COVER SHEET SECTION 13, T. 44 S., R. 29 E., & SECTION 6, T. 44 S., R. 30 E., HENDRY COUNTY, FLORIDA TO SERVE "GERBER GROVES WATER CONTROL DISTRICT" SHEET INDEX COVER SHEET LOCATION MAP PS 2E(2) SITE AERIAL PS 2E(2) ELEVATION VIEW PS 3E SITE AERIAL PS 3E ELEVATION VIEW PS 5E(2) SITE AERIAL PS 5E(2) ELEVATION VIEW PS 6E SITE AERIAL PS 6E ELEVATION VIEW PS 7E SITE AERIAL PS 7E ELEVATION VIEW PS 8W SITE AERIAL PS 8W ELEVATION PS 8E SITE AERIAL PS 8E ELEVATION VIEW IRRIGATION SITE AERIAL IRRIGATION ELEVATION VIEW SHEET 1 SHEET 2 SHEET 3 SHEET 4 SHEET 5 SHEET 6 SHEET 7 SHEET 8 SHEET 9 SHEET 10 SHEET 11 SHEET 12 SHEET 13 SHEET 14 SHEET 15 SHEET 16 SHEET 17 SHEET 18 LOCATION MAP NOT TO SCALE JACKSONVILLE DAYTONA BEACH MELBOURNE - COCOA FT PIERCE WEST PALM BEACH FT LAUDERDALE MIAMI FT MYERS NAPLES ST PETERSBURG TAMPA LAKELAND ORLANDO NEW PORT RICHEY OCALA GAINESVILLE TALLAHASSEE PANAMA CITY FORT WALTON BEACH PENSACOLA TURNPIKE BEE LINE EXPRESSWAY FLORIDA S LAKE CITY BARTOW ST AUGUSTINE KEY WEST CHIPLEY DELAND PALM BEACH VILLAGE OF NORTH CLEWISTON PROJECT LOCATION SCALE: 1" = NTS SHEET 1 OF 18 DATE: 11-11-2015 REVISIONS BY DATE JOHNSON - PREWITT & ASSOCIATES, INC. ENGINEERS PLANNERS LAND SURVEYORS STATE AUTHORIZATION NUMBER LB1042, EB1042 P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com "2015 PUMP STATION REPLACEMENT PROJECT" CONSTRUCTION PLANS SECTIONS 04, 08, 16, TOWNSHIP 44 SOUTH, RANGE 30 EAST HENDRY COUNTY, FLORIDA NOVEMBER - 2015 GENERAL NOTES: THE FOLLOWING SPECIFICATIONS AND DRAWINGS IN THIS SET WILL BE THE BASIS FOR COMPARING DIFFERENT BIDS. DIFFERENT MATERIALS OR METHOD OF CONSTRUCTION MAY BE APPROVED BY THE OWNER AFTER THE CONTRACTOR IS SELECTED. CONTRACTOR AND SUBCONTRACTORS MUST OBTAIN MANUFACTURE'S CATALOGS AND PART LIST FOR ALL ITEMS INCLUDED IN THE CONSTRUCTION. EXCAVATION IS UNCLASSIFIED. CONTRACTOR RESPONSIBLE FOR OBTAINING A DEWATERING PERMIT SHOULD A DEWATERING PERMIT REQUIRED. ALL SPOT ELEVATIONS, CONTOURS AND OTHER TOPOGRAPHIC INFORMATION IS BASED ON NGVD 1929 DATUM. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING UTILITY LINES ARE NOT IMPACTED AND SHALL CALL 1-800-432-4770 PRIOR TO ANY EXCAVATION.

Upload: others

Post on 21-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

COVER SHEET

SECTION 13, T. 44 S., R. 29 E., &

SECTION 6, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

SHEET INDEX

COVER SHEET

LOCATION MAP

PS 2E(2) SITE AERIAL

PS 2E(2) ELEVATION VIEW

PS 3E SITE AERIAL

PS 3E ELEVATION VIEW

PS 5E(2) SITE AERIAL

PS 5E(2) ELEVATION VIEW

PS 6E SITE AERIAL

PS 6E ELEVATION VIEW

PS 7E SITE AERIAL

PS 7E ELEVATION VIEW

PS 8W SITE AERIAL

PS 8W ELEVATION

PS 8E SITE AERIAL

PS 8E ELEVATION VIEW

IRRIGATION SITE AERIAL

IRRIGATION ELEVATION VIEW

SHEET 1

SHEET 2

SHEET 3

SHEET 4

SHEET 5

SHEET 6

SHEET 7

SHEET 8

SHEET 9

SHEET 10

SHEET 11

SHEET 12

SHEET 13

SHEET 14

SHEET 15

SHEET 16

SHEET 17

SHEET 18

LOCATION MAP

NOT TO SCALE

JACKSONVILLE

DAYTONA BEACH

MELBOURNE -

COCOA

FT PIERCE

WEST

PALM

BEACH

FT LAUDERDALE

MIAMI

FT MYERS

NAPLES

ST PETERSBURG

TAMPA

LAKELAND

ORLANDO

NEW PORT RICHEY

OCALA

GAINESVILLE

TALLAHASSEE

PANAMA

CITY

FORT WALTON

BEACHPENSACOLA

T

U

R

N

P

I

K

E

BEE LINE

EXPRESSWAY

F

L

O

R

I

D

A

S

LAKE CITY

BARTOW

ST AUGUSTINE

KEY WEST

CHIPLEY

DELAND

PALM BEACH

VILLAGE OF NORTH

CLEWISTON

PROJECT LOCATION

SCALE: 1" = NTSSHEET 1 OF 18DATE: 11-11-2015 REVISIONS BYDATE

Scale: 1" =

xxx

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

"2015 PUMP STATION REPLACEMENT PROJECT"

CONSTRUCTION PLANS

SECTIONS 04, 08, 16, TOWNSHIP 44 SOUTH, RANGE 30 EAST

HENDRY COUNTY, FLORIDA

NOVEMBER - 2015

GENERAL NOTES:

THE FOLLOWING SPECIFICATIONS AND DRAWINGS IN THIS SET

WILL BE THE BASIS FOR COMPARING DIFFERENT BIDS.

DIFFERENT MATERIALS OR METHOD OF CONSTRUCTION MAY BE

APPROVED BY THE OWNER AFTER THE CONTRACTOR IS

SELECTED.

CONTRACTOR AND SUBCONTRACTORS MUST OBTAIN

MANUFACTURE'S CATALOGS AND PART LIST FOR ALL ITEMS

INCLUDED IN THE CONSTRUCTION.

EXCAVATION IS UNCLASSIFIED.

CONTRACTOR RESPONSIBLE FOR OBTAINING A DEWATERING

PERMIT SHOULD A DEWATERING PERMIT REQUIRED.

ALL SPOT ELEVATIONS, CONTOURS AND OTHER TOPOGRAPHIC

INFORMATION IS BASED ON NGVD 1929 DATUM.

THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING UTILITY

LINES ARE NOT IMPACTED AND SHALL CALL 1-800-432-4770

PRIOR TO ANY EXCAVATION.

Page 2: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 2 MILES SHEET 2 OF 18DATE: 11-11-2015

LOCATION MAP

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

Scale

: 1" =

2 M

IL

ES

PS 3E

STATE ROAD 80

ST

AT

E R

OA

D 2

9

SEARS ROAD

PS 6E

PS 7EPS 8W

IRRIGATION PUMP STATION

PS 5E (2) LOCATION

NORTH RESERVOIR

PS 2E(2) LOCATION

SOUTH RESERVOIR

PS 8E

Page 3: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 2E(2) PUMP STATION, CONTROL PANEL, AND OTHER ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL +/- 17,000 GPM PUMP, POWER UNIT, FRAME, GRATE, PUMP HOUSE, FUEL TANK, RIP RAP AND ANY OTHER ACCESSORIES NECESSARY FOR THE OPERATION

OF THE PUMP. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH10" MARKINGS; LABELED TO READ WATER

DEPTH IN CANAL.

FURNISH AND INSTALL FUEL TANK, 500 GALLON DOUBLE WALLED.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFF-SITE.

SCALE: 1" = 60' SHEET 3 OF 18DATE: 11-11-2015

PUMP STATION 2E(2) REPLACEMENT

SECTION 16, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

AERIAL

1"= 60'

REMOVE AND REPLACE EXISTING

DRAINAGE PUMP STATION.

FUEL TANK LOCATION TO BE

FIELD LOCATED BY OWNER

SOUTH RESERVOIR LEVEE

SOUTH RESERVOIR

SOUTH RESERVOIR LEVEE

EXISTING CULVERT

TO REMAIN

Page 4: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

1

2

PERMITTED

TOP OF LEVEE ELEV. 33.96'

1.5

1

15.0'

H.W. EL. 26.0'

L.W. EL. 22.0'

RESERVOIR

17,000 GPM PUMP CAPACITY

MATCH EXISTING

1.5

1

10

'

10' MIN.

PUMP SUMP

ELEV. 15.0'

8' M

IN

SOUTH RESERVOIR

SOUTH RESERVOIR

TOP OF LEVEE ELEV. 33.96'

CANAL BOTTOM

CANAL BOTTOM

17,000 GPM PUMP CAPACITY

10

'

RIP

R

AP

RIP

R

AP

SODDED AREA TO MEET

RIP RAP EXTENTS.

SCALE: AS SHOWN SHEET 4 OF 18DATE: 11-11-2015

PUMP STATION 2E(E) REPLACEMENT

SECTION 16, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN TO

REFUSAL

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE

FRAME, GRATE AND PUMP

HOUSE DETAIL

PROPOSED DESIGN SECTION

FLAP GATE

NOTES:

MINIMUM 9.5' TDH

17,000 GPM PUMP CAPACITY

DISCHARGE PIPE 85' IN LENGTH

FUEL TANK TO BE FIELD LOCATED DURING

INSTALLATION BY OWNER.

DISTURBED AREAS TO BE SODDED.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP.

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP

BELOW ELEVATION 15.0' IN THE BID PACKAGE.

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

EXISTING CANAL SECTION

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

Page 5: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 5 OF 18DATE: 11-11-2015

PUMP STATION 3E REPLACEMENT

SECTION 08, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

CA

NA

L 2 (G

OO

D C

AN

AL

)

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 3E PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL 16,800 GPM CAPACITY PUMP, CONTROL PANEL, FRAME, GRATE, PUMP HOUSE, AND RIP RAP AND ANY OTHER ACCESSORIES NECESSARY FOR THE

OPERATION OF THE PUMP. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL 36" X 90' CAP CULVERT WITH 10.5' F.G. RISER AND CATWALK TO RISER.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH 10" MARKING; LABELED TO READ

WATER DEPTH IN CANAL.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE & REPLACE

IRRIGATION CULVERT & RISER

REMOVE AND REPLACE EXISTING

DRAINAGE PUMP STATION

CONTROL PANEL TO BE FIELD

LOCATED BY THE OWNER

CANAL 3

Page 6: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

15.0'

1.5

1

HIGH WATER ELEVATION 26.0'

LOW WATER ELEVATION 22.0'

1.5

1

16,800 GPM PUMP CAPACITY

ROAD ELEV. 31.0'

CANAL 3

CA

NA

L 2 (G

OO

DN

O C

AN

AL)

15

'

3

1

.

0

'

3

1

.

0

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

31.0'

15

'

3

1

.

0

'

3

1

.

0

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

31.0'

36" X 90' CAP CULVERT WITH 10.5' F.G. RISER. INVERT ELEV. 18.5'

16,800 GPM PUMP

8' M

IN

10

'1

0'

10' MIN

SCALE: AS SHOWN SHEET 6 OF 18DATE: 11-11-2015

PUMP STATION 3E REPLACEMENT

SECTION 08, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN TO

REFUSAL

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE

FRAME, GRATE AND PUMP

HOUSE DETAIL

PROPOSED CANAL SECTION

FLAP GATE

NOTES:

MINIMUM 6' TDH

DISCHARGE PIPE 90' IN LENGTH

CONTROL PANEL TO BE FIELD LOCATED DURING INSTALLATION BY OWNER.

CONTROL PANEL TO BE EQUIPPED WITH SOFT START STARTER.

FLOAT TO BE INSTALLED ON INTAKE SIDE OF PUMP.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP BELOW ELEVATION 15.0' IN THE BID PACKAGE

IRRIGATION CULVERT TO BE 36" X 90' CAP CULVERT WITH 10.5' F.G. RISER, INVERT ELEV. 18.5'

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

SLOPE PUMP SUM TO

EXISTING CANAL BOTTOM

12" THICK SHELL

ROCK BASE

Page 7: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 7 OF 18DATE: 11-11-2015

PUMP STATION 5E(2) REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 5E(2) PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL +/-15,000 GPM CAPACITY PUMP, POWER UNIT, FRAME,GRATE, PUMP HOUSE, FUEL TANK, RIP RAP AND ANY OTHER ACCESSORIES NECESSARY FOR THE

OPERATION OF THE PUMP. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGHT WITH 10" MARKINGS; LABELED TO READ WATER DEPTH IN CANAL.

FURNISH AND INSTALL FUEL TANK IS TO BE 500 GALLON DOUBLE WALL TANK.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE

EXISTING PUMP STATION;

FUEL TANK LOCATION TO BE

FIELD LOCATED BY OWNER

NORTH RESERVOIR

NORTH RESERVOIR LEVEE

NO

RT

H R

ES

ER

VO

IR

LE

VE

E

Page 8: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

15.5'

NORTH RESERVOIR TOP OF

LEVEE PERMITTED ELEV. 32.44'

15,000 GPM PUMP

1

2

RESERVOIR

1

1.5

L.W. EL. 22.0'

MATCH EXISTING WIDTH

H.W. EL. 26.0'

8' M

IN

NORTH RESERVOIR

10'

10'

15,000 GPM PUMP

RIP

R

AP

RIP

R

AP

NORTH RESERVOIR LEVEE

TOP OF LEVEE ELEV. 32.44'

DISTURBED AREA TO BE

SODDED TO RIP RAP EXTENTS

10' MIN.

SCALE: AS SHOWN SHEET 8 OF 18DATE: 11-11-2015

PUMP STATION 5E(2) REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN TO

REFUSAL

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

NOTES:

MINIMUM 9' TDH

DISCHARGE PIPE 80' IN LENGTH

FUEL TANK TO BE FIELD LOCATED DURING INSTALLATION BY

OWNER.

DISTURBED AREAS TO BE SODDED.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP.

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP

BELOW ELEVATION 15.5' IN THE BID PACKAGE.

EXISTING SECTION

Page 9: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 9 OF 18DATE: 11-11-2015

PUMP STATION 6E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

C

A

N

A

L

2

(

G

O

O

D

C

A

N

A

L

)

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 6E PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL +/- 23,800 GPM PUMP, CONTROL PANEL, FRAME, GRATE, PUMP HOUSE, RIP RAP AND ANY OTHER ACCESSORIES FOR THE PUMP STATION TO OPERATION.

CONTRACTOR RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH 10" MARKINGS; LABELED TO READ WATER

DEPTH IN CANAL.

FURNISH AND INSTALL 36" X 65' CAP CULVERT WITH 9.5' F.G. RISER AND CATWALK TO RISER

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE EXISTING

DRAINAGE PUMP STATION;

CONTROL PANEL LOCATION TO

BE FIELD LOCATED BY OWNER

REMOVE & REPLACE

IRRIGATION CULVERT & RISER

CANAL 6

Page 10: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

13.0'

1.5

1

HIGH WATER ELEVATION 25.0'

LOW WATER ELEVATION 21.0'

1.5

1

ROAD ELEVATION 31.0'

23,800 GPM PUMP CAPACITY

23,800 GPM PUMP CAPACITY

CANAL 6

CA

NA

L 2 (G

OO

DN

O C

AN

AL)

ROAD ELEV. 31.0'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

31.0'

CA

NA

L B

OT

TO

M

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

IRRIGATION CULVERT INVERT 19.5'

15

'

31.0'

3

1

.

0

'

3

1

.

0

'

3

1

.

0

'

3

1

.

0

'

8' M

IN

10

'1

0'

RIP

R

AP

RIP

R

AP

10'

SCALE: AS SHOWN SHEET 10 OF 18DATE: 11-11-2015

PUMP STATION 6E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN

TO REFUSAL

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

NOTES:

MINIMUM 6' TDH

DISCHARGE PIPE 70' IN LENGTH

CONTROL PANEL TO BE FIELD LOCATED DURING INSTALLATION BY OWNER.

CONTROL PANEL TO BE EQUIPPED WITH SOFT START STARTER.

FLOAT TO BE INSTALLED ON INTAKE SIDE OF PUMP.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP

IRRIGATION CULVERT TO BE 36" X 65' CAP CULVERT WITH 9.5' F.G. RISER, INVERT ELEV. 19.5'

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP BELOW ELEVATION 13.0' IN THE BID PACKAGE.

12" THICK SHELL ROCK BASE

SLOPE PUMP SUM TO

EXISTING CANAL BOTTOM

Page 11: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 11 OF 18DATE: 11-11-2015

PUMP STATION 7E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

C

A

N

A

L

2

(

G

O

O

D

N

O

C

A

N

A

L

)

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 7E PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL 19,500 GPM CAPACITY PUMP, CONTROL PANEL, PUMP HOUSE, RIP RAP, AND ANY OTHER ACCESSORIES NECESSARY FOR THE OPERATION OF THE

PUMP. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' LENGTH WITH 10" MARKINGS, LABELED TO READ WATER

DEPTH IN CANAL.

FURNISH AND INSTALL 36" X 70' CAP CULVERT WITH 9.5' F.G. RISER AND CATWALK TO RISER.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE

DRAINAGE PUMP STATION;

CONTROL PANEL TO BE FIELD

LOCATED BY OWNER.

REMOVE & REPLACE

IRRIGATION CULVERT AND RISER

CANAL 7

Page 12: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

13.5'

MATCH EXISTING

19,500 GPM PUMP CAPACITY

ROAD ELEVATION 31.0'

19,500 GPM PUMP CAPACITY

IRRIGATION CULVERT INVERT ELEV. 19.5'

CANAL 7

CA

NA

L B

OT

TO

M

10' MIN.

CA

NA

L 2 (G

OO

DN

O C

AN

AL)

ROAD ELEV. 31.0'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

31.0'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

15

'

31.0'

3

1

.

0

'

3

1

.

0

'

3

1

.

0

'

3

1

.

0

'

10

'

10

'

RIP

R

AP

RIP

R

AP

8' M

IN

SCALE: AS SHOWN SHEET 12 OF 18DATE: 11-11-2015

PUMP STATION 7E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN TO REFUSAL

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

NOTES:

MINIMUM 6' TDH

DISCHARGE PIPE 78' IN LENGTH

CONTROL PANEL TO BE FIELD LOCATED DURING INSTALLATION BY OWNER.

CONTROL PANEL TO BE EQUIPPED WITH SOFT START STARTER ON THE INTAKE

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP

IRRIGATION CULVERT TO BE 36" X 70' CAP CULVERT WITH 9.5' F.G. RISER, INVERT ELEV. 19.5'

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP BELOW ELEVATION 13.5' IN THE BID PACKAGE.

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

SLOPE PUMP SUM TO

EXISTING CANAL BOTTOM

12" THICK SHELL ROCK BASE

Page 13: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 13 OF 18DATE: 11-11-2015

PUMP STATION 8W REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

C

A

N

A

L

2

(

G

O

O

D

C

A

N

A

L

)

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 8W PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL 14,000 GPM PUMP, CONTROL PANEL, FRAME, GRATE, PUMP HOUSE, RIP RAP AND ANY OTHER ACCESSORIES FOR THE OPERATION OF THE PUMP.

CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH 10" MARKINGS; LABELED TO READ WATER

DEPTH IN CANAL.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE

DRAINAGE PUMP STATION;

CONTROL PANEL LOCATION TO

BE FIELD LOCATED BY OWNER

Page 14: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

14,000 GPM PUMP CAPACITY

ROAD ELEVATION 30.5'

MATCH EXISTING WIDTH

14,000 GPM PUMP CAPACITY

ROAD ELEV. 30.5'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

30.5'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

30.5'

3

0

.

5

'

3

0

.

5

'

3

0

.

5

'

3

0

.

5

'

10

'

8' M

IN

10

'

RIP

R

AP

RIP

R

AP

SCALE: AS SHOWN SHEET 14 OF 18DATE: 11-11-2015

PUMP STATION 8W REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN

TO REFUSAL

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

12" THICK SHELL ROCK BASE

NOTES:

MINIMUM 6' TDH

DISCHARGE PIPE 90' IN LENGTH

CONTROL PANEL TO BE FIELD LOCATED

CONTROL PANEL TO BE EQUIPPED WITH SOFT START STARTER ON THE INTAKE

DURING INSTALLATION BY OWNER.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP

IRRIGATION CULVERT TO BE 36" X 70' CAP CULVERT WITH 9.5' F.G. RISER, INVERT 19.5'

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP BELOW ELEVATION 14.5' IN

THE BID PACKAGE.

Page 15: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 15 OF 18DATE: 11-11-2015

PUMP STATION 8E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING PS 8E PUMP STATION, CONTROL PANEL, PUMP HOUSE, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL +/-6,000 GPM PUMP, CONTROL PANEL, FRAME, GRATE, PUMP HOUSE, RIP RAP AND ANY OTHER ACCESSORIES NECESSARY FOR THE OPERATION OF THE

PUMP STATION. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH 10" MARKINGS; LABELED TO READ WATER

DEPTH IN CANAL.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE EXISTING

DRAINAGE PUMP STATION

CONTROL PANEL LOCATION TO BE

FIELD LOCATED BY OWNER

Page 16: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

15.5'

15' +/-

6,000 GPM PUMP CAPACITY

ROAD ELEV. 29.5'

6,000 GPM PUMP

15

'

SLOPE 4:1TO EXISTING

ROAD BEYOND 15'

29.5'

2

9

.

5

' 2

9

.

5

'

ROAD ELEV. 29.5'

15

'

SLOPE 4:1TO EXISTING

ROAD BEYOND 15'

29.5'

2

9

.

5

' 2

9

.

5

'

5'

5'

SCALE: AS SHOWN SHEET 16 OF 18DATE: 11-11-2015

PUMP STATION 8E REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN

TO REFUSAL

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

SLOPE TO NATURAL GROUND

EXISTING CANAL SECTION

NOTES:

MINIMUM 6' TDH

DISCHARGE PIPE 55' IN LENGTH

CONTROL PANEL TO BE FIELD LOCATED DURING INSTALLATION BY OWNER.

CONTROL PANEL TO BE EQUIPPED WITH SOFT START STARTER.

FLOAT TO BE INSTALLED ON INTAKE SIDE OF PUMP.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP.

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP BELOW ELEVATION

15.5' IN THE BID PACKAGE.

12" THICK SHELL ROCK BASE

RIP RAP

RIP RAP

Page 17: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

SCALE: 1" = 60' SHEET 17 OF 18DATE: 11-11-2015

IRRIGATION PUMP STATION REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

Scale: 1" =

60'

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

C

A

N

A

L

2

(

G

O

O

D

C

A

N

A

L

)

AERIAL

SCALE 1" = 60'

GENERAL PROJECT DESCRIPTION:

REMOVE EXISTING IRRIGATION PUMP STATION, CONTROL PANEL, FRAME, AND ASSOCIATED ACCESSORIES.

FURNISH AND INSTALL (2) 18,750 GPM PUMPS, CONTROL PANELS, FRAME, GRATE, PUMP HOUSE, RIP RAP AND ANY OTHER ACCESSORIES NECESSARY FOR THE OPERATION OF

THE PUMP STATION. CONTRACTOR IS RESPONSIBLE FOR MAKING ALL CONNECTIONS SUCH THAT THE PUMP IS OPERABLE UPON COMPLETION.

FURNISH AND INSTALL STAFF GAUGE ON INTAKE SIDE OF PUMP. STAFF GAUGE TO BE FIBERGLASS, 7" WIDE AND 8' IN LENGTH WITH 10" MARKINGS; LABELED TO READ WATER

DEPTH IN CANAL.

CONTRACTOR IS RESPONSIBLE FOR PROPERLY REMOVING AND DISPOSING OF ALL MATERIALS RESULTING FROM DEMOLITION OF THE EXISTING PUMP STATION OFFSITE.

REMOVE AND REPLACE

IRRIGATION PUMP STATION;

CONTROL PANEL LOCATION TO

BE FIELD LOCATED BY OWNER

Page 18: 2015 PUMP STATION REPLACEMENT PROJECTdnhiggins.com/docs/2015101 Construction Plans.pdf · proposed design section flap gate notes: minimum 9.5' tdh 17,000 gpm pump capacity discharge

MATCH EXISTING, 24 +/-

ROAD ELEVATION 29.5'

11.5'

(2) 18,750 GPM PUMP CAPACITY

ROAD ELEV. 29.5'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

29.5'

15

'

SLOPE 4:1TO EXISTING ROAD

BEYOND 15'

29.5'

2

9

.

5

'

2

9

.

5

'

2

9

.

5

'

2

9

.

5

'

14' M

IN

.

7' O

.C

.

12'

40'30'

18,750 GPM PUMP CAPACITY

18,750 GPM PUMP CAPACITY

SCALE: AS SHOWN SHEET 18 OF 18DATE: 11-11-2015

IRRIGATION PUMP STATION REPLACEMENT

SECTION 04, T. 44 S., R. 30 E.,

HENDRY COUNTY, FLORIDA TO SERVE

"GERBER GROVES WATER CONTROL DISTRICT"

REVISIONS BYDATE

JOHNSON - PREWITT & ASSOCIATES, INC.

ENGINEERS PLANNERS LAND SURVEYORS

STATE AUTHORIZATION NUMBER LB1042, EB1042

P.O. BOX 1029 850 WEST VENTURA AVENUE CLEWISTON, FLORIDA

PH: (863) 983-9188 FAX: (863) 983-9854 www.johnsonprewitt.com

ELEVATION VIEW

SCALE 1" = 20'

TRASH RACK

PILES DRIVEN

TO REFUSAL

PLACE FILTER FABRIC UNDER 8-12"

BOULDER RUBBLE RIP RAP 18" THICK

PLAN VIEW

SCALE 1" = 20'

MANUFACTURER TO PROVIDE FRAME,

GRATE AND PUMP HOUSE DETAIL

FLAP GATE

PROPOSED DESIGN SECTION

NOTES:

MINIMUM 9' TDH

DISCHARGE PIPE 65' IN LENGTH

CONTROL PANEL(S) TO BE FIELD LOCATED DURING

INSTALLATION BY OWNER.

CONTROL PANEL(S) TO BE EQUIPPED WITH SOFT START

STARTER.

FLOAT TO BE INSTALLED ON INTAKE SIDE OF PUMP.

STAFF GAUGE TO BE INSTALLED ON INTAKE SIDE OF PUMP.

CONTRACTOR MAY PROPOSE TO EXCAVATE PUMP SUMP

BELOW ELEVATION 11.5' IN THE BID PACKAGE.

SLOPE TO EXISTING CANAL BOTTOM

12" THICK SHELL ROCK BASE