-

main switched on or switch off in the event of an overload on the side of the consumers.

Sprinkler operation is automatically cancelled after the sprinkler requirement is removed after an entered idle

time or can only be ended manually (demand VDS 2100-22). If the automatic system is parametrised for

manual shutdown, the LED of the OFF operating mode flashes as soon as the sprinkler input is free. Stopping

can then be carried out via the OFF operating mode (or always via Emergency Stop).

If stopping should commence after the idle time and the Off operating mode is selected, the generator

switches off and is switched back to mains operation if the mains voltage is intact. However, the genset

remains switched on until the sprinkler input is free again. In this case, if stopping should commence inde-

pendently of the sprinkler input, the Emergency Stop must be actuated.

ERROR MESSAGES / PROGRAMMABLE OPERATION DISPLAYS Any of the 10 LEDs can either display an error message or be parametrised as an operation display.

Use as an operation display

These displays are independent of the selected operating mode. Thus, they can be used as displays of opera-

tional conditions via contact inputs or as internal flags of operation conditions as normal signal lamps. The

PARAWIN software is required for parametrisation. The flag list contained in it can be found further down.

Use as an error message

The automatic system includes the possibility of processing 10 alarms. The alarms are designated with

labelled text strips. The control is carried out by contact inputs or internal flags (overspeed, battery un-

dervoltage, mains or generator voltage error, etc.). The PARAWIN software is required for parametrisation.

Page 10: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 10 / 21 - 08/28/17

The flag list referenced in it is specified further down. For contact inputs, the respective alarm is triggered

with the closing (operating current circuit) or with the opening (standby current circuit) of the signal contact

against L-.

The alarms are basically divided into three groups:

Alarms that are only monitored delayed after start-up of the motor (e.g. LOW OIL PRESSURE). The release

can be recognised on the green MONITORING ON display.

Alarms that are also monitored when the motor stops (e.g. BATTERY UNDERVOLTAGE), except in the OFF

operating mode. They are designated as without delay.

The alarm messages 9 and 10 are always monitored, even in the OFF operating mode. They are used for

messages (e.g. LEAKS). The horn is not switched on in the OFF operating mode, but the alarms are not in-

cluded in the collective alarm. They behave like normal alarms if an active operating mode (so not OFF)

is selected.

The alarms are configured as follows:

Alarm is active or locked

Contact is in standby current or operating current

Delayed or undelayed monitoring

Warning or switching-off function

In addition for warning alarms: With or without generator switch-off and stop after idle time in automatic

operation.

Function and operation

The accruing of an error message is displayed by the LED flashing. At the same time, the acoustic signal (for

the entered duration) is controlled. With a pulse of the ALARM OFF key (or automatically after the entered

time), the acoustic signal is switched off. However, the LED continues to flash. If the value 0 sec. is entered

for the duration of the horn switch-on, no automatic switch-off is carried out: The horn remains switched on

until manually deleted.

Due to a second button actuation of ALARM OFF, the message switches from flashing light to continuous

light. Due to the necessary second acknowledgement, e.g. the switching off of the acoustic signal generator

after an automatic switch-off, it can be distinguished which error message has newly occurred.

The display is deleted after the error is eliminated after renewed actuation of the ALARM OFF key.

For messages that lead to the switching-off of the genset, the further operation is inhibited, displayed by

AUTOMATIC SYSTEM LOCKED. In order to unlock, the OFF operating mode (any actuated external Emergency

OFF buttons must also be unlocked) must be selected.

Attention: If the generator is switched off due to a warning alarm in automatic operation, the motor is

stopped after the idle time and the automatic system is locked.

Alarms 9 and 10

Both these alarms can be delayed from 0 to 240 sec. by the signal transmission, i.e. for the alarm contact to

issue an error, the signal must be pending for a parametrised time. Furthermore, both these alarms are also

effective in the Off operating mode (Off), but without switching on the horn. Thus, criteria (e.g. tank over-

filling, leakage warning) that always have to be reported can be monitored.

Internal error messages

The following alarms are created by the software. They can be locked or activated by the parametrisation

(the exception is the false start message, which is always active).

Error messages of the voltage monitor

The criteria of the voltage monitor, recognised as faulty, released for monitoring (<U, >U, <f, >f), can be

displayed. They can, individually or collectively, control an error message or only be displayed.

Overspeed

For the overspeed monitoring, either the generator frequency or the frequency of a pick-up is used (according

to the parametrisation). The speed threshold can be parametrised.

Page 11: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 11 / 21 - 08/28/17

False start

This alarm is always active and cannot be locked. If the genset has not started after the parametrised start

amount (normal or sprinkler operation), the alarm is issued. The FALSE START / MOTOR ERROR LED is per-

manently switched on (without flashing), the automatic system is locked for further start attempts. The

automatic system is unlocked via the OFF operating mode, so that a new start sequence can begin.

Speed measurement failed

If all criteria for the speed recognition, and thus for the error monitoring fail (according to parametrisation;

available generator voltage, generator terminal D+, Pick-up), the FALSE START/MOTOR ERROR alarm is

triggered, the genset is switched off and the automatic system is locked. For the display, the LED flashes in a

quick rhythm.

However, if this alarm occurs during the sprinkler operation, the genset remains in operation, the monitoring

of the motor remains switched on

Generator failed

This alarm can be locked or released. If the generator is driven together with the cooling fan, a belt rip can be

recognised. With available generator voltage, the generator must also have a positive signal on the terminal

D+. If it ceases or is not pending with an available generator voltage, the GENERATOR FAILED alarm is trig-

gered after approx. 10 seconds.

This error is displayed by a flashing impulse of the FALSE START / MOTOR ERROR LED.

Motor does not switch off

If the motor still runs after the stop process has expired (switching off of the stop solenoid) or without re-

newed starting order, the stop process is repeated and the FALSE START/MOTOR ERROR message is displayed.

The automatic system is not locked, so that the genset can immediately switch to generator operation for a

start requirement (power failure or sprinkler requirement).

This error is displayed by a flashing impulse of the FALSE START / MOTOR ERROR LED.

Synchronisation fault

The duration of the synchronisation can be monitored. If no switching is carried out during the parametrised

time, the switching is carried out optionally with an interruption or continued further without interruption.

The parametrisable SYNCHRONISATION HINDERED alarm does not switch on the collective alarm or the horn.

If this is required, the function can be placed on one of the alarms from 1 to 8.

The MAINS IS ON or GENERATOR IS ON LED of the selected mode briefly flashes once during the synchroni-

sation of the switch.

If the SYNCHRONISATION HINDERED alarm (if parametrised) is pending, this LED briefly flashes twice.

However, it is overridden by the MAINS IS ON or GENERATOR IS ON signal.

Monitoring of mains and generator switches

These messages are displayed via the different flashing pulses of the respective ON LEDs. The following

four functions can be summarised, so that only one alarm or signal relay SWITCHING ERROR is seized if

required. The reason for triggering the alarm is displayed by the respective LED in the mimic diagram. It is

important to note that the error function of the ALARM Off is deleted with the first press of a button, but must

be acknowledged several times for deleting the alarm (see above).

Summary of the error function for the control of a joint alarm or a signal relay.

Key figures of the alarms

Mains circuit breaker

tripping

Mains Off hindered Generator circuit

breaker tripped

Generator Off hindered

1 2 4 8

The key figures are added and converted into a hexadecimal number.

Decimal number/hexadecimal number table

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F

Page 12: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 12 / 21 - 08/28/17

The flag for the required summary is the summary of the digits 42, followed by the determined hexadecimal

number (always with the leading zero).

Example: The GENERATOR CIRCUIT BREAKER TRIPPED and GENERATOR OFF HINDERED functions should

trigger an alarm. The sum of the key figures is (4+8) =12. The table shows that the hexadecimal number 0C

results for the decimal number 12. Thus, 420C is parametrised as a flag.

Mains circuit breaker tripping

The alarm is internally controlled if no MAINS IS ON feedback is carried out after the mains switch-on pulse

has expired. After a mains circuit breaker tripped, the MAINS IS ON LED flashes like a normal alarm with

equally long light and dark phases, the acoustic signal is issued and the collective alarm message is switched

on. Due to the ALARM OFF, the first actuation switches off the acoustic signal and the message is acknowl-

edged with a second press of ALARM OFF.

According to the parametrisation, the genset starts if a mains circuit breaker trips in the AUTOMATIC position

and takes over the supply. In this case, the alarm must be deleted for switching back to mains operation.

After deleting has been carried out, mains operation is switched back to after the switching-back delay if the

mains voltage is intact.

Switching off mains hindered

The alarm is given if no MAINS IS OFF feedback is registered approx. 2 seconds after the switch-off com-

mand for the generator circuit breaker. In the event of emergency power failure, the genset is switched off

after the idle time, as the generator operation cannot be switched over. The MAINS IS ON LED flashes with

quick pulses. After the error has been rectified, the message must be deleted via ALARM OFF or by the selec-

tion of OFF operating mode.

Generator circuit breaker tripped

The alarm is internally controlled if no generator feedback is carried out after the GENERATOR IS ON switch-

on pulse has expired. After a generator circuit breaker tripped, the GENERATOR IS ON LED flashes like a

normal alarm with equally long light and dark phases, the acoustic signal is issued and the collective alarm

message is switched on. If the message is not acknowledged, the genset switches off after the idle time in

automatic operation.

Switching off generator hindered

The alarm is given if no GENERATOR IS OFF feedback is registered approx. 2 seconds after the switch-off

command for the generator circuit breaker. The genset includes a renewed start command and goes to gener-

ator operation. If a switch-off alarm occurs, the genset is now stopped. After the error has been rectified, the

message must be deleted via ALARM OFF or by the selection of OFF operating mode.

EMERGENCY STOP / EMERGENCY OFF (EXTERNAL) In order to trigger the Emergency Stop function, a pulse on the QUICK STOP INPUT (EMERGENCY STOP) is

sufficient. The input can be optionally switched (parametrisable) to operation or standby current. Thus,

independent of the operating mode:

the generator is switched off,

the genset is shut down,

the auxiliary drive is switched off,

the automatic system is locked for further start processes (display: AUTOMATIC SYSTEM LOCKED).

In order to unlock, the OFF operating mode must be switched. If the QUICK STOP signal is still pending, it

cannot be unlocked. The AUTOMATIC SYSTEM LOCKED display remains switched on.

START PROGRAM

Start process, diesel engine

Start delay 2 sec. (preheating time)

Starter on for 10 sec.

Pause 7 sec.

3 start attempts

6 start attempts for sprinkler operation

Delay MONITORING ON 7 sec.

Switch-back delay 60 sec.

Idle time 180 sec.

Sprinkler operation idle time 0 sec.

Stop time 30 sec.

Page 13: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 13 / 21 - 08/28/17

The parametrised standard values for a diesel engine are specified here. If the diesel engine is equipped with

preheating equipment, the start delay during an automatic start serves as the preheating time.

Start process, gas engine

Starter on:

purging; if the starter speed is exceeded, the switching-on of the ignition is delayed (e.g. after 2 sec.),

then (another 2 sec.) open gas solenoid valve,

starter now on for another 7 seconds,

then close gas solenoid valve,

starter off,

ignition off after 6 sec.,

new start sequence after 1 sec.

The parametrised standard values for a gas engine are specified here.

Page 14: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 14 / 21 - 08/28/17

TECHNICAL DATA

Design

Unit for front installation.

Dimension (,, depth) 260 x 170 x 80 mm.

Weight approx. 2.2 kg.

Arbitrary installation position.

Protection class (installed) IP 44.

Ambient temperature,

Storage -20 °C ... +70 °C.

Operation -10 °C ... +50°C.

Standards/Regulations DIN VDE 0160.

Auxiliary voltage

Switchable 9-12-15 V or 14-24-35 V DC.

Analogue inputs

3-phase (to N phases) mains voltage monitor

for nominal voltage 231/400 Volt, adjustable

in 1 Volt steps.

The UNDERVOLTAGE display is carried out for

hindered rotating field.

Adjustable switching points: 50 - 300 Volt.

Mains frequency 45 to 65 Hz, adjustable in 0.01

Hz steps of 40 to 70 Hz.

2-phase generator voltage monitor for nominal

voltage 400 V, adjustable in 1 Volt steps. Ad-

justable 250 - 480 Volt.

Generator frequency 45 to 65 Hz, adjustable in

0.01 Hz steps of 40 to 70 Hz.

Battery voltage monitor.

Digital inputs and outputs

Input for generator D+ with pre-excitation for

AC generators.

10 connections for alarm contacts.

18 general control inputs.

17 output relays, of which 14 are

parametrisable, starting and stop relay contact

load max. 16 Amp.

3 relays 35 DC, max. 1 Amp.

10 relays max. 10 Amp.

Input for pick-up for the speed measurement.

Serial interface

USB interface for parametrisation, for coupling via

an additional mode to a control system or to a

remote monitoring.

CHANGE HISTORY TA211NC3-1-8 UK

Created Changed Version

24/01/14 First edition 24/01/14

08/28/2017 Name change from NC3-1 to NC3-1-8

Page 15: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 15 / 21 - 08/28/17

Page 15 of 21

WIRING LIST FOR THE REPLACEMENT OF A NC3-1-8 WITH A KEA 211 NC3-1-8

Terminal Function

Position

PARAWIN Note, standard parametrisation

NC3 KEA

A1 43 Mains voltage L1

A2 44 Mains voltage L2

A3 45 Mains voltage L3

46 Mains voltage N Must also be connected

A5 41 Generator voltage L1

A6 42 Generator voltage L2

B1 57 Control voltage mains L1

Control mains contactor K1 Fixed function

B2 58

B3 59 Control voltage gen. L1

Control gen. contactor K2 Fixed function

B4 60

B5 26 Feedback mains switch Parametrisable as closer or opener

B6 27 Feedback gen. contactor Parametrisable as closer or opener

B7 5 Mains voltage good

Contact voltage for K8 K8

Mains voltage good

Contact voltage must also be connected. L- 6

B8 28 Remote start command with

connection

B9 72 Closer

Trestle pole

Opener

K9 Motor is running B10 73

74

B11 78 Closer

Trestle pole

Opener

K10 Attention: Closer with freewheeling diode

Start prerequisites L+ 79

80

B12 X2/8 Start inhibitor Parametrisable as a start release

B13 1 Supply L+ Supply of basic unit. Further connections designated with L+,

L1+ and L2+ require the contact voltage to be switched.

B14 2

54 Supply L-

Supply of basic unit

Connection 54: L- for freewheeling diodes

D6 75 Closer

Opener

Trestle pole

K12 Parametrisable D4 77

D5 76

B17 34 Generator terminal D+

B18 30 Emergency Stop Optionally NO or NC contact.

16 Alarm 1

B19 17 Alarm 2

18 Alarm 3

B20 19 Alarm 4

B21 20 Alarm 5

21 Alarm 6

B22 22 Alarm 7 Free alarm/Display

B23 23 Alarm 8 Free alarm/Display

24 Alarm 9 Free alarm/Display

25 Alarm 10 Free alarm/Display

C1 51 Trestle pole internally

present on L1+

Opener K3

Closer K3

K3

Shut-down operating current

Shut-down standby current, output with freewheeling diode

C7 53

C2 52

C3 55 Contact voltage L+ for relays K4, K5, K6

C4 56 Closer K5 Starter with freewheeling diode, fixed function:

C8 71 Closer K4 Horn, internal contact voltage L2+, freewheeling diode

C6 64 Closer K6 Operating solenoid, internal contact voltage L2+, freewheel-

ing diode

C12 61 Closer

Trestle pole

Opener

K7

Preheating, closer with freewheeling diode

Connect L+ here, as freewheeling diode intended

C11 62

63

Page 16: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 16 / 21 - 08/28/17

Page 16 of 21

Terminal

Function Position

PARAWIN Note, standard parametrisation

NC3 KEA

C9 68 Closer

Trestle pole

Opener

K11 Parametrisable C10 69

70

B15 65 Closer

Trestle pole

Opener

K13 Ready for operation B16 66

67

D7 7 Closer K14 Genset is running

D8 8

X2/1 Pick-up screen It is necessary to foresee that the connection is only on

terminal X2/1

E1 X2/2 Pick-up, return

E2 X2/3 Pick-up, pulse

D3 31 Sprinkler operation

D1 33 Transmission synchronisa-

tion On

D2 X2/7 Remote start without load

29

Selection of operating

mode on site locked,

remote selection possible

For L- at this connection:

Selection of operating mode on site locked, remote selection

possible

F8 External horn off

Acknowledge external error

1st press of the button, horn off; 2nd press of the button,

message Off F12 32

F9 X2/4 External selection Off F9, X2/4 - external selection Off

F10, X2/5 - external selection Auto

F5, X2/6 - external selection Test

External selection Manual via F5 and F9 simultaneously

F10 X2/5 External selection Auto

F5 X2/6 External selection Test

F11 External selection Manual

Three additionally parametrisable signal relays, 35 DC, 1 Amp. They switch the joint signal of terminal 15

(optionally L+ or L-).

K15 relay: Terminal 12,

K16 relay: Terminal 13

K17 relay: Terminal 14.

The K15 and K16 relays can be used for the switch-on pulse of a mains and a generator circuit breaker. Here,

an auxiliary relay (with freewheeling diodes via the coils) should be used.

Information:

If freewheeling diodes are intended in the automatic system, the polarity of the contact voltages must not

be mixed up.

Deviations of the connection or of functions are marked here in blue.

Standard parametrisations of the relay are specified here in green.

All relays of the switchgear and of (also externally) controlled inductances must be equipped with free-

wheeling diodes or respective wiring in order to prevent switch-off peaks. Exceptions from this are the

relay outputs which are already equipped with freewheeling diodes internally. Please check these

measures.

Page 17: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 17 / 21 - 08/28/17

Page 17 of 21

PARAMETRISATION

Remote start / Start by internal mains monitor

The automatic start can be carried out by four parametrisable functional types. Thus, all possibilities of the

NC3-1-8 are enabled in a simple manner.

(1) Start only via the internal mains voltage monitor.

(2) Start only by the external start command with load.

(3) Start only if the internal mains voltage monitor and simultaneously the external start command with

load command issued.

(4) Start only if the internal mains voltage monitor or the external start command with load issues the

command.

Attention: For start triggering (3), the start is carried out when the internal voltage monitor indicates a power

failure and the remote start is also issued. If only the remote start is removed, but the power has failed, the

genset is switched off, however it is not switched back to the failed mains. The switching-on of the mains is

carried out at the end of the power failure.

Alarms and operation displays

The following parameters (excerpt from PARAWIN) are intended per display:

(1) No - LED 1: Display only, no error message (2) 3C08 - control via flag entry (3) AUWI - coding of the functions (4) No - error message without saving

Parameter (1) is set to <No>.

Parameter (2) determines the input signal. The following table shows the flag of the input terminals:

Connection to X1 Flag Connection to X1 Flag

Terminal 16 0201 Terminal 21 0240

Terminal 17 0202 Terminal 22 0280

Terminal 18 0204 Terminal 23 0302

Terminal 19 0210 Terminal 24 0304

Terminal 20 0220 Terminal 25 0308

The list with further possible input signals of internally derived flags is inserted as Annex A. The 3C08

entry in this example controls the alarm in the event of overspeed.

Parameter (3) determines the function (coding) of the error message. The following abbreviations are used:

A – operating current R – standby current

U – undelayed V – delayed

W – warning S – switch-off

I – generator remains on 0 – generator is switched off

For OPERATING CURRENT, the alarm is triggered if a contact is closed. For STANDBY CURRENT, the alarm is

respectively triggered if a contact is opened.

A DELAYED alarm is only activated after start-up of the motor and the parametrised delay MONITORING ON,

an UNDELAYED ALARM is also active during standstill of the motor. In the OFF operating mode, all alarms

except 13 and 14 are not monitored.

A STOPPING alarm stops the motor, switches off the generator and locks the automatic system, a WARNING

ALARM only shows the emergence of the alarm.

Furthermore, it can be parametrised for warning alarms if the generator remains SWITCHED ON (I) or

SWITCHED OFF (0) in the event of an error. If a warning alarm occurs in automatic operation, which shuts

down the generator, the genset is switched off after the idle time shut-down and the automatic system is

locked.

Page 18: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 18 / 21 - 08/28/17

Page 18 of 21

Parameter (4) determines whether the message should remain saved if the input signal has ceased or if it is

automatically deleted. The parametrisation of this function must be weighed up carefully. It only makes

sense for warning error messages that do not switch off the generator.

Example: This can be useful for the Battery undervoltage error message after several start attempts, for

example. The operator of the system is informed (as always) by the acoustic signal and the collective alarm

in the event that this message occurs.

The battery charging takes place and can be used again after a corresponding amount of time. As long as the

BATTERY UNDERVOLTAGE message (then actually no longer available) is pending, the collective alarm

would also be active and possibly inhibits the accruing of a more important error.

Alarms 9 and 10

Both these alarms can be delayed from 0 to 240 sec. by the signal transmission, i.e. the alarm contact issues

an error, the signal must be pending for a parametrised time. Furthermore, both these alarms are also effec-

tive in the Off operating mode (Off), but without switching on the horn. Thus, criteria (e.g. tank overfilling,

leakage warning) that always have to be reported can be monitored.

Error messages of the voltage monitor

The criteria of the voltage monitor, recognised as faulty, released for monitoring (<U, >U, <f, >f), can be

displayed. They can, individually or collectively, control an error message or only be displayed. For this, the

required error message (or only display, according to the parametrisation of this message) of the input flag

can be found in the following table. It is important to note that a message must be entered as WARNING and

DOES NOT SWITCH-OFF GENERATOR for mains errors, as otherwise no emergency power supply mode is

possible. The messages must also always be parametrised in OPERATING CURRENT.

Function Flag Function Flag Function Flag Function Flag

Mains <U 3A01 Gen. <U 3A10 Mains <U or >U 3A03 Gen. <U or >U 3A30

Mains >U 3A02 Gen. >U 3A20 Mains <f or >f 3A0C Gen. <f or >f 3AC0

Mains <f 3A04 Gen. <f 3A40 Mains <U or <f 3A05 Gen. <U or <f 3A50

Mains >f 3A08 Gen. >f 3A80 Mains >U or >f 3A0A Gen. >U or >f 3AA0

Further combinations are possible. For this, please contact our service department. 0

Sprinkler operation

The following functions are intended for the operation of an electrical sprinkler pump:

Switching of all switching-off alarms (overspeed alarm remains switched off for electronic speed sensor,

demand VDS 2100-22) to warning

Optionally, the inhibition of the generator switching-off function for GENERATOR OVERCURRENT, for

example

Start program to 6 (parametrisable) start attempts

For ending the sprinkler requirement: Cessation of the sprinkler operation after the SPRINKLER IDLE TIME,

or only manual switching off

For the duration of the acceleration time of the sprinkler pump: Switching off the emergency power con-

sumers or no interruption of the emergency power supply.

The time stage for the sprinkler operation idle time can be set in the range of 20 to 2500 seconds. If it is

parametrised to 0 sec., the genset does not automatically switch off (demand VDS 2100-22). In this case, the

LED of the OFF operating mode flashes. The genset can then only be stopped via the OFF operating mode (or

always via QUICK STOP).

The interruption of the emergency current operation for the switching on of the sprinkler pump can be para-

metrised in the range of 0 to 25 sec. For the 0 sec. setting, there is no switching-off of the consumers. The

switching-off of the consumers begins with the SPRINKLER OPERATION signal.

If the sprinkler requirement is met, the emergency power consumers are also switched on during a power

failure or remote start. For return of the power or after removal of the remote start command, the emergency

power consumers are switched back to the mains after the switch-back delay.

Page 19: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 19 / 21 - 08/28/17

Page 19 of 21

Further relay functions

In order to control further functions of the switchgear (lamp test, manual operation or similar) diverse func-

tions are parametrisable to relay. The list of functions with the respective flags is listed further down. Fur-

thermore, non-listed functions of the relay can also be controlled. The possibility and the respective parame-

ter must be queried in the KUHSE SERVICE DEPARTMENT.

Example: A relay can be parametrised in such a way that it (for an intended manual level in the switchgear)

applies in the MANUAL and TEST operating mode.

The K15 to K17 (closer) relays switch the common potential of terminal 15. They can be used for issuing the

switch-on pulse for the mains and generator circuit breaker, indication of operational conditions, alarms, etc.

A list of the available flags is listed below.

FLAG FOR OPERATION DISPLAYS, RELAY AND ERROR MESSAGE INPUTS Genset is running 0D10

Genset available 3304

Alarm 1 2201

Alarm 2 2202

Alarm 3 2204 Alarm 4 2208

Alarm 5 2210

Alarm 6 2220

Alarm 7 2240

Alarm 8 2280

Alarm 9 2301

Alarm 10 2302

False start alarm 2304

Alarm 9 in standby current 5A01

Alarm 10 in standby current 5a02

Starting speed exceeded 3C01

Starter 3E02

Battery undervoltage 1820

Battery undervoltage

Standby current 4001

OFF operating mode 0010

MANUAL operating mode 0020

AUTO operating mode 0040

TEST operating mode 0080

Operating solenoid 0F80

Operating solenoid advanced 4e40

Speed sensor failed 0B08

Speed sensor lower 0B01

Speed sensor higher 0B02

Gas solenoid valve 3E08

Generator Off hindered 4208

Generator ON, persistent

command 3F02

Generator ON, pulse 3F08

Generator circuit breaker

tripped 4204

Generator undervoltage 3A10

Generator overvoltage 3A20

Generator underfrequency 3A40

Generator overfrequency 3A80

Generator voltage is good 0E80

Heating 3E01

Auxiliary drive I 5320

Auxiliary drive II 5340

Horn ON 0e02

Standalone operation 3708

Motor does not switch off 3E20

Mains Off, persistent com-

mand 3F01

Mains On, pulse 3F04

Mains operation 3710

Mains voltage is good 0E04

Mains Off hindered 4202

Mains circuit breaker tripping 4201

Mains undervoltage 3A01

Mains overvoltage 3A02

Mains underfrequency 3A04

Mains overfrequency 3A08

Nominal speed exceeded 3C04

Start release, time-out 1480

Collective fault of warning

alarms 3804

Collective fault of switch-off

alarms 3810

Collective fault of all alarms 3840

Collective fault of warning

alarms, standby current

function

3808

Collective fault of switch-off

alarms, standby current

function

3820

Collective fault of all alarms,

standby current function 3880

Start preconditions on 3410

Stop solenoid 3E04

Synchronising unit ON 4C08

Synchronisation fault 4480

Alarm OFF button 0540

LED Test button 0580

Overspeed exceeded 3C08

Monitoring is on 0D20

X 1, connection 16 0201

X 1, connection 17 0202

X 1, connection 18 0204

X 1, connection 19 0210

X 1, connection 20 0220

X 1, connection 21 0240

X 1, connection 22 0280

X 1, connection 23 0302

X 1, connection 24 0304

X 1, connection 25 0308

X 1, connection 26 0310

X 1, connection 27 0320

X 1, connection 28 0340

X 1, connection 29 0401

X 1, connection 30 0402

X 1, connection 31 0404

X 1, connection 32 0408

X 1, connection 33 0420

X 1, connection 34 0440

X 2, connection 4 0610

X 2, connection 5 0608

X 2, connection 6 0604

X 2, connection 7 0602

X 2, connection 8 0601

Ignition speed exceeded 3C02

Ignition 3E10

No function 0101

Page 20: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 20 / 21 - 08/28/17

Page 20 of 21

CIRCUIT DIAGRAM OF THE RELAY BOARD WITH STANDARD PARAMETRISATION NC3-1-8

Attention: The K 1, K 2 and K 5 relays have a fixed function. All others can be assigned a parametrisable

function. The installed freewheeling diodes must be observed. The position numbers are related to the para-

metrisation with PARAWIN.

K 3 K 5 K 1 K 2

Stop solenoid Starter Mains off Generator on

K 7 K 6 K 13 K 11

Preheating Operating solenoid Gen. available Error message

1

K 4 K 9 K 12 K10

Horn Gen. running Error message 2 Start preconditions

Page 21: 2A211NC3-1-8UK OPERATING MANUAL Replacement automatic … · 2017-08-30 · Mimic diagram / Voltage monitor The mimic diagram displays the mains infeed, the generator, the mains and

3

TA211NC3-1-8 UK - 21 / 21 - 08/28/17

Page 21 of 21

TERMINAL AND VOLTAGE SELECTOR POSITION PLAN OF THE BASIC UNIT

Generator terminal D+

Transfer synch. on

Remote acknowledge-

ment

Sprinkler operation

Quick Stop

Operating mode

inhibited

Remote start

Gen. is off

Mains is off

Alarm 10

Alarm 9

Alarm 8

Alarm 7

Alarm 6

Alarm 5

Alarm 4

Alarm 3

Alarm 2

Alarm 1

+ for K15-K17

K17 relay

K16 relay

K15 relay

K14

K14

K8

K8

Minus supply

Plus supply

X2 terminal strip

For seizure, see

wiring list.

Voltage switching

Open = 24 V DC

Closed = 12 V DC