Product Data4WCZ6024 through 4WCZ6060 Single Packaged Convertible Heat Pump 16 SEER 2 - 5 Ton

22-1807-11A-EN

Page 2: 22-1807-11A-EN Product Data

2

It's Hard to Stop a Trane.Single Packaged Electric Heat Pump SystemTrane offers a complete family of electric heat pump heating and cooling systems, designed to keep you comfortable all year long, regardless of the weather, while keeping your operating costs as low as possible. A heat pump operates efficiently as both an air conditioner and a heater. In the summer, the heat pump cools your home just like any other air conditioner by pulling the heat from the inside and releasing it outdoors. In the winter, it captures the heat that is always present in the outdoor air and transfers it indoors.

Introducing the new TRANE Single Packaged Electric Heat Pump System.

Single Packaged Electric Heat Pump Systems are easy and versatile to install. Because cooling and heating functions are all contained in a single cabinet, a Trane packaged heat pump system is easy to install and service. It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow in-stallation. When connected to an optional Trane thermostat control and air distribu-tion ducts, you have a highly efficient, total home comfort system.

Single Packaged Electric Heat Pump Systems are unmatched in quality and reliability. All major components on these products, including the compressor, have been designed and manufactured for maximum service. Every Climatuff® com-pressor is designed and manufactured to exacting specifications. Each design is life tested in extreme environments to ensure reliable and long lasting operation in normal applications. Each compressor has internal motor protection for added reliability.

Page 3: 22-1807-11A-EN Product Data

3

Contents

Optional Equipment Listing 4

General Data 5

Indoor Blower Performance 9

Typical Wiring 12

Optional Equipment 28

33

Mechanical Specifications 39

Dimensional Data and Weights

Page 4: 22-1807-11A-EN Product Data

4

Optional EquipmentOPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [✓] indicates accessories included)

Hinged Filter Access Door (4WCZ6024-036) ⑩ ................................................................. BAYACCDOR1A[ ]Hinged Filter Access Door (4WCZ6048-060) ⑩ ................................................................. BAYACCDOR2A[ ]Roof Curb Full Perimeter (4WCZ6024-036) ③ .....................................................................BAYCURB050A[ ]Roof Curb Full Perimeter (4WCZ6048-060) ③ .....................................................................BAYCURB051A[ ]Roof Curb Utility Extension Kit (BAYCURB050A) ......................................................................BAYUTIL101B[ ]Roof Curb Utility Extension Kit (BAYCURB051A) ......................................................................BAYUTIL102B[ ]0-25% Motorized Outside Air Damper (4WCZ6024-036) .....................................................BAYDMPR101A[ ]0-25% Motorized Outside Air Damper (4WCZ6048-060) .....................................................BAYDMPR102A[ ]Outside Air Control for V.S. Economizer (4WCZ6024-060) ...................................................BAYOSAC001B[ ]0-25% Manual Fresh Air Damper (4WCZ6024-036) ①⑨. .....................................................BAYOSAH001A[ ]0-25% Manual Fresh Air Damper (4WCZ6048-060) ①⑨. .....................................................BAYOSAH002A[ ]16" Round Duct Adapter (2 per box) (4WCZ6024-036) ⑥ ................................................... BAYSQRD001A[ ]18" Round Duct Adapter (2 per box) (4WCZ6024-060) ⑥ ................................................... BAYSQRD002A[ ]0-100% Mod Economizer w/Baro. Relief (4WCZ6024-036) ①②④ ...................................... BAYECON103A[ ]0-100% Mod. Economizer w/Baro. Relief (4WCZ6048-060) ①②④. ..................................... BAYECON104A[ ]0-100% Horizontal Economizer (4WCZ6024-036) ①② . ...................................................... BAYECON203A[ ]0-100% Horizontal Economizer (4WCZ6048-060) ①② . ...................................................... BAYECON204A[ ]Economizer Relay Kit (required for Heat Pump applications) ..................................................BAYRLAY006A[ ] Enthalpy Control for Economizer (solid state). ........................................................................BAYENTH001A[ ]Remote Potentiometer (All-BAYECON***A) ...............................................................................BAYSTAT023[ ]1"-2" Filter Frame (4WCZ6024-036) (20 x 25 filter not included) ①. ....................................... BAYFLTR101B[ ]1"-2" Filter Frame (4WCZ6048-060) (20 x 20,20X18 filter not included) ①. ............................ BAYFLTR201B[ ]Evaporator Defrost Control (Low Ambient Cooling) Kit ⑤. .....................................................BAYLOAM011A[ ]Head Pressure Control (Low Ambient Cool) (208/240v) Kit ⑤ ..............................................BAYLOAM105A[ ] Crankcase Heater Scroll (4WCZ6048-060 1/3,060 1/3)(230v) ⑤. .........................................BAYCCHT102A[ ]Crankcase Heater Scroll (4WCZ6024-036)(230v) ⑤. ............................................................BAYCCHT103A[ ]Crankcase Heater Scroll (4WCZ6048, 060)(460v) ⑤. ...........................................................BAYCCHT404B[ ]Crankcase Heater Scroll (4WCZ6036)(460v) ⑤. ...................................................................BAYCCHT405A[ ]Adapter Curb 4WCZ6024-036 to BAYCURB030,38 .............................................................. BAYADAP050A[ ] Adapter Curb 4WCZ6024-036 to BAYCURB033 ................................................................... BAYADAP051A[ ] Adapter Curb 4WCZ6048-060A to BAYCURB030,38 ........................................................... BAYADAP052A[ ] Adapter Curb 4WCZ6048-060A to BAYCURB033 ................................................................ BAYADAP053A[ ] Adapter Curb 4WCZ6048-060A to BAYCURB034 ................................................................ BAYADAP054A[ ]12" Duct Shroud Covers Horizontal 4WCZ6024-060 ⑦. ........................................................BAYCOVR112A[ ]18" Duct Shroud Covers Horizontal 4WCZ6024-060 ⑦. ........................................................BAYCOVR118A[ ] Extreme Condition Mounting Kit - All BAYCURB & BAYADAP ...............................................BAYEXMK001A[ ]Extreme Condition Mounting Kit - All BAYUTIL ......................................................................BAYEXMK002A[ ] Extreme Condition Mounting Kit - All Slab Mounts .................................................................BAYEXMK003A[ ]Lifting Lug Kit BAYLlFT002B[ ]

NOTES: ① Must use internal filter frame when economizer or fresh air kit is used. ② Dry bulb control standard with economizer. ③ Ships knocked down. ④ Downflow only. ⑤ Low Ambient cooling requires crankcase heater (BAYCCHT----A). ⑥ It is the responsibility of the installing dealer to properly size the ductwork for each specific application. ⑦ BAYCOVR112,118A will not cover BAYSQRD002A applications. ⑧ BAYOSAH001A and BAYOSAH002A are not compatible with BAYACCDOR1A or BAYACCDOR2A. ⑨ BAYACCDOR1A requires BAYFLTR101B & BAYACCDOR2A requires BAYFLTR201B. They are not backward compatible to BAYFLTR101/201A.

Page 5: 22-1807-11A-EN Product Data

5

General DataMODELRATED Volts/PH/HzPerformance CoolingBTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEER Sound Power Rating [dB(A)] ②Performance Heating①(High Temp.)BTUH / COP (High)Power Input (KW)(Low Temp.) BTUH / COP (High)Power Input (KW)(High Temp.)BTUH / COP (Low)Power Input (KW)(Low Temp.) BTUH / COP (Low)Power Input (KW)HSPF (BTU / Watt-Hr.)⑥POWER CONN.—V/Ph/HzMin. Brch. Cir. Ampacity③Fuse Size — Max. / Recmd. (amps) COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlINDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.④Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.⑤Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)⑦REFRIGERANT / Charge (lbs.)DIMENSIONSCrated (in.)WEIGHT / Shipping / Net (lbs.)

4WCZ6024A1000A208-230/1/60

240008001.84

203006201.1

12.0/18.4/16.066.8

20200 / 3.60

1.6811300 / 2.17

1.5315100 / 3.44

1.298300 / 1.96

1.248.2

208-230/1/6019.5

30 / 302-STAGE SCROLL

208-230/1/6011.7 / 58.3SPINE-FIN

2 / 2415.493/8

EXPANSION VALVEPLATE FIN

4 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23.4

DIRECT / 12550

1/12 / 810208-230/1/60

0.54 / 0.82CENTRIFUGAL

10 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1/2 / VARIABLE208-230/1/60

4.3 / 4.3NO

THROWAWAY4.0

R410A / 8.06H X W X L48 / 45 / 52442 / 372

① Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on AHRI Standard 210/240.

② Sound Power values are not adjusted for AHRI 270-95 tonal corrections.

③ Calculated in accordance with currently prevailing Nat'l Electrical Code.

④ Standard Air — Dry Coil — Outdoor.

⑤ Standard Air — Wet Coil — Indoor.

⑥ Rated in accordance with D.O.E. test procedure.

⑦ Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recom-mendations with clean resistance of 0.05" W.C.

Page 6: 22-1807-11A-EN Product Data

6

MODELRATED Volts/PH/HzPerformance CoolingBTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEER Sound Power Rating [dB(A)]②Performance Heating①(High Temp.)BTUH / COP (High)Power Input (KW)(Low Temp.) BTUH / COP (High)Power Input (KW)(High Temp.)BTUH / COP (Low)Power Input (KW)(Low Temp.) BTUH / COP (Low)Power Input (KW)HSPF (BTU / Watt-Hr.)⑥POWER CONN.—V/Ph/HzMin. Brch. Cir. Ampacity③Fuse Size — Max. / Recmd. (amps) COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlINDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.④Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.⑤Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)⑦REFRIGERANT / Charge (lbs.)DIMENSIONSCrated (in.)WEIGHT / Shipping / Net (lbs.)

① Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

② Sound Power values are not adjusted for ARI 270-95 tonal corrections.

③ Calculated in accordance with currently prevailing Nat'l Electrical Code.

④ Standard Air — Dry Coil — Outdoor.

⑤ Standard Air — Wet Coil — Indoor.

⑥ Rated in accordance with D.O.E. test procedure.

⑦ Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendations with clean resistance of 0.05" W.C.

4WCZ6036B1000A208-230/1/60

3600011252.89

288008251.65

12.2 / 17.45 / 1670

31000 / 3.432.65

19200 / 2.302.45

22400 / 3.431.92

12000 / 1.891.868.3

208-230/1/6024.3

35 / 352-STAGE SCROLL

208-230/1/6015.3 / 83

SPINE-FIN2 / 2415.493/8

EXPANSION VALVEPLATE FIN

4 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23.4

DIRECT / 13020

1/6 / 830208-230/1/60

0.9 / 1.65CENTRIFUGAL

10 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1/2 / VARIABLE208-230/1/60

4.3 / 4.3NO

THROWAWAY4.0

R410A / 7.8H X W X L

47.86 / 44.5 / 52.03468 / 372

4WCZ6036B3000A208-230/3/60

3600011252.89

288008251.65

12.2 / 17.45 / 1670

31000 / 3.432.65

19200 / 2.302.45

22400 / 3.431.92

12000 / 1.891.868.3

208-230/3/6019.7

30 / 302-STAGE SCROLL

208-230/3/6011.6 / 73

SPINE-FIN2 / 2415.493/8

EXPANSION VALVEPLATE FIN

4 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23.4

DIRECT / 13020

1/6 / 830208-230/1/60

0.9 / 1.65CENTRIFUGAL

10 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1/2 / VARIABLE208-230/1/60

4.3 / 4.3NO

THROWAWAY4.0

R410A / 7.8H X W X L

47.86 / 44.5 / 52.03468 / 372

4WCZ6036B4000A460/3/60

3600011252.89

288008251.65

12.2 / 17.45 / 1670

31000 / 3.432.65

19200 / 2.302.45

22400 / 3.431.92

12000 / 1.891.868.3

460/3/6011.9

15 / 15SCROLL460/3/605.7 / 38

SPINE-FIN2 / 2415.493/8

EXPANSION VALVEPLATE FIN

4 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23.4

DIRECT / 13020

1/6 / 830460/1/600.5 / 0.84

CENTRIFUGAL10 X 10

DIRECT / VARIABLESEE FAN PERFORMANCE TABLE

1/2 / VARIABLE208-230/1/60

4.3 / 4.3NO

THROWAWAY4.0

R410A / 7.8H X W X L

47.86 / 44.5 / 52.03468 / 372

General Data

Page 7: 22-1807-11A-EN Product Data

7

4WCZ6036B4000A460/3/60

3600011252.89

288008251.65

12.2 / 17.45 / 1670

31000 / 3.432.65

19200 / 2.302.45

22400 / 3.431.92

12000 / 1.891.868.3

460/3/6011.9

15 / 15SCROLL460/3/605.7 / 38

SPINE-FIN2 / 2415.493/8

EXPANSION VALVEPLATE FIN

4 / 153.543/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER23.4

DIRECT / 13020

1/6 / 830460/1/600.5 / 0.84

CENTRIFUGAL10 X 10

DIRECT / VARIABLESEE FAN PERFORMANCE TABLE

1/2 / VARIABLE208-230/1/60

4.3 / 4.3NO

THROWAWAY4.0

R410A / 7.8H X W X L

47.86 / 44.5 / 52.03468 / 372

MODELRATED Volts/PH/HzPerformance CoolingBTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEER Sound Power Rating [dB(A)]Performance Heating(High Temp.)BTUH / COP (High)Power Input (KW)(Low Temp.) BTUH / COP (High)Power Input (KW)(High Temp.)BTUH / COP (Low)Power Input (KW)(Low Temp.) BTUH / COP (Low)Power Input (KW)HSPF (BTU / Watt-Hr.)POWER CONN.—V/Ph/HzMin. Brch. Cir. AmpacityFuse Size — Max. / Recmd. (amps) COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlINDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANT / Charge (lbs.)DIMENSIONSCrated (in.)WEIGHT / Shipping / Net (lbs.)

① Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

② Sound Power values are not adjusted for ARI 270-95 tonal corrections.

③ Calculated in accordance with currently prevailing Nat'l Electrical Code.

④ Standard Air — Dry Coil — Outdoor.

⑤ Standard Air — Wet Coil — Indoor.

⑥ Rated in accordance with D.O.E. test procedure.

⑦ Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendations with clean resistance of 0.05" W.C.

General Data4WCZ6048B1000A

208-230/1/60

4750015753.42

3900011502.22

12.0 / 17.5 / 16.072

42000 / 3.833.32

23200 / 2.272.99

31200 / 3.772.4

17000 / 2.122.328.5

208-230/1/6034.2

50 / 502-STAGE SCROLL

208-230/1/6021.2 / 104.0SPINE-FIN

2 / 2423.573/8

EXPANSION VALVEPLATE FIN

4 / 155.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14220

1/6 / 830208-230/1/60

0.9 / 1.65CENTRIFUGAL

10 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE3/4 / VARIABLE208-230/1/60

6.8 / 6.8NO

THROWAWAY5.3

R410A / 8.8H X W X L

52.0 / 47.0 / 62.0607 / 479

4WCZ6048B3000A208-230/3/60

4750015753.42

3900011502.22

12.0 / 17.5 / 16.072

42000 / 3.833.32

23200 / 2.272.99

31200 / 3.772.4

17000 / 2.122.328.5

208-230/3/6025.2

35 / 352-STAGE SCROLL

208-230/3/6014 / 83.1

SPINE-FIN2 / 2423.57

3/8EXPANSION VALVE

PLATE FIN4 / 15

5.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14220

1/6 / 830208-230/1/60

0.9 / 1.65CENTRIFUGAL

10 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE3/4 / VARIABLE208-230/1/60

6.8 / 6.8NO

THROWAWAY5.3

R410A / 8.8H X W X L

52.0 / 47.0 / 62.0607 / 479

4WCZ6048B4000A460/3/60

4750015753.42

3900011502.22

12.0 / 17.5 / 16.072

42000 / 3.833.32

23200 / 2.272.99

31200 / 3.772.4

17000 / 2.122.328.5

460/3/6015.3

20 / 202-STAGE SCROLL

460/3/606.4 / 41.0

SPINE-FIN2 / 2423.573/8

EXPANSION VALVEPLATE FIN

4 / 155.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14220

1/6 / 830460/1/600.5 / 0.84

CENTRIFUGAL10 X 10

DIRECT / VARIABLESEE FAN PERFORMANCE TABLE

3/4 / VARIABLE208-230/1/60

6.8 / 6.8NO

THROWAWAY5.3

R410A / 8.8H X W X L

52.0 / 47.0 / 62.0607 / 479

Page 8: 22-1807-11A-EN Product Data

8

MODELRATED Volts/PH/HzPerformance CoolingBTUH (High)Indoor Airflow (CFM)Power Input (KW)BTUH (Low)Indoor Airflow (CFM)Power Input (KW)EER - HI / LOW / SEER Sound Power Rating [dB(A)]Performance Heating(High Temp.)BTUH / COP (High)Power Input (KW)(Low Temp.) BTUH / COP (High)Power Input (KW)(High Temp.)BTUH / COP (Low)Power Input (KW)(Low Temp.) BTUH / COP (Low)Power Input (KW)HSPF (BTU / Watt-Hr.)POWER CONN.—V/Ph/HzMin. Brch. Cir. AmpacityFuse Size — Max. / Recmd. (amps) COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlINDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANT / Charge (lbs.)DIMENSIONSCrated (in.)WEIGHT / Shipping / Net (lbs.)

① Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

② Sound Power values are not adjusted for ARI 270-95 tonal corrections.

③ Calculated in accordance with currently prevailing Nat'l Electrical Code.

④ Standard Air — Dry Coil — Outdoor.

⑤ Standard Air — Wet Coil — Indoor.

⑥ Rated in accordance with D.O.E. test procedure.

⑦ Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendations with clean resistance of 0.05" W.C.

General Data4WCZ6060B1000A

208-230/1/60

5700017804.97

4450012502.79

11.5 / 15.9 / 15.074

53500 / 3.54.45

34000 / 2.463.99

37000 / 3.433.19

19000 / 1.813.028.3

208-230/1/6042.0

60 / 602-STAGE SCROLL

208-230/1/6027.1 / 152.9SPINE-FIN

2 / 2423.573/8

EXPANSION VALVEPLATE FIN

4 / 155.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14700

1/4 / 830208-230/1/60

1.4 / 3.4CENTRIFUGAL

11 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1 / VARIABLE208-230/1/60

6.9 / 6.9NO

THROWAWAY5.3

R410A / 9.8H X W X L

52.0 / 47.0 / 62.0623 / 495

4WCZ6060B3000A208-230/3/60

5700017804.97

4450012502.79

11.5 / 15.9 / 15.074

53500 / 3.54.45

34000 / 2.463.99

37000 / 3.433.19

19000 / 1.813.028.3

208-230/3/6030.0

45 / 452-STAGE SCROLL

208-230/3/6016.5 / 110.0SPINE-FIN

2 / 2423.573/8

EXPANSION VALVEPLATE FIN

4 / 155.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14700

1/4 / 830208-230/1/60

1.4 / 3.4CENTRIFUGAL

11 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1 / VARIABLE208-230/1/60

6.9 / 6.9NO

THROWAWAY5.3

R410A / 9.8H X W X L

52.0 / 47.0 / 62.0623 / 495

4WCZ6060B4000A460/3/60

5700017804.97

4450012502.79

11.5 / 15.9 / 15.074

53500 / 3.54.45

34000 / 2.463.99

37000 / 3.433.19

19000 / 1.813.028.3

460/3/6017

20 / 202-STAGE SCROLL

460/3/607.2 / 52

SPINE-FIN2 / 2423.57

3/8EXPANSION VALVE

PLATE FIN4 / 15

5.03/8

EXPANSION VALVE3/4 FEMALE NPT

PROPELLER28.2

DIRECT / 14700

1/4 / 830208-230/1/60

1.4 / 3.4CENTRIFUGAL

11 X 10DIRECT / VARIABLE

SEE FAN PERFORMANCE TABLE1 / VARIABLE208-230/1/60

6.9 / 6.9NO

THROWAWAY5.3

R410A / 9.8H X W X L

52.0 / 47.0 / 62.0623 / 495

Page 9: 22-1807-11A-EN Product Data

9

Indoor Blower PerformanceIndoor Fan Performance 4WCZ6024

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9Low 590 583 575 571 566 546 525 507 488High 721 724 727 717 706 701 695 678 660Low 627 624 621 615 608 593 578 559 540High 801 806 811 806 800 789 777 745 712Low 672 673 673 664 654 648 641 620 599High 880 888 895 894 893 883 872 817 761

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9Low 601 588 571 562 563 549 525 517 504High 734 731 722 706 702 706 695 692 681Low 638 622 619 617 613 600 588 575 554High 815 803 808 808 807 798 791 766 731Low 676 676 678 668 656 646 642 641 632High 885 892 902 900 896 881 874 844 803

350 CFM/Ton Se�ng

400 CFM/Ton Se�ng

450 CFM/Ton Se�ng

HorizontalExternal Sta�c Pressure (in. wg)

350 CFM/Ton Se�ng

400 CFM/Ton Se�ng

450 CFM/Ton Se�ng

Down FlowExternal Sta�c Pressure (in. wg)

Indoor Fan Performance 4WCZ6036

Page 10: 22-1807-11A-EN Product Data

10

Indoor Fan Performance 4WCZ6048

Indoor Fan Performance 4WCZ6060

Indoor Blower Performance

Indoor Blower Performance

4WCZ6024 AIRFLOW WITH AUXILIARY HEAT (CFM)

SWITCH SETTINGS SELECTION NOMINAL AIRFLOW

7-OFF 8-OFF LOW 700 CFM

7-ON 8-OFF HIGH 800 CFM

7-OFF 8-ON HIGH 800 CFM

7-ON 8-ON HIGH 800 CFM

Page 11: 22-1807-11A-EN Product Data

11

SWITCH SETTINGS SELECTION NOMINAL AIRFLOW

7-OFF 8-OFF LOW 1400 CFM

7-ON 8-OFF HIGH 1600 CFM

7-OFF 8-ON HIGH 1600 CFM

7-ON 8-ON HIGH 1600 CFM

SWITCH SETTINGS SELECTION NOMINAL AIRFLOW

7-OFF 8-OFF LOW 1050 CFM

7-ON 8-OFF HIGH 1200 CFM

7-OFF 8-ON HIGH 1200 CFM

7-ON 8-ON HIGH 1200 CFM

4WCZ6048 AIRFLOW WITH AUXILIARY HEAT (CFM)

4WCZ6036 AIRFLOW WITH AUXILIARY HEAT (CFM)

5-OFF 6-OFF NONE 100%5-ON 6-OFF 45 SEC 100%5-OFF 6-ON 90 SEC 50%5-ON 6-ON ** 50-100%

** This ENHANCED MODE selection provides a ramping up and ramping down of the indoor blower speed to provide improved comfort, quietness, and potential energy savings. The Graph below shows the ramping process

COOLING FAN DELAY OPTIONS

SWITCH SETTINGS DELAYNOMINAL AIRFLOW

4WCZ6060 AIRFLOW WITH AUXILIARY HEAT (CFM)

SWITCH SETTINGS SELECTION NOMINAL AIRFLOW

7-OFF 8-OFF LOW 1400 CFM

7-ON 8-OFF HIGH 1600 CFM

7-OFF 8-ON HIGH 1600 CFM

7-ON 8-ON HIGH 1600 CFM

Indoor Blower Performance

OFF OFF

35%

56%

35% Dehumidify

Fast Coil Cooling

EnhancedEfficiency

7.5minutes

3minutes

(Fan Only)

1minute

SY

ST

EM

AIR

FL

OW

(C

FM

) 50%

80%

50%

100%

Only if required

SECOND STAGE

FIRST STAGE

70% Only if required

EnhancedComfort

CCOOMMPPRREESSSSOORR OOPPEERRAATTIIOONN OONN OOFFFF

Page 12: 22-1807-11A-EN Product Data

12

Typical Wiring4WCZ6024

Page 13: 22-1807-11A-EN Product Data

13

Typical Wiring4WCZ6024

Page 14: 22-1807-11A-EN Product Data

14

Typical Wiring4WCZ6036B1

Page 15: 22-1807-11A-EN Product Data

15

Typical Wiring4WCZ6036B1

Page 16: 22-1807-11A-EN Product Data

16

Typical Wiring4WCZ6036B3

Page 17: 22-1807-11A-EN Product Data

17

Typical Wiring4WCZ6036B3

Page 18: 22-1807-11A-EN Product Data

18

Typical Wiring4WCZ6036B4

Page 19: 22-1807-11A-EN Product Data

19

Typical Wiring4WCZ6036B4

Page 20: 22-1807-11A-EN Product Data

20

Typical Wiring4WCZ6048B1

Page 21: 22-1807-11A-EN Product Data

21

Typical Wiring4WCZ6048B1

Page 22: 22-1807-11A-EN Product Data

22

Typical Wiring4WCZ6060B1

Page 23: 22-1807-11A-EN Product Data

23

Typical Wiring4WCZ6060B1

Page 24: 22-1807-11A-EN Product Data

24

Typical Wiring4WCZ6048-6060B3

Page 25: 22-1807-11A-EN Product Data

25

Typical Wiring4WCZ6048-6060B3

Page 26: 22-1807-11A-EN Product Data

26

Typical Wiring4WCZ6048-6060B4

Page 27: 22-1807-11A-EN Product Data

27

Typical Wiring4WCZ6048-6060B4

Page 28: 22-1807-11A-EN Product Data

28

Optional Equipment

BAYCURB050A FULL PERIMETER ROOF MOUNTING CURB FOR 4WCZ6024-036

46 3/8

17 7/8

3

3 5/8

19 1/2

2 3/16

19 1/2

14

1 1/2

38 7/8

15

35 7/843 3/8

The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.

Page 29: 22-1807-11A-EN Product Data

29

Optional Equipment

BAYCURB051A Full Perimeter Roof Mounting Curb for 4WCZ6048, 060

56 1/8

15 7/8

3

10 7/819 1/2

4 3/4

19 1/2

14

41 7/8

20

1 1/2

38 7/8 53 1/8

The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.

Page 30: 22-1807-11A-EN Product Data

30

Optional Equipment

The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not respon-sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.

BAYFLTR101, 201B, 1" - 2" Filter Rack(Mounts in Filter/Coil Section)

BAYACCDOR1A & BAYACCDOR2A Hinged Filter Access DoorReplaces Filter/Coil Access Panel

Filter

Page 31: 22-1807-11A-EN Product Data

31

BAYECON103,104A Down Discharge Economizer and Rain Hood(Mounts Over Horizontal Return Air Opening)

A

B

C D

E

BAYCON203,204A Horizontal Economizer and Rain Hood

Optional Equipment

Return DuctRoofcurb

Relief damper

Mist elimi-nator

Economizer rain hood

HVAC Unit

Outside air dampers

Return air dampers

Required filter kit, order separately

A

The drawings on this page are prepared by the manufac-turer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to con-struct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.

Economizer

Gaskets (2)

Rain HoodDuct

Mixed Air Sensor

Economizer Models A

BAYECON103A

4WCZ6024 4WCZ60364DCZ60364YCZ6036

20 1/8"

BAYECON104A4WCZ6048-0604DCZ6048-0604YCZ6048-060

24 3/8"

Economizer A B C D E F

BAYECON203AA 22" 20"16

7/8"15

11/16"11

11/16"15"

BAYECON204AA 26"22

21/32"19"

17 11/16"

14 11/16"

21-3/8"

Page 32: 22-1807-11A-EN Product Data

32

Optional Equipment

A

B

CD

FULLYOPEN

2/31/3

FULLYCLOSED

BAYOSAH001,002A, 25% Outside Air Damper(Replaces Filter/Coil Access Panel)

The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.

BAYDMPR101,102A, 25% Motorized Outside Air Damper(Mounts Over Horizontal Return AIr Opening)

D

CB

A

E

Manual Fresh

Air ModelUnit Application Models A B C D

BAYOSAH001

4YC,WC3018-036

4TC*3018-036

4W/T/Y/DCY4024-036

4W/Y/DCZ6024-036

22 7/16" 20 11/16" 12 3/8" 9 3/16"

BAYOSAH002

4YC,WC3042-060

4TC*3042-060

4W/T/Y/DCY4042-060

4W/Y/DCZ6048-060

25 3/16" 20 11/16" 12 3/8" 9 3/16"

Unit Application Models A B C D E

BAYDMPR101A

4YC,WC3018-036

4TC3018-036

4W/T/Y/DCY4024-036

4W/Y/DCZ6024-036

15 13/16" 11 13/16" 10 1/4" 11 1/2" 12 1/4"

BAYDMPR102A

4YC,WC3042-060

4TC3042-060

4W/T/Y/DCY4042-060

4W/Y/DCZ6048-060

18 3/16" 15 1/8" 10 1/4" 11 1/2" 12 1/4"

Page 33: 22-1807-11A-EN Product Data

33

Dimensional Data and Weights

Figure 1. WCZ6024/36 (1 of 3)

D673945G01_RevD

NOTE: The view labeled “Bottom Side” represents the Base as viewed looking up

from underneath the unit.

Page 34: 22-1807-11A-EN Product Data

34

Dimensional Data and Weights

Figure 2. WCZ6024/36 (2 of 3)

D673945G01_RevD

Page 35: 22-1807-11A-EN Product Data

35

Dimensional Data and Weights

Figure 3. WCZ6024/36 (3 of 3)

Page 36: 22-1807-11A-EN Product Data

36

Dimensional Data and Weights

Figure 4. WCZ6048 through WCZ6060 (1 of 3)

NOTE: The view labeled “Bottom Side” represents the Base as viewed looking up from

underneath the unit.

Page 37: 22-1807-11A-EN Product Data

37

Dimensional Data and Weights

Figure 5. WCZ6048 through WCZ6060 (2 of 3)

Page 38: 22-1807-11A-EN Product Data

38

Dimensional Data and Weights

Figure 6. WCZ6048 through WCZ6060 (3 of 3)

Page 39: 22-1807-11A-EN Product Data

39

Mechanical SpecificationsGeneral

The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV se-quence. Units shall be designed to operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be rated in ac-cordance with A.H.R.I. standards.

Unit Casing

All components shall be mounted in a weather-resistant steel cabinet with an enamel finish. Access panels shall be pro-vided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless glass fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff.

Compressor

The compressor shall be hermetically sealed, high efficiency Climatuff® two-stage compressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard.

Refrigeration System

All units shall have TXV in cooling and TXV in heating. Service pressure tap ports, and a refrigerant line filter dryer shall be stan-dard.

Evaporator Coil (2-4 Ton Models)

All aluminum micro channel, extruded tubes, mechanically bonded to aluminum fins and factory pressure and leak tested at 480-650 psig. All units have TXV to con-trol refrigerant flow. (5 Ton Models) Internally enhanced 3/8" OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 - 650 psig. All units have TXV to control refrigerant flow.

Condenser Coil —

The Spine Fin™ condenser coil shall be continuously wrapped, corrosion resis-tant all aluminum with minimum brazed joints. This coil is 3/8 inch O.D. seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2,000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.

Indoor Air Fan — Direct-drive, forward-curved, centrifugal wheel in a Composite Vortica® Blower housing. Motor shall have thermal overload protection. Perma-nently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts.

Condenser Fan — Direct-drive, draw thru propeller type. Weather-proofed permanent split capacitor fan motor shall have built-in thermal overload and perma-nently lubricated motor bearings.

System Controls

System controls include condenser fan, evaporator fan and compressor contac-tors.

Accessories

Roof Curb — The roof curb shall be de-signed to mate with the unit and provide support and complete weathertight instal-lation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal be-tween supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes fac-tory-installed wood nailer strips.

Electric Heaters — Each heater assem-bly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed.

Single Source Power Entry — This ac-cessory when used with electric heat accessory shall allow single source power connection to unit and heater combina-tion. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut-to-length in-terconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit compo-nents shall install within the unit cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes.

Fully Modulating Economizer — This accessory shall be field installed and be composed of the following items: 0-100% fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage wiring plug for electrical connec-tions. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometic relief damper shall be standard with the economizer and provide a pres-sure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment “off” cycle. Economizer re-quires BAYRLAY004A relay kit to interface the economizer to the heat pump.

Manual Outside Air Dampers — Rain hood and screen shall be field installed. Suitable for up to 25% outside air.

Start Kit — Extra compressor starting ca-pacity for single phase equipment.

Control Options

Standard Indoor Thermostats — Two stage heating/cooling or one stage heat-ing/cooling thermostats shall be available in either manual or automatic changeover.

Programmable Electronic Night Set-back Thermostat — Programmable electronic thermostat shall provide heat-ing setback and cooling setup with 7-day, programming capability. 1H/1C or 2H/2C models available.

Page 40: 22-1807-11A-EN Product Data

Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.

The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org.

Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

© 2020 Trane22-1807-11A-EN 28 May 2020 Supersedes 22-1807-11-EN (June 2017)