NEW BRAUNFELS UTILITIES.
4" X 12" X 12"CONCRETE BLOCK
HYDRANTS ARE NOT TO BE PLACED IN SIDEWALK AREAS. SEE NEW BRAUNFELS UTILITIESSTANDARD SPECIFICATIONS FOR LOCATION OF HYDRANT.
FOR BURY DEPTHS GREATER THAN 5', ONE BARREL EXTENSION NOT EXCEEDING2' IN LENGTH SHALL BE INSTALLED DIRECTLY BELOW THE FIRE HYDRANT.
CONCRETE BLOCKING WITH A MIN. 1 1/2 FT BEARING AREA ,
CRUSHED STONE OR GRAVEL SHALL BE PLACED AROUND THE BOTTOMOF THE HYDRANT FOR A RADIUS OF AT LEAST 12" AND EXTENDAT LEAST 12" ABOVE THE OUTLET. DO NOT BLOCK DRAIN HOLES.
CLASS A CONCRETE
1.
2.
3.
4.
CLASS A CONCRETE. DO NOT BLOCK DRAIN HOLES.
2
THRUST BLOCKINGREQUIRED FOR PIPESIZE & SOIL CONDITION
APPROVED EQUAL)(FLANGED, MEG-A-LUG ORSHALL BE RESTRAINEDWATER MAIN AND HYDALL JOINTS BETWEEN
6" PRESSUREREDUCING VALVE
SEE NOTE 4
6" M.J. XFLANGED TEE
18" MIN.
2" MIN.8" MAX.
36"
SEENOTE3
24"
BOX AND LID LOCATION INFORMATION OFOPENINGS IN TOP OF BOX, CONTACT
DRAWING NO.SHEET:SCALE:
DRAWN BY:
APPROVED BY:
UPDATED:
STANDARD DRAWING:
NEW BRAUNFELS UTILITIESWATER SYSTEMS ENGINEERING