© 2008 Trane Pub. No. 22-1808-03
Product Data4YCZ6036A through 4YCZ6060A
Single Packaged Convertible Gas/Electric16 SEER3, 4 & 5 Ton, 75 - 120 KBTUR-410A
22-1808-03
2© 2008 Trane
�������������� ��������Single Packaged Convertible Gas/Electric SystemTrane offers a complete family of packaged gas/electric heating and coolingsystems, designed to give you the unbeatable combination of energy efficiencyand lower operating costs. In warm weather, the package gas/electric systemfunctions as an all-electric, high efficiency air conditioner. In cold weather, itoperates as a natural gas or propane gas furnace, offering you the best of bothenergy worlds.
Introducing the new TRANE Single Packaged ConvertibleGas/Electric System.
Single Packaged Convertible Gas/Electric Systems are easy and versa-tile to install. Because cooling andheating functions are all contained in asingle cabinet, a Trane single packageconvertible gas/electric system is easy toinstall and service. It can be flushmounted beside your home at groundlevel or placed on the roof for horizontalor downflow installation. When connectedto an optional Trane thermostat controland air distribution ducts, you have ahighly efficient, total home comfortsystem.
Single Packaged Convertible Gas/Electric Systems are unmatched inquality and reliability. All major compo-nents on these products, including thecompressor, have been designed andmanufactured for maximum service. EveryClimatuff® two stage compressor isdesigned and manufactured to exactingspecifications. Each design is life tested inextreme environments to ensure reliableand long lasting operation in normalapplications. Each compressor hasinternal motor protection for addedreliability.
3
Contents
Optional Equipment Listing 4
General Data 5
Performance Data
Cooling 10Indoor Fan 12
Typical Wiring 14
Optional Equipment 17
Dimensional Data 22
Mechanical Specifications 28
4© 2008 Trane
Optional Equipment Listing
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [✓✓✓✓✓] indicates accessories included)
Hinged Filter Access Door (4YCZ6036) ............................................................................... BAYACCDOR1A[ ]Hinged Filter Access Door (4YCZ6048-060) ....................................................................... BAYACCDOR2A[ ]Roof Curb Full Perimeter (4YCZ6036A) 3 ........................................................................... BAYCURB050A[ ]Roof Curb Full Perimeter (4YCZ6048-60A) 3 ...................................................................... BAYCURB051A[ ]Roof Curb Utility Extension Kit (BAYCURB050A) .................................................................... BAYUTIL101B[ ]Roof Curb Utility Extension Kit (BAYCURB051A) .................................................................... BAYUTIL102B[ ]Outside Air Control for V.S. Economizer (4YCZ6036A) ........................................................ BAYOSAC001B[ ]Outside Air Control for V.S. Economizer (4YCZ6048-060) ................................................... BAYOSAC002B[ ]0-25% Motorized Outside Air Damper (4YCZ6036) ........................................................... BAYDMPR101A[ ]0-25% Motorized Outside Air Damper (4YCZ6048-060) ................................................... BAYDMPR102A[ ]0-25% Manual Fresh Air Damper (4YCZ6036A) 1. .............................................................. BAYOSAH001A[ ]0-25% Manual Fresh Air Damper (4YCZ6048-60A) 1. ......................................................... BAYOSAH002A[ ]16" Round Duct Adapter (2 per box) (4YCZ6036A) 6 ......................................................... BAYSQRD001A[ ]18" Round Duct Adapter (2 per box) (4YCZ6036-60A) 6 .................................................... BAYSQRD002A[ ]0-100% Mod Economizer w/Baro. Relief (4YCZ6036A) 124 ........................................... BAYECON103A[ ]0-100% Mod. Economizer w/Baro. Relief (4YCZ6048-60A) 124. .................................... BAYECON104A[ ]0-100% Horizontal Economizer (4YCZ6036A) 12 . ........................................................... BAYECON203A[ ]0-100% Horizontal Economizer (4YCZ6048-60A) 12 . ...................................................... BAYECON204A[ ]Enthalpy Control for Economizer (solid state). ...................................................................... BAYENTH001A[ ]Remote Potentiometer (All-BAYECON***A) ............................................................................... BAYSTAT023[ ]1"-2" Filter Frame (4YCZ6036A) (20 x 25 filter not included) 1. ........................................... BAYFLTR101B[ ]1"-2" Filter Frame (4YCZ6048-60A) (20 x 20,20X18 filter not included) 1. .......................... BAYFLTR201B[ ]LP Conversion Kit (All 40K, 120K Models) ............................................................................. BAYLPKT100A[ ]LP Conversion Kit (All 64K, 96K Models) ...............................................................................BAYLPKT101A[ ]LP Conversion Kit (All 75K Models) ....................................................................................... BAYLPKT102A[ ]Evaporator Defrost Control (Low Ambient Cooling) Kit 5. ................................................... BAYLOAM011A[ ]Head Pressure Control (Low Ambient Cool) (208/240v) Kit 5. ........................................... BAYLOAM105A[ ]Crankcase Heater Scroll(4YCZ6036,48,60A1/3)(230v) 5. ................................................... BAYCCHT102A[ ]Adapter Curb 4YCZ6036A to BAYCURB030,38 ................................................................. BAYADAP050A[ ]Adapter Curb 4YCZ6036A to BAYCURB033 ...................................................................... BAYADAP051A[ ]Adapter Curb 4YCZ6048-060A to BAYCURB030,38 .......................................................... BAYADAP052A[ ]Adapter Curb 4YCZ6048-060A to BAYCURB033 ............................................................... BAYADAP053A[ ]Adapter Curb 4YCZ6048-060A to BAYCURB034 ............................................................... BAYADAP054A[ ]12" Duct Shroud Covers Horizontal 4YCZ6036-060A7. ..................................................... BAYCOVR112A[ ]18" Duct Shroud Covers Horizontal 4YCZ6036-060A 7. .................................................... BAYCOVR118A[ ]Extreme Condition Mounting Kit - All BAYCURB & BAYADAP ........................................... BAYEXMK001A[ ]Extreme Condition Mounting Kit - All BAYUTIL .................................................................... BAYEXMK002B[ ]Extreme Condition Mounting Kit - All Slab Mounts ............................................................... BAYEXMK003A[ ]Lifting Lug Kit - All models ....................................................................................................... BAYLlFT002B[ ]
NOTES: 1 Must use filter frame when economizer/fresh air kit is used.2 Dry bulb control standard with economizer.3 Ships knocked down.4 Downflow only.5 Low Ambient cooling requires crankcase heater (BAYCCHT----A).6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application.7 BAYCOVR112,118A will not cover BAYSQRD002A applications
5
General Data
11111 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.
22222 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
33333 Convertible to LPG.
44444 This value is approximate. For more precise value, see Unit Nameplate.
55555 Based on U.S. Government Standard Tests.
66666 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendationwith a clean resistance of 0.05" W.C.
77777 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
MODELRATED Volts/PH/HzPerformance Cooling BTUH�BTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEERSound Power Rating [dB(A)]7Performance Heating�Input BTUH - 1st Stage (Natural Gas)Input BTUH - 2nd Stage (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)�POWER CONN.—V/PH/HZMin. Brch. Cir. Ampacity�Fuse Size — Max./Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANT — Charge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHT— Shipping (lbs.) / Net (lbs.)
4YCZ6036A1075A208-230/1/60
3560011752.93
252008301.85
12.0 / 13.6 / 16.6070
562507500079.5
30 / 602 / #33
208-230/1/6026.0
40 / 402-STAGE SCROLL
208-230/1/6016.7 / 82.0SPINE-FIN
2 / 2415.493/8
PLATE FIN4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER23.4
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL10 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L48.0 / 44.5 / 52.0
488 / 392
4YCZ6036A1096A208-230/1/60
3560011752.93
252008301.85
12.0 / 13.6 / 16.6070
720009600080.0
40 / 703 / #37
208-230/1/6026.0
40 / 402-STAGE SCROLL
208-230/1/6016.7 / 82.0SPINE-FIN
2 / 2415.493/8
PLATE FIN4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER23.4
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL10 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L48.0 / 44.5 / 52.0
493 / 397
4YCZ6036A3075A208-230/3/60
3560011752.93
252008301.85
12 / 13.6 / 16.670
562507500079.5
30 / 602 / #33
208-230/3/6019.1
30 / 302-STAGE SCROLL
208-230/3/6011.2 / 58
SPINE-FIN2 / 2415.49
3/8PLATE FIN
4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER23.4
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL10 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L47.86 / 44.5 / 52.03
488/394
6© 2008 Trane
General Data4YCZ6036A3096A
208-230/3/60
3560011752.93
252008301.85
12 / 13.6 / 16.670
7200096000
8040 / 703 / #37
208-230/3/6019.1
30 / 302-STAGE SCROLL
208-230/3/6011.2 / 58
SPINE-FIN2 / 2415.49
3/8PLATE FIN
4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.7
CENTRIFUGAL10 X 3/8
DIRECT / 15SEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L47.86 / 44.5 / 52.03
493 / 397
4YCZ6036A4075A460/3/60
3560011752.93
252008301.85
12.0 / 13.6 / 16.6070
562507500079.0
30 / 602 / #33
460/3/6010.4
15 / 152-STAGE SCROLL
460/3/604.49 / 29.0SPINE-FIN
2 / 2415.493/8
PLATE FIN4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830460/1/600.5 / 0.84
CENTRIFUGAL10 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 3460/3412
460/1/600.4NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L48.0 / 44.5 / 52.0
488 / 392
4YCZ6036A4096A460/3/60
3560011752.93
252008301.85
12.0 / 13.6 / 16.6070
720009600080.0
40 / 703 / #37
460/3/6010.4
15 / 152-STAGE SCROLL
460/3/604.49 / 29.0SPINE-FIN
2 / 2415.493/8
PLATE FIN4 / 153.543/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830460/1/600.5 / 0.84
CENTRIFUGAL10 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1/2 / VARIABLE208-230/1/60
4.3 / 4.3CENTRIFUGAL
DIRECT / 21/45 / 3460/3412
460/1/600.4NO
THROWAWAY4.0
R410A / 6.941/2
H X W X L48.0 / 44.5 / 52.0
493 / 397
MODELRATED Volts/PH/HzPerformance Cooling BTUH�BTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEERSound Power Rating [dB(A)]7Performance Heating�Input BTUH - 1st Stage (Natural Gas)Input BTUH - 2nd Stage (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)�POWER CONN.—V/PH/HZMin. Brch. Cir. Ampacity�Fuse Size — Max./Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANT — Charge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHT— Shipping (lbs.) / Net (lbs.)
11111 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.
22222 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
33333 Convertible to LPG.
44444 This value is approximate. For more precise value, see Unit Nameplate.
55555 Based on U.S. Government Standard Tests.
66666 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendationwith a clean resistance of 0.05" W.C.
77777 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
7
General Data4YCZ6048A1096A
208-230/1/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
720009600080.0
30 / 603 / #37
208-230/1/6034.1
50 / 502-STAGE SCROLL
208-230/1/6021.2 / 96.0SPINE-FIN
2 / 2423.57
3/8PLATE FIN
4 / 155.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
659 / 531
4YCZ6048A1120A208-230/1/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
90000120000
80.040 / 703 / #32
208-230/1/6034.1
50 / 502-STAGE SCROLL
208-230/1/6021.2 / 96.0SPINE-FIN
2 / 2423.573/8
PLATE FIN4 / 15
5.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
665 / 537
4YCZ6048A3096A208-230/3/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
720009600080.0
30 / 603 / #37
208-230/3/6024.5
35 / 352-STAGE SCROLL
208-230/3/6013.5 / 88.0SPINE-FIN
2 / 2423.573/8
PLATE FIN4 / 15
5.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
659 / 531
MODELRATED Volts/PH/HzPerformance Cooling BTUH�BTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEERSound Power Rating [dB(A)]7Performance Heating�Input BTUH - 1st Stage (Natural Gas)Input BTUH - 2nd Stage (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)�POWER CONN.—V/PH/HZMin. Brch. Cir. Ampacity�Fuse Size — Max./Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANT — Charge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHT— Shipping (lbs.) / Net (lbs.)
11111 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.
22222 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
33333 Convertible to LPG.
44444 This value is approximate. For more precise value, see Unit Nameplate.
55555 Based on U.S. Government Standard Tests.
66666 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendationwith a clean resistance of 0.05" W.C.
77777 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
8© 2008 Trane
4YCZ6048A4120A460/3/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
90000120000
80.040 / 703 / #32
460/3/6015.3
20 / 202-STAGE SCROLL
460/3/606.41 / 41.0SPINE-FIN
2 / 2423.573/8
PLATE FIN4 / 15
5.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830460/1/600.5 / 0.84
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 3460/3412
460/1/600.4NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
665 / 537
4YCZ6048A4096A460/3/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
720009600080.0
30 / 603 / #37
460/3/6015.3
20 / 202-STAGE SCROLL
460/3/606.41 / 41.0SPINE-FIN
2 / 2423.57
3/8PLATE FIN
4 / 155.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830460/1/600.5 / 0.84
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 3460/3412
460/1/600.4NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
659 / 531
General DataMODELRATED Volts/PH/HzPerformance Cooling BTUH�BTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEERSound Rating No.�Performance Heating�Input BTUH - 1st Stage (Natural Gas)�Input BTUH - 2nd Stage (Natural Gas)�AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)�POWER CONN.—V/PH/HZMin. Brch. Cir. Ampacity�Fuse Size — Max./Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANT — Charge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHT— Shipping (lbs.) / Net (lbs.)
4YCZ6048A3120A208-230/3/60
4800015204.0
3480011202.58
12.0 / 13.48 / 16.0071
90000120000
80.040 / 703 / #32
208-230/3/6024.5
35 / 352-STAGE SCROLL
208-230/3/6013.5 / 88.0SPINE-FIN
2 / 2423.573/8
PLATE FIN4 / 15
5.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/6 / 830
208-230/1/600.9 / 1.65
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
3/4 / VARIABLE208-230/1/60
6.8 / 6.8CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY5.3
R410A / 8.51/2
H X W X L52.00 / 47.0 / 62.0
665 / 537
11111 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.Standard 270.
22222 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
33333 Convertible to LPG.
44444 This value is approximate. For more precise value, see Unit Nameplate.
55555 Based on U.S. Government Standard Tests.
66666 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendationwith a clean resistance of 0.05" W.C.
9
General DataMODELRATED Volts/PH/HzPerformance Cooling BTUH�BTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEERSound Rating No.�Performance Heating�Input BTUH - 1st Stage (Natural Gas)�Input BTUH - 2nd Stage (Natural Gas)�AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)�POWER CONN.—V/PH/HZMin. Brch. Cir. Ampacity�Fuse Size — Max./Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.�Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)�REFRIGERANT — Charge (lbs.)�GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHT— Shipping (lbs.) / Net (lbs.)
4YCZ6060A1120A208-230/1/60
5750019505.0
4050013253.2
11.4 / 12.65 / 15.1073
90000120000
80.030 / 603 / #32
208-230/1/6037.1
60 / 602-STAGE SCROLL
208-230/1/6023.0 / 118.0SPINE-FIN
2 / 2423.57
3/8PLATE FIN
4 / 155.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/4 / 830
208-230/1/601.4 / 3.37
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1 / VARIABLE208-230/1/60
6.9 / 6.9CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY6.7
R410A / 9.01/2
H X W X L52.00 / 47.0 / 62.0
676 / 548
4YCZ6060A3120A208-230/3/60
5750019505.0
4050013253.2
11.4 / 12.65 / 15.1073
90000120000
80.030 / 603 / #32
208-230/3/6030.3
45 / 452-STAGE SCROLL
208-230/3/6017.6 / 123.0SPINE-FIN
2 / 2423.57
3/8PLATE FIN
4 / 155.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/4 / 830
208-230/1/601.4 / 3.37
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1 / VARIABLE208-230/1/60
6.9 / 6.9CENTRIFUGAL
DIRECT / 21/45 / 2800/1500
208-230/1/600.34NO
THROWAWAY6.7
R410A / 9.01/2
H X W X L52.00 / 47.0 / 62.0
676 / 548
4YCZ6060A4120A460/3/60
5750019505.0
4050013253.2
11.4 / 12.65 / 15.1073
90000120000
80.030 / 603 / #32
460/3/6019.2
25 / 252-STAGE SCROLL
460/3/609.23 / 62.0SPINE-FIN
2 / 2423.573/8
PLATE FIN4 / 15
5.03/8
EXPANSION VALVE3/4 FEMALE NPT
PROPELLER28.2
DIRECT / 11/4 / 830460/1/600.7 / 1.68
CENTRIFUGAL11 X 10
DIRECT / VARIABLESEE FAN PERFORMANCE TABLE
1 / VARIABLE208-230/1/60
6.9 / 6.9CENTRIFUGAL
DIRECT / 21/45 / 3460/3412
460/1/600.4NO
THROWAWAY6.7
R410A / 9.01/2
H X W X L52.00 / 47.0 / 62.0
676 / 548
11111 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.Standard 270.
22222 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
33333 Convertible to LPG.
44444 This value is approximate. For more precise value, see Unit Nameplate.
55555 Based on U.S. Government Standard Tests.
66666 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendationwith a clean resistance of 0.05" W.C.
10© 2008 Trane
Performance Data CoolingHIGH STAGE: 4YCZ6036A AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTALAMB WB CAP 72 75 78 80 KW
85
59 33.9 28.7 32.4 33.9 33.9 2.763 35.3 23.2 26.9 30.5 33.0 2.767 38.1 18.2 21.9 25.5 27.9 2.771 41.1 13.2 16.8 20.4 22.9 2.7
95
59 31.8 27.8 31.4 31.8 31.8 2.963 33.2 22.4 26.0 29.6 32.0 2.967 35.7 17.3 21.0 24.6 27.0 3.071 38.6 12.3 15.9 19.6 22.0 3.0
105
59 29.7 26.9 29.7 29.7 29.7 3.263 31.0 21.5 25.1 28.7 31.0 3.267 33.4 16.5 20.1 23.8 26.2 3.271 36.1 11.4 15.1 18.7 21.1 3.2
115
59 27.7 26.0 27.7 27.7 27.7 3.463 28.8 20.6 24.3 27.9 28.8 3.467 31.1 15.6 19.2 22.9 25.3 3.571 33.6 10.6 14.2 17.9 20.3 3.5
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 1050 0.97 0.98HIGH 1350 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1175 35600 16.60 12.00
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
LOW STAGE: 4YCZ6036A AT 900 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
75
59 25.3 21.5 24.1 25.3 25.3 1.363 26.3 17.4 20.1 22.8 24.6 1.367 28.4 13.7 16.4 19.1 20.9 1.371 30.6 10.0 12.7 15.4 17.2 1.3
85
59 23.4 20.6 23.3 23.4 23.4 1.563 24.4 16.6 19.3 22.0 23.8 1.567 26.3 13.0 15.7 18.3 20.1 1.571 28.4 9.3 12.0 14.6 16.4 1.5
90
59 22.5 20.2 22.5 22.5 22.5 1.663 23.4 16.3 19.0 21.6 23.4 1.667 25.3 12.6 15.3 17.9 19.7 1.771 27.3 8.9 11.6 14.2 16.0 1.7
95
59 21.6 19.8 21.6 21.6 21.6 1.763 22.5 15.9 18.6 21.2 22.5 1.767 24.2 12.2 14.9 17.6 19.3 1.871 26.1 8.5 11.2 13.9 15.6 1.8
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 790 0.97 0.98HIGH 1010 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER830 25286 16.60 13.62
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
HIGH STAGE: 4YCZ6048A AT 1600 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
85
59 45.8 38.6 43.4 45.8 45.8 3.663 47.7 31.3 36.1 41.0 44.2 3.667 51.4 24.6 29.4 34.2 37.5 3.771 55.5 17.8 22.7 27.5 30.8 3.7
95
59 43.0 37.3 42.2 43.0 43.0 3.963 44.9 30.1 35.0 39.8 43.0 3.967 48.3 23.4 28.3 33.1 36.3 4.071 52.2 16.7 21.5 26.4 29.6 4.0
105
59 40.3 36.1 40.3 40.3 40.3 4.263 42.0 28.9 33.8 38.6 41.9 4.367 45.3 22.2 27.1 31.9 35.2 4.371 48.9 15.6 20.4 25.3 28.5 4.3
115
59 37.5 34.9 37.5 37.5 37.5 4.663 39.1 27.8 32.6 37.5 39.1 4.667 42.2 21.1 26.0 30.8 34.0 4.771 45.5 14.4 19.3 24.1 27.4 4.7
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 1400 0.97 0.98HIGH 1800 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1540 48000 16.00 12.00
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
11
LOW STAGE: 4YCZ6048A AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
75
59 34.4 29.3 32.9 34.4 34.4 1.863 35.9 23.8 27.4 31.1 33.5 1.867 38.7 18.8 22.4 26.0 28.5 1.971 41.7 13.7 17.4 21.0 23.4 1.9
85
59 32.1 28.2 31.8 32.1 32.1 2.163 33.5 22.8 26.4 30.1 32.5 2.167 36.1 17.8 21.4 25.1 27.5 2.271 38.9 12.8 16.4 20.0 22.5 2.2
90
59 31.0 27.7 31.0 31.0 31.0 2.363 32.3 22.3 25.9 29.6 32.0 2.367 34.8 17.3 21.0 24.6 27.0 2.371 37.5 12.3 15.9 19.6 22.0 2.3
95
59 29.8 27.2 29.8 29.8 29.8 2.463 31.1 21.8 25.4 29.1 31.1 2.467 33.5 16.9 20.5 24.1 26.5 2.571 36.1 11.8 15.5 19.1 21.5 2.5
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 1050 0.97 0.98HIGH 1350 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1120 34866 16.00 13.53
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
HIGH STAGE: 4YCZ6060A AT 2000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
85
59 54.7 47.2 53.4 54.7 54.7 4.563 57.0 37.9 44.1 50.3 54.4 4.567 61.4 29.4 35.6 41.7 45.9 4.671 66.3 20.8 27.0 33.2 37.3 4.6
95
59 51.5 45.8 51.5 51.5 51.5 4.963 53.7 36.6 42.8 48.9 53.0 5.067 57.8 28.1 34.3 40.4 44.5 5.171 62.4 19.5 25.7 31.9 36.0 5.1
105
59 48.3 44.4 48.3 48.3 48.3 5.463 50.3 35.3 41.5 47.6 50.3 5.467 54.2 26.7 32.9 39.1 43.2 5.571 58.6 18.2 24.3 30.5 34.6 5.5
115
59 45.1 43.0 45.1 45.1 45.1 5.863 47.0 33.9 40.1 46.2 47.0 5.967 50.7 25.4 31.6 37.8 41.9 6.071 54.7 16.9 23.1 29.3 33.4 6.0
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 1750 0.97 0.98HIGH 2250 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1940 57500 15.10 11.40
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
LOW STAGE: 4YCZ6060A AT 1500 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
75
59 40.3 35.6 40.2 40.3 40.3 2.363 42.1 28.7 33.4 38.0 41.0 2.367 45.3 22.4 27.0 31.6 34.7 2.371 48.9 16.0 20.6 25.3 28.3 2.3
85
59 37.6 34.4 37.6 37.6 37.6 2.663 39.2 27.6 32.2 36.8 39.2 2.667 42.3 21.3 25.9 30.5 33.6 2.771 45.6 14.9 19.5 24.1 27.2 2.7
90
59 36.3 33.8 36.3 36.3 36.3 2.863 37.8 27.0 31.7 36.2 37.8 2.867 40.7 20.7 25.3 29.9 33.0 2.971 44.0 14.3 19.0 23.6 26.7 2.9
95
59 34.9 33.3 34.9 34.9 34.9 3.063 36.4 26.5 31.1 35.7 36.4 3.067 39.2 20.1 24.8 29.4 32.5 3.171 42.3 13.8 18.4 23.0 26.1 3.1
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIER
LOW 1310 0.97 0.98HIGH 1680 1.03 1.02
ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1330 40894 15.10 12.68
ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°FWB air entering indoor coil, 95°F DB air entering outdoor coil. (B) HighTemperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB airentering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heatingis the same as for cooling.
Performance Data Cooling
12© 2008 Trane
Indoor Blower PerformanceIndoor Fan Performance 4YCZ6036A
Indoor Fan Performance 4YCZ6048A
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Low - 741 743 744 744 743 742 740 737 - -High - 1059 1062 1063 1063 1062 1059 1057 1053 - -Low - 825 837 843 844 844 842 839 836 - -High - 1179 1196 1204 1206 1205 1203 1199 1194 - -Low - 976 964 959 957 953 949 945 945 - -High - 1394 1377 1371 1367 1362 1355 1350 1350 - -
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Low - 722 745 747 744 742 743 744 736 - -High - 1032 1064 1068 1063 1060 1062 1063 1052 - -Low - 830 841 842 840 839 838 836 828 - -High - 1186 1201 1203 1201 1198 1197 1194 1184 - -Low - 978 965 964 963 958 948 941 949 - -High - 1397 1378 1377 1376 1368 1354 1344 1356 - -
External Static Pressure (in. wg)
External Static Pressure (in. wg)Down Flow
350 CFM/Ton Setting
400 CFM/Ton Setting
450 CFM/Ton Setting
Horizontal
350 CFM/Ton Setting
400 CFM/Ton Setting
450 CFM/Ton Setting
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0Low - 954 973 977 973 966 957 950 944 - -High - 1363 1390 1396 1390 1379 1368 1358 1349 - -Low - 1121 1106 1104 1106 1108 1108 1104 1097 - -High - 1601 1580 1577 1580 1583 1583 1577 1567 - -Low - 1223 1254 1268 1271 1268 1264 1261 1258 - -High - 1747 1792 1811 1816 1812 1806 1801 1797 - -
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0Low - 948 977 977 970 969 975 979 962 - -High - 1354 1396 1396 1386 1384 1393 1399 1375 - -Low - 1102 1106 1109 1113 1116 1119 1120 1118 - -High - 1574 1580 1585 1589 1594 1599 1601 1597 - -Low - 1295 1277 1272 1273 1274 1273 1272 1273 - -High - 1851 1824 1817 1818 1820 1819 1817 1819 - -
350 CFM/Ton Setting
400 CFM/Ton Setting
450 CFM/Ton Setting
External Static Pressure (in. wg)
External Static Pressure (in. wg)
Horizontal
Down Flow
350 CFM/Ton Setting
400 CFM/Ton Setting
450 CFM/Ton Setting
Indoor Fan Performance 4YCZ6060A
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0Low 1163 1238 1259 1256 1246 1240 1237 1230High - 1662 1768 1799 1794 1780 1771 1767 1757 - -Low 1443 1427 1422 1422 1423 1422 1418 1410High - 2062 2038 2031 2032 2034 2032 2025 2015 - -
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0Low - 1259 1219 1208 1207 1206 1199 1188 1185 - -High - 1799 1742 1726 1725 1723 1712 1698 1692 - -Low - 1410 1393 1386 1384 1383 1380 1368 1344 - -High - 2015 1990 1980 1977 1976 1971 1955 1920 - -
350 CFM/Ton Setting
400 CFM/Ton Setting
Down Flow
Horizontal External Static Pressure (in. wg)
External Static Pressure (in. wg)
350 CFM/Ton Setting
400 CFM/Ton Setting
13
Indoor Blower PerformanceHeating Airflow, horizontal or downflow from .2 to .6” wg.
Low Stage High Stage7-OFF 8-OFF A 1375 18007-ON 8-OFF B 1450 19007-OFF 8-ON C 1525 19757-ON 8-ON D 1575 2075
* can be 1, 3 or 4
Switch Settings Selection
4YCZ6060*120ANominal Airflow
SelectionLow Stage High Stage
7-OFF 8-OFF A 725 10007-ON 8-OFF B 775 10757-OFF 8-ON C 850 11507-ON 8-ON D 925 1250
SelectionLow Stage High Stage
7-OFF 8-OFF A 825 11007-ON 8-OFF B 875 11757-OFF 8-ON C 950 12757-ON 8-ON D 1025 1375
* can be 1, 3 or 4
4YCZ6036A*075
4YCZ6036A*096Switch Settings Nominal Airflow
Switch Settings Nominal Airflow
* can be 1, 3 or 4
SelectionLow Stage High Stage
7-OFF 8-OFF A 1075 13757-ON 8-OFF B 1100 14507-OFF 8-ON C 1150 15007-ON 8-ON D 1200 1575
SelectionLow Stage High Stage
7-OFF 8-OFF A 1050 15007-ON 8-OFF B 1100 15757-OFF 8-ON C 1150 16257-ON 8-ON D 1200 1700
* can be 1, 3 or 4
Switch Settings
Switch Settings Nominal Airflow4YCZ6048A*096
4YCZ6048A*120Nominal Airflow
* can be 1, 3 or 4
14© 2008 Trane
Typical Field Wiring
15
Typical Wiring
16© 2008 Trane
Typical Wiring
17
Optional Equipment
BAYCURB050A FULL PERIMETER ROOF MOUNTING CURB FOR 4YCZ6036A
46 3/8
17 7/8
3
3 5/8
19 1/2
2 3/16
19 1/2
14
1 1/2
38 7/8
15
35 7/843 3/8
The drawings on this page are prepared by themanufacturer in order to provide detail regardingjob layout only. These drawings are not intended tobe used as a basis to construct, build or modify theitems depicted in the drawings. The manufacturer isnot responsible for the unauthorized use of thesedrawings and expressly disclaims any liability fordamages resulting from such unauthorized use.
18© 2008 Trane
Optional Equipment
BAYCURB051A Full Perimeter Roof Mounting Curb for4YCZ6048-060A
56 1/8
15 7/8
3
10 7/819 1/2
4 3/4
19 1/2
14
41 7/8
20
1 1/2
38 7/8 53 1/8
The drawings on this page are prepared by themanufacturer in order to provide detail regardingjob layout only. These drawings are not intended tobe used as a basis to construct, build or modify theitems depicted in the drawings. The manufacturer isnot responsible for the unauthorized use of thesedrawings and expressly disclaims any liability fordamages resulting from such unauthorized use.
19
Optional Equipment
The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawingsare not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is notresponsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from suchunauthorized use.
BAYFLTR101, 201B, 1" - 2" Filter Rack(Mounts in Filter/Coil Section)
BAYACCDOR1A & BAYACCDOR2A Hinged Filter Access DoorReplaces Filter/Coil Access Panel
Filter
20© 2008 Trane
BAYECON103,104A Down Discharge Economizer and Rain Hood(Mounts Over Horizontal Return Air Opening)
A
B
C D
E
BAYECON203,204A Horizontal Economizer and Rain Hood
ReturnDuctRoofcurb
Reliefdamper
Misteliminator
Economizerrain hood
HVAC Unit
Outside airdampers
Return airdampers
Required filterkit, orderseparately
A
Optional Equipment
The drawings on this page areprepared by the manufacturer inorder to provide detail regarding joblayout only. These drawings are notintended to be used as a basis toconstruct, build or modify the itemsdepicted in the drawings. Themanufacturer is not responsible forthe unauthorized use of thesedrawings and expressly disclaimsany liability for damages resultingfrom such unauthorized use.
Economizer Models A
BAYECON103A4WCZ6036A4DCZ6036A4YCZ6036A
20 1/8"
BAYECON104A4WCZ6048-060A4DCZ6048-060A4YCZ6048-060A
24 3/8"
Economizer A B C D E
BAYECON203AA 22" 20" 16 7/8" 15 11/16 11 11/16
BAYECON204AA 24" 22 21/32" 19" 17 11/16 14 11/16
Economizer
Gaskets (2)
Rain HoodDuct
Mixed Air Sensor
21
BAYOSAH001,002A, 25% Outside Air Damper(Replaces Filter/Coil Access Panel)
Optional Equipment
BAYDMPR101,102A, 25% Motorized Outside Air Damper(Mounts Over Horizontal Return AIr Opening)
D
CB
A
E
Unit ApplicationModels
A B C D E
BAYDMPR101A2/4YC,WC3018-036A
4TC3018-036A4W/T/Y/DCY4024-0600
15 13/16" 11 13/16" 10 1/4" 11 1/2" 12 1/4"
BAYDMPR102A2/4YC,WC3042-060A
4TC3042-060A4W/T/Y/DCY4024-060
18 3/16" 15 1/8" 10 1/4" 11 1/2" 12 1/4"
A
B
CD
FULLYOPEN
2/31/3
FULLYCLOSED
The drawings on this page are preparedby the manufacturer in order to providedetail regarding job layout only. Thesedrawings are not intended to be used asa basis to construct, build or modify theitems depicted in the drawings. Themanufacturer is not responsible for theunauthorized use of these drawings andexpressly disclaims any liability fordamages resulting from such unautho-rized use.
Manual FreshAir Model
Unit ApplicationModels
A B C D
BAYOSAH0012/4YC,WC3018-036A
4TC*3018-036A4W/T/Y/DCY4024-060A
22 7/16" 20 11/16" 12 3/8" 9 3/16"
BAYOSAH0022/4YC,WC3042-060A
4TC*3042-060A4W/T/Y/DCY4024-060
25 3/16" 20 11/16" 12 3/8" 9 3/16"
22© 2008 Trane
Dimensional Data
4YCZ6036A (1 of 3)
23
Dimensional Data
4YCZ6036A (2 of 3)
24© 2008 Trane
4YCZ6036A (3 of 3)
25
Dimensional Data
4YCZ6048A through 4YCZ6060A (1 of 3)
26© 2008 Trane
Dimensional Data
4YCZ6048A through 4YCZ6060A (2 of 3)
27
4YCZ6048A through 4YCZ6060A (3 of 3)
28© 2008 Trane
Mechanical SpecificationsGeneral
All units shall be factory assembled, piped,internally wired and fully charged withrefrigerant. All units shall be designed tooperate at outdoor ambient temperaturesas high as 115°F. Cooling capacities shallbe rated in accordance with A.R.I.standards. The 4YCZ6 heating/cooling unitdesign is UL listed, specifically for outdoorapplications using natural gas or propane.All units shall be designed for outdoorrooftop or ground level installation. Unitcasing is constructed of heavy gauge,galvanized steel and painted with aweather-resistant powder paint.
Shipped for horizontal application,convertible to downflow.
Casings
All panels shall be heavy gauge steel,gasketed and insulated. Foil-facedinsulation shall be in the heat exchangersection. Foil-faced insulation shall be in theevaporator section. Base pan shall beheavy gauge steel. WEATHERGUARD™exterior corrosion resistant screws shall beused for added resistance to rust andcorrosion.
Controls
Refrigeration cycle controls shall includecondenser fan, evaporator fan andcompressor contactors. Compressors shallbe equipped with a combination internalwinding thermostat/current overload.Internal high pressure relief shall also beprovided.
Refrigeration System
Compressors —
The Climatuff® two-stage compressorfeatures internal over temperature andpressure protector, total dipped hermeticmotor. Other features include: roto locksuction and discharge refrigerationconnections, centrifugal oil pump, and lowvibration and noise.
Evaporator Coil — Internally enhanced3/8-inch OD seamless copper tubingmechanically bonded to aluminum fins,factory pressure and leak tested at 250 to300 psig. All units have TXV to controlrefrigeration flow.
Condenser Coil —
The Spine Fin™ condenser coil shall becontinuously wrapped, corrosion resistantall aluminum with minimum brazed joints.This coil is 3/8 inch OD seamless alumi-num tubing glued to a continuous alumi-num fin. Coils are lab tested to withstand2,000 pounds of pressure per square inch.The outdoor coil provides low airflowresistance and efficient heat transfer. Thecoil is protected on all four sides bylouvered panels.
Indoor Air Fan — Direct-drive, forward-curved, centrifugal wheel in a CompositeVortica® Blower housing. Motor shallhave thermal overload protection.Permanently lubricated motor bearings.Motor/blower assembly isolated from unitwith rubber mounts.
Condenser Fan — Direct-drive, drawthrough propeller type. Weather-proofedpermanent split capacitor fan motor shallhave built-in thermal overload andpermanently lubricated motor bearings.
Low Ambient — Standard refrigerantsystem operation down to 55°F. Lowambient accessory required for operationto 0°F ambient condition.
Gas-Fired Heating System — Modelsshall provide completely assembled, wiredand piped gas fired heating systems withinunit. Design certified by UL, specifically foroutdoor application. Threaded gasconnection on the unit.
Electronic Ignition System — Mainburner is lit each time thermostat calls forgas heat. Flame sensor proves flame andkeeps the main burners on. Should a lossof flame occur, the main valve closes andthe spark recurs within 0.8 second. Whenthermostat is satisfied, main burner isextinguished.
Forced Combustion Blower — Insuresflame stability under varying windconditions. Gives higher combustionefficiency and location flexibility.
Heat Exchanger — stainless steeltubes. Free floating design.
Burners — stainless steel. Multi-port inshot.
Accessories(U.S. Domestic Models)
Roof Curb — The roof curb shallbe designed to mate with the unitand provide support and completeweather-tight installation whenproperly installed. Curb shall shipknocked down for field assembly,and include wood nailer strips.
Modulating Economizer — Thisaccessory shall be field installedand be composed of the followingitems: 0-100% fresh air damper,damper drive motor fixed dry bulbenthalpy control, and low voltagepolarized plug for electricalconnections. Solid state enthalpy ordifferential enthalpy control isoptional. Economizer operationsshall be controlled by the presetposition of the enthalpy control. Abarometic relief damper shall bestandard with the economizer andprovide a pressure operateddamper that shall be gravity closingand prohibit entrance of outside airon equipment “off” cycle.
Manual Fresh Air Hood
Manual outside air provides a fixedoutside air quantity from 0 to 25percent. Includes hood andbirdscreen.
Low Ambient Control
Control allows cycling ofcompressor under low ambientcooling conditions. Required forcooling operation to 0°F.
Propane Gas
Conversion Kit — For conversionfrom natural gas to LP gas.
Trane6200 Troup HighwayTyler, TX 75707-9010 The Manufacturer has a policy of continuous product and product data improvement and it reserves the right to
change design and specifications without notice.