220 - st. john final report · 2016. 7. 28. · project no. 1025760 report to toronto catholic...

52
FINAL REPORT Asbestos Containing Building Material Assessment Toronto Catholic District School Board St. John Catholic School 780 Kingston Road Toronto, Ontario PROJECT NO. 1025760

Upload: others

Post on 15-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

FINAL REPORT Asbestos Containing Building Material Assessment Toronto Catholic District School Board St. John Catholic School 780 Kingston Road Toronto, Ontario PROJECT NO. 1025760

Page 2: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board

80 Sheppard Avenue East Toronto, Ontario

M2N 6E8

FOR Asbestos-Containing Building Materials Assessment – Final Report

ON St. John Catholic School 780 Kingston Road

Toronto, Ontario

May 21, 2008

Jacques Whitford 7271 Warden Avenue

Markham, Ontario L3R 5X5

Phone: 905-474-7700

Fax: 905-479-9326

www.jacqueswhitford.com

Page 3: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 i

EXECUTIVE SUMMARY

Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of St. John Catholic School, located at 780 Kingston Road in Toronto, Ontario.

The purpose of the assessment was to assist the TCDSB to meet the requirements of the new asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act (OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-containing materials (ACMs) that may require special attention.

The assessment was performed for the purposes of long term management of asbestos, and not for construction or renovations purposes. Additional intrusive testing may be required prior to using this information for construction or renovation.

The work was carried out in accordance with the requirements of the OHSA.

Based on visual assessment and laboratory analysis, asbestos-containing materials were identified to be present at the subject facility. Table 1 below provides a summary of the materials identified and recommendations on their management.

Table 1 – Summary of Findings and Recommendations

Issue Comments Recommendation

Asbestos Friable asbestos-containing materials were identified to be present in the form of insulating cement on pipe fittings, corrugated paper-like straight pipe insulation, hot water tank body insulation, boiler body insulation, breeching insulation, and stucco texturized material. These materials were observed to be in good condition.

Non-friable asbestos-containing materials were identified to be present in the form of 12”x12” and 9”x9” vinyl floor tiles. These materials were observed to be in good condition.

Presumed asbestos-containing materials (PACMs) were identified to be present in the form of cement soffit, fire doors, caulking materials, roofing materials, mastics and chalkboards. These materials were observed to be in good condition and were not sampled to preserve their integrity.

Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content. Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05. Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.

The statements made in this Executive Summary text are subject to the same limitations included in the Closure Section 8.0, and are to be read in conjunction with the remainder of this report.

Page 4: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 ii

Table of Contents EXECUTIVE SUMMARY ............................................................................................................ i 

Asbestos-Containing Building Materials Assessment ......................................................... 1 

1.0  INTRODUCTION ........................................................................................................................ 1 1.1  Assessment Objectives .............................................................................................................. 1 1.2  Scope of Work ............................................................................................................................ 1 

2.0  DOCUMENT REVIEW ............................................................................................................... 2 

3.0  ASSESSMENT METHODOLOGY ............................................................................................. 2 

4.0  ASSESSMENT LIMITATIONS .................................................................................................. 3 

5.0  REGULATORY FRAMEWORK ................................................................................................. 3 

6.0  ASSESSMENT RESULTS AND DISCUSSION ........................................................................ 4 6.1  Friable Asbestos-Containing Materials ...................................................................................... 5 6.2  Non-Friable Asbestos-Containing Materials ............................................................................... 5 6.3  Presumed Asbestos-Containing Materials ................................................................................. 5 6.4  Non-Asbestos-Containing Materials ........................................................................................... 6 

7.0  RECOMMENDATIONS .............................................................................................................. 6 

8.0  CLOSURE .................................................................................................................................. 6 

List of Tables

Table 1 – Summary of Findings and Recommendations ..................................................................... i

List of Appendices

APPENDIX 1 Floor Plans Showing Locations of Asbestos-Containing Materials ....................... 1 APPENDIX 2 Summary of Results of Analysis of Bulk Samples for Asbestos Content .............. 2 APPENDIX 3 Summary of Occurrences of Asbestos-Containing Materials ................................ 3 APPENDIX 4 Laboratory Analytical Report – Asbestos: Polarized Light Microscopy ................. 4 APPENDIX 5 Evaluation Criteria for Assessing Asbestos-Containing Materials ......................... 5 APPENDIX 6 Terms and Definitions ............................................................................................ 6 APPENDIX 7 Summary of Results of Analysis of Bulk Samples from Previous TCDSB

Asbestos Surveys (SAP inventory) ....................................................................... 7

Page 5: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 1

ASBESTOS-CONTAINING BUILDING MATERIALS ASSESSMENT

1.0 INTRODUCTION Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of St. John Catholic School, located at 780 Kingston Road in Toronto, Ontario.

The purpose of the assessment was to assist the TCDSB to meet the requirements of the new asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act (OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-containing materials (ACMs) that may require special attention.

The assessment was performed for the purposes of long term management of asbestos, and not for construction or renovations purposes. Additional intrusive testing may be required prior to using this information for construction or renovation.

The work was carried out in accordance with the requirements of the OHSA.

1.1 Assessment Objectives

The objective of the assessment was to:

prepare an assessment report that identifies asbestos-containing materials present at the subject facility; and,

provide recommendations for the management of these materials.

1.2 Scope of Work

The scope of work for this assessment involved the following:

a “room-by-room” visual assessment of readily accessible room spaces of the subject facility for the presence of asbestos-containing building materials;

an inventory of building materials/components that are suspected to contain asbestos;

the collection of representative bulk samples from building materials suspected of containing asbestos fibres;

laboratory analysis for the determination of the type and concentration of asbestos present in the samples submitted; and,

preparation of a report documenting the results of the assessment, providing an interpretation of the laboratory analysis results and recommendations for the management of asbestos containing materials.

Page 6: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 2

2.0 DOCUMENT REVIEW The SAP inventory provided by Toronto Catholic District School Board and documents on site, where available, were reviewed by Jacques Whitford.

3.0 ASSESSMENT METHODOLOGY A room-by-room visual assessment of the subject facility was made in order to check for the presence of materials suspected of containing asbestos.

During the assessment, locations to collect discrete bulk asbestos samples of suspect building materials were identified. Samples of representative materials were then collected at these locations in accordance with the requirements of Ontario Regulation 278/05 made under the Occupational Health and Safety Act.

An assessment of the condition, accessibility and exposure risk was completed for each occurrence of an asbestos-containing material. The Public Works and Government Services Canada (PWGSC) document entitled “Deputy Ministers Directive 057 – Asbestos Management” (Last Revised June 16th, 1999) was used as the basis for the criteria that was applied in evaluating the presence of asbestos-containing materials at the subject areas, where applicable.

Samples of suspect ACMs from various building materials were collected and submitted to EMSL Laboratories Inc. (EMSL) located in Westmont, New Jersey, for analysis using Polarized Light Microscopy (PLM) with dispersion staining. The analysis was conducted following the U.S. EPA/600/R-93/116 Methods. EMSL is certified under the National Voluntary Laboratory Accreditation Program (NVLAP) to perform asbestos analysis of bulk samples.

The number of bulk samples was based on the requirements of the new asbestos regulation that specifies the minimum number of samples of a particular building material that should be collected and tested to consider a material non-asbestos-containing. A positive stop option was used during the laboratory analysis of the building materials suspected to contain asbestos. Multiple samples of visually similar material were collected and submitted for laboratory analysis.

The positive stop option involves testing a series of samples from a particular building material until test results indicate the presence of asbestos. When this occurs, the remaining samples are not tested. This is a cost effective method of limiting the number of samples that are ultimately tested.

Additionally, materials that had been previously sampled and identified to contain asbestos were referenced from available reports and not re-tested.

A summary list of the bulk samples collected by Jacques Whitford, including a description of the material, sampling location, type of analysis and laboratory test results is provided in Appendix 2. A summary list of the bulk samples that had been sampled previously in TCDSB surveys and identified to contain asbestos is provided in Appendix 7.

Page 7: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 3

4.0 ASSESSMENT LIMITATIONS This report reflects the observations made within the subject facility only, and the results of analyses performed on specific materials sampled during the assessment. Analytical results reflect the sampled materials at the specific sampling locations.

Rooms 105A, 125, 126, 127D and 321 were not accessible during the assessment. Also access above solid ceilings was limited.

Due to access restrictions imposed by working in occupied and operational spaces, the asbestos content of some building materials could not be determined at some locations. Where applicable, building materials that were not sampled but that may contain asbestos include, but are not limited to the following:

sub-grade materials;

curtains;

flooring material concealed beneath carpeting, ceramic tile, brickwork, hardwood flooring and/or concealed beneath existing sub-floors;

drywall and/or wall plaster materials concealed behind new and/or additional walls;

woven tape inside duct connection joints;

inner ducting insulation;

refractory brick;

insulation material present inside walls (i.e. suspected asbestos-containing vermiculite insulation inside concrete block and/or brick walls);

pipe straight-run and pipe elbow insulation within wall cavities, inaccessible ceiling spaces or crawlspaces;

insulation materials inside fire doors;

the mechanical inner linings of heating, ventilation and air conditioning (HVAC) units; and,

heat protection materials inside mechanical installations and light fixtures.

If encountered during renovation or other activities, any suspected ACMs not identified within this report should be presumed to contain asbestos and handled as such until otherwise shown to be non asbestos-containing through analytical testing.

5.0 REGULATORY FRAMEWORK Asbestos is included in the Designated Substances Regulations made under Ontario's OHSA. The Designated Substance Regulation respecting Asbestos (R.R.O. 1990, Reg. 837, amended to O. Reg. 279/05) primarily regulates worker exposure to asbestos during manufacturing of asbestos containing products, but also includes requirements related to respiratory equipment, measurement of airborne fibres, and medical surveillance of exposed workers.

Page 8: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 4

The Ontario Regulation 278/05 made under the OHSA for Asbestos on Construction Projects and in Buildings and Repair Operations, clearly defines asbestos-containing material as a material that contains 0.5 per cent or more asbestos by dry weight. The new asbestos regulation (O. Reg. 278/05) became effective as of November 1, 2005.

The General Waste Management Regulation (O. Reg. 347/90), under the Environmental Protection Act (EPA) of Ontario, sets out the requirements for the proper disposal of asbestos waste in Ontario. The waste must be placed in a double sealed container, properly labeled, free of cuts, tears or punctures and disposed of at a licensed waste station which has been properly notified of the presence of asbestos waste.

6.0 ASSESSMENT RESULTS AND DISCUSSION The result of the assessment for asbestos-containing building materials is discussed below. The evaluation criterion for assessing asbestos-containing materials is provided in Appendix 5. A list of definitions for technical terms used in this report is provided in Appendix 6.

Asbestos-containing materials are grouped into two classifications, friable and non-friable materials. Friable ACMs are those that can easily be crumbled or broken apart by mere hand pressure. When these materials break apart asbestos fibres are then released into the atmosphere. Non-friable ACMs or “manufactured products” are materials that by the nature of their manufacturing/construction do not readily allow the release of asbestos fibres. These materials should not be cut or shaped with power tools, since this procedure may allow for the release of the asbestos fibres.

O. Reg. 278/05 requires that an Asbestos Management Program (AMP) be implemented in buildings that have been identified to contain friable and non-friable ACMs.

A summary list of the bulk samples that were collected during the assessment including a description of the material, sampling location, type of analysis and laboratory test results is provided in Appendix 2.

A summary list of the bulk samples that had been identified to contain asbestos in the SAP inventory provided by TCDSB is provided in Appendix 7.

A copy of the PLM laboratory Certificate of Analysis is provided in Appendix 4.

A summary of occurrences of asbestos-containing materials for areas that were inspected is provided in Appendix 3. Each ACM occurrence includes the following information:

room component that contains ACM;

location of the ACM within the room space;

ACM description;

estimated quantity;

original sample number or representative sample number;

friability; and,

condition.

Page 9: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 5

6.1 Friable Asbestos-Containing Materials

During the assessment, friable ACMs were identified but were not sampled as they had been previously identified in the SAP inventory provided by the TCDSB. Friable ACMs were observed at the subject facility in the form of:

Insulating cement on pipe fittings;

Corrugated paper-like pipe straight insulation;

Hot water tank body insulation;

Boiler body insulation;

Breeching insulation; and,

Stucco texturized material.

Refer to Appendix 7 for the type and asbestos content; and Appendix 3 for specific location and condition of these ACMs.

6.2 Non-Friable Asbestos-Containing Materials

During the assessment, non-friable ACMs were identified by laboratory analysis to be present at the subject facility in the form of:

12”x12” vinyl floor tiles; and,

9”x9” vinyl floor tiles.

Refer to Appendix 2 and Appendix 7 for the type and asbestos content; and Appendix 3 for specific location and condition of these ACMs.

6.3 Presumed Asbestos-Containing Materials

Presumed asbestos-containing materials were observed to be present at the subject facility. The following materials were identified but not sampled:

Window and door caulking materials;

Roof caulking materials;

Roofing materials;

Mastics;

Chalkboards;

Fire doors; and,

Cement soffit.

The cement soffit could not be sampled due to height limitations. The other materials were not sampled during the assessment to avoid damage. The materials were observed to be in good condition. As these materials are known to have been manufactured with asbestos, they should be presumed to be asbestos-containing unless proven otherwise by laboratory analysis.

Page 10: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 6

6.4 Non-Asbestos-Containing Materials Refer to Appendix 2 for a list of materials identified as non-asbestos containing through sampling and laboratory analysis.

7.0 RECOMMENDATIONS Based on visual assessment and laboratory analysis, Jacques Whitford recommends the following with regards to the ACMs and PACMs in the facility assessed:

Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content;

Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05; and,

Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.

8.0 CLOSURE This report has been prepared for the sole benefit of the Toronto Catholic District School Board. The report may not be used by any other person or entity without the express written consent of Jacques Whitford Limited and the Toronto Catholic District School Board.

Any use which a third party makes of this report, or any reliance on decisions based on it, are the responsibility of such third parties. Jacques Whitford Limited accepts no responsibility for damages, if any, suffered by any third party as a result of decisions made or actions based on this report.

The information and conclusions contained in this report are based upon work undertaken by trained professional and technical staff in accordance with generally accepted engineering and scientific practices current at the time the work was performed. Conclusions presented in this report should not be construed as legal advice.

The conclusions presented in this report represent the best technical judgment of Jacques Whitford Limited based on the data obtained from the work. The conclusions are based on the site conditions encountered by Jacques Whitford Limited at the time the work was performed at the specific assessment and/or sampling locations, and can only be extrapolated to an undefined limited area around these locations. The extent of the limited area depends on building construction and conditions, weather, building usage and other factors. Due to the nature of the investigation and the limited data available, Jacques Whitford Limited cannot warrant against undiscovered environmental liabilities.

If any conditions become apparent that differ significantly from our understanding of conditions as presented in this report, we request that we be notified immediately to reassess the conclusions provided herein.

Page 11: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 7

We trust that the above is satisfactory for your purposes at this time. Should you have any questions or concerns, or require additional information, please do not hesitate to contact the undersigned at your convenience.

This report was prepared by Anil Panchal and reviewed by Martin Ling and Steven D. Fulford.

Sincerely,

JACQUES WHITFORD LIMITED

Original signed by: Original signed by: Anil Panchal Steven D. Fulford Report Author Senior Technical Reviewer Original signed by: Martin Ling Project Manager Enclosures P:\CMiC Jobs\1025xxx\1025760\REPORTS\220 - St. John\220 - St. John_final report.docx

Page 12: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 1 Floor Plans Showing Locations of

Asbestos-Containing Materials

Page 13: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 14: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 15: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 16: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 2 Summary of Results of Analysis of Bulk Samples

for Asbestos Content

Page 17: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Summary of Bulk Sample Analysis for Asbestos Type and Content

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

220-BS-01A None Detected PLM12" x 12" vinyl floor tile - white with grey smudges

Rm 320

220-BS-01B None Detected PLM12" x 12" vinyl floor tile - white with grey smudges

Rm 320

220-BS-01C None Detected PLM12" x 12" vinyl floor tile - white with grey smudges

Rm 320

220-BS-02A None Detected PLM12" x 12" vinyl floor tile - beige smudges

Rm 118

220-BS-02B None Detected PLM12" x 12" vinyl floor tile - beige smudges

Rm 118

220-BS-02C None Detected PLM12" x 12" vinyl floor tile - beige smudges

Rm 318

220-BS-03A None Detected PLM12" x 12" vinyl floor tile - green with aqua smudges

Rm 112

220-BS-03B None Detected PLM12" x 12" vinyl floor tile - green with aqua smudges

Rm 220

220-BS-03C None Detected PLM12" x 12" vinyl floor tile - green with aqua smudges

Rm 112

220-BS-04A None Detected PLM12" x 12" vinyl floor tile - white smearsRm 220

220-BS-04B None Detected PLM12" x 12" vinyl floor tile - white smearsRm 220

220-BS-04C None Detected PLM12" x 12" vinyl floor tile - white smearsRm 220

220-BS-05A 2% Chrysotile PLM12" x 12" vinyl floor tile - redRm 305

220-BS-05B SP PLM12" x 12" vinyl floor tile - redRm 305

220-BS-05C SP PLM12" x 12" vinyl floor tile - redRm 305

220-BS-06A 2% Chrysotile PLM12" x 12" vinyl floor tile - beige with brown streaks

Rm 310A

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

1

Notes:

21-May-08

Page 18: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

220-BS-06B SP PLM12" x 12" vinyl floor tile - beige with brown streaks

Rm 310A

220-BS-06C SP PLM12" x 12" vinyl floor tile - beige with brown streaks

Rm 310A

220-BS-07A None Detected PLM12" x 12" vinyl floor tile - light blue smudges

Rm 113

220-BS-07B None Detected PLM12" x 12" vinyl floor tile - light blue smudges

Rm 113

220-BS-07C None Detected PLM12" x 12" vinyl floor tile - light blue smudges

Rm 113

220-BS-08A None Detected PLM12" x 12" vinyl floor tile - blue with white smudges

Rm 115

220-BS-08B None Detected PLM12" x 12" vinyl floor tile - blue with white smudges

Rm 115

220-BS-08C None Detected PLM12" x 12" vinyl floor tile - blue with white smudges

Rm 115

220-BS-09A 2% Chrysotile PLM9" x 9" vinyl floor tile - beige with light brown streaks

Rm 302A

220-BS-09B SP PLM9" x 9" vinyl floor tile - beige with light brown streaks

Rm 302A

220-BS-09C SP PLM9" x 9" vinyl floor tile - beige with light brown streaks

Rm 302A

220-BS-10A 5% Chrysotile PLM9" x 9" vinyl floor tile - yellowRm 117

220-BS-10B SP PLM9" x 9" vinyl floor tile - yellowRm 117

220-BS-10C SP PLM9" x 9" vinyl floor tile - yellowRm 117

220-BS-11A 15% Chrysotile PLM9" x 9" vinyl floor tile - green with beige streaks

Rm 206

220-BS-11B SP PLM9" x 9" vinyl floor tile - green with beige streaks

Rm 206

220-BS-11C SP PLM9" x 9" vinyl floor tile - green with beige streaks

Rm 206

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

2

Notes:

21-May-08

Page 19: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

220-BS-12A 2% Chrysotile PLM9" x 9" vinyl floor tile - beigeRm 317

220-BS-12B SP PLM9" x 9" vinyl floor tile - beigeRm 317

220-BS-12C SP PLM9" x 9" vinyl floor tile - beigeRm 317

220-BS-13A 2% Chrysotile PLM9" x 9" vinyl floor tile - grey with light brown streaks

Rm 221

220-BS-13B SP PLM9" x 9" vinyl floor tile - grey with light brown streaks

Rm 221

220-BS-13C SP PLM9" x 9" vinyl floor tile - grey with light brown streaks

Rm 221

220-BS-14A 15% Chrysotile PLM9" x 9" vinyl floor tile - beige with red streaks

Rm 202

220-BS-14B SP PLM9" x 9" vinyl floor tile - beige with red streaks

Rm 202

220-BS-14C SP PLM9" x 9" vinyl floor tile - beige with red streaks

Rm 202

220-BS-15A 15% Chrysotile PLM9" x 9" vinyl floor tile - red with beige streaks

Rm 202

220-BS-15B SP PLM9" x 9" vinyl floor tile - red with beige streaks

Rm 202

220-BS-15C SP PLM9" x 9" vinyl floor tile - red with beige streaks

Rm 202

220-BS-16A 10% Chrysotile PLM9" x 9" vinyl floor tile - red with white streaks

Rm 117

220-BS-16B SP PLM9" x 9" vinyl floor tile - red with white streaks

Rm 117

220-BS-16C SP PLM9" x 9" vinyl floor tile - red with white streaks

Rm 117

220-BS-17A 4% Chrysotile PLM9" x 9" vinyl floor tile - yellow with brown streaks

Rm 216

220-BS-17B SP PLM9" x 9" vinyl floor tile - yellow with brown streaks

Rm 216

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

3

Notes:

21-May-08

Page 20: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

220-BS-17C SP PLM9" x 9" vinyl floor tile - yellow with brown streaks

Rm 216

220-BS-18A None Detected PLM9" x 9" vinyl floor tile - red with beige smears

Rm 208

220-BS-18B None Detected PLM9" x 9" vinyl floor tile - red with beige smears

Rm 208

220-BS-18C None Detected PLM9" x 9" vinyl floor tile - red with beige smears

Rm 208

220-BS-20A None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Rm 314

220-BS-20B None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Rm 314

220-BS-20C None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Rm 314

220-BS-21A None Detected PLM2' x 4' acoustical ceiling tile - pinhole pattern

Corridor 101

220-BS-21B None Detected PLM2' x 4' acoustical ceiling tile - pinhole pattern

Corridor 124

220-BS-21C None Detected PLM2' x 4' acoustical ceiling tile - pinhole pattern

Corridor 101

220-BS-22A None Detected PLMPlasterRm 225

220-BS-22B None Detected PLMPlasterRm 318

220-BS-22C None Detected PLMPlasterRm 318

220-BS-22D None Detected PLMPlasterRm 318

220-BS-22E None Detected PLMPlasterRm 312

220-BS-22F None Detected PLMPlasterRm 216

220-BS-22G None Detected PLMPlasterRm 217

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

4

Notes:

21-May-08

Page 21: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

220-BS-23A None Detected PLMJoint fill compoundRm 314

220-BS-23B None Detected PLMJoint fill compoundRm 314

220-BS-23C None Detected PLMJoint fill compoundRm 314

220-BS-23D None Detected PLMJoint fill compoundRm 314

220-BS-23E None Detected PLMJoint fill compoundRm 314

220-BS-23F None Detected PLMJoint fill compoundRm 314

220-BS-23G None Detected PLMJoint fill compoundRm 314

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

5

Notes:

21-May-08

Page 22: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 3 Summary of Occurrences of Asbestos

Containing Materials

Page 23: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Summary of Occurrences of Asbestos-Containing Materials

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

insulating cement on pipe fitting 70-80 ns No 50% Chrysotile Yes No C good ACM as identified in

SAP inventory

101 (corridor) above ceilingmechanical1

cement soffit 10 sq. m ns No ns No Yes C good PACM101 (corridor) soffitexterior1

stucco texturized material 500 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

102, 111, 116, 117, 118, 119

ceilingceiling1

corrugated paper-like straight pipe insulation

20 m ns No 33% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

105 below ceilingmechanical1

insulating cement on pipe fitting 85-100 ns No 50% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

105 below ceilingmechanical1

breeching insulation 10 sq. m ns No 57% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

105 below ceilingmechanical1

hot water tank body insulation 12 sq. m ns No 57% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

105 below ceilingmechanical1

boiler body insulation 2 units (10 sq. m)

ns No 57% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

105 below ceilingmechanical1

fire door 1 ns No ns No Yes A good PACM105 doordoor1

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

1

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 24: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

fire door 1 ns No ns No Yes A good PACM105B doordoor1

insulating cement on pipe fitting nq ns No 50% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

106 above ceilingmechanical1

corrugated paper-like straight pipe insulation

nq ns No 57% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

106 above ceilingmechanical1

insulating cement on pipe fitting nq ns No 50% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

107 above ceilingmechanical1

corrugated paper-like straight pipe insulation

1 m ns No 33% Chrysotile Yes No C good ACM as identified in

SAP inventory

108 above ceiling (above access

hatch)

mechanical1

insulating cement on pipe fitting 2 ns No 50% Chrysotile Yes No C good ACM as identified in

SAP inventory

108 above ceiling (above access

hatch)

mechanical1

9" x 9" vinyl floor tile - beige 40 sq. m Ref 220-BS-12A No 2% Chrysotile No Yes A good ACM110 floorfloor1

9" x 9" vinyl floor tile - red with beige streaks

65 sq. m Ref 220-BS-15A No 15% Chrysotile No Yes A good ACM111, 116 floorfloor1

9" x 9" vinyl floor tile - beige with light brown streaks

70 sq. m Ref 220-BS-09A No 2% Chrysotile No Yes A good ACM111, 120 floorfloor1

corrugated paper-like straight pipe insulation

3 m ns No 33% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

116 above ceilingmechanical1

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

2

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 25: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

9" x 9" vinyl floor tile - beige with red streaks

35 sq. m Ref 220-BS-14A No 15% Chrysotile No Yes A good ACM116 floorfloor1

9" x 9" vinyl floor tile - grey with light brown streaks

120 sq. m Ref 220-BS-13A No 2% Chrysotile No Yes A good ACM116, 122, 127A, 127B

floorfloor1

9" x 9" vinyl floor tile - yellow 45 sq. m 220-BS-10A Yes 5% Chrysotile No Yes A good ACM117 floorfloor1

9" x 9" vinyl floor tile - red with white streaks

45 sq. m 220-BS-16A Yes 10% Chrysotile No Yes A good ACM117 floorfloor1

stucco texturized material 9 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

123A ceilingceiling1

cement soffit 6 sq. m ns No ns No Yes C good PACM123B, 123C soffitexterior1

insulating cement on pipe fitting 3 ns No 50% Chrysotile Yes No C good ACM as identified in

SAP inventory

123C above ceilingmechanical1

cement soffit 6 sq. m ns No ns No Yes C good PACM124 (corridor) soffitexterior1

insulating cement on pipe fitting 25-30 ns No 50% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

127 below ceilingmechanical1

insulating cement on pipe fitting 6 ns No 50% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

127A below ceilingmechanical1

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

3

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 26: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

9" x 9" vinyl floor tile as identified in SAP inventory

nq ns No No Yes A good No access to room. ACM as

identified in SAP inventory

127D floorfloor1

9" x 9" vinyl floor tile - yellow with brown streaks

10 sq. m Ref 220-BS-17A No 4% Chrysotile No Yes A good ACM128 floorfloor1

cement soffit 12 sq. m ns No ns No Yes C good PACMstair B, stair C soffitexterior1

stucco texturized material 30 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

stair A ceilingceiling1, 2

9" x 9" vinyl floor tile - red with beige streaks

225 sq. m Ref 220-BS-15A No 15% Chrysotile No Yes A good ACM201, 209, 224, 225

floorfloor2

9" x 9" vinyl floor tile - red with beige streaks

40 sq. m 220-BS-15A Yes 15% Chrysotile No Yes A good ACM202 floorfloor2

9" x 9" vinyl floor tile - beige with red streaks

40 sq. m 220-BS-14A Yes 15% Chrysotile No Yes A good ACM202 floorfloor2

9" x 9" vinyl floor tile - green with beige streaks

90 sq. m Ref 220-BS-11A No 15% Chrysotile No Yes A good ACM204, 205, 207 floorfloor2

stucco texturized material 625 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

205, 206, 207, 208, 215, 216, 223, 224, 225, 226

ceilingceiling2

9" x 9" vinyl floor tile - green with beige streaks

72 sq. m 220-BS-11A Yes 15% Chrysotile No Yes A good ACM206 floorfloor2

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

4

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 27: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

9" x 9" vinyl floor tile - beige with red streaks

55 sq. m Ref 220-BS-14A No 15% Chrysotile No Yes A good ACM208, 208A floorfloor2

corrugated paper-like straight pipe insulation

3 m ns No 57% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

211 below ceilingmechanical2

9" x 9" vinyl floor tile - yellow with brown streaks

275 sq. m Ref 220-BS-17A No 4% Chrysotile No Yes A good ACM213, 215, 217, 222, 223

floorfloor2

12" x 12" vinyl floor tile - beige with brown streaks

70 sq. m Ref 220-BS-06A No 2% Chrysotile No Yes A good ACM215, 223 floorfloor2

9" x 9" vinyl floor tile - yellow with brown streaks

70 sq. m 220-BS-17A Yes 4% Chrysotile No Yes A good ACM216 floorfloor2

9" x 9" vinyl floor tile - grey with light brown streaks

70 sq. m 220-BS-13A Yes 2% Chrysotile No Yes A good ACM221 floorfloor2

9" x 9" vinyl floor tile - grey with light brown streaks

80 sq. m Ref 220-BS-13A No 2% Chrysotile No Yes A good ACM226 floorfloor2

stucco texturized material 200 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

301, 322 ceilingceiling3

stucco texturized material 525 sq. m ns No 12% Chrysotile Yes Yes C good ACM as identified in

SAP inventory

302, 303, 304, 305, 310, 310A, 311, 318, 319, 320

ceilingceiling3

9" x 9" vinyl floor tile - green with beige streaks

75 sq. m Ref 220-BS-11A No 15% Chrysotile No Yes A good ACM302, 303, 319 floorfloor3

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

5

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 28: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

9" x 9" vinyl floor tile - red with beige streaks

100 sq. m Ref 220-BS-15A No 15% Chrysotile No Yes A good ACM302, 304, 305, 307

floorfloor3

9" x 9" vinyl floor tile - beige with light brown streaks

15 sq. m 220-BS-09A Yes 2% Chrysotile No Yes A good ACM302A floorfloor3

9" x 9" vinyl floor tile - beige with red streaks

85 sq. m Ref 220-BS-14A No 15% Chrysotile No Yes A good ACM303, 304, 305, 307

floorfloor3

12" x 12" vinyl floor tile - red 45 sq. m 220-BS-05A Yes 2% Chrysotile No Yes A good ACM305 floorfloor3

insulating cement on pipe fitting 2 ns No 50% Chrysotile Yes Yes A good ACM as identified in

SAP inventory

306 below ceilingmechanical3

9" x 9" vinyl floor tile - grey with light brown streaks

280 sq. m Ref 220-BS-13A No 2% Chrysotile No Yes A good ACM310, 312, 315, 316, 319

floorfloor3

12" x 12" vinyl floor tile - beige with brown streaks

40 sq. m 220-BS-06A Yes 2% Chrysotile No Yes A good ACM310A floorfloor3

9" x 9" vinyl floor tile - beige 55 sq. m 220-BS-12A Yes 2% Chrysotile No Yes A good ACM317 floorfloor3

9" x 9" vinyl floor tile as identified in SAP inventory

nq ns No No Yes A good No access to room. ACM as

identified in SAP inventory

321 floorfloor3

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

6

* Based on a non-intrusive inspection of visible surfaces within the room space.

21-May-08

Page 29: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 4 Laboratory Analytical Report – Asbestos:

Polarized Light Microscopy

Page 30: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-01A170801002-0001

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-01B170801002-0002

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-01C170801002-0003

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-02A170801002-0004

Floor Tile Beige None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-02B170801002-0005

Floor Tile Beige None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-02C170801002-0006

Floor Tile Beige None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-03A170801002-0007

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-03B170801002-0008

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

1

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 31: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-03C170801002-0009

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-04A170801002-0010

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-04B170801002-0011

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-04C170801002-0012

Floor Tile White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-05A170801002-0013

Floor Tile RedNon-FibrousHeterogeneous

Chrysotile2%Non-fibrous (other)98%

220-BS-05B170801002-0014

Floor Tile Stop Positive (Not Analyzed)

220-BS-05C170801002-0015

Floor Tile Stop Positive (Not Analyzed)

220-BS-06A170801002-0016

Floor Tile Beige/BrownNon-FibrousHeterogeneous

Chrysotile2%Non-fibrous (other)98%

2

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 32: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-06B170801002-0017

Floor Tile Stop Positive (Not Analyzed)

220-BS-06C170801002-0018

Floor Tile Stop Positive (Not Analyzed)

220-BS-07A170801002-0019

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-07B170801002-0020

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-07C170801002-0021

Floor Tile Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-08A170801002-0022

Floor Tile Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-08B170801002-0023

Floor Tile Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-08C170801002-0024

Floor Tile Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

3

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 33: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-09A170801002-0025

Floor Tile BeigeNon-FibrousHomogeneous

Chrysotile2%Non-fibrous (other)98%

220-BS-09B170801002-0026

Floor Tile Stop Positive (Not Analyzed)

220-BS-09C170801002-0027

Floor Tile Stop Positive (Not Analyzed)

220-BS-10A170801002-0028

Floor Tile Yellow/BlackNon-FibrousHeterogeneous

Chrysotile5%Non-fibrous (other)95%

220-BS-10B170801002-0029

Floor Tile Stop Positive (Not Analyzed)

220-BS-10C170801002-0030

Floor Tile Stop Positive (Not Analyzed)

220-BS-11A170801002-0031

Floor Tile Green/BlackNon-FibrousHeterogeneous

Chrysotile15%Non-fibrous (other)85%

220-BS-11B170801002-0032

Floor Tile Stop Positive (Not Analyzed)

4

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 34: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-11C170801002-0033

Floor Tile Stop Positive (Not Analyzed)

220-BS-12A170801002-0034

Floor Tile BeigeNon-FibrousHeterogeneous

Chrysotile2%Non-fibrous (other)98%

220-BS-12B170801002-0035

Floor Tile Stop Positive (Not Analyzed)

220-BS-12C170801002-0036

Floor Tile Stop Positive (Not Analyzed)

220-BS-13A170801002-0037

Floor Tile GrayNon-FibrousHeterogeneous

Chrysotile2%Non-fibrous (other)98%

220-BS-13B170801002-0038

Floor Tile Stop Positive (Not Analyzed)

220-BS-13C170801002-0039

Floor Tile Stop Positive (Not Analyzed)

220-BS-14A170801002-0040

Floor Tile BeigeNon-FibrousHeterogeneous

Chrysotile15%Non-fibrous (other)85%

5

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 35: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-14B170801002-0041

Floor Tile Stop Positive (Not Analyzed)

220-BS-14C170801002-0042

Floor Tile Stop Positive (Not Analyzed)

220-BS-15A170801002-0043

Floor Tile Red/BlackNon-FibrousHeterogeneous

Chrysotile15%Non-fibrous (other)85%

220-BS-15B170801002-0044

Floor Tile Stop Positive (Not Analyzed)

220-BS-15C170801002-0045

Floor Tile Stop Positive (Not Analyzed)

220-BS-16A170801002-0046

Floor Tile RedNon-FibrousHeterogeneous

Chrysotile10%Non-fibrous (other)90%

220-BS-16B170801002-0047

Floor Tile Stop Positive (Not Analyzed)

220-BS-16C170801002-0048

Floor Tile Stop Positive (Not Analyzed)

6

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 36: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-17A170801002-0049

Floor Tile YellowNon-FibrousHeterogeneous

Chrysotile4%Non-fibrous (other)96%

220-BS-17B170801002-0050

Floor Tile Stop Positive (Not Analyzed)

220-BS-17C170801002-0051

Floor Tile Stop Positive (Not Analyzed)

220-BS-18A170801002-0052

Floor Tile Red None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-18B170801002-0053

Floor Tile Red None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-18C170801002-0054

Floor Tile Red None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-20A170801002-0058

Ceiling Tile White/Gray None Detected

FibrousHeterogeneous

Cellulose25%Glass40%

Non-fibrous (other)35%

220-BS-20B170801002-0059

Ceiling Tile White/Gray None Detected

FibrousHeterogeneous

Cellulose25%Glass40%

Non-fibrous (other)35%

7

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 37: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-20C170801002-0060

Ceiling Tile White None Detected

FibrousHeterogeneous

Cellulose25%Glass40%

Non-fibrous (other)35%

220-BS-21A170801002-0061

Ceiling Tile Beige None Detected

FibrousHomogeneous

Cellulose20%Glass60%

Non-fibrous (other)20%

220-BS-21B170801002-0062

Ceiling Tile Beige None Detected

FibrousHomogeneous

Cellulose20%Glass60%

Non-fibrous (other)20%

220-BS-21C170801002-0063

Ceiling Tile Beige None Detected

FibrousHomogeneous

Cellulose20%Glass60%

Non-fibrous (other)20%

220-BS-22A170801002-0064

Plaster White/Gray None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-22B170801002-0065

Plaster White/Gray None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-22C170801002-0066

Plaster White/Gray None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-22D170801002-0067

Plaster White/Gray None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

8

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 38: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

170801002

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 02/18/08 12:00 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:2/26/2008Analysis Date:

Report Date: 5/7/2008

EMSL Analytical, Inc.19501 NE 10th Ave. Bay A, N. Miami Beach, FL 33179Phone: (305) 650-0577 Fax: (305) 650-0578 Email: [email protected]

220-BS-22E170801002-0068

Plaster White/Gray None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-22F170801002-0069

Plaster White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-22G170801002-0070

Plaster White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

Revised per client request 5/7/2008

9

Kimberly Wallace, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.NVLAP Lab Code 200204-0

Kim Wallace (11)Sean Scales (56)

Page 39: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

040811090

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario, Canada L3R 5X5

Customer PO: 1025760/985Received: 05/08/08 9:35 AM

1025760/985

Customer ID: JACQ30J

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

EMSL Order:

EMSL Proj:5/14/2008Analysis Date:

Report Date: 5/14/2008

EMSL Analytical, Inc.107 Haddon Ave., Westmont, NJ 08108Phone: (856) 858-4800 Fax: (856) 858-4960 Email: [email protected]

220-BS-23A040811090-0001

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23B040811090-0002

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23C040811090-0003

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23D040811090-0004

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23E040811090-0005

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23F040811090-0006

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

220-BS-23G040811090-0007

RM 314 White/Blue None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

1

Stephen Siegel, CIH, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.Analysis performed by EMSL Westmont (NVLAP #101048-0), NY ELAP 10872

Alexis Turner (7)

Page 40: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 5 Evaluation Criteria for Assessing Asbestos

Containing Materials

Page 41: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 Appendix 5-1

Criteria for Assessing Asbestos Containing Materials

A description of the criteria used in evaluating the condition, accessibility and exposure risk of asbestos-containing materials is provided below. The criteria is generally based on the Public Works and Government Services Canada (PWGSC) document entitled “Deputy Ministers Directive 057 – Asbestos Management” (Last Revised 1999/07/16) and industry standards of practice.

Assessment of Condition

Spray Applied Fireproofing, Insulation and Textured Finishes

In evaluating the condition of ACM spray applied as fireproofing, thermal insulation or texture, decorative or acoustic finishes, the following criteria apply:

Good

Surface of material shows no significant signs of damage, deterioration or delamination. Up to one percent visible damage to surface is allowed within range of GOOD. Evaluation of sprayed fireproofing requires the Assessor to be familiar with the irregular surface texture typical of sprayed asbestos products. GOOD condition includes unencapsulated or unpainted fireproofing or texture finishes, where no delamination or damage is observed, and encapsulated fireproofing or texture finishes where the encapsulation has been applied after the damage or fallout occurred.

Poor

Sprayed materials show signs of damage, delamination or deterioration. More than one percent damage to surface of ACM spray.

In observation areas, where damage exists in isolated locations, both GOOD and POOR condition may be reported. The extent or percentage of each condition will be recorded on the Assessor reassessment form.

FAIR condition is not utilized or considered as a valid criterion in the evaluation of sprayed fireproofing, sprayed insulation, or texture coat finishes.

The evaluation of ACM spray applied as fireproofing, non-mechanical thermal insulation, or texture, decorative or acoustic finishes which are present above ceilings, may be limited by the number of observations made, and by building components such as ducts or full height walls that obstruct the above ceiling observations. Persons entering the ceiling area are advised to be watchful for ACM DEBRIS prior to accessing or working above ceilings in areas of building with ACM, regardless of the reported condition.

Other ACM

In evaluating the condition of mechanical insulation (on boilers, breaching, ductwork, piping, tanks, equipment etc.) the following criteria are used:

Page 42: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 Appendix 5-2

Good

Insulation is completely covered in jacketing and exhibits no evidence of damage or deterioration. No insulation is exposed. Includes conditions where the jacketing has minor surface damage (i.e., scuffs or stains), but the jacketing is not penetrated.

Fair

Minor penetration damage to jacketed insulation (cuts, tears, nicks, deterioration or delamination) or undamaged insulation that has never been jacketed. Insulation is exposed but not showing surface disintegration. The extent of missing insulation ranges should be minor to none.

Poor

Original insulation jacket is missing, damaged, deteriorated or delaminated. Insulation is exposed and significant areas have been dislodged. Damage cannot be readily repaired. The evaluation of mechanical insulation may be limited by the number of observations made and building components such as ducts or full height walls that obstruct observations. In these circumstances, it is not possible to observe each foot of mechanical insulation from all angles.

Non-Friable and Potentially Friable Materials

Non-friable materials generally have little potential to release airborne fibres, even when damaged by mechanical breakage. However, some non-friable materials, i.e., exterior asbestos cement products, may have deteriorated so that the binder no longer effectively contains the asbestos fibres. In such cases of significantly deteriorated non-friable material, the material will be treated as a friable product.

Evaluation of Accessibility

The accessibility of building materials known or suspected of being ACM is rated according to the following criteria:

Access (A)

Areas of the building within reach of all building users. Includes areas such as gymnasiums, workshops, and storage areas where activities of the building users may result in disturbance of ACM not normally within reach from floor level.

Access (B)

Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladder. Includes: frequently entered pipe chases, tunnels and service areas or areas within reach from a fixed ladder or catwalk, i.e., tops of equipment, mezzanines.

Access (C) Exposed

Areas of the building above 8'0" where use of a ladder is required to reach the ACM. Only refers to ACM materials that are exposed to view, from the floor or ladder, without removing or opening other building components such as ceiling tiles, or service access doors or hatches. Does not include infrequently accessed service areas of the building.

Page 43: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 Appendix 5-3

Access (C) Concealed

Areas of the building which require the removal of a building component, including lay-in ceilings and access panels into solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc. Observations are limited to the extent visible from the access points.

Access (D)

Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc. where demolition of the ceiling, wall or equipment, etc., is required to reach the ACM. Evaluation of the condition and extent of ACM is limited or impossible, depending on the Assessor's ability to visually examine the materials In Access D.

Page 44: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 6 Terms and Definitions

Page 45: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

© 2008 PROJECT 1025760 May 21, 2008 Appendix 6-1

Terms and Definitions

Asbestos

Any of the following asbestiform silicate minerals: actinolite asbestos, anthophyllite asbestos, chrysotile, crocidolite, cumming tonite-grunerite asbestos (amosite), tremolite asbestos with a dry weight concentration greater than 0.5%.

Friable

Capable of being crumbled, pulverized or reduced to powder by hand pressure.

HEPA Filter

A high efficiency particulate aerosol filter that is at least 99.97 per cent efficient in collecting a 0.3 micrometre aerosol.

Homogeneous Material

A material that is uniform in colour and texture

Polarized Light Microscopy (PLM)

Polarized Light Microscopy is a technique accepted by the US Environmental Protection Agency as a screening method for detecting asbestos fibres in bulk material samples.

Presumed Asbestos Containing Materials (PACMs)

Materials that are known to have been manufactured contain asbestos. Testing of the material is required to determine if the material contains asbestos fibres.

Recommended Corrective Actions (RCAs)

Areas identified to consist of asbestos-containing or presumed asbestos-containing materials that require attention to repair or remove damaged materials.

Building

Any structure, vault, chamber or tunnel including, without limitation, the electrical, plumbing, heating and air handling equipment (including rigid duct work) of the structure, vault, chamber or tunnel.

Page 46: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing

APPENDIX 7 Summary of Results of Analysis of Bulk Samples

- SAP inventory

Page 47: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 48: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 49: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 50: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 51: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing
Page 52: 220 - St. John final report · 2016. 7. 28. · PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 FOR Asbestos-Containing