Safety Precautions
Product Contents
Product PIN Diagram
LED indicators
Product Dimensions
Installation of Panel with Casing
Wire Legend
Power Wiring Diagram
FR1200 Connection
Weigand Connection
Exit button Connection
Lock connection
Door Sensor Connection
Aux. Input Connection
Aux. Output Connection
Ethernet Connection
RS485 Connection
DIP switch settings
Electrical Specifications
Troubleshooting
Specifications
1
02
0406
06
07
08
091011
1212
13
1315
15
1617
18
1920
21
http://www.zkteco.com/ -
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
3/24
1
2
Safety Precautions
Do not install the device in an area
subject to direct sun light, Humidity
or dust
Do not place a magnet near the
product. Magnetic objects such as
magnet, CRT, TV, monitor or speaker
may damage the device.
Do not place the device next to
heating equipments
Be careful not to let liquid like
water, drinks or chemicals leak
inside the device.
Clean the device often to remove
dust on it
01 02 03
04 05 06
Do not let children touch the
device without supervision.
The list below is to keep users safety and prevent any loss. Please read carefully before installation.
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
4/24
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
5/244
Product Contents
Basic Contents
Inbio460
Wall Mounting Screws2 pcs. Wall Plugs2 pcs. Surge Suppressing Diode4 p
Screw Driver 2 pcs. Software CD InBio Installation Guide
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
6/245
Product Contents
Optional accessories
Weigand Card Reader Prox Card
Card EnrollerZK4500 FP Enrollment reader
FR1200 FP Reader K1-1 Exit Button
Inbio Metal Case RS485 convertor
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
7/246
Product PIN Diagram
#4 Door Card
Reader
#4 Door Exit
Button
#3 Door Card
Reader
#3 Door Exit
Button
#2 Door Exit
Button
#2 Door Card
Reader
#1 Door Card
Reader
#1 Door Exit
Button
State Indictor
FR1200
Fingerprint
Reader
Aux Input 4
Aux Input 1
SD Card Slot
LINK LED
ACT LED
Ethernet Port
DIP Switch
PC RS485 Port
Aux Output 1
Aux Output 4
#1 Door Lock
#4 Door Sensor
Lock Power
Inbio Power
LED indicators
LINK
(Green)
LED solid green indicates
TCP/IP communication is
normal
ACT
(Yellow)
Flashing LED indicates data
communication is in progress
EXT RS485
(Yellow &
Green)
Flashing LED indicates data
communication in progress
PC RS485
(Yellow &
Green)
Flashing LED indicates data
communication is in progress
POWER
(Red)
Flashing LED indicates the
panel is powered on.
RUN(Green)
Flashing LED indicates that
panel is in normal workingmode
CARD
(Yellow)
Flashing LED indicates that
the card is read by the panel.
#1 Door Sensor
#4 Door Lock
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
8/24
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
9/248
Installation of Panel & Case
Metal Case
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
10/24
Wire Legend
9
Detector Infrared sensors FR1200 Inbio-Box #1Exit Button #1Card Reader #4 Exit Switch #4 Card Reader
12V
Power SupplyNormally Open LockNormally Close LockAlarmFloodlightRS485 ConvertorNetwork
12V DC
PowerDC
i i di
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
11/24
Power wiring diagram
10
WithBackup Battery
AC
Switching power supply
Inbio460
AC
Switching power supply
Inbio460
Backup Battery
+
-
110-220V
110-220V
Without
Backup Battery
FR1200 C i
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
12/24
FR1200 Connection
11
#1 FR1200 #2 FR1200 #3 FR1200 #8 FR1200
DIP Switch Setting For FR1200 Device ID
1. There are six DIP switches on the back of FR1200 , Switches 1-4 is for RS485
address , switch 5 is reserved , switch 6 is for reducing noise on long RS485 cable.
2. Set the odd number for IN reader, and the even number for OUT reader(for eg.
For two readers for one door- the RS485 address 1 is for IN reader, RS485 address
2 is for OUT reader )
3. If FR1200 is powered from Inbio460 panel ,the length of wire should be less
than 100 meters or 330 ft.
4. The External RS485 interface can supply maximum 500mA current , The
FR1200s startup current is 240mA. So Inbio460 only can only power two FR1200s.5. If the cable length is more than 200 meters or 600 ft , the number 6 switch
should be ON as below
Important Notes
12V DC
12V DC
Distance
More than 200 meters
W i d C ti
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
13/24
Weigand Connection
12
Weigand Card Reader
Exit Button Connection
Beeper
Green LED
Weigand D1
Weigand D0
GND
DC+(6-14V)
BUT
GND
DV12VDV12V
NO
COM
NC
separate power supply
NoticeZK ABK Exit Button
K1-1 Exit Switch
12V DC Power Supply
L k C ti
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
14/24
13
Lock Connection
12V DC
GND
Sensor
Sensor
12V DC
GND
GND
12V DC
Sensor
Sensor
GND
12V DC
FR107
FR107For Normally Open -Lock powered from panel power supply
For Normally Closed -Lock powered from panel power supply
Lock Connection
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
15/24
Lock Connection
14
Important Notes:
InBio is set to supply lock power by default from built-in
power supply , If you want to use external power supply ,
you must take the following steps
1. Take apart the cover of inbio460
2. Select the desired lock relay and find its jumpers
3. Take off the jumpers and change to
4. Connect the lock as shown in the diagram below.
Steps:
Inbio460 Detach from Rail Remove Top Cover Lock Relay
Terminals Default SettingChanged Setting Jumpers
FR107
GND
12V DC
SEN SEN GND 12V DC
5 1 15 5 1 15
Connecting a Lock with External Power supply
Switching Wet Contact to Dry Contact
Auxiliary Input/Output
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
16/24
15
Auxiliary Input/Output
Aux. Input Connection
Aux. output Connection
COM
NO
NC
GND12V DC
COM
NO
NC
GND12V DC
Smoke Detector
Alarm
Ethernet Connection
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
17/24
16
Ethernet Connection
Direct connection
To connect Inbio460 with a PC directly, connect both devices with a straight network cable. As the Inbio460 supports auto MDI/MDIX ,
it is not necessary to use a crossover type cable.
Important Notes:
ZK4500 Enrollment
readerCR10 Card Issuer
1. Both 10Base-T and 100Base-T
are supported2. The cable length must be less
than 100 meters or 330 ft.
3. For more than 100 meters ,
please use HUB to amplify the
signal
TCP/IP
CR10 Card Issuer
ZK4500 Enrollment
reader
The CR10 and ZK4500 are connected to the server
using USB connection.
RS485 Connection
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
18/24
17
RS485 Connection
Important Notes
#1 Inbio460
#63 Inbio460
Do's and Dont's for RS 485 connection
RS485-RS485+GND
1. RS485 communication wires should be a shielded or twisted pair cable.
RS485 communication wires should be connected in a bus cascade instead
of a star form, to achieve a better shielding effect by reducing signal
reflection during communications.
2. A single 485 bus can be connected with 63 access control panels at the
most, but preferably less than 32 panels should be connected.
3. To eliminate signal attenuation in communication cables and suppress
interference, if the bus is longer than 200 meters, set the number 8 DIP
switch to the ONposition. This is equivalent to a parallel connection of one
120ohm resistance between the 485+ and 485- lines.
Distance
More than 200 meters
#1 Inbio460 #* Inbio460
DIP Switch Setting
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
19/24
18
DIP Switch Setting
Introduction RS485 Address
1. Number 1-6 are reserved to set the device number for RS485
communication. The code is binary, and the numbering starts from left to
right. When the switch is set to ON position, it indicates 1 (on); when the
switch is set downwards, it indicates 0 (off). For example, to set a device
number 39=1+2+4+32, which corresponds to the binary code 111001, put
number 1, 2, 3, and 6 to ON position, as illustrated below.
2. For more details, please check the table at the end of this document
Restore factory setting
1. If you forget the inBio IP address or the device does not work
normally, you can use the number 7 terminal to restore inbio460 to
factory default settings. The parameters which gets reset are
device IP address, communication password ,gateway ,subnet mask.
2. The switch is OFF by default. When it is moved upwards anddownwards for three times within 10 seconds and finally returned
to OFF position, the factory settings will be restored after the
access control panel is restarted.
1 times 2 times 3 times OFF
Terminal Resistance
1. Number 8 is for setting the RS485 termination resistance. Putting the
switch to ON position is equivalent to parallel connection of a 120ohm
termination resistance between 485+ and 485-
2. As shown in diagram below, for more info please read RS485 connection
important notes
120ohm
Electrical Specification
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
20/24
Electrical Specification
19
Min. Typ. Max. Notes
Working power supply
Voltage(V) 9.6 12 14.4 Use regulated DC power adaptor only
Current(A) 2
Electronic lock relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 2
Auxiliary relay output
Switching voltage(V) 36V Use regulated DC power adaptor only
Switching Current(A) 1.25
Switch Aux. input
VIH (V) TBD
VIL (V) TBD
Pull-up resistance () 4.7k The input ports are pulled up with 4.7k resistors
WEIGAND Input
Voltage(V) 10.8 12 13.5
Current(mA) 500
ZK Electronic lock
Voltage(V) 10.8 12 13.2
Current(mA) 500
Troubleshooting
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
21/24
Troubleshooting
20
1. Fingerprint can not be read well or it takes too long.
Check whether a finger or fingerprint sensor is stained with sweat, water, or dust
Retry after cleaning the finger and fingerprint sensor with dry cloth.
If a finger is way too dry, rub your finger on the palm and retry.
Try to reset fingerprint sensor by pressing the reset button at the bottom of the reader
2. Fingerprint is matched but authorization keeps failing.
Check whether the user access is restricted.
Inquire with administrator whether the enrolled fingerprint has been deleted from the device
for some reason.
3. How Many kinds of WEIGAND format can be supported. The panel is set to read 26 bit by default.
However there are 9 other bit formats which can be selected from the software. In addition you
can also define your custom bit format.
4. How many verification modes can be support.
Card Only
Fingerprint Only Password Only
Card plus fingerprint
Card plus password
Card or fingerprint
Reset Button
Specification
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
22/24
Specification
21
Communication RS485, Ethernet
Baud Rate for RS485 9600-115200 baud
Power Supply 12V DC, 3A
Device Capacity Card capacity 30,000 ; Log events capacity 100,000 ; Finger capacity 3,000
LED Indicator Indication for communication, power, status and prox card
Environment Operating Temp: 32-113F (0-45C) Operating Humidity: 20% to 80%
Number of doors controlled four door one way or two door two way
Number of card readers supported 4
Number of FR1200 supported 8
FR1200 Sensor Fingerprint sensor 500dpi Optical / Optical sensor
Types of readers supported 26-bit Weigand, others upon request
Number of Inputs 12 (4 Exit Device, 4 Door Status, 4 AUX)
Number of Outputs 8 (4- Form C relay for lock and 4- Form C relay for Aux output)
Weight 7.8lbs (3.55kg)
Enclosure Stainless Steel
Mounting Wall Mount
Dimensions (Bundle Only) 15.7in. 3.56in. 13.0in. 400mm(L) X 90.5mm(W) X 330mm(H)
Dimensions ( Board Only) 8.89in. 4.17in. 1.42in. 226mm(L) X 106mm(W) X 36mm(H)
CPU 32 bit 400MHz
RAM 32MB
Flash 128MB
Certified
PC485 Table
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
23/24
22
Place AddressSwitch Setting
1 2 3 4 5 6Address No. 1 2 4 8 16 32
01 ON OFF OFF OFF OFF OFF02 OFF ON OFF OFF OFF OFF03 ON ON OFF OFF OFF OFF04 OFF OFF ON OFF OFF OFF05 ON OFF ON OFF OFF OFF06 OFF ON ON OFF OFF OFF07 ON ON ON OFF OFF OFF08 OFF OFF OFF ON OFF OFF09 ON OFF OFF ON OFF OFF10 OFF ON OFF ON OFF OFF11 ON ON OFF ON OFF OFF12
OFF
OFF
ON
ON
OFF
OFF
13 ON OFF ON ON OFF OFF14 OFF ON ON ON OFF OFF15 ON ON ON ON OFF OFF16 OFF OFF OFF OFF ON OFF17 ON OFF OFF OFF ON OFF18 OFF ON OFF OFF ON OFF19 ON ON OFF OFF ON OFF20 OFF OFF ON OFF ON OFF21 ON OFF ON OFF ON OFF22 OFF ON ON OFF ON OFF23 ON ON ON OFF ON OFF24 OFF OFF OFF ON ON OFF25 ON OFF OFF ON ON OFF26 OFF ON OFF ON ON OFF27 ON ON OFF ON ON OFF28 OFF OFF ON ON ON OFF29 ON OFF ON ON ON OFF30 OFF ON ON ON ON OFF31 ON ON ON ON ON OFF32 OFF OFF OFF OFF OFF ON
Place AddressSwitch Setting
1 2 3 4 5 6Address No. 1 2 4 8 16 32
33 ON OFF OFF OFF OFF ON34 OFF ON OFF OFF OFF ON35 ON ON OFF OFF OFF ON36 OFF OFF ON OFF OFF ON37 ON OFF ON OFF OFF ON38 OFF ON ON OFF OFF ON39 ON ON ON OFF OFF ON40 OFF OFF OFF ON OFF ON41 ON OFF OFF ON OFF ON42 OFF ON OFF ON OFF ON43 ON ON OFF ON OFF ON44 OFF OFF ON ON OFF ON45 ON OFF ON ON OFF ON46 OFF ON ON ON OFF ON47 ON ON ON ON OFF ON48 OFF OFF OFF OFF ON ON49 ON OFF OFF OFF ON ON50 OFF ON OFF OFF ON ON51 ON ON OFF OFF ON ON52 OFF OFF ON OFF ON ON53 ON OFF ON OFF ON ON54 OFF ON ON OFF ON ON55 ON ON ON OFF ON ON56 OFF OFF OFF ON ON ON57 ON OFF OFF ON ON ON58 OFF ON OFF ON ON ON59 ON ON OFF ON ON ON60 OFF OFF ON ON ON ON61 ON OFF ON ON ON ON62 OFF ON ON ON ON ON63 ON ON ON ON ON ON
-
8/12/2019 203MDZ_Inbio460 Installation Guide ZKACCESS
24/24
ZK USA office:
201 Circle Drive North, Suite 116
Piscataway, NJ 08854, USA
Tel: +1 732-412-6007
Fax +1 732-412-6008
zkaccess.com
Copyright 2013 ZKAccess Inc. All right reserved.