SECTION A INDEX Page NumberProduct Description
Form 7 Gray Iron Conduit Bodies . . . . . . . . . . . . . . . . . . . . . .AA1-AA2Form 7 Covers, Gaskets & Wire Guards . . . . . . . . . . . . . . . . . . . . .AA3Form 7 Conduit Bodies - Dimensional Data . . . . . . . . . . . . . .AA4-AA6
Spec 5 Malleable Iron Conduit Bodies . . . . . . . . . . . . . . . . . . .AB1-AB2Spec 5 Conduit Body, Cover & Gasket Assemblies . . . . . . . . . . . . .AB3Spec 5 Covers, Gaskets & Wire Guards . . . . . . . . . . . . . . . . .AB4-AB5 Spec 5 Conduit Bodies - Dimensional Data . . . . . . . . . . . . . .AB6-AB8
Aluminum Conduit Bodies for Rigid Conduit . . . . . . . . . . . . . .AC1-AC2Aluminum Conduit Body, Cover & Gasket Assemblies . . . . . . . . . .AC3Aluminum Conduit Bodies for EMT . . . . . . . . . . . . . . . . . . . . . . . . .AC4Aluminum Covers, Gaskets & Wire Guards . . . . . . . . . . . . . . . . . .AC5Aluminum Conduit Bodies - Dimensional Data . . . . . . . . . . . .AC6-AC9
Mogul Conduit Bodies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AD1Mogul Conduit Bodies - Dimensional Data . . . . . . . . . . . . . . . . . . .AD2
FS/FD Cast Device Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . .AE1-AE2FS/FD Dry Location Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AE3FS/FD Wet Location Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AE4FS/FD Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AE4OCB Outdoor Connection Box . . . . . . . . . . . . . . . . . . . . . . . . . . . .AE5FS/FD Cast Device Boxes - Dimensional Data . . . . . . . . . . . . . . . .AE6
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Notes
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Type LR
Type LL
Type LB
Trade Size Catalog Catalog(inches) Number Number
Gray Iron Aluminum
⁄/™ LB17 LB17-SA‹/¢ LB27 LB27-SA1 LB37 LB37-SA1⁄/¢ LB47 LB47-SA
1⁄/™ LB57 LB57-SA2 LB67 LB67-SA2⁄/™ LB77 LB77-SA3 LB87 LB87-SA
3⁄/™ LB974 LB107
⁄/™ T17 T17-SA‹/¢ T27 T27-SA1 T37 T37-SA1⁄/¢ T47 T47-SA
1⁄/™ T57 T57-SA2 T67 T67-SA2⁄/™ T773 T87
3⁄/™ T974 T107
⁄/™ LL17 LL17-SA‹/¢ LL27 LL27-SA1 LL37 LL37-SA1⁄/¢ LL47 LL47-SA
1⁄/™ LL57 LL57-SA2 LL67 LL67-SA2⁄/™ LL773 LL87
3⁄/™ LL974 LL107
⁄/™ LR17 LR17-SA‹/¢ LR27 LR27-SA1 LR37 LR37-SA1⁄/¢ LR47 LR47-SA
1⁄/™ LR57 LR57-SA2 LR67 LR67-SA2⁄/™ LR773 LR87
3⁄/™ LR974 LR107
AA1 AA1Form 7 Conduit Bodies
Types LB, T, LL, LR
Use: To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Flat back design for greater wiring capacity and surface mounting.• Complete interchangeability with othermanufacturers’ Form 7 conduit bodies.• Internal volume and maximum wire clearlymarked on castings.• Time-saving Clip-on™ covers in steel, grayiron or aluminum.• Easy-Glide™ wire guard for 11⁄4” trade sizeand larger, see Page - AA3.• For covers and gaskets, see Page - AA3.
Material/Finish: • Gray Iron/Zinc Electroplated/AluminumEnamel • Copper-free Aluminum/Aluminum Enamel
Optional Finish:Hot Dip Galvanized. Add suffix “G” to GrayIron catalog number. Contact your local rep-resentative for pricing and availability.
Third Party Certification:UL Listed: E-18095Suitable for wet locations when used with gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations when used with gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed. Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AA4 - AA6.
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Form 7 Conduit BodiesFor Rigid Conduit & IMC
Type T
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Type TB
Type X
Type TA
Type C
Form 7 Conduit BodiesFor Rigid Conduit & IMC
AA2 AA2Form 7 Conduit Bodies
Types TB, TA, X, C, L, E
Use: To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Flat back design for greater wiring capacity and surface mounting.• Complete interchangeability with othermanufacturers’ Form 7 conduit bodies.• Internal volume and maximum wire clearlymarked on castings.• Time-saving Clip-on™ covers in steel, grayiron or aluminum.• Easy-Glide™ wire guard for 11⁄4” trade sizeand larger, see Page - AA3.• For covers and gaskets, see Page - AA3.
Material/Finish: • Gray Iron/Zinc Electroplated/AluminumEnamel • Copper-free Aluminum/Aluminum Enamel
Optional Finish:Hot Dip Galvanized. Add suffix “G” to GrayIron catalog number. Contact your local rep-resentative for pricing and availability.
Third Party Certification:UL Listed: E-18095Suitable for wet locations when used with gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations when used with gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed. Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AA4 - AA6.
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Trade Size Catalog Catalog(inches) Number Number
Gray Iron Aluminum
⁄/™ TB17 TB17-SA‹/¢ TB27 TB27-SA1 TB37 TB37-SA
1⁄/¢ TB47 TB47-SA
1⁄/™ TB57 TB57-SA2 TB67 TB67-SA
⁄/™ TA17‹/¢ TA271 TA37
1⁄/¢ TA47
1⁄/™ TA572 TA67
⁄/™ X17 X17-SA‹/¢ X27 X27-SA1 X37 X37-SA
1⁄/¢ X47
1⁄/™ X572 X67
⁄/™ C17 C17-SA‹/¢ C27 C27-SA1 C37 C37-SA
1⁄/¢ C47 C47-SA
1⁄/™ C57 C57-SA2 C67 C67-SA
2⁄/™ C77 C77-SA3 C87 C87-SA
⁄/™ L17‹/¢ L271 L37
1⁄/¢ L47
1⁄/™ L572 L67
⁄/™ E17 E17-SA‹/¢ E27 E27-SA1 E37 E37-SA
Type E
Type L(Provided with one blank steel cover)
Type 170Stamped Steel and AluminumClip-on™ Cover
Use:To cover conduit body opening.
Features:• Centering tabs• Easy installation• Easy removal
Material/Finish: Stamped Steel/Zinc Pre-GalvanizedStainless Steel ScrewsZinc Electroplated Clips
Optional Material:Aluminum add suffix -SA as shown below
Third Party Certification:UL Listed: E-18095Suitable for wet locations when usedwith gaskets, Type GASK on Form 7conduit bodies.
CSA Certified: LR-9795 Suitable for wet locations when usedwith gaskets, Type GASK on Form 7conduit bodies.
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed. Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog Catalog(inches) Number Number
Steel Aluminum
1⁄2 170 170-SA3⁄4 270 270-SA1 370 370-SA11⁄4 470 470-SA
11⁄2 570 570-SA2 670 670-SA21⁄2-3 870 870-SA31⁄2-4 970 970-SA
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AA3 AA3Form 7 Conduit Bodies
Covers, Gaskets and Wire GuardsFor Form 7 Conduit Bodies
Type GASKSolid Cover GasketUse:To provide a worry-free, rain tight seal whenused with Type 170 or 170F covers thathave heavy-duty cover screw washers.
Material: Closed-Cell Neoprene.Temperature Rating: 212°F/100°C.
Note: UL/CSA not applicable.
Trade Size Catalog(inches) Number
1⁄2 GASK5713⁄4 GASK5721 GASK57311⁄4 GASK574
11⁄2 GASK5752 GASK57621⁄2-3 GASK57831⁄2-4 GASK579
Type 170FCast Gray Iron andAluminum Clip-on™ Cover
Use: To cover conduit body opening.
Features:• Centering tabs• Easy installation• Easy removal
Material/Finish: Gray Iron/Zinc ElectroplatedStainless Steel ScrewsZinc Electroplated Clips
Optional FinishHot Dip Galvanized. Add suffix “G” to GrayIron catalog number. Contact your local rep-resentative for pricing and availability.
Optional MaterialCast Aluminum add suffix -SA as shown below
Third Party Certification:UL Listed: E-18095Suitable for wet locations when usedwith gaskets, Type GASK on Form 7conduit bodies.
CSA Certified: LR-9795 Suitable for wet locations when usedwith gaskets, Type GASK on Form 7conduit bodies.
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed. Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog Catalog(inches) Number Number
Gray Iron Cast Aluminum
1⁄2 170F 170F-SA3⁄4 270F 270F-SA1 370F 370F-SA11⁄4 470F 470F-SA
11⁄2 570F 570F-SA2 670F 670F-SA21⁄2-3 870F 870F-SA31⁄2-4 970F 970F-SA
Type 170 Type 170F
Type GASK
Type EWEasy-Glide™ Wire GuardUse:To ease the job of wire pulling when usedwith O-Z/Gedney conduit bodies.
Features:• Reusable• Protects wire insulation• Fits all conduit body hub configurations.
Material: Spring Steel
Trade Size Catalog (inches) Number
For O-Z/Gedney Form 7 Conduit Bodies11⁄4-11⁄2-2 EW7-1220S21⁄2-3-31⁄2-4 EW7-2540S
Type EW
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Form 7 Conduit BodiesFor Rigid Conduit & IMC
AA4 AA4Form 7 Conduit Bodies
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
LB17 1⁄2 49⁄16 21⁄4 13⁄8 115⁄16 33⁄16 4 N/ALB27 3⁄4 53⁄16 21⁄2 19⁄16 11⁄8 313⁄16 6.9 3 #6AWGLB37 1 6 27⁄8 13⁄4 13⁄8 41⁄2 10.5 3 #4AWGLB47 11⁄4 61⁄2 35⁄16 23⁄16 13⁄4 5 19.3 3 #3AWGLB57 11⁄2 71⁄8 311⁄16 27⁄16 115⁄16 57⁄16 26.5 3 #1AWG
LB67 2 81⁄8 41⁄4 3 27⁄16 63⁄8 46 3 #1/0AWGLB77 21⁄2 101⁄2 51⁄8 41⁄4 39⁄16 83⁄8 102 3 #3/0AWGLB87 3 101⁄2 57⁄8 41⁄4 39⁄16 83⁄8 126 3 #3/0AWGLB97 31⁄2 1211⁄16 69⁄16 51⁄4 41⁄2 101⁄4 210 3 #300MCMLB107 4 1211⁄16 71⁄16 51⁄4 41⁄2 101⁄4 238 3 #300MC
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
LR17 1⁄2 49⁄16 13⁄8 21⁄4 15⁄16 33⁄16 4 N/ALR27 3⁄4 53⁄16 15⁄8 27⁄16 11⁄8 313⁄16 6.9 3 #6AWGLR37 1 6 17⁄8 23⁄4 13⁄8 41⁄2 10.5 3 #4AWGLR47 11⁄4 61⁄2 25⁄16 33⁄16 13⁄4 5 19.5 3 #2AWGLR57 11⁄2 71⁄8 29⁄16 39⁄16 115⁄16 57⁄16 27 3 #2AWG
LR67 2 81⁄8 31⁄8 41⁄8 27⁄16 63⁄8 50 3 #3/0AWGLR77 21⁄2 101⁄2 35⁄8 53⁄4 39⁄16 83⁄8 102 3 #250MCMLR87 3 101⁄2 43⁄8 53⁄4 39⁄16 83⁄8 126 3 #250MCMLR97 31⁄2 1211⁄16 47⁄8 615⁄16 41⁄2 101⁄4 210 3 #350MCMLR107 4 1211⁄16 53⁄8 615⁄16 41⁄2 101⁄4 238 3 #350MCM
Type LR
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
LL17 1⁄2 49⁄16 13⁄8 21⁄4 15⁄16 33⁄16 4 N/ALL27 3⁄4 53⁄16 15⁄8 27⁄16 11⁄8 313⁄16 6.9 3 #6AWGLL37 1 6 17⁄8 23⁄4 13⁄8 41⁄2 10.5 3 #4AWGLL47 11⁄4 61⁄2 25⁄16 33⁄16 13⁄4 5 19.5 3 #2AWGLL57 11⁄2 71⁄8 29⁄16 39⁄16 115⁄16 57⁄16 27 3 #2AWG
LL67 2 81⁄8 31⁄8 41⁄8 27⁄16 63⁄8 50 3 #3/0AWGLL77 21⁄2 101⁄2 35⁄8 53⁄4 39⁄16 83⁄8 102 3 #250MCMLL87 3 101⁄2 43⁄8 53⁄4 39⁄16 83⁄8 126 3 #250MCMLL97 31⁄2 1211⁄16 47⁄8 615⁄16 41⁄2 101⁄4 210 3 #350MCMLL107 4 1211⁄16 53⁄8 615⁄16 41⁄2 101⁄4 238 3 #350MCM
Type LL
Type LB
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
T17 1⁄2 55⁄8 13⁄4 27⁄16 15⁄16 33⁄16 6 N/AT27 3⁄4 61⁄4 2 25⁄8 11⁄8 313⁄16 19.5 3 #6AWGT37 1 71⁄4 21⁄4 3 13⁄8 41⁄2 15 3 #4AWGT47 11⁄4 77⁄16 25⁄16 33⁄16 13⁄4 5 20 3 #3AWGT57 11⁄2 83⁄16 29⁄16 39⁄16 115⁄16 57⁄16 27 3 #2AWG
T67 2 93⁄16 31⁄8 41⁄8 27⁄16 63⁄8 50 3 #2AWGT77 21⁄2 12 35⁄8 53⁄4 39⁄16 83⁄8 102 3 #1/0AWGT87 3 121⁄16 43⁄8 53⁄4 39⁄16 83⁄8 126 3 #1/0AWGT97 31⁄2 145⁄16 47⁄8 615⁄16 41⁄2 101⁄4 210 3 #3/0AWGT107 4 145⁄16 53⁄8 615⁄16 41⁄2 101⁄4 238 3 #3/0AWG
Type T
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Form 7 Conduit BodiesFor Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
TA17 1⁄2 55⁄8 25⁄8 27⁄16 15⁄16 33⁄16 6 N/ATA27 3⁄4 61⁄4 27⁄8 25⁄8 11⁄8 313⁄16 9.5 3 #6AWGTA37 1 71⁄4 31⁄4 3 13⁄8 41⁄2 15 3 #4AWGTA47 11⁄4 77⁄16 35⁄16 33⁄16 13⁄4 5 20 3 #3AWG
TA57 11⁄2 83⁄16 311⁄16 39⁄16 115⁄16 57⁄16 27 3 #2AWGTA67 2 93⁄16 41⁄4 41⁄8 27⁄16 63⁄8 50 3 #2AWG
Type TA
AA5 AA5Form 7 Conduit Bodies
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
X17 1⁄2 55⁄8 13⁄4 35⁄1615⁄16 33⁄16 6 N/A
X27 3⁄4 61⁄4 2 31⁄2 11⁄8 313⁄16 9.5 3 #6AWGX37 1 71⁄4 21⁄4 37⁄8 13⁄8 41⁄2 15 3 #4AWGX47 11⁄4 77⁄16 25⁄16 41⁄8 13⁄4 5 20 3 #3AWG
X57 11⁄2 83⁄16 29⁄16 45⁄8 115⁄16 57⁄16 27 3 #2AWGX67 2 93⁄16 31⁄8 53⁄16 27⁄16 63⁄8 50 3 #2AWG
Type X
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
TB17 1⁄2 55⁄8 25⁄8 19⁄1615⁄16 33⁄16 6 N/A
TB27 3⁄4 61⁄4 27⁄8 17⁄8 11⁄8 313⁄16 9.5 3 #6AWGTB37 1 71⁄4 31⁄4 2 13⁄8 41⁄2 15 3 #4AWGTB47 11⁄4 77⁄16 35⁄16 23⁄16 13⁄4 5 20 3 #3AWG
TB57 11⁄2 83⁄16 35⁄8 27⁄16 115⁄16 57⁄16 27 3 #2AWGTB67 2 93⁄16 41⁄4 3 27⁄16 63⁄8 50 3 #2AWG
Type TB
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Form 7 Conduit BodiesFor Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
C17 1⁄2 53⁄8 13⁄8 13⁄8 15⁄16 33⁄16 4 N/AC27 3⁄4 6 15⁄8 19⁄16 11⁄8 313⁄16 6.9 3 #6AWGC37 1 7 17⁄8 13⁄4 13⁄8 41⁄2 10.5 3 #4AWGC47 11⁄4 77⁄16 25⁄16 23⁄16 13⁄4 5 20 3 #3AWG
C57 11⁄2 83⁄16 29⁄16 27⁄16 115⁄16 57⁄16 27 3 #2AWGC67 2 93⁄16 31⁄8 3 27⁄16 63⁄8 50 3 #1/0AWGC77 21⁄2 12 35⁄8 41⁄4 39⁄16 83⁄8 102 3 #2/0AWGC87 3 12 43⁄8 41⁄4 39⁄16 83⁄8 126 3 #2/0AWG
Type C
AA6 AA6Form 7 Conduit Bodies
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
L17 1⁄2 49⁄16 13⁄8 21⁄4 15⁄16 33⁄16 5 N/AL27 3⁄4 53⁄16 13⁄4 27⁄16 11⁄8 313⁄16 8 3 #6AWGL37 1 6 2 23⁄4 13⁄8 41⁄2 13 3 #4AWGL47 11⁄4 61⁄2 21⁄2 33⁄16 13⁄4 5 22 3 #2AWG
L57 11⁄2 71⁄8 23⁄4 39⁄16 115⁄16 57⁄16 31 3 #2AWGL67 2 81⁄8 31⁄4 31⁄4 27⁄16 63⁄8 54 3 #2AWG
Type L
Dimensions in InchesCatalog Trade Volume Max No.Number Size a b c d e Cu. In. Conductors
E17 1⁄2 49⁄16 13⁄8 13⁄8 15⁄16 33⁄16 3.9 N/AE27 3⁄4 53⁄16 15⁄8 19⁄16 11⁄8 313⁄16 6.5 3 #6AWGE37 1 6 17⁄8 13⁄4 13⁄8 41⁄2 10 3 #4AWG
Type E
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB1 AB1Spec 5™ Malleable Iron Conduit Bodies
Type T
Type LB
Type T-GHot Dip Galvanized
Type LB-GHot Dip Galvanized
Spec 5™ Malleable Iron Conduit Bodies For Rigid Conduit & IMC
Trade Size Catalog(inches) Number
Malleable IronZinc Plated
⁄/™ LB-50‹/¢ LB-751 LB-1001⁄/¢ LB-125
1⁄/™ LB-1502 LB-2002⁄/™ LB-2503 LB-300
3⁄/™ LB-3504 LB-400
⁄/™ T-50‹/¢ T-751 T-1001⁄/¢ T-125
1⁄/™ T-1502 T-2002⁄/™ T-2503 T-300
3⁄/™ T-3504 T-400
Types LB, T, LB-G & T-G
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Raintight when used with gasketed covers.• Malleable iron suitable for use in concrete.• Easy-Glide™ wire guard for 11⁄4” trade sizeand larger, see Page AB5.• For covers and gaskets, see Pages AB4and AB5.• Complete interchangeability with othermanufacturers’ style “5” or “35” ConduitBodies.• Internal volume and maximum wire clearlymarked on castings.
Material/Finish: Malleable Iron/
Zinc Electroplated Aluminum Enamel
Optional Finish:Hot Dip Galvanized. Add suffix “G” to stan-dard catalog number. Contact your localrepresentative for pricing and availability.
Third Party Certification:UL Listed E-18095Suitable for wet locations when usedwith gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations when usedwith gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AB6 - AB8
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Trade Size Catalog(inches) Number
Malleable IronHot Dip Galvanized
⁄/™ LB-50G‹/¢ LB-75G1 LB-100G1⁄/¢ LB-125G
1⁄/™ LB-150G2 LB-200G2⁄/™ LB-250G3 LB-300G
3⁄/™ LB-350G4 LB-400G
⁄/™ T-50G‹/¢ T-75G1 T-100G1⁄/¢ T-125G
1⁄/™ T-150G2 T-200G2⁄/™ T-250G3 T-300G
3⁄/™ T-350G4 T-400G
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB2 AB2Spec 5™ Malleable Iron Conduit Bodies
Type LR
Type LL
Type TB
Spec 5™ Malleable Iron Conduit Bodies For Rigid Conduit & IMC
Types LL, LR, TB, X, C
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Raintight when used with gasketed covers.• Malleable iron suitable for use in concrete.• Easy-Glide™ wire guard for 11⁄4” trade sizeand larger, see Page AB5.• For covers and gaskets, see Pages AB4and AB5.• Complete interchangeability with othermanufacturers’ style “5” or “35” ConduitBodies.• Internal volume and maximum wire clearlymarked on castings.
Material/Finish: Malleable Iron/
Zinc Electroplated Aluminum Enamel
Optional Finish:Hot Dip Galvanized. Add suffix “G” to stan-dard catalog number. Contact your localrepresentative for pricing and availability.
Third Party Certification:UL Listed E-18095Suitable for wet locations when usedwith gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations when usedwith gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AB6 - AB8
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Trade Size Catalog(inches) Number
Malleable IronZinc Plated
⁄/™ LL-50‹/¢ LL-751 LL-1001⁄/¢ LL-125
1⁄/™ LL-1502 LL-2002⁄/™ LL-2503 LL-300
3⁄/™ LL-3504 LL-400
⁄/™ LR-50‹/¢ LR-751 LR-1001⁄/¢ LR-125
1⁄/™ LR-1502 LR-2002⁄/™ LR-2503 LR-300
3⁄/™ LR-3504 LR-400
⁄/™ TB-50‹/¢ TB-751 TB-1001⁄/¢ TB-125
1⁄/™ TB-1502 TB-200
⁄/™ X-50‹/¢ X-751 X-1001⁄/¢ X-125
1⁄/™ X-1502 X-200
⁄/™ C-50‹/¢ C-751 C-1001⁄/¢ C-125
1⁄/™ C-1502 C-2002⁄/™ C-2503 C-300
3⁄/™ C-3504 C-400
Type X
Type C
Trade Size Catalog(inches) Number
⁄/™ LB-50CG‹/¢ LB-75CG1 LB-100CG1⁄/¢ LB-125CG
1⁄/™ LB-150CG2 LB-200CG
⁄/™ T-50CG‹/¢ T-75CG1 T-100CG1⁄/¢ T-125CG
1⁄/™ T-150CG2 T-200CG
⁄/™ LL-50CG‹/¢ LL-75CG1 LL-100CG1⁄/¢ LL-125CG
1⁄/™ LL-150CG2 LL-200CG
⁄/™ LR-50CG‹/¢ LR-75CG1 LR-100CG1⁄/¢ LR-125CG
1⁄/™ LR-150CG2 LR-200CG
⁄/™ C-50CG‹/¢ C-75CG1 C-100CG1⁄/¢ C-125CG
1⁄/™ C-150CG2 C-200CG
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Spec 5™ Malleable Iron Conduit Bodies
Types LB, LL, LR, C, T
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT)• Packaged complete under one CatalogNumber• Ready to use
Material/Finish: Conduit body - Malleable IronZinc Electroplated with Aluminum EnamelCover - Type BS Steel Zinc Electroplated Gasket - Type SGN Neoprene
Optional Finish:Hot Dip Galvanized. Add suffix “G” to stan-dard catalog number. Contact your localrepresentative for pricing and availability.
Third Party Certification:UL Listed:E-18095Suitable for wet locations
CSA Certified:LR-9795Suitable for wet locations.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AB6 - AB8.
Note: For additional information, pleaserefer to:• Conduit Bodies on pages AB1 and AB2.• Covers and Gaskets on page AB4.• Easy-Glide™ Wire Guards on page AB5.
Spec 5™ Conduit Body, Cover & Gasket AssembliesFor Rigid Conduit & IMC
Type LB-CG
Type LL-CG
Type LR-CG
Type C-CG
Type T-CG
AB3AB3
Type BC-GFlat Top Design Cover
Use:To cover conduit body opening.
Material/Finish: Gray Iron/Hot Dip Galvanized stainless steelscrews.
Third Party Certification:UL Listed:E-18095Suitable for wet locations when usedwith gaskets, Type SG on malleableiron conduit bodies.
CSA Certified:LR-9795Suitable for wet locations when usedwith gaskets, Type SG on malleableiron conduit bodies.
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog (inches) Number
1⁄2 BC-50G3⁄4 BC-75G1 BC-100G11⁄4-11⁄2 BC-125G
2 BC-200G21⁄2-3 BC-250G31⁄2-4 BC-350G
Type BS-SDomed Top Design Cover
Use:To cover conduit body opening.
Material/Finish: Stamped Steel Pre-GalvanizedStainless Steel ScrewsNatural Finish
Third Party Certification:UL Listed:E-18095Suitable for wet locations when usedwith gaskets, Type SGN or SG onmalleable iron conduit bodies.
CSA Certified:LR-9795Suitable for wet locations when usedwith gaskets, Type SGN or SG onmalleable iron conduit bodies.
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog (inches) Number
1⁄2 BS-50S3⁄4 BS-75S1 BS-100S11⁄4-11⁄2 BS-125S
2 BS-200S21⁄2-3 BS-250S31⁄2-4 BS-350S
Type SG & SGNSolid Cover Sealing Gasket
Use:To provide a worry-free, raintight seal whenused with Type BS or BC covers.
Material: Velbuna Composition Closed-Cell NeopreneTemperature Rating: 212°F/100°C
Note: UL/CSA not applicable.
Trade Size Catalog Catalog(inches) Number Number
Velbuna Neoprene
1⁄2 SG-50 SGN-503⁄4 SG-75 SGN-751 SG-100 SGN-10011⁄4-11⁄2 SG-125 SGN-125
2 SG-200 SGN-20021⁄2-3 SG-250 SGN-25031⁄2-4 SG-350 SGN-350
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Spec 5™ Covers & GasketsFor O-Z/Gedney Malleable Iron Conduit Bodies
AB4 AB4Spec 5™ Malleable Iron Conduit Bodies
Type BS-S Type SG & SGN Type BC-G
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB5 AB5Spec 5™ Malleable Iron Conduit Bodies
Spec 5™ Covers, Gaskets & Wire GuardsFor O-Z/Gedney Malleable Iron Conduit Bodies
Type BCCClip-On™ Cover
Use:To cover conduit body opening.
Material/Finish: Gray Iron/Zinc ElectroplatedStainless Steel ScrewsSteel, Zinc-Plated Clips
Third Party Certification:UL Listed:E-18095Suitable for wet locations when used with gaskets, Type SGNC onmalleable iron conduit bodies.
CSA Certified:LR-9795Suitable for wet locations when used with gaskets, Type SGNC onmalleable iron conduit bodies.
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog (inches) Number
1⁄2 BCC-503⁄4 BCC-751 BCC-10011⁄4-11⁄2 BCC-125
2 BCC-20021⁄2-3 BCC-25031⁄2-4 BCC-350
Type SGNCCover Gasket
Use:To provide a worry-free, raintight seal whenused with Clip-On™ Type BCC cover.
Material: Closed-Cell NeopreneTemperature Rating: 212°F/100°C
Note: UL/CSA not applicable.
Trade Size Catalog (inches) Number
1⁄2 SGNC-503⁄4 SGNC-751 SGNC-10011⁄4-11⁄2 SGNC-125
2 SGNC-20021⁄2-3 SGNC-25031⁄2-4 SGNC-350
Type EWEasy-Glide™ Wire Guard
Use:To ease the job of wire pulling when usedwith O-Z/Gedney conduit bodies
Features:• Reusable• Protects wire insulation• Fits all conduit body hub configurations
Material: Spring Steel
Trade Size Catalog (inches) Number
For O-Z/Gedney Malleable Iron Conduit Bodies11⁄4-2 EW-1220S21⁄2-3 EW-2530S31⁄2-4 EW-3540S
Type BCC Type SGNC
Type EW
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB6 AB6Spec 5™ Malleable Iron Conduit Bodies
Spec 5™ Malleable Iron Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D F H J Cu. In. Conductors
LB-50 1⁄2 13⁄8 13⁄8 4 11⁄2 4 45⁄8 4.0 N/ALB-75 3⁄4 15⁄8 15⁄8 45⁄8 15⁄8 45⁄8 53⁄8 7.0 3 #6AWGLB-100 1 17⁄8 2 53⁄8 17⁄8 53⁄8 61⁄4 12.0 3 #4AWGLB-125 11⁄4 25⁄8 25⁄8 71⁄4 21⁄4 7 81⁄4 32.0 3 #2AWGLB-150 11⁄2 25⁄8 23⁄4 73⁄8 23⁄8 7 81⁄4 36.0 3 #1/0AWG
LB-200 2 31⁄4 35⁄8 95⁄8 23⁄4 91⁄8 105⁄8 70.0 3 #4/0AWGLB-250 21⁄2 43⁄8 4 123⁄8 33⁄8 115⁄8 133⁄4 142.0 3 #300MCMLB-300 3 43⁄8 43⁄4 123⁄8 35⁄8 115⁄8 133⁄4 173.0 3 #400MCMLB-350 31⁄2 55⁄8 51⁄2 15 41⁄4 14 163⁄4 292.0 3 #500MCMLB-400 4 55⁄8 55⁄8 15 41⁄4 14 163⁄4 324.0 3 #500MCM
LB-50G 1⁄2 13⁄8 13⁄8 4 11⁄2 4 43⁄4 4.0 N/ALB-75G 3⁄4 15⁄8 15⁄8 45⁄8 11⁄2 45⁄8 45⁄8 7.0 3 #6AWGLB-100G 1 17⁄8 2 53⁄8 17⁄8 53⁄8 61⁄4 12.0 3 #4AWGLB-125G 11⁄4 25⁄8 25⁄8 71⁄4 21⁄4 7 81⁄4 32.0 3 #2AWGLB-150G 11⁄2 25⁄8 23⁄4 73⁄8 23⁄8 7 83⁄8 36.0 3 #1/0AWG
LB-200G 2 31⁄4 35⁄8 95⁄8 23⁄4 91⁄8 105⁄8 70.0 3 #4/0AWGLB-250G 21⁄2 43⁄8 4 123⁄8 33⁄8 115⁄8 133⁄4 142.0 3 #300MCMLB-300G 3 43⁄8 43⁄4 123⁄8 35⁄8 115⁄8 133⁄4 173.0 3 #400MCMLB-350G 31⁄2 55⁄8 51⁄2 15 41⁄4 137⁄8 163⁄4 292.0 3 #500MCMLB-400G 4 55⁄8 55⁄8 15 41⁄2 14 163⁄4 324.0 3 #500MCM
Type LB
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D G Cu. In. Conductors
T-50 1⁄2 53⁄8 13⁄8 13⁄8 4 13⁄8 4.0 N/AT-75 3⁄4 61⁄8 15⁄8 15⁄8 45⁄8 15⁄8 7.0 3 #6AWGT-100 1 71⁄8 17⁄8 2 53⁄8 13⁄4 12.0 3 #4AWGT-125 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 21⁄4 32.0 3 #2AWGT-150 11⁄2 91⁄4 25⁄8 23⁄4 71⁄4 21⁄4 36.0 3 #1AWG
T-200 2 117⁄8 31⁄4 31⁄2 95⁄8 25⁄8 70.0 3 #2/0AWGT-250 21⁄2 151⁄8 43⁄8 4 123⁄8 35⁄8 142.0 3 #4/0AWGT-300 3 151⁄8 43⁄8 43⁄4 123⁄8 35⁄8 173.0 3 #4/0AWGT-350 31⁄2 183⁄8 51⁄2 51⁄2 15 41⁄2 290.0 3 #350MCMT-400 4 183⁄8 51⁄2 51⁄2 15 41⁄2 324.0 3 #350MCM
T-50G 1⁄2 53⁄8 13⁄8 13⁄8 4 13⁄8 4.0 N/AT-75G 3⁄4 61⁄8 15⁄8 15⁄8 45⁄8 15⁄8 7.0 3 #6AWGT-100G 1 71⁄8 17⁄8 2 53⁄8 13⁄4 12.0 3 #4AWGT-125G 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 21⁄4 32.0 3 #2AWGT-150G 11⁄2 91⁄8 25⁄8 23⁄4 71⁄4 21⁄4 36.0 3 #1AWG
T-200G 2 117⁄8 31⁄4 31⁄2 95⁄8 25⁄8 70.0 3 #2/0AWGT-250G 21⁄2 151⁄8 43⁄8 4 123⁄8 35⁄8 142.0 3 #4/0AWGT-300G 3 151⁄8 43⁄8 43⁄4 123⁄8 35⁄8 173.0 3 #4/0AWGT-350G 31⁄2 183⁄8 51⁄2 51⁄2 15 41⁄2 290.0 3 #350MCMT-400G 4 183⁄8 51⁄2 51⁄2 15 41⁄2 324.0 3 #350MCM
Type T
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB7 AB7Spec 5™ Malleable Iron Conduit Bodies
Spec 5™ Malleable Iron Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LL-50 1⁄2 13⁄8 13⁄8 4 13⁄8 4 45⁄8 4.0 N/ALL-75 3⁄4 15⁄8 15⁄8 45⁄8 15⁄8 45⁄8 53⁄8 7.0 3 #6AWGLL-100 1 17⁄8 2 53⁄8 13⁄4 53⁄8 61⁄4 12.0 3 #4AWGLL-125 11⁄4 25⁄8 25⁄8 71⁄4 21⁄4 67⁄8 81⁄4 32.0 3 #2AWGLL-150 11⁄2 25⁄8 23⁄4 71⁄4 21⁄4 67⁄8 81⁄4 36.0 3 #1AWG
LL-200 2 31⁄4 31⁄2 95⁄8 25⁄8 9 105⁄8 70.0 3 #2/0AWGLL-250 21⁄2 43⁄8 4 123⁄8 35⁄8 115⁄8 133⁄4 142.0 3 #4/0AWGLL-300 3 43⁄8 43⁄4 123⁄8 35⁄8 115⁄8 133⁄4 173.0 3 #4/0AWGLL-350 31⁄2 55⁄8 55⁄8 15 41⁄2 137⁄8 163⁄4 292.0 3 #350MCMLL-400 4 55⁄8 55⁄8 15 41⁄2 137⁄8 163⁄4 324.0 3 #350MCM
Type LL
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LR-50 1⁄2 13⁄8 13⁄8 4 13⁄8 4 45⁄8 4.0 N/ALR-75 3⁄4 15⁄8 15⁄8 45⁄8 15⁄8 45⁄8 53⁄8 7.0 3 #6AWGLR-100 1 17⁄8 2 53⁄8 13⁄4 53⁄8 61⁄4 12.0 3 #4AWGLR-125 11⁄4 25⁄8 25⁄8 71⁄4 21⁄4 7 81⁄4 32.0 3 #2AWGLR-150 11⁄2 25⁄8 23⁄4 71⁄4 21⁄4 7 81⁄4 36.0 3 #1AWG
LR-200 2 31⁄4 31⁄2 95⁄8 25⁄8 9 105⁄8 70.0 3 #2/0AWGLR-250 21⁄2 43⁄8 4 123⁄8 35⁄8 115⁄8 133⁄4 142.0 3 #4/0AWGLR-300 3 43⁄8 43⁄4 123⁄8 35⁄8 115⁄8 133⁄4 173.0 3 #4/0AWGLR-350 31⁄2 55⁄8 55⁄8 15 41⁄2 137⁄8 163⁄4 292.0 3 #350MCMLR-400 4 55⁄8 55⁄8 15 41⁄2 137⁄8 163⁄4 324.0 3 #350MCM
Type LR
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D F Cu. In. Conductors
TB-50 1⁄2 53⁄8 13⁄8 13⁄8 4 11⁄2 4.0 N/ATB-75 3⁄4 61⁄4 11⁄2 15⁄8 45⁄8 11⁄2 7.0 3 #6AWGTB-100 1 71⁄8 17⁄8 2 53⁄8 17⁄8 13.0 3 #4AWGTB-125 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 21⁄4 32.0 3 #2AWG
TB-150 11⁄2 91⁄4 25⁄8 23⁄4 71⁄4 23⁄8 36.0 3 #1AWGTB-200 2 117⁄8 31⁄8 31⁄2 95⁄8 23⁄4 70.0 3 #2/0AWG
Type TB
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AB8 AB8Spec 5™ Malleable Iron Conduit Bodies
Spec 5™ Malleable Iron Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D E Cu. In. Conductors
X-50 1⁄2 53⁄8 13⁄8 13⁄8 4 23⁄4 4.0 N/AX-75 3⁄4 61⁄8 15⁄8 15⁄8 45⁄8 31⁄8 7.0 3 #6AWGX-100 1 71⁄8 17⁄8 2 53⁄8 31⁄2 12.0 3 #4AWGX-125 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 41⁄2 32.0 3 #2AWG
X-150 11⁄2 91⁄4 25⁄8 27⁄8 71⁄4 45⁄8 36.0 3 #1AWGX-200 2 117⁄8 31⁄8 31⁄2 91⁄2 51⁄4 70.0 3 #2/0AWG
Type X
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D Cu. In. Conductors
C-50 1⁄2 53⁄8 13⁄8 13⁄8 4 4.0 N/AC-75 3⁄4 61⁄8 15⁄8 15⁄8 45⁄8 7.0 3 #6AWGC-100 1 71⁄8 17⁄8 2 53⁄8 12.0 3 #4AWGC-125 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 32.0 3 #2AWGC-150 11⁄2 91⁄4 25⁄8 23⁄4 71⁄4 36.0 3 #1AWG
C-200 2 117⁄8 31⁄8 31⁄2 95⁄8 70.0 3 #2/0AWGC-250 21⁄2 151⁄8 43⁄8 4 123⁄8 153.0 3 #4/0AWGC-300 3 151⁄8 43⁄8 43⁄4 123⁄8 181.0 3 #4/0AWGC-350 31⁄2 183⁄8 51⁄2 51⁄2 15 290.0 3 #350MCMC-400 4 183⁄8 51⁄2 55⁄8 15 320.0 3 #350MCM
Type C
Trade Size Catalog Catalog(inches) Number Number
Die-Cast Sand-Cast
⁄/™ LB-50A‹/¢ LB-75A1 LB-100A1⁄/¢ LB-125A
1⁄/™ LB-150A2 LB-200A2⁄/™ LB-250A3 LB-300A
3⁄/™ LB-350A4 LB-400A
⁄/™ T-50A‹/¢ T-75A1 T-100A1⁄/¢ T-125A
1⁄/™ T-150A2 T-200A2⁄/™ T-250A3 T-300A
3⁄/™ T-350A4 T-400A
⁄/™ LL-50A‹/¢ LL-75A1 LL-100A1⁄/¢ LL-125A
1⁄/™ LL-150A2 LL-200A2⁄/™ LL-250A3 LL-300A
3⁄/™ LL-350A4 LL-400A
⁄/™ LR-50A‹/¢ LR-75A1 LR-100A1⁄/¢ LR-125A
1⁄/™ LR-150A2 LR-200A2⁄/™ LR-250A3 LR-300A
3⁄/™ LR-350A4 LR-400A
⁄/™ C-50A‹/¢ C-75A1 C-100A1⁄/¢ C-125A
1⁄/™ C-150A2 C-200A2⁄/™ C-250A3 C-300A
3⁄/™ C-350A4 C-400A
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Aluminum Conduit Bodies
Type LR-A
Type LL-A
Aluminum Conduit Bodies For Rigid Conduit & IMC
Types LB, T, LL, LR, C
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Raintight when used with gasketed covers.• Easy-Glide™ wire guard for 21⁄2” trade sizeand larger, see Page AC5.• For covers and gaskets, see Page AC5.• Internal volume and maximum wire clearlymarked on castings.
Material/Finish: 1⁄2” - 2” Trade SizeDie-cast Copper-free Aluminum/
Aluminum Enamel21⁄2” - 4” Trade Size Sand-cast Copper-free Aluminum/
Aluminum Enamel
Third Party Certification:UL Listed: E-18095Suitable for wet locations whenused with gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations whenused with gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AC6, AC7
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Type C-A
AC1 AC1
Type LB-A
Type T-A
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Aluminum Conduit Bodies
Aluminum Conduit Bodies For Rigid Conduit & IMC
Trade Size Catalog Catalog(inches) Number Number
Die-Cast Sand-Cast
⁄/™ TB-50A‹/¢ TB-75A1 TB-100A1⁄/¢ TB-125A
1⁄/™ TB-150A2 TB-200A
⁄/™ X-50A‹/¢ X-75A1 X-100A1⁄/¢ X-125A
1⁄/™ X-150A2 X-200A
Types TB, X
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Tapered threaded hubs (NPT).• Raintight when used with gasketed covers.• Easy-Glide™ wire guard for 11⁄4” trade sizeand larger, see Page AC5.• For covers and gaskets, see Page AC5.• Internal volume and maximum wire clearlymarked on castings.
Material/Finish: 1⁄2” - 2” Trade SizeSand-cast Copper-free Aluminum/
Aluminum Enamel
Third Party Certification:UL Listed: E-18095Suitable for wet locations when usedwith gasketed covers.
CSA Certified: LR-9795 Suitable for wet locations when usedwith gasketed covers.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Page AC6 - AC7.
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
AC2AC2
Type TB-A
Type X-A
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Aluminum Conduit Bodies
Types LB, T, LL, LR, C
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:•Tapered threaded hubs (NPT)• Packaged complete under one CatalogNumber• Ready to use
Material/FinishConduit Body - Die-cast, Copper-freeAluminum with Aluminum EnamelCover - Type BS AluminumGasket - Type SGN Neoprene
Third Party Certification:UL Listed:E-18095Suitable for wet locations.
CSA Certified:LR-9795Suitable for wet locations.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AC6 - AC7.
Note: For additional information, pleaserefer to:• Conduit Bodies on page AC1.• Covers and Gaskets on page AC5.
Conduit Body, Cover & Gasket AssembliesFor Rigid Conduit & IMC
Type LB-ACG
Type LL-ACG
Trade Size Catalog(inches) Number
Die-Cast
⁄/™ LB-50ACG‹/¢ LB-75ACG1 LB-100ACG1⁄/¢ LB-125ACG
1⁄/™ LB-150ACG2 LB-200ACG
⁄/™ T-50ACG‹/¢ T-75ACG1 T-100ACG1⁄/¢ T-125ACG
1⁄/™ T-150ACG2 T-200ACG
⁄/™ LL-50ACG‹/¢ LL-75ACG1 LL-100ACG1⁄/¢ LL-125ACG
1⁄/™ LL-150ACG2 LL-200ACG
⁄/™ LR-50ACG‹/¢ LR-75ACG1 LR-100ACG1⁄/¢ LR-125ACG
1⁄/™ LR-150ACG2 LR-200ACG
⁄/™ C-50ACG‹/¢ C-75ACG1 C-100ACG1⁄/¢ C-125ACG
1⁄/™ C-150ACG2 C-200ACG
Type LR-ACG
Type C-ACG
Type T-ACG
AC3 AC3
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Type LB-TW
Type LL-TW
Trade Size Catalog Catalog(inches) Number Number
Die-Cast Sand Cast
⁄/™ LB-50A-TW‹/¢ LB-75A-TW1 LB-100A-TW
1⁄/¢ LB-125A-TW
1⁄/™ LB-150A-TW2 LB-200A-TW
2⁄/™ LB-250A-TW3 LB-300A-TW
3⁄/™ LB-350A-TW4 LB-400A-TW
⁄/™ T-50A-TW‹/¢ T-75A-TW1 T-100A-TW
1⁄/¢ T-125A-TW
1⁄/™ T-150A-TW2 T-200A-TW
⁄/™ LL-50A-TW‹/¢ LL-75A-TW1 LL-100A-TW
1⁄/¢ LL-125A-TW
1⁄/™ LL-150A-TW2 LL-200A-TW
⁄/™ LR-50A-TW‹/¢ LR-75A-TW1 LR-100A-TW
1⁄/¢ LR-125A-TW
1⁄/™ LR-150A-TW2 LR-200A-TW
⁄/™ C-50A-TW‹/¢ C-75A-TW1 C-100A-TW
1⁄/¢ C-125A-TW
1⁄/™ C-150A-TW2 C-200A-TW
Type LR-TW
Types LB, T, LL, LR, C
Use:To provide access to conductors for pulling,splicing, maintenance and future changes/upgrades. Allows connection of straightconduit runs, branch conduit runs and 90°bends.
Features:• Slotted hex head steel hardened cup-point set screw for EMT.• Easy-Glide™ Wire Guard for 21⁄2” TradeSize and larger, see Page AC5.• Internal volume and maximum wire clearlymarked on castings.• For covers and gaskets, see Page AC5.
Material/Finish: 1⁄2” - 2” Trade SizeDie-cast Copper-free Aluminum/
Aluminum Enamel21⁄2” - 4” Trade Size Sand-cast Copper-free Aluminum/
Aluminum Enamel
Third Party Certification:UL Listed:E-18095
CSA Certified:LR-9795
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Pages AC8 - AC9.
Aluminum Conduit Bodies Set Screw Type for EMT (Thinwall Conduit)
Aluminum Conduit Bodies
Type C-TW
Type T-TW
AC4AC4
Type EWEasy-Glide™ Wire Guard
Use:To ease the job of wire pulling when usedwith O-Z/Gedney conduit bodies
Features:• Reusable• Protects wire insulation• Fits all conduit body hub configurations
Material: Spring Steel
Trade Size Catalog (inches) Number
For O-Z/Gedney Sand-Cast Aluminum Conduit Bodies
11⁄4-2 EW-1220S21⁄2-3 EW-2530S31⁄2-4 EW-3540S
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Covers, Gaskets & Wire GuardsFor O-Z/Gedney Aluminum Conduit Bodies
Type BS-ADomed Top Design Cover
Use:To cover conduit body openings.
Material/Finish: Stamped Copper-free AluminumStainless Steel ScrewsNatural Finish
Third Party Certification:UL Listed:E-18095
CSA Certified:LR-9795
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Trade Size Catalog (inches) Number
1⁄2 BS-50A3⁄4 BS-75A1 BS-100A11⁄4-11⁄2 BS-125A
2 BS-200A21⁄2-3 BS-250A31⁄2-4 BS-350A
Type SG & SGNSolid Cover Sealing Gasket
Use:To provide a worry-free, raintight seal whenused with Type BS-A covers.
Material: Velbuna CompositionClosed-Cell Neoprene
Material: Temperature Rating: 212°F/100°C.
Trade Size Catalog Catalog(inches) Number Number
Velbuna Neoprene
1⁄2 SG-50 SGN-503⁄4 SG-75 SGN-751 SG-100 SGN-10011⁄4-11⁄2 SG-125 SGN-125
2 SG-200 SGN-20021⁄2-3 SG-250 SGN-25031⁄2-4 SG-350 SGN-350
Type BS-A Type SG & SGN
AC5 AC5
Type EW
Aluminum Conduit Bodies
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Aluminum Conduit Bodies
Aluminum Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LL-50A 1⁄2 11⁄4 13⁄8 4 11⁄2 35⁄8 41⁄2 4.3 N/ALL-75A 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLL-100A 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLL-125A 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWGLL-150A 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1AWG
LL-200A 2 31⁄8 33⁄8 91⁄2 25⁄8 75⁄8 101⁄8 77.5 3 #2/0AWGLL-250A 21⁄2 43⁄8 37⁄8 123⁄8 35⁄8 115⁄8 133⁄4 142.0 3 #4/0AWGLL-300A 3 43⁄8 43⁄4 123⁄8 31⁄2 115⁄8 133⁄4 173.0 3 #4/0AWGLL-350A 31⁄2 55⁄8 51⁄4 15 41⁄2 137⁄8 165⁄8 292.0 3 #350MCMLL-400A 4 55⁄8 55⁄8 15 43⁄8 137⁄8 165⁄8 324.0 3 #350MCM
Type LL-A
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LR-50A 1⁄2 11⁄4 13⁄8 4 11⁄2 35⁄8 41⁄2 4.3 N/ALR-75A 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLR-100A 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLR-125A 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWGLR-150A 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1AWG
LR-200A 2 31⁄8 33⁄8 91⁄2 25⁄8 75⁄8 101⁄8 77.5 3 #2/0AWGLR-250A 21⁄2 43⁄8 37⁄8 123⁄8 35⁄8 115⁄8 133⁄4 142.0 3 #4/0AWGLR-300A 3 43⁄8 43⁄4 123⁄8 31⁄2 115⁄8 133⁄4 173.0 3 #4/0AWGLR-350A 31⁄2 55⁄8 51⁄4 15 41⁄2 137⁄8 165⁄8 292.0 3 #350MCMLR-400A 4 55⁄8 55⁄8 15 41⁄2 137⁄8 165⁄8 350.0 3 #350MCM
Type LR-A
AC6 AC6
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D F H J Cu. In. Conductors
LB-50A 1⁄2 11⁄4 13⁄8 4 13⁄8 35⁄8 41⁄2 4.3 N/ALB-75A 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLB-100A 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLB-125A 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWGLB-150A 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1/0AWG
LB-200A 2 31⁄8 33⁄8 91⁄2 25⁄8 81⁄4 101⁄8 77.5 3 #4/0AWGLB-250A 21⁄2 43⁄8 4 123⁄8 33⁄8 115⁄8 133⁄8 142.0 3 #300MCMLB-300A 3 43⁄8 43⁄4 123⁄8 33⁄8 115⁄8 133⁄8 173.0 3 #400MCMLB-350A 31⁄2 55⁄8 55⁄8 15 41⁄4 137⁄8 163⁄4 292.0 3 #500MCMLB-400A 4 55⁄8 55⁄8 15 41⁄2 14 165⁄8 324.0 3 #500MCM
Type LB-A
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D G Cu. In. Conductors
T-50A 1⁄2 5 11⁄4 13⁄8 4 11⁄2 4.2 N/AT-75A 3⁄4 55⁄8 11⁄2 15⁄8 45⁄8 15⁄8 7.1 3 #6AWGT-100A 1 63⁄4 13⁄4 2 51⁄4 2 12.0 3 #4AWGT-125A 11⁄4 83⁄8 21⁄2 25⁄8 71⁄4 21⁄4 31.5 3 #2AWGT-150A 11⁄2 83⁄8 21⁄2 23⁄4 71⁄4 21⁄4 34.5 3 #1AWG
T-200A 2 105⁄8 31⁄8 33⁄8 91⁄2 25⁄8 75.0 3 #2/0AWGT-250A 21⁄2 151⁄8 43⁄8 4 123⁄8 35⁄8 142.0 3 #4/0AWGT-300A 3 151⁄4 43⁄8 43⁄4 123⁄8 35⁄8 182.0 3 #4/0AWGT-350A 31⁄2 181⁄4 51⁄2 51⁄4 147⁄8 43⁄8 290.0 3 #350MCMT-400A 4 181⁄8 51⁄2 51⁄2 147⁄8 43⁄8 320.0 3 #350MCM
Type T-A
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Aluminum Conduit Bodies
Aluminum Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D Cu. In. Conductors
C-50A 1⁄2 5 11⁄4 13⁄8 4 4.2 N/AC-75A 3⁄4 55⁄8 11⁄2 15⁄8 45⁄8 7.1 3 #6AWGC-100A 1 63⁄4 13⁄4 2 53⁄8 12.0 3 #4AWGC-125A 11⁄4 83⁄8 21⁄2 25⁄8 71⁄4 31.5 3 #2AWGC-150A 11⁄2 83⁄8 21⁄2 23⁄4 71⁄4 34.5 3 #1AWG
C-200A 2 105⁄8 31⁄8 33⁄8 91⁄2 75.0 3 #2/0AWGC-250A 21⁄2 151⁄8 43⁄8 4 121⁄2 153.0 3 #4/0AWGC-300A 3 151⁄8 43⁄8 43⁄4 121⁄2 181.0 3 #4/0AWGC-350A 31⁄2 181⁄4 51⁄2 51⁄2 15 290.0 3 #350MCMC-400A 4 181⁄8 51⁄2 55⁄8 15 320.0 3 #350MCM
Type C-A
AC7 AC7
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D F Cu. In. Conductors
TB-50A 1⁄2 51⁄4 11⁄4 13⁄8 4 13⁄8 4.0 N/ATB-75A 3⁄4 6 11⁄2 15⁄8 45⁄8 11⁄2 7.0 3 #6AWGTB-100A 1 71⁄4 13⁄4 2 53⁄8 17⁄8 13.0 3 #4AWGTB-125A 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 21⁄4 32.0 3 #2AWG
TB-150A 11⁄2 91⁄4 25⁄8 23⁄4 71⁄4 23⁄8 34.0 3 #1AWGTB-200A 2 117⁄8 31⁄8 31⁄2 95⁄8 23⁄4 70.0 3 #2/0AWG
Type TB-A
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D E Cu. In. Conductors
X-50A 1⁄2 53⁄8 13⁄8 13⁄8 4 23⁄4 4.0 N/AX-75A 3⁄4 61⁄8 15⁄8 15⁄8 45⁄8 31⁄8 7.0 3 #6AWGX-100A 1 71⁄8 17⁄8 2 53⁄8 31⁄2 12.0 3 #4AWGX-125A 11⁄4 91⁄8 25⁄8 25⁄8 71⁄4 41⁄2 32.0 3 #2AWG
X-150A 11⁄2 91⁄4 25⁄8 27⁄8 71⁄4 45⁄8 36.0 3 #1AWGX-200A 2 117⁄8 31⁄8 31⁄2 91⁄2 51⁄2 70.0 3 #2/0AWG
Type X-A
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AC8 AC8Aluminum Conduit Bodies
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D F H J Cu. In. Conductors
LB-50A-TW 1⁄2 11⁄4 13⁄8 4 13⁄8 35⁄8 41⁄2 4.3 N/ALB-75A-TW 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLB-100A-TW 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLB-125A-TW 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWGLB-150A-TW 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1/0AWG
LB-200A-TW 2 31⁄8 33⁄8 91⁄2 25⁄8 81⁄4 101⁄8 77.5 3 #4/0AWGLB-250A-TW 21⁄2 43⁄8 4 123⁄8 33⁄8 115⁄8 133⁄8 142.0 3 #300MCMLB-300A-TW 3 43⁄8 43⁄4 123⁄8 33⁄8 115⁄8 133⁄8 173.0 3 #300MCMLB-350A-TW 31⁄2 55⁄8 55⁄8 15 41⁄4 137⁄8 163⁄4 292.0 3 #500MCMLB-400A-TW 4 55⁄8 55⁄8 15 41⁄2 14 165⁄8 324.0 3 #500MCM
Type LB
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LL-50A-TW 1⁄2 11⁄4 13⁄8 4 11/2 35⁄8 41⁄2 4.3 N/ALL-75A-TW 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLL-100A-TW 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLL-125A-TW 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWG
LL-150A-TW 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1AWGLL-200A-TW 2 31⁄8 33⁄8 91⁄2 25⁄8 75⁄8 101⁄8 77.5 3 #2/0AWG
Type LL
Aluminum Conduit BodiesSet Screw Type for EMT (Thinwall Conduit)
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D G Cu. In. Conductors
T-50A-TW 1⁄2 5 11⁄4 13⁄8 4 11⁄2 4.2 N/AT-75A-TW 3⁄4 55⁄8 11⁄2 15⁄8 45⁄8 15⁄8 7.1 3 #6AWGT-100A-TW 1 63⁄4 13⁄4 2 51⁄4 2 12.0 3 #4AWGT-125A-TW 11⁄4 83⁄8 21⁄2 25⁄8 71⁄4 21⁄4 31.5 3 #2AWG
T-150A-TW 11⁄2 83⁄8 21⁄2 23⁄4 71⁄4 21⁄4 34.5 3 #1AWGT-200A-TW 2 105⁄8 31⁄8 33⁄8 91⁄2 25⁄8 75.0 3 #2/0AWG
Type T
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AC9 AC9Aluminum Conduit Bodies
Dimensional Data:
Dimensions in InchesCatalog Trade Volume Max No.Number Size A B C D Cu. In. Conductors
C-50A-TW 1⁄2 5 11⁄4 13⁄8 4 4.2 N/AC-75A-TW 3⁄4 55⁄8 11⁄2 15⁄8 45⁄8 7.1 3 #6AWGC-100A-TW 1 63⁄4 13⁄4 2 53⁄8 12.0 3 #4AWGC-125A-TW 11⁄4 83⁄8 21⁄2 25⁄8 71⁄4 31.5 3 #2AWG
C-150A-TW 11⁄2 83⁄8 21⁄2 23⁄4 71⁄4 34.5 3 #1/0AWGC-200A-TW 2 105⁄8 31⁄8 33⁄8 91⁄2 75.0 3 #3/0AWG
Type C
Aluminum Conduit Bodies Set Screw Type for EMT (Thinwall Conduit)
Dimensions in InchesCatalog Trade Volume Max No.Number Size B C D G H J Cu. In. Conductors
LR-50A-TW 1⁄2 11⁄4 13⁄8 4 11/2 35⁄8 41⁄2 4.3 N/ALR-75A-TW 3⁄4 11⁄2 15⁄8 45⁄8 15⁄8 41⁄4 51⁄8 7.3 3 #6AWGLR-100A-TW 1 13⁄4 2 53⁄8 2 5 61⁄8 12.2 3 #4AWGLR-125A-TW 11⁄4 21⁄2 25⁄8 71⁄4 21⁄4 61⁄2 77⁄8 34.0 3 #2AWG
LR-150A-TW 11⁄2 21⁄2 23⁄4 71⁄4 21⁄4 61⁄2 77⁄8 35.8 3 #1AWGLR-200A-TW 2 31⁄8 33⁄8 91⁄2 25⁄8 75⁄8 101⁄8 77.5 3 #2/0AWG
Type LR
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
NotesAC10 AC10
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
Mogul Conduit Bodies
Type C8X
Type LB6X
Type UB6X
Type T8X
Trade Size Catalog Catalog(inches) Number Number
Cast Iron Aluminum
1 C8X-100G C8X-100A1⁄/¢ C8X-125G C8X-125A1⁄/™ C8X-150G C8X-150A2 C8X-200G C8X-200A
2⁄/™ C8X-250G C8X-250A3 C8X-300G C8X-300A3⁄/™ C8X-350G C8X-350A4 C8X-400G C8X-400A
1 T8X-100G T8X-100A1⁄/¢ T8X-125G T8X-125A1⁄/™ T8X-150G T8X-150A2 T8X-200G T8X-200A
2⁄/™ T8X-250G T8X-250A3 T8X-300G T8X-300A3⁄/™ T8X-350G T8X-350A4 T8X-400G T8X-400A
1 LB6X-100G LB6X-100A1⁄/¢ LB6X-125G LB6X-125A1⁄/™ LB6X-150G LB6X-150A2 LB6X-200G LB6X-200A
2⁄/™ LB6X-250G LB6X-250A3 LB6X-300G LB6X-300A3⁄/™ LB6X-350G LB6X-350A4 LB6X-400G LB6X-400A
1 UB6X-100G UB6X-100A1⁄/¢ UB6X-125G UB6X-125A1⁄/™ UB6X-150G UB6X-150A2 UB6X-200G UB6X-200A
2⁄/™ UB6X-250G UB6X-250A3 UB6X-300G UB6X-300A3⁄/™ UB6X-350G UB6X-350A4 UB6X-400G UB6X-400A
Types C8X, T8X, LB6X, UB6XUse:To provide adequate access and wiringarea for pulling large and heavy conductors.
Features:• Type C8X meets NEC and CEC 8 to 1ratio.• Type T8X meets NEC and CEC 8 to 1ratio on C pulls only.• Types LB6X and UB6X meet NEC andCEC 6 to 1 ratio.• Supplied with cover and attached gasket.• Smooth integral hub bushings prevent wirepulling damage.• Raintight-suitable for use in wet locations.
Material/Finish: Cast Iron/Hot Dipped GalvanizedCopper-free Aluminum/Aluminum PaintStainless Steel ScrewsClosed-Cell Neoprene Gasket
Third Party Certification:UL Listed:E-18095Raintight-Suitable for wet locations.
CSA Certified:LR-9795 Raintight-Suitable for wet locations.
Applicable Third Party Standards:UL Standard: 514A, 514BCSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, FB-2.10
Dimensional Data:See Page AD2
Note: Conduit bodies are suitable for use inClass I, Div. 2 hazardous locations per NECSection 501.4(B).
Mogul Conduit Bodies For Rigid Conduit & IMC
AD1 AD1
Type EWEasy-Glide™ Wire GuardUse:To ease the job of wire pulling when usedwith O-Z/Gedney conduit bodies.
Features:• Reusable.• Protects wire insulation.• Fits all conduit body hub configurations.
Material: Spring Steel
Type EW
Trade Size Catalog (inches) Number
For O-Z/Gedney Mogul Conduit Bodies
1-2 EW-1220S21⁄2-3 EW-2530S31⁄2-4 EW-3540S
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AD2 AD2Mogul Conduit Bodies
Mogul Conduit Bodies For Rigid Conduit & IMC
Dimensional Data:
Dimensions in Inches
Catalog Trade AssembledNumber Size Length Height Width 8X Length
C8X-100 1 12 3 25⁄8 10C8X-125 11⁄4 121⁄16 35⁄16 25⁄8 10C8X-150 11⁄2 181⁄8 37⁄8 33⁄16 16C8X-200 2 181⁄16 47⁄16 33⁄16 16
C8X-250 21⁄2 271⁄8 53⁄16 411⁄16 24C8X-300 3 271⁄4 515⁄16 411⁄16 24C8X-350 31⁄2 353⁄8 73⁄16 511⁄16 32C8X-400 4 357⁄16 79⁄16 511⁄16 32
Type C8XG & Type C8XA
Dimensions in Inches
Catalog Trade AssembledNumber Size Length Height Width 8X Length
T8X-100 1 12 3 25⁄8 10T8X-125 11⁄4 121⁄16 35⁄16 25⁄8 10T8X-150 11⁄2 181⁄8 37⁄8 33⁄16 16T8X-200 2 181⁄16 47⁄16 33⁄16 16
T8X-250 21⁄2 271⁄8 53⁄16 411⁄16 24T8X-300 3 271⁄4 515⁄16 411⁄16 24T8X-350 31⁄2 353⁄8 73⁄16 511⁄16 32T8X-400 4 357⁄16 79⁄16 511⁄16 32
Type T8XG & Type T8XA
Dimensions in Inches
Catalog Trade AssembledNumber Size Length Height Width 6X Length
LB6X-100 1 95⁄8 35⁄8 21⁄2 71⁄2LB6X-125 11⁄4 95⁄8 35⁄8 21⁄2 71⁄2LB6X-150 11⁄2 147⁄16 55⁄8 3 12LB6X-200 2 147⁄16 55⁄8 3 12
LB6X-250 21⁄2 22 71⁄2 41⁄2 18LB6X-300 3 22 71⁄2 41⁄2 18LB6X-350 31⁄2 281⁄2 91⁄4 51⁄2 24LB6X-400 4 281⁄2 91⁄4 51⁄2 24
Type LB6XG & Type LB6XA
Dimensions in Inches
Catalog Trade AssembledNumber Size Length Height Width 6X Length
UB6X-100 1 107⁄16 37⁄8 25⁄8 71⁄2UB6X-125 11⁄4 107⁄16 43⁄16 25⁄8 71⁄2UB6X-150 11⁄2 159⁄16 51⁄8 33⁄16 12UB6X-200 2 159⁄16 53⁄4 33⁄16 12
UB6X-250 21⁄2 231⁄16 81⁄2 411⁄16 18UB6X-300 3 235⁄16 81⁄2 411⁄16 18UB6X-350 31⁄2 30 103⁄8 511⁄16 24UB6X-400 4 30 103⁄8 511⁄16 24
Type UB6XG & Type UB6XA
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE1 AE1Cast Device Boxes
Type FS & FD Single Gangwith mounting feet
Type FSL & FDL Single Gang
Type FSR & FDR Single Gang
Type FSC & FDC Single Gangwith mounting feet
Type FSS Single Gang
TypesFS - ShallowFD - Deep
Use:Accommodates wiring devices and providesopening to splice, tap or pull conductors.
Features:• Tapered threaded hubs (NPT) with integral bushings.• Both FS and FD styles are deeper than similar boxes, providing greater internal volume.• Internal grounding screw standard on all boxes.• Mounting feet standard on FS, FD, FSC,FDC, FSA and FDA styles. FS/FD boxeswithout mounting lugs may be supported by the attached conduits per NEC Section314-23(E).• Available single gang, two gang and tandem styles.• Suitable for use in wet locations whenused with gasketed covers.• Gray Iron is suitable for concrete use.• For use with FS style covers on PagesAE3 and AE4 as well as standard deviceplates made of steel, brass, bakelite, etc.
Material/Finish: Gray Iron/Zinc Electroplated/Aluminum Enamel.Copper-free Aluminum/Aluminum Enamel.
Optional Finish:Hot Dip Galvanized. Add suffix “G” to GrayIron catalog number. Contact your local representative for pricing and availability.
Third Party Certification:UL Listed:E-18095Raintight-Suitable for wet locationswhen used with gasketed covers.See pages AE3 and AE4.
CSA Certified:LR-9795Raintight-Suitable for wet locationswhen used with gasketed covers.See pages AE3 and AE4.
Dimensional Data:See page AE6.
Cast Device BoxesFor Rigid Conduit & IMC
Type FSA & FDA Single Gangwith mounting feet
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1
Suggested Specifications:Where cast device boxes are required formounting wiring devices or splicing, taps orpulling conductors, they are zinc electroplat-ed gray iron with aluminum enamel or cop-per-free aluminum. They are UL Listed andCSA Certified for wet locations when usedwith gasketed covers.
Trade Size Catalog Catalog(inches) Number Number
Gray Iron Aluminum
⁄/™ FS-1-50 FS-1-50A‹/¢ FS-1-75 FS-1-75A1 FS-1-100
⁄/™ FD-1-50 FD-1-50A‹/¢ FD-1-75 FD-1-75A1 FD-1-100
⁄/™ FSC-1-50 FSC-1-50A‹/¢ FSC-1-75 FSC-1-75A1 FSC-1-100
⁄/™ FDC-1-50 FDC-1-50A‹/¢ FDC-1-75 FDC-1-75A1 FDC-1-100
⁄/™ FSL-1-50‹/¢ FSL-1-75
⁄/™ FDL-1-50‹/¢ FDL-1-75
⁄/™ FSR-1-50‹/¢ FSR-1-75
⁄/™ FDR-1-50‹/¢ FDR-1-75
⁄/™ FSS-1-50‹/¢ FSS-1-75 FSS-1-75A
⁄/™ FSA-1-50‹/¢ FSA-1-75
⁄/™ FDA-1-50‹/¢ FDA-1-75
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE2 AE2Cast Device Boxes
Type FSCC & FDCC Single Gang
Type FSX & FDX Single Gang
Type FS-2 & FD-2 Two Gangwith mounting feet
Type FSCT & FDCT Single Gang
Trade Size Catalog Catalog(inches) Number Number
Gray Iron Aluminum
⁄/™ FSCC-1-50‹/¢ FSCC-1-75 FSCC-1-75A
⁄/™ FDCC-1-50‹/¢ FDCC-1-75
⁄/™ FSCT-1-50‹/¢ FSCT-1-751 FSCT-1-100
⁄/™ FDCT-1-50‹/¢ FDCT-1-751 FDCT-1-100
⁄/™ FSX-1-50‹/¢ FSX-1-75
⁄/™ FDX-1-50‹/¢ FDX-1-75
⁄/™ FS-2-50‹/¢ FS-2-75 FS-2-75A1 FS-2-100
⁄/™ FD-2-50‹/¢ FD-2-751 FD-2-100
⁄/™ FSC-2-50‹/¢ FSC-2-75 FSC-2-75A1 FSC-2-100
⁄/™ FDC-2-50‹/¢ FDC-2-751 FDC-2-100
‹/¢ FS-2T-75
Type FSC-2 & FDC-2 Two Gangwith mounting feet
TypesFS - ShallowFD - Deep
Use:Accommodates wiring devices and providesopening to splice, tap or pull conductors.
Features:• Tapered threaded hubs (NPT) with integral bushings.• Both FS and FD styles are deeper than similar boxes, providing greater internal volume.• Internal grounding screw standard on all boxes.• Mounting feet standard on FS, FD, FSC,FDC, FSA and FDA styles. FS/FD boxeswithout mounting lugs may be supported bythe attached conduits per NEC Section314-23(E).• Available single gang, two gang and tan-dem styles.• Suitable for use in wet locations whenused with gasketed covers.• Gray Iron is suitable for concrete use.• For use with FS style covers on PagesAE3 and AE4 as well as standard deviceplates made of steel, brass, bakelite, etc.
Material/Finish: Gray Iron/Zinc Electroplated/Aluminum Enamel.Copper-free Aluminum/Aluminum Enamel.
Optional Finish:Hot Dip Galvanized. Add suffix “G” to GrayIron catalog number. Contact your local representative for pricing and availability.
Third Party Certification:UL Listed:E-18095Raintight-Suitable for wet locationswhen used with gasketed covers.See pages AE3 and AE4.
CSA Certified:LR-9795Raintight-Suitable for wet locationswhen used with gasketed covers.See pages AE3 and AE4.
Dimensional Data:See page AE6.
Cast Device BoxesFor Rigid Conduit & IMC
Type FS-2T Tandemwith mounting feet
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1
Suggested Specifications:Where cast device boxes are required formounting wiring devices or splicing, taps orpulling conductors, they are zinc electroplat-ed gray iron with aluminum enamel or cop-per-free aluminum. They are UL Listed andCSA Certified for wet locations when usedwith gasketed covers.
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE3 AE3Cast Device Boxes
Types FS-1, FS-2
Use:To cover and seal FS and FD style boxesand to mount wiring devices.
Features:• Various styles and sizes to meet mostapplications.• Stainless Steel screws to prevent corrosion (on blank gray iron covers only).• Blank covers are weatherproof when usedwith sealing gaskets (ordered separately).See page AE4.• Covers also mount on ordinary boxes withstandard device box openings.
Material/Finish: Gray Iron/Zinc-ElectroplatedSteel/Zinc-ElectroplatedAluminum/Aluminum Enamel
Third Party Certification:UL Listed:E-18095
CSA Certified:LR-9795
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1, OS-1
Cast Device Box CoversFor FS & FD Boxes
BlankSteel
FS-1-BCS
BlankGray Iron Cast AluminumFS-1-BC FS-1-BCA
Toggle SwitchSteel
FS-1-SCS
Duplex ReceptacleSteel Gray Iron Cast Alum.FS-1-DCS FS-1-DC FS-1-DCA
Round Receptacle15⁄8 dia.. Steel 113⁄32 dia.. SteelFS-1-LRCS FS-1-SRCS
BlankSteel
FS-2-BCS
BlankGray Iron Cast AluminumFS-2-BC FS-2-BCA
Toggle SwitchSteel
FS-2-SCS
Duplex ReceptacleSteel
FS-2-DCS
Toggle Switch & Duplex Receptacle
SteelFS-2-SDCS
CatalogNumber
Single GangFS-1-BCSFS-1-BCFS-1-BCAFS-1-SCSFS-1-DCSFS-1-DCFS-1-DCAFS-1-LRCSFS-1-SRCS
Two GangFS-2-BCSFS-2-BCFS-2-BCAFS-2-SCSFS-2-DCSFS-2-SDCS
Suitable for Wet Locations When Installed With Sealing Gaskets.
Suitable for Dry Locations Only.
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE4 AE4Cast Device Boxes
Types FS-1, FS-2
Use:To cover and seal FS and FD style boxesand to mount wiring devices.
Features:• Various styles and sizes to meet mostapplications.• Stainless steel screws to prevent corrosion.• All wet location covers supplied with sealing gaskets.• Covers also mount on ordinary boxes with standard device box openings.
Material/Finish: Aluminum/Aluminum EnamelNeoprene Gaskets
Third Party Certification:UL Listed:E-18095
CSA Certified:LR-9795
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18Fed Spec: A-A-50563NEMA: FB-1
Cast Device Box Covers & GasketsSuitable for Wet Locations
Duplex ReceptacleDie-Cast Aluminum
FS-1-WDCA
Round ReceptacleDie-cast Aluminum
FS-1-WRCA
Ground Fault ReceptacleAluminum
FS-1-GFCA
Sealing GasketNeopreneFS-1-SG
Locking Toggle SwitchSand-cast Aluminum
FS-2-WSCA
Locking Toggle SwitchSand-cast Aluminum
FS-1-WSCA
Pull SwitchSand-cast Aluminum
FS-1-WPCA
Sealing GasketNeopreneFS-2-SG
CatalogNumber
Single GangFS-1-WDCAFS-1-WRCAFS-1-GFCAFS-1-SGFS-2-WSCAFS-1-WPCA
Two GangFS-2-WSCAFS-2-SG
Electrical Rating15 Amp - 125 Volts15 Amp - 250 Volts20 Amp - 125 Volts
113⁄32" Diameter
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE5 AE5Cast Device Boxes
Type OCB
Use:Provides a simple method of installingreceptacles used for head-bolt heater out-lets in cold area, recreational vehicles,parking areas, trucking terminals, etc.Replaces makeshift enclosures and is aneasy way to install outdoor wiring devices.
Features:• Easy installation.• Standard set-screw design provides easyslip-fit mounting on either unthreaded orthreaded 4” trade size rigid or IMC conduit.• Set screws allow permanent positioning ofreceptacle openings as required.• Use with standard receptacles and covers.• Has four standard FS openings whichaccommodate single, duplex and GFIreceptacles and weatherproof covers.• Corrosion resistant construction.• Compact profile.• Large volume for wiring capacity to allowfeed-thru and splices.
Material/Finish: Copper-free Aluminum/Aluminum Enamel
Third Party Certification:UL Listed:E-18095
CSA Certified:LR-9795
Applicable Third Party Standards:UL Standard: 514ACSA Standard: C22.2 No. 18
Outdoor Connection Box
Type OCB Typical Application
Dimensions in Inches
Catalog Hub Size Wiring Number Duplex A BNumber with 3 Capacity Receptacle
Set Screws (cu. inches) Openings
OCB404-SA 4 99 4 69⁄16 47⁄8
Dimensional Data:
Effective February, 2002Copyright 2002 Printed in U.S.A.
7770 N. Frontage RoadSkokie, Illinois 60077
AE6 AE6Cast Device Boxes
Cast Device BoxesFor Rigid Conduit & IMC
Dimensional Data:
Type FS & FD
Dimensions in InchesCatalog Trade Number Size A B C D E F
All FS 1⁄2 3⁄4 23⁄8 23⁄165⁄8 411⁄16 315⁄16
Type 3⁄4 3⁄4 23⁄8 23⁄163⁄4 49⁄16 313⁄16
Boxes 1 7⁄8 23⁄8 23⁄167⁄8 - -
All FD 1⁄2 3⁄4 31⁄16 27⁄8 5⁄8 411⁄16 315⁄16
Type 3⁄4 3⁄4 31⁄16 27⁄8 3⁄4 49⁄16 315⁄16
Boxes 1 7⁄8 31⁄16 27⁄8 7⁄8 - -
Internal Volume(cu. inches)
Single GangFS 21.0FD 28.0
Double GangFS 33.2FD 46.0Tandem 44.0