2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 1
2012 IRC® Townhouses Design, Construction, Fire and Life Safety Provisions
2012 IRC® Townhouses Design, Construction, Fire and Life Safety Provisions
Based on the 2012 International Residential Code® (IRC®)
Welcome and Overview Welcome and Overview
Introductions Icebreaker Overview of the day
2012 IRC Townhouse Fire and Life Safety Provisions 2
Description Description
Participants will be better able to apply the fire and life/safety provisions for townhouse construction using the 2012 IRC. Addresses issues based on exterior wall and
opening protection, separation of dwelling and dwelling units and means of egress. Covers issues based on exterior wall and
opening protection, separation of dwelling and dwelling units and means of egress.
2012 IRC Townhouse Fire and Life Safety Provisions 3Page 1
ObjectivesObjectives Upon completion, participants will be better able to: Locate the townhouse fire, life and safety
provisions in the 2012 IRC. Identify fire-resistive dwelling separation in
townhouse design and construction. Apply the requirements of the IRC to townhouse
construction for garages and carports, means of egress, fire protection systems and accessibility. Explain the intent of multiple dwelling unit
separation and other life and safety provisions of the code.
2012 IRC Townhouse Fire and Life Safety Provisions 4Page 1
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 2
TownhousesTownhousesModule 1
2012 IRC Townhouse Fire and Life Safety Provisions 5
Introduction Introduction
In order for the designer of a multiple dwelling-unit project to get started with the code requirements, he or she will need to determine if his or her project fits into the scope of the IRC.
2012 IRC Townhouse Fire and Life Safety Provisions 6Workbook Page 3
Introduction Introduction
If it does not meet the scope then it will need to be designed and constructed using the IBC. The differences between the two codes will be discussed more in detail later in the program.
2012 IRC Townhouse Fire and Life Safety Provisions 7Page 5
Comparative IRC/IBC Comparative IRC/IBC
8Page 6
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 3
Comparative IRC/IBC Comparative IRC/IBC
9Page 6
Required under 2012 IRC
2012 IRC Townhouse Fire and Life Safety Provisions
R101.2 – ScopeR101.2 – Scope Apply to detached one- and two-family dwellings and
townhouses not more than three stories above gradeplane in height, with a separate means-of-egress and their accessory structures.
10Page 7
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Dwelling UnitsR202 – Dwelling Units A single unit providing
complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.
11Page 7
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Dwelling UnitsR202 – Dwelling UnitsAny building that contains one or two dwelling units used, intended or designed to be built, used, rented, leased, let or hired out to be occupied, or that are occupied for living purposes.
2012 IRC Townhouse Fire and Life Safety Provisions 12Page 8
2012 IRC Townhouse Fire and Life Safety Principles
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 4
R202 – TownhousesR202 – Townhouses A single-family dwelling
unit constructed in a group of three or more attached units in which each unit extends from foundation to roof and with a yard or public way on at least two sides.
2012 IRC Townhouse Fire and Life Safety Provisions 13Page 9
R202 – TownhousesR202 – Townhouses
Definition of townhouse Refers to a single-family dwelling unit
constructed in a group, but it does not make reference to a dwelling. Single-family dwelling unit is a single unit
providing living facilities for one or more persons. Dwelling is any building that contains one or
two dwelling units that are occupied for living purposes.
14Workbook Page 6
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – TownhousesR202 – Townhouses Definition, would eliminate the possibility of a
two-unit upper/lower dwelling, from being in a townhouse configuration because each unit could not extend from the foundation up to the roof, which is basically the location of the fire-resistive separation wall or walls.
15Page 9
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – TownhousesR202 – Townhouses Made up of three or more dwelling units. All of the dwelling units are to have a yard or
public way on two sides. The “yard or public way on at least two sides”
provision for townhouses is meant to establish an open side of the dwelling where an occupant could exit in an emergency, and emergency personnel could assist the occupant of the dwelling, if needed.
16Workbook Page 6
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 5
R202 – TownhousesR202 – Townhouses
A three-unit row-style dwelling project is proposed with each unit separated by at line is proposed. Does it meet the definition of “Townhouse”?
17Page 10
2012 IRC Townhouse Fire and Life Safety Provisions
Yes. It has three or more units, and each dwelling unit has a yard or public way on at least two sides.
R202 – TownhousesR202 – Townhouses
A three-unit row-style dwelling project with no lot line separation is proposed. Does it meet the definition of “Townhouse”?
2012 IRC Townhouse Fire and Life Safety Provisions 18Page 11
Yes. It has three or more units, and each dwelling unit has a yard or public way on at least two sides.
R202 – TownhousesR202 – Townhouses
A four-unit back-to-back style dwelling project is proposed. Does it meet the definition of Townhouse?
19Page 11
2012 IRC Townhouse Fire and Life Safety Provisions
Yes. It has three or more units, and each dwelling unit has a yard or public way on at least two sides.
R202 – TownhousesR202 – Townhouses
A six-unit back-to-back style dwelling project is proposed. Does it meet the definition of “Townhouse”?
20Page 12
2012 IRC Townhouse Fire and Life Safety Provisions
No. It has three or more units, and although the corner units have two sides open to a yard or public way, the middle units only have one side open. It cannot be constructed using the provisions in Section R302.2 of the IRC
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 6
Townhouses Townhouses
If the structure with six dwelling units shown in the figure below does not meet the definition of townhouse in the IRC, can it still be constructed using some other provision in the code?
2012 IRC Townhouse Fire and Life Safety Provisions 21Page 13
Yes. It could be designed and constructed as a series of Group R-3 dwellings using the provisions of the International Building Code (IBC).
R202 – TownhousesR202 – Townhouses
A five-unit back-to-back style dwelling project is proposed containing a single middle dwelling unit and two dwelling units at each end corner. Does it meet the definition of “Townhouse”?
22Page 14
2012 IRC Townhouse Fire and Life Safety Provisions
Yes. It has three or more units, the corner units have two sides with a yard or public way (front and side), and the middle unit has a front and rear that is open to a yard or public way (front and rear). This scenario does not change if the lot lines are removed from the example.
R202 – TownhousesR202 – Townhouses
A six-unit staggered back-to-back style project is proposed. Does it meet the definition of “Townhouse”?
23Page 15
2012 IRC Townhouse Fire and Life Safety Provisions
No. Although it has three or more units, and the outside corner units have at least two full sides open, the two interior dwelling units (B & E) both have only one full side open and a half of one side open.
R202 – TownhousesR202 – Townhouses
Why would a builder/designer want to construct a townhouse using the provisions contained in the IRC versus. those contained in the IBC?
24Page 15
2012 IRC Townhouse Fire and Life Safety Provisions
Generally, the requirements in the IBC are more restrictive and most likely more costly than those in the IRC (protection for supporting walls, no rated horizontal floor or roof assemblies, penetrations of horizontal assemblies, means of egress, fire suppression systems, etc.).
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 7
R302.2 – TownhousesR302.2 – Townhouses Each townhouse shall be considered a separate
building and shall be separated by fire-resistance-rated wall assemblies meeting the requirements of Section R302.1 for exterior walls.
Dwelling units in a townhouse building will be separated by a 1-hour fire-resistance-rated wall assemblies meeting ASTM 119 or UL 263.
25Page 15
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2 – TownhousesR302.2 – Townhouses
1-hour fire-resistance-rated wall assembly
26Page 16
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2 – TownhousesR302.2 – Townhouses Dwelling units in a townhouse are separated by
a single 1-hour assembly, where in the 2006 IRC and previous editions, dwelling units in a townhouse were separated by either two 1-hour assemblies or one 2-hour assembly.
This change coincides with the requirement for a fire sprinkler system in townhouses that will be discussed later in this program.
2012 IRC Townhouse Fire and Life Safety Provisions 27Page 16
R302.2 – TownhousesR302.2 – Townhouses Designer may consider still using the 2-hour
walls as a means to meet a specific sound transmission rating requirement in their jurisdiction.
Use of two 1-hour walls will also be discussed later in the program when constructing two attached dwelling units separated by a lot line.
28Page 16
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 8
R302.2 – TownhousesR302.2 – Townhouses What is a 1-hour fire-
resistance-rated wall? A 1-hour fire-
resistance rating refers to a wall assembly tested in accordance with ASTM E 119 or UL 263 according to Section R 302.2.
29Page 16
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2 – TownhousesR302.2 – Townhouses
Some walls are tested from both sides (symmetrical wall systems) and some walls are tested from one side only (unsymmetrical wall systems).
30Page 17
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2 – TownhousesR302.2 – Townhouses Floor/ceiling and wall assemblies are considered
to be generic materials, unless specified as a proprietary material (specific manufacturer noted in listing of the assembly).
Each proprietary system shall be built utilizing the components specified by the company or companies listed under a detailed description for that system, in other words, substitution of materials is not permitted.
31Page 17
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2 – TownhousesR302.2 – Townhouses Each of the dwelling units in
a townhouse is considered to be a “separate building.”
There is no charging language that directs the user to establish an imaginary line between the dwelling units contained in the townhouse.
32Page 18
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 9
R302.2 – TownhousesR302.2 – Townhouses User needs to establish an
imaginary line between the dwelling units if there is no real lot line between them.
If there is a lot line between the dwelling units, then imaginary lines between buildings (dwellings) need not be considered.
33Page 18
2012 IRC Townhouse Fire and Life Safety Provisions
R302 – Exterior Wall LocationR302 – Exterior Wall Location Code operates on the philosophy that an owner
will have no control over what occurs on an adjacent property, and therefore the location of all structures on the property need to be regulated, considering the rate of fire spread, intensity and duration.
2012 IRC Townhouse Fire and Life Safety Provisions 34Page 18-19
R302 – Exterior Wall LocationR302 – Exterior Wall Location Basis for provisions in the code regulating the
fire-resistive characteristics and openings in exterior walls of dwellings and townhouses when those walls are within specific distances of the lot line.
2012 IRC Townhouse Fire and Life Safety Provisions 35Page 18-19
R302 – Exterior Wall LocationR302 – Exterior Wall Location
36
2012 IRC Page 48
Page 19 2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 10
R302 – Exterior Wall LocationR302 – Exterior Wall Location
37
2012 IRC Page 49
2012 IRC Townhouse Fire and Life Safety Provisions Page 20
R302 – Exterior Wall LocationR302 – Exterior Wall Location
2012 IRC Townhouse Fire and Life Safety Provisions 38
The distances are measured at a right angle from the face of the exterior wall.
Page 20
R302 – Exterior Wall LocationR302 – Exterior Wall Location Single-family dwelling
is placed 5 feet (1524 mm) away and parallel to a lot line.
Exterior wall element is not required to be fire-resistance rated if the fire separation distance is at least 5 feet (1527 mm).
39Page 21
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
The distance measured from the building face to one of the following:1. To the closest interior
lot line, such as a lot line between two residential lots.
40Page 22
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 11
R202 – Fire Separation DistanceR202 – Fire Separation Distance
2. To the centerline of a street, an alley or public way.
41Page 23
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
3. To an imaginary line between two buildings on the same lot.
42Page 23
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Front and rear wall of the single-family dwelling are not required to be fire-resistance rated no matter how close the dwelling is to the lot line which is parallel to the gable end wall.
43Page 24
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Exterior gable end wall of the dwelling is located 5 feet (1524 mm) from a lot line.
Gable end roof overhang projects 12 inches (305 mm) beyond the face of the exterior wall, and it extends to a point 4 feet (1219 mm) from the lot line.
Table R302.1(1), this projection within 5 feet (1524 mm) of the lot line is required to be 1-hour fire-resistance-rated on the underside.
2012 IRC Townhouse Fire and Life Safety Provisions 44Page 25
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 12
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Table R302.1(2) the 1-hour fire-resistance-rated requirement for this gable-end roof overhang is reduced to 2 feet (610 mm).
Additional provision in footnote “a” brings it to 0 feet where the subdivision requires all structures to be equipped throughout with an automatic fire sprinkler system
2012 IRC Townhouse Fire and Life Safety Provisions 45Page 25
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Single family dwelling is placed 4 feet (1219 mm) from a lot line.
Exterior wall element is required to be 1-hour fire-resistance rated assembly, if the fire separation distance is less than 5 feet (1524 mm).
46Page 26
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Projections are cornices and eave overhangs, such as the gable and roof overhang, that project beyond the exterior wall.
When structures are in close proximity to a lot line these projections create problems that are a result of trapping the convected heat from a fire in an adjacent building (or dwelling).
47Page 26
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Because this trapped heat increases the hazard for the building, the code describes the location of a vertical plane which any projection may not extend beyond, and another vertical plane where projections would need to be protected on the underside.
48Page 26
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 13
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Cantilevered floors and balconies that project parallel of the lot line, such as the upper floor cantilever are not considered projections for the purpose of determining exterior wall and opening protection.
49Page 247
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Exterior wall placed 4 feet (1219 mm) from the lot line will need to be designed and constructed as a 1-hour fire-resistance-rated wall.
12-inch (305mm) gable end roof overhang is now located 3 feet (914 mm) from the lot line.
50Page 28
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
12-inch (305 mm) gable end roof projection will need a minimum fire-resistance rating of 1-hour on the underside.
2012 IRC Townhouse Fire and Life Safety Provisions 51Page 28
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Table R302.1(1) limits the amount of openings (windows and doors), in an exterior wall located between 3 feet (914 mm) and 5 feet (1524 mm) of the lot line to 25 percent of the area of the wall.
2012 IRC Townhouse Fire and Life Safety Provisions 52Page 29
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 14
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Table R302.1(1) limits the openings, such as windows, to a maximum of 25 percent of the wall area when located between 3 feet (914 mm) and 5 feet (1524 mm) of the lot line, there are no provisions for exceptions when using fire-rated glazing. 25 percent maximum cannot be increased
by the use of fire-rated glazing.
53Workbook Page 27
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Fire separation distance is less than 3 feet (914 mm), no window or door openings are allowed in the 1-hour fire-resistive-rated exterior wall.
54Page 30
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Fire Separation DistanceR202 – Fire Separation Distance
Many zoning codes would not permit a single family dwelling to be located less than 3 feet (914 mm) from a lot line, many municipalities allow zero-lot line setbacks for townhouses.
55Page 30
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two-family Dwelling R302.3 – Two-family Dwelling
What is a two-family dwelling, and what is the difference between a dwelling and a two-family dwelling?
56Page 31
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 15
R202 – Dwelling unitR202 – Dwelling unit Dwelling is a building
that contains one or two dwelling units that are occupied for living purposes
57Page 31
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two Family DwellingR302.3 – Two Family Dwelling
Two-family dwelling can have two dwelling units, also known as a
duplex, twin-home, flats, etc., that are literally contained in the same structure. Does not have a lot line between the two
dwelling units.
58Page 32
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two Family DwellingR302.3 – Two Family Dwelling
There are provisions for fire separation between the dwelling units, but if a lot line was placed between the dwelling units, it would then require separation based on the provisions for exterior walls in Table R302.1, and it would no longer be considered a two-family dwelling as described in Section R302.3.
59Page 32
2012 IRC Townhouse Fire and Life Safety Provisions
R202 – Dwelling UnitR202 – Dwelling Unit Single unit providing
complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.
60Page 32
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 16
R302.3 – Two family dwellingR302.3 – Two family dwelling Two-family dwelling is
a dwelling that contains two dwelling units that are on the same property, but these two dwelling units are not separated by a lot line.
61Page 33
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two family dwellingR302.3 – Two family dwelling Dwelling units in two-
family dwellings shall be separated from each other by wall and/or floor assemblies having not less than a 1-hour fire-resistance rating when tested in accordance with ASTM E 119 or UL 263.
62Page 33
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two family dwellingR302.3 – Two family dwelling
Penetrations of wall or floor assemblies, in two-family dwellings need to be protected in accordance with Section R302.4 to maintain the integrity of the 1-hour assembly between the two dwelling units.
2012 IRC Townhouse Fire and Life Safety Provisions 63Page 34
R302.3 – Two family dwellingR302.3 – Two family dwellingFire-resistance-rated wall assemblies in two-family dwellings shall extend to the underside of the roof sheathing and be tight against the exterior wall.
2012 IRC Townhouse Fire and Life Safety Provisions 64Page 35
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 17
R302.3 – Two family dwellingR302.3 – Two family dwelling Parapets, such as the
one, are only addressed with townhouses, which contain three or more dwelling units.
65Page 36
2012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two family dwellingR302.3 – Two family dwelling
Openings in the 1-hour fire-resistance-rated floor/ceiling assembly, can contain openings for ductwork, such as warm air supply vents and cold air return vents only if they are included in the listing of the tested assembly.
2012 IRC Townhouse Fire and Life Safety Provisions 66Page 37
R302.3 – Two family dwellingR302.3 – Two family dwelling
Exceptions:1. A fire-resistance rating of ½ hour shall be
permitted in buildings equipped throughout with an automatic sprinkler system installed in accordance with NFPA 13.
67
This exception does not allow an NFPA 13R or 13D as a substitution for the 1-hour fire-resistance-rated assembly even though both NFPA 13R and 13D address certain residential applications.
Page 372012 IRC Townhouse Fire and Life Safety Provisions
R302.3 – Two family dwellingR302.3 – Two family dwelling2. Wall assemblies need not extend through attic
spaces when the ceiling is protected by not less than 5/8-inch (16 mm) Type X gypsum board and an attic draftstop is provided above and along the wall assembly separating the dwellings. Structural framing (or walls) supporting the
ceiling shall also be protected by not less than ½-inch (12.7 mm) gypsum board or equivalent.
68Page 38
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 18
R302.3 – Two family dwellingR302.3 – Two family dwelling
Instead of installing a 1-hour fire-resistance-rated wall up to the roof sheathing to separate the two dwelling units (on the same lot).
2012 IRC Townhouse Fire and Life Safety Provisions 69Page 38
R317.1 – Two family dwellingR317.1 – Two family dwelling
There are no provisions in the code that limit openings, such as windows or doors, in the walls that support this 5/8-inch (15.9 mm) Type X gypsum board ceiling.
70Page 38
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistance-rated AssembliesFire-resistance-rated Assemblies
When using Exception 2 in Section R302.3 shown in the figure below, the code requires the walls that support the 5/8-inch (15.9 mm) Type X gypsum board ceiling of the two dwelling units, to be protected with ½ inch (12.7 mm) gypsum board.
71Page 39
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistance-rated AssembliesFire-resistance-rated Assemblies
Are these supporting walls required to be 1-hour fire-resistance-rated assemblies?
2012 IRC Townhouse Fire and Life Safety Provisions 72Page 39
No. They are only required to be protected with the ½ inch gypsum board. Openings and penetrations are also not regulated based upon this exception.
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 19
R302.3.1 – Supporting constructionR302.3.1 – Supporting construction Floor assemblies are
required to be fire-resistance-rated, such as the 1- hour fire-resistance-rated floor assembly separating upper/lower dwelling units, the supporting construction of such assemblies shall have an equal or greater fire-resistance rating.
2012 IRC Townhouse Fire and Life Safety Provisions 73Page 40
R302.3.1 – Supporting constructionR302.3.1 – Supporting construction No provisions in the
code that limit openings, such as windows in the 1-hour fire-resistance –rated supporting walls that support the 1-hour floor assembly, unless due to location on lots as noted in R302.1.
2012 IRC Townhouse Fire and Life Safety Provisions 74Page 40
R302.3.1 – Supporting constructionR302.3.1 – Supporting construction
Could a door opening be placed in the 1-hour fire-resistance-rated assembly between the dwelling units in a two-family dwelling as a means for the occupants of each dwelling unit to access each other’s dwelling unit such as shown?
2012 IRC Townhouse Fire and Life Safety Provisions 75Page 41
R302.3.1 – Supporting constructionR302.3.1 – Supporting construction
Families want to live next to their elderly parents, where they may want to have access in the event of an emergency, yet maintain some level of privacy otherwise, could they access through a door opening in the 1-hour wall between the dwelling units?
76Page 41
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 20
Two attached single-family dwellings separated by a lot line.Two attached single-family dwellings separated by a lot line. Code clearly addresses single-family
dwellings, two-family dwellings and townhouses when it comes to the fire resistance of exterior walls and opening protection limitations; although, the construction of two attached single-family dwellings constructed with a lot line separation are not so clearly noted.
2012 IRC Townhouse Fire and Life Safety Provisions 77Page 42
Two attached single-family dwellings separated by a lot line.Two attached single-family dwellings separated by a lot line. Two attached single-family
dwellings are constructed with a lot line between the two dwellings, they are not considered two-family dwellings because two-family dwellings are not separated by a lot line, and they are not considered townhouses because townhouses are constructed in groups of three or more dwelling units.
78Page 42
2012 IRC Townhouse Fire and Life Safety Provisions
Two attached single-family dwellings separated by a lot line.Two attached single-family dwellings separated by a lot line. Two single family dwellings
are attached, yet separated by a lot line, they are considered two separate dwellings, not a two-family dwelling. Because of this lot line separation, each of these two attached single-family dwelling units need exterior wall and opening protection as required in Section R302.1.
79Page 43
2012 IRC Townhouse Fire and Life Safety Provisions
Two attached single-family dwellings separated by a lot lineTwo attached single-family dwellings separated by a lot line A lot line separating the
two attached single-family dwellings, each of these two attached single-family dwelling units will need to provide exterior wall and opening protection as noted in Section R302.1.
80Page 43
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 21
Two attached single-family dwellings separated by a lot lineTwo attached single-family dwellings separated by a lot line No provisions in the IRC that permit a reduction
in the two 1-hour fire-resistance-rated walls between two attached single-family dwelling units separated by a lot line.
No provisions that permit the use of a single 2-hour fire-resistance-rated wall instead of the required two 1-hour fire-resistance-rated walls.
81Page 43
2012 IRC Townhouse Fire and Life Safety Provisions
Two attached single-family dwellings separated by a lot lineTwo attached single-family dwellings separated by a lot line Townhouses require one 1-hour fire-resistance-
rated wall between the dwelling units of the townhouse, whether a lot line exists or not.
This is based somewhat on the requirement for a residential fire sprinkler system.
An automatic residential fire sprinkler system is required for townhouses and for one- and two-family dwellings.
82Page 44
2012 IRC Townhouse Fire and Life Safety Provisions
Fire separation - Scenario 1Fire separation - Scenario 1 A designer has proposed two
attached, single-family dwellings separated by a lot line.
A concrete/masonry exterior foundation wall around the exterior perimeter of these two dwellings except at the common wall location between the dwellings.
Foundation plan indicates a post and beam support along the lot line in the crawl space between these two dwelling units.
83Page 45
2012 IRC Townhouse Fire and Life Safety Provisions
Fire separation -Scenario 1Fire separation -Scenario 1 Post and beam system in the
crawl space between the dwelling units will be draft stopped as proposed by the designer as a means to provide fire separation between the two dwelling units in the crawl space.
Will this draftstop and post beam system meet the minimum code requirements for the required fire-resistance-rated separation between the dwelling units in the crawl space?
84Page 45
2012 IRC Townhouse Fire and Life Safety Provisions
No. The exterior wall and opening protection is to extend from the foundation to the roof sheathing at the lot line, and so the two 1-hour fire-resistance-rated walls need to extend down through the crawl space to the footing/foundation.
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 22
Fire separation -Scenario 2Fire separation -Scenario 2
A designer has proposed the four-unit townhouse as shown in the figures below.
There is a concrete/masonry exterior foundation wall around the exterior perimeter of the entire townhouse structure.
2012 IRC Townhouse Fire and Life Safety Provisions 85
Fire separation -Scenario 2Fire separation -Scenario 2
Four dwelling units rest above a crawl space and are separated from each adjoining dwelling unit in the crawl space by an open post and beam system.
The designer has proposed the installation of a draftstop in the crawl space in line with the two 1-hour rated wall assemblies above as a means to separate the dwelling units.
2012 IRC Townhouse Fire and Life Safety Provisions 86Page 46-47
Fire separation -Scenario 2Fire separation -Scenario 2
Will this draftstop meet minimum code requirements for the separation between the dwelling units?
No. The exterior wall protection needs to extend from the foundation to the roof sheathing, and as such, the draftstop would not provide this required separation.
2012 IRC Townhouse Fire and Life Safety Provisions 87Page 46-47
Fire separation Fire separation
88Page 48
2012 IRC Townhouse Fire and Life Safety Provisions
Designer of the four unit townhouse has resubmitted a plan of the crawl space area for the approval of the building official, where the concrete/masonry foundation wall with a 2-hour minimum fire-resistance rating separates each dwelling unit in the crawl space area.
Will this comply with code?
Yes, as long as the details of the 2-hour fire-resistance-rated assembly comply withthe listing or manufacturer’s installation instructions.
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 23
Fire separation Fire separation
2012 IRC Townhouse Fire and Life Safety Provisions 89Page 49
Designer of the four unit townhouse has submitted an alternate plan of the crawl space area for the approval of the building official, where two 1-hour fire-resistance-rated walls separate each of the dwelling units in the crawl space area.
Will this comply with code?
Yes, they would comply as long as the details of the two 1-hour fire-resistance-ratedassemblies comply with the listing.
R302.2 – TownhousesR302.2 – Townhouses At this common wall
location between dwelling units, there may be a lot line, or it may have been designed using imaginary lot lines based on the definition of fire separation distance.
2012 IRC Townhouse Fire and Life Safety Provisions 90Page 50
R302.2 – TownhousesR302.2 – Townhouses Exception: A common 1-
hour fire-resistance-rated wall assembly tested in accordance with ASTM E 119 or UL 263 is permitted for townhouses if such walls do not contain plumbing or mechanical equipment, ducts or vents in the cavity of the common wall.
2012 IRC Townhouse Fire and Life Safety Provisions 91Workbook Page 51
R302.2 – TownhousesR302.2 – Townhouses Reduction of the common wall separation from
two hours in the 2006 IRC and earlier, to one hour between dwelling units is based on the 2012 IRC provision in Section R313 that requires townhouses to have an automatic fire sprinkler system.
92Page 51
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 24
R302.1 – Exterior walls R302.1 – Exterior walls Although the Exception to Section R302.2 allows
a single 1-hour fire-resistance-rated wall between dwelling units within townhouses that contain automatic fire sprinkler systems, some townhouse designs may include traditional double-walls between the dwelling units either because of adopted sound transmission standards or as the designer/builder’s choosing.
93Workbook Page 46
2012 IRC Townhouse Fire and Life Safety Provisions
R302.1 – Exterior walls R302.1 – Exterior walls Townhouse designs may
include traditional double-walls between the dwelling units either because of adopted sound transmission standards or as the designer/builder’s choosing.
Some of the drawings will indicate single 1-hour walls, and some will indicate the optional double 1-hour walls.
94Workbook Page 51
2012 IRC Townhouse Fire and Life Safety Provisions
R302.1 – Exterior walls R302.1 – Exterior walls IRC does address exterior wall and opening
protection for dwelling units and townhouses because of the location on lot, there are no requirements in the IRC for the overall construction type to be anything other than nonrated construction throughout.
Unless specifically required by other provisions of the code, the combustible framing could literally be left exposed.
95Workbook Page 52
2012 IRC Townhouse Fire and Life Safety Provisions
R302.1 – Exterior walls R302.1 – Exterior walls No code provisions in the IRC that would limit
the maximum square footage of either a dwelling or the individual dwelling unit within the townhouse structure or the maximum square footage of the townhouse as a group.
There are also no provisions that require more than one exit, or that limit travel distance.
96Workbook Page 52
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 25
Exterior Wall ConstructionExterior Wall ConstructionModule 2
2012 IRC Townhouse Fire and Life Safety Provisions 97
Exterior Wall Construction Exterior Wall Construction Each of the dwelling
units in this townhouse has an exterior wall located with a fire separation distance of less than 5 feet (1524 mm).
Walls need to meet the requirements of Section 302.1 and Table 302.1
98Page 53
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Common wall or walls between the dwelling
units need to be constructed as a minimum 1-hour fire-resistance rating in townhouses with automatic fire sprinkler systems.
Openings in this wall are not permitted (such as windows and doors).
99Page 53
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Designer needs to
submit a design for the exterior wall (or walls) that includes sufficient information and details to allow a determination as to the fire-resistance rating along with all of the components that make up the wall assembly.
100Page 53
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 26
Exterior Wall Construction Exterior Wall Construction The wall assembly on the plan should reflect the
exact information noted in the submitted listed assembly, including, but not limited to: File number assigned by the listing agency. It is not
uncommon to find a design for a suggested fire-resistance-rated wall assembly noted on a plan that lacks this key element.
Fire rating needs to be indicated as an hourly designation, such as ½ hour, 1-hour, 2-hour, 3-hour or 4-hour fire-resistive-wall assembly.
101Page 54
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Sound rating. Sound Transmission, is
adopted by the municipality, the air-borne sound insulation for wall and floor/ceiling assemblies shall meet a Sound Transmission Class (STC) rating of 45 when tested in accordance with ASTM E 90.
2012 IRC Townhouse Fire and Life Safety Provisions 102Page 54
Exterior Wall Construction Exterior Wall Construction Penetrations need to
maintain this rating as it needs to be airtight.
Substituting mechanical fasteners for designed adhesives, or the use of more fasteners, may affect the rating.
2012 IRC Townhouse Fire and Life Safety Provisions 103Page 54
Exterior Wall Construction Exterior Wall Construction Stud width and spacing. Although the code
permits stud spacing up to 24 inches (610 mm) on center, a fire-resistance-rated-wall assembly may require stud spacing at 16 inches (406 mm) on center. This is important to recognize if the wall stud spacing is increased based on green building value engineering principles. The listing may actually contain a staggered-stud configurations.
Thickness of gypsum board.
104Page 55
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 27
Exterior Wall Construction Exterior Wall Construction Type of gypsum board. Regular gypsum board is
made of a noncombustible core material typically with a paper face and back paper comprised of newsprint and post-consumer waste materials. Type X gypsum board has superior fire resistance with the addition of glass fibers and vermiculite in the gypsum board. Improved Type X, also known as proprietary Type C gypsum board, has a higher level of fire resistance because of the formulations of material in the product.
105Page 56
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Generic or proprietary brand of gypsum board.
Some listed wall assemblies use a proprietary brand of gypsum board, and as such, the user of the particular assembly may not substitute other brands of gypsum, even if the same thickness and type of gypsum board are used.
Orientation of gypsum board (parallel or perpendicular to framing).
Fastener type (nail or screw).
106Page 56
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Fastener length, head diameter and shank
diameter. Joint offset if required. An assembly may require
the gypsum board to be staggered at least one framing member from the adjacent sheet of gypsum board, particularly when using double-thickness applications.
Other information as required.
107Page 56
2012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction
It is unlikely that a listed assembly will reference staples for fasteners, the building official could allow the use of staples if testing indicated the staples provided the same holding power as the required nails or screws under fire conditions.
108Workbook Page 50
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 28
Exterior Wall Construction Exterior Wall Construction
Code does not refer to a minimum or maximum joint spacing between the sheets of the gypsum board, reference should be made to both the manufacturer of the gypsum board for recommendations and to the listing of the assembly for additional requirements.
109Page 56
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive-rated Wall ConstructionFire-resistive-rated Wall Construction
110Page 57
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive-rated Wall ConstructionFire-resistive-rated Wall Construction
1. Can nails be substituted for screws, or screws substituted for nails, when installing gypsum board that is part of a fire-resistance-rated wall assembly?
111Page 57
2012 IRC Townhouse Fire and Life Safety Provisions
1. Yes, for some listings, but not all. Refer to the listing agency for recommendations or requirements regarding substitutions. Normally, substitutions cannot be made unless specifically noted in the listing or by the listing agency. For example, the Gypsum Association's Fire Resistance Design Manual allows nails that comply with ASTM C 514 or ASTM F 547, that are suitable for the intended use and having dimensions not less than those specified in the manual to be permitted as a substitution. It also allows screws meeting ASTM C 1002 to be permitted to be substituted for the prescribed nails, one for one, when the length and head diameter of the screws equal or exceed those of the nails specified in the tested system. Substitutions of fasteners should also be approved prior to installation by the building official.
Fire-resistive-rated Wall ConstructionFire-resistive-rated Wall Construction
2. Could a designer propose fire-resistance-rated wall assemblies contained in Chapter 7 of the IBC for use in dwellings constructed using the provisions of the IRC, such as noted in the table below?
YES
112Page 57
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 29
Exterior Wall Construction Exterior Wall Construction
1-hour fire-resistance-rated wall needs to extend into the soffit area at the roof overhang in buildings with continuous soffits. Does the listing for the wall assembly
recognize this application? It may not.
113Page 58
2012 IRC Townhouse Fire and Life Safety Provisions
Building official will need to make a determination if this soffit area complies with the intent of the code and the listed assembly.
Critical to verify that the gypsum board is properly fastened into framing members during construction.
Is there a lookout framed into the bottom of the soffit that will provide this nailing surface at all sides?
Bottom of the soffit needs to be tight against this 1-hour fire-resistance-rated assembly.
2012 IRC Townhouse Fire and Life Safety Provisions 114Page 58
Exterior Wall Construction Exterior Wall Construction
1152012 IRC Townhouse Fire and Life Safety Provisions
Exterior Wall Construction Exterior Wall Construction Fire-resistance-rated walls require an inspection
as noted in Section R109. Affords the building inspector the opportunity to
evaluate the assembly from top to bottom, including the extension of the fire-resistance-rated assembly in the attic, to the exterior wall and into the soffit area.
116Page 58
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 30
R302.2.1 – Continuity R302.2.1 – Continuity The fire-resistance-rated wall or assembly
separating the townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab.
117Workbook Page 532012 IRC Townhouse Fire and Life Safety Provisions
R302.2.1 – Continuity R302.2.1 – Continuity A 1-hour fire-resistance-rated wall assembly extends from the front to back between the dwelling units and also the attached garages of the dwelling units.
2012 IRC Townhouse Fire and Life Safety Provisions 118Page 59
R302.2.1 – Continuity R302.2.1 – Continuity Lot line or imaginary line between the dwelling
units must extend to the centerline of a street, alley or public way.
No openings, such as windows or doors, are permitted in this 1-hour fire-resistance-rated common walls.
Fire-resistance-rated walls between the dwelling units are not required to extend between the decks at the rear of the structure, as the decks are not considered to be accessory structures.
119Page 60
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.1 – Continuity R302.2.1 – Continuity Designer of this four unit
townhouse, chooses to install an 8-foot-high (2438 mm) wood privacy wall between the rear decks of the dwelling units, this privacy wall can be installed of combustible materials with no fire-resistance rating, as code does not require the 1-hour fire-resistance-rated wall to extend between the decks, as it only needs to extend to the rear of the dwelling.
120Page 60
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 31
R302.2.2 – ParpetsR302.2.2 – Parpets Constructed in
accordance with Section R302.2.3.
Constructed as an extension of the fire-resistance-rated wall separation between dwelling units that serve as a means of limiting the spread of fire from dwelling unit to dwelling unit.
121Page 61
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.3 – Parapet constructionR302.2.3 – Parapet construction
Have the same fire-resistance rating as that required for the supporting wall or walls.
On any side adjacent to a roof surface, the parapet shall have noncombustible faces for the uppermost 18 inches (457 mm), to include counterflashing and coping materials.
122Page 62
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Constructed for townhouses as an extension of exterior walls or common walls as follows:1. Where roof surfaces
adjacent to the wall or walls are not at the same elevation, the parapet needs to extend not less than 30 inches (762 mm) above the roof surfaces, item 1.
123Page 62
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
2. Where roof surfaces adjacent to the wall or walls are at different elevations and the higher roof is not more than 30 inches (762 mm) above the lower roof, the parapet shall extend not less than 30 inches (762 mm) above the lower surface, item 2.
124Page 63
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 32
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Exception (to Item 2) Is not required in the
two cases above when the roof is covered with a minimum Class C roof covering, and the roof decking or sheathing is of noncombustible materials
125Page 63
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.3 – Parapet constructionR302.2.3 – Parapet construction
Approved fire-retardant-treated wood for a distance of 4 feet (1219 mm) on each side of the wall or walls.
One layer of 5/8-inch (16 mm) Type X gypsum board is installed directly beneath the roof decking or sheathing.
126Page 63
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Supported by a minimum of nominal 2-inch (51 mm) ledgers attached to the sides of the roof framing members.
A minimum distance of 4 feet (1219 mm) on each side of the wall or walls
127Page 63-64
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Class C roof covering is not readily flammable and affords a measurable degree of fire protection to the roof deck. The shingle package should be labeled to indicate Class C (or better, such as Class B or Class A).
Noncombustible generally refers to a metal, concrete or poured gypsum deck surface.
128Page 64
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 33
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Fire-retardant-treated plywood Pressure-treated with fire-retardant salts to inhibit
combustion in accordance with American Wood Protection Association (previously known as “the American Wood Preservers Association”) Standard U1 to have a flame spread index of 25 or less when subjected to a 30-minute fire test. Some of the chemical treatments may reduce the structural capacity of the plywood, and recommendations should be obtained from the manufacturer and treating service to verify any reductions in span ratings.
129Page 64
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
One layer of 5/8-inch (15.9 mm) gypsum board could be laid on top of the roof framing members, but the design of the roof framing members need to compensate for the 5/8-inch (15.9 mm) difference in the level of the roof sheathing or decking and for the additional weight of the gypsum board.
130Page 65
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
One layer of 5/8-inch (51 mm) gypsum board could be installed between the roof framing members directly below the nonfire retardant roof decking or sheathing with 2 x ledgers fastened to the roof framing members. There are no provisions in the code that address sealing of any gap that may occur between the gypsum board and the roof framing member .
131Page 65
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
3. A parapet is not required where roof surfaces adjacent to the wall or walls are at different elevations and the roof is more than 30 inches above the lower roof, Item 3.
132Page 65
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 34
R302.2.2 – Parapet constructionR302.2.2 – Parapet construction
Common wall construction from the lower roof to the underside of the higher roof deck, shall have not less than a 1-hour fire-resistance rating. The wall shall be rated from exposure from both sides.
Because both of the walls are less than 3 feet (914 mm) from the lot line between the dwelling units, no openings for windows or doors are permitted.
2012 IRC Townhouse Fire and Life Safety Provisions 133Page 65-66
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence Each individual townhouse shall be structurally
independent. Objective of structural independence is that a
collapse due to a fire in one individual dwelling within the townhouse will not cause the failure of an adjoining dwelling.
1342012 IRC Townhouse Fire and Life Safety Provisions Page 67
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence Exceptions:
1. Foundations supporting exterior walls or common walls. This would allow a single concrete or masonry foundation wall, to support two separate wall assemblies between the dwelling units.
135Page 66-68
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence2. Structural roof and wall sheathing from each
unit may fasten to the common wall framing. This provision allows the structural roof and wall sheathing to run past the common wall area as it is arguably more important than the ability of the wall sheathing to carry the fire horizontally along the roof or wall.
3. Nonstructural wall covering, such as siding products, may extend over the common wall area without requiring a break or control joint.
136Workbook Page 61
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 35
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence4. Flashing of roof
covering materials is permitted over the common wall area.
137Page 67-68
2012 IRC Townhouse Fire and Life Safety Provisions
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence5. Townhouses separated
by a common 1-hour fire-resistance-rated wall, are exempt from the structural independence provisions of this section. There are no specific requirements that address the ability of the framing members to break away in the event of a fire.
138Page 67-68
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4 Dwelling unit rated penetrationsR302.4 Dwelling unit rated penetrations Penetrations of wall
or floor/ceiling assemblies required to be fire-resistance rated shall be protected accordingly to this section to maintain the integrity of the fire-resistance-rated assembly.
139Page 68
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4 Dwelling unit rated penetrationsR302.4 Dwelling unit rated penetrations
Apply to penetrations of fire-resistive-rated walls and floor/ceiling assemblies that are part of the dwelling unit separation in either a two-family dwelling or in dwelling units in townhouses. Addresses all of the combustible piping
and tubing, ductwork, and other equipment that may pass in or through the wall or floor assembly.
140Page 68
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 36
R302.2.4 – Structural IndependenceR302.2.4 – Structural Independence
If the penetration of a rated assembly is not properly constructed, the assembly itself is jeopardized and may not perform as intended. The method of penetration needs to be
identified, such as membrane or through penetration, and a means to protect it needs to be evaluated.
141Page 68
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1 – Through penetrationsR302.4.1 – Through penetrations
Through penetration is an opening that passes through the entire fire-resistance-rated wall assembly, such as for a pipe, conduit or similar material that compromises the integrity of the assembly. Through penetrations need to comply with this section.
142Page 69
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1 – Through penetrationsR302.4.1 – Through penetrations
1. In concrete or masonry wall or floor assemblies, where the penetrating item is a maximum 6 inches (152 mm) nominal diameter and the area of the opening through the wall does not exceed 144 square inches (92 900 m2), concrete, grout or mortar is permitted where installed to the full thickness of the wall or floor assembly or the thickness required to maintain the fire-resistance rating.
1432012 IRC Townhouse Fire and Life Safety Provisions Page 69
R302.4.1 – Through penetrationsR302.4.1 – Through penetrations
2. Material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 or UL 263 time temperature fire conditions.
This allows the designer some flexibility to look at other materials besides concrete, grout or mortar to fill the annular space around the metal pipe penetration.
144Page 70
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 37
R302.4.1 – Through penetrationsR302.4.1 – Through penetrations
The exception previously noted for through penetrations of concrete or masonry floors will only apply for the separation between two dwelling units in a dwelling; it will not occur in a townhouse situation.
145Workbook Page 63
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1 – Through penetrationsR302.4.1 – Through penetrations
A townhouse has no provisions that allow one-dwelling unit above another dwelling unit. A two-story dwelling unit within a
townhouse does not require any fire-resistance-rated floor assembly between the first and second floor.
146Workbook Page 63
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1.1 – Fire Resistance-rated-assemblyR302.4.1.1 – Fire Resistance-rated-assembly Penetrations shall be installed as tested in the
approved fire-resistance-rated assembly. When constructing a tested/listed wall assembly
for example, that all of the penetrations need to be installed exactly according to the way they were installed based on the fire test and that no substitutions are to be made to the assembly.
147Page 70
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1.2 – Penetration firestop systemR302.4.1.2 – Penetration firestop system Protected by an approved penetration firestop
system installed as tested in accordance with ASTM E 814 or UL 1479 and shall have an F rating of not less than the required fire-resistance rating of the wall penetrated.
148Page 70
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 38
R302.4.1.2 – Penetration firestop systemR302.4.1.2 – Penetration firestop system “F” (flame) rating indicates the time period, in
hours, that the through-penetration fire-stop system remained in place without allowing the passage of fire during the fire exposure test.
F rating needs to be at least equal in hours to the required fire-resistance-rated wall assembly.
149Page 70
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.1.2 – Penetration firestop systemR302.4.1.2 – Penetration firestop system
When a penetrating material is something other than a metal pipe, such as a plastic water pipe or plastic-coated electrical conduit, the designer will need to look for a firestop system for that plastic pipe penetration that will maintain the fire-resistance rating.
150Page 70
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations An opening that passes
through only one side of a fire-resistance-rated wall assembly, such as for a pipe, conduit, receptacle box or similar material that compromises the integrity of the assembly.
Membrane penetrations need to comply with this section.
151Workbook Page 65
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations Where walls or a
ceiling need to have a fire-resistance-rating, recessed fixtures need to be installed such that the required fire resistance will not be reduced.
152Page 71
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 39
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations Exceptions:
1. Membrane penetrations of maximum 2-hour fire-resistance-rated walls and partitions, are allowed for steel electrical boxes that do not exceed 16 square inches (0.0103 m2) in area [typically this means a 2-gang electrical box, because a 3-gang box exceeds 16 square inches (0.0103 m2) provided the aggregate area of the opening through the membrane does not exceed 100 square inches (0.0645 m2)].
1532012 IRC Townhouse Fire and Life Safety Provisions Page 712012 IRC Townhouse Fire and Life Safety Provisions
R304.4.2 – Membrane penetrationsR304.4.2 – Membrane penetrations Annular space between the wall membrane and
the box shall not exceed 1/8 inch (3.1 mm). Actual annular space exceeds this provision,
some other means to protect the opening around the metal box will be needed.
154Page
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations Electric boxes are installed in a stud cavity, there
exists the possibility of fire, smoke and hot gases, along with sound, to travel between the dwelling units.
Boxes on opposite sides of the stud wall need to be separated as follows:
155Page 72
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations1.1 By a horizontal distance of not less than 24
inches (610 mm) where the wall or partition is constructed with individual noncommunicating stud cavities, which is usually the maximum the studs could be spaced in most listed assemblies, except at walls or partitions constructed using parallel rows of studs or staggered studs;
156Page 72
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 40
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations1.2 By a horizontal distance of not less than the
depth of the wall cavity when the wall cavity is filled with cellulose loose-fill, rockwool or slag mineral wool (fiberglass) insulation. This specific provision does not recognize the use of spray-applied foam plastic insulation as a means to separate the boxes;
157Page 72
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations1.3 By solid fireblocking. Section R302.11 contains
a list of fireblocking materials that could be used to separate the boxes;
1.4 By protecting both boxes with listed putty pads; or
1.5 By other listed materials and methods.
158Page 72
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations2. Listed electrical boxes of any materials, other than
the steel electrical boxes previously noted, provided the boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. This provision generally refers to plastic electrical boxes that have been tested for use in fire-resistance-rated assemblies. Typically, there will be a UL marking on the inside of the box that indicates the hourly rating of the particular box.
159Workbook Page 66
2012 IRC Townhouse Fire and Life Safety Provisions
R302.4.2 – Membrane penetrationsR302.4.2 – Membrane penetrations3. The annular space
created by the penetration of a fire sprinkler provided it is covered by a metal escutcheon plate.
160Page 73
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 41
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 1 The plan view of a four-unit
townhouse, there is a lot line that separates dwelling unit “B” from dwelling unit “C,” and it extends in both North and South to a public way. The East wall of the garage is 4 feet (1219 mm) from the lot line.
161Page 74
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
1. Is this East wall of the attached garage B required to be fire-resistance-rated because it is 4 feet (1219) from the lot line?
162Page 74
2012 IRC Townhouse Fire and Life Safety Provisions
Yes. Table R302.1 requires a minimum of 1-hour fire-resistance-rated construction if the fire separation distance is less than 5 feet (1524 mm). This provision requires the wall to be listed with exposure from both sides.
Fire-resistive Wall ConstructionFire-resistive Wall Construction
2. Are window openings permitted in this same wall?
Yes. Openings, such as windows and doors, are permitted as long as they do not exceed 25 percent of the wall area.
163Page 74
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 2 Is the rear elevation of the
same four-unit townhouse The parapet exception was
used between the dwellings at the “common walls,” and, as such, the roof is protected 4 feet (1219 mm) back of the lot line between the dwelling units.
164Page 75
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 42
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Is the rear exterior wall of the townhouse required to be fire-resistance-rated construction within four feet (1219 mm) of the common walls between the dwelling units?
No. It is perpendicular to the line used to determine the fire separation distance.
165Page 75
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 3 The rear view of the four-
unit townhouse, noted in the two previous scenarios, there are a series of roof vents near the ridge. Each of these four dwelling units is properly separated along the lot lines.
166Page 76
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 3 Are these roof vents
required to be located any certain minimum distance away from this lot line between the dwelling units?No. The code does not limit the placement of roof vents.
167Page 76
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 4 There are a series of
windows that appear to be placed approximately 2 to 3 feet (610 mm to 914 mm) from the lot line.
168Page 76
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 43
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 4 Does the code require these
window openings to be placed any minimum distance away from the lot line separating the dwelling units?No. As the windows are located in the wall perpendicular to the lot line, all of the window openings can remain unprotected and they can be placed anywhere in that wall.
169Page 76
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 5 The shows a townhouse with
six dwelling units with lot lines as noted. It is understood that the project meets the definition of townhouse because each dwelling unit has two sides open to a yard or public way. There is 1-hour fire-resistance-rated wall construction between all of the dwelling units.
170Page 77
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 5 Does the exterior wall between dwelling
unit “E” and the open lot serving unit “B” (indicated by lot line “X” on the plan) need to be a 1-hour fire-resistance-rated wall? Yes, because it is less than 5 feet (1524
mm) from the lot line.
171Workbook Page 71
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 5 Can the same wall
have any window openings?
No, because it is less than 3 feet (914 mm) from the lot line.
172Page 77
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 44
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 5 Can the roof overhang
above this wall of dwelling unit “E” project over the lot line?No. Projections beyond the exterior wall are not to extend over the lot line.
173Page 77
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 6 The figure is a plan view of a
three unit townhouse with attached decks at the rear of dwelling unit “A” and dwelling unit “C.” Lot lines separate the dwelling units from front to back. There is a minimum 1-hour fire-resistance-rated walls between all the dwelling units.
174Page 78
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 6 What level of fire separation is
needed between the attached deck of dwelling unit “A” and the exterior wall of dwelling unit “B” along the lot line?The exterior wall of dwelling unit B along the lot line is required to be at least 1-hour fire-resistance rated, and no openings are permitted in this wall.
175Page 78
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 7 The Townhouse figure below shows a
townhouse where each dwelling unit has a separate tuck-under garage that is only accessed through the individual dwelling unit.
176Page 79
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 45
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 7 Do the requirements for fire separation between the
attached garage and the dwelling unit change because they are contained in a townhouse?
No. The separation between the attached garage and the dwelling unit is to comply with Section R302.5.
2012 IRC Townhouse Fire and Life Safety Provisions 177Page 79
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 8 A townhouse is proposed above an
underground parking ramp. The ramp is separated from the townhouse above by a 3-hour poured-in-place concrete floor/ceiling. All of the vehicle parking spaces are open to one another, and there is a 2-hour rated common stairway leading up to the dwelling units.
178Page 79
2012 IRC Townhouse Fire and Life Safety Provisions
Fire-resistive Wall ConstructionFire-resistive Wall Construction
Scenario 8 Can this structure be built using the provisions in
the IRC?
No. This structure would not meet the scope of the IRC, and would most likely need to be
constructed as a Group R-2 apartment with a Group S-2 occupancy (parking garage) below,
using the provisions in the IBC.
179Page 79
2012 IRC Townhouse Fire and Life Safety Provisions
Garages and Carports—R309Garages and Carports—R309Module 3
2012 IRC Townhouse Fire and Life Safety Provisions 180
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 46
R309 – Garages and CarportsR309 – Garages and Carports A series of dwelling
units with attached garages are constructed as a townhouse, the provisions for fire separation between the attached garage and the dwelling do not change.
2012 IRC Townhouse Fire and Life Safety Provisions 181Page 81
R309 – Garages and CarportsR309 – Garages and Carports The most restrictive provision of the code will
always apply. Attached garages of adjacent dwellings are
separated by a lot line or imaginary line, the garage wall between the two attached garages will need to provide the extension of the two 1-hour fire-resistance-rated walls construction between the units.
182Workbook Page 74
2012 IRC Townhouse Fire and Life Safety Provisions
R-309.4R-309.4 R309.4 Automatic
garage door openers. Automatic garage door openers, if provided, shall be listed and labeled in accordance with UL 325.
2012 IRC Townhouse Fire and Life Safety Provisions 183Page 81
Garage Fire Suppression R309.5 Garage Fire Suppression R309.5
Private garages shall be protected by fire sprinklers where the garage wall has been designed based on Table R302.1(2), Footnote a.
Sprinklers in garages shall be connected to an automatic sprinkler system that complies with Section P2904. Garage sprinklers shall be residential sprinklers or quick-response sprinklers, designed to provide a density of 0.05 gpm/ft2. Garage doors shall not be considered obstructionswith respect to sprinkler placement in accordance with UL 325.
184Workbook Page 732012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 47
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation The garage needs to be separated
from the dwelling as follows:
2012 IRC Townhouse Fire and Life Safety Provisions 185Page 82
2012 IRCPage 51
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation Garages beneath habitable rooms separated
from the dwelling by 5/8–inch (16 mm) Type X gypsum board or equivalent.
186Page 82
2012 IRC Townhouse Fire and Life Safety Provisions
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation Type X gypsum board on ceiling beneath
habitable rooms shall be installed perpendicular to the ceiling framing and shall be fastened at maximum 6 inches (152 mm) on center by minimum 1 7/8-inch (48 mm) 6d coated nails or equivalent drywall screws according to Note “e” of Table R702.3.5, for minimum thickness and application of gypsum board.
187Page 82
2012 IRC Townhouse Fire and Life Safety Provisions
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation Supporting walls, beam and posts shall be
protected by ½-inch (13 mm) gypsum board when the separation is a floor-ceiling assembly.
Reference should be made to the manufacturer of the gypsum board for any recommendations regarding any minimum or maximum joint space between the sheets of the gypsum board.
188Page 82
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 48
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation The gypsum board used for the separation is not part of
a fire-resistance-rated assembly, and as such, there are no requirements in this section for joint treatment.
Although the code contains specific requirements for the nails and screws used as fasteners for the gypsum board, it makes no reference to the use of staples. The building official could allow the use of staples if testing could be provided that indicated the staples provided the same holding power as the required nails under fire conditions.
189Page 82
2012 IRC Townhouse Fire and Life Safety Provisions
R302.6 – Dwelling/garage fire separationR302.6 – Dwelling/garage fire separation Garages located less than 3 feet (914 mm) from
a dwelling unit on the same lot shall be protected with not less than ½-inch (12.7 mm) gypsum board applied to the interior side of exterior walls that are within this area.
2012 IRC Townhouse Fire and Life Safety Provisions 190Page 83
R302.5 Dwelling/garage opening/penetration protection R302.5 Dwelling/garage opening/penetration protection Solid wood doors not less than 1 3/8 inches (35
mm) in thickness; Solid or honeycomb core steel doors not less
than 1 3/8 inches (35 mm) thick; 20-minute fire-rated doors with a self-closing
device. This door is allowed to swing into the dwelling or
into the garage. If the door swings into the garage, it will need a proper landing.
191Page 83
2012 IRC Townhouse Fire and Life Safety Provisions
R302.5 Dwelling/garage opening/penetration protection R302.5 Dwelling/garage opening/penetration protection May contain glazing if approved by the building
official. This is not a fire door assembly, only the door is
rated, but a building official might reasonably conclude that fire-resistant-safety glazing would provide some equivalent protection. NFPA 80 could provide additional guidance.
192Page 83
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 49
R302.5 Dwelling/garage opening/penetration protection R302.5 Dwelling/garage opening/penetration protection Proper fire-resistive separation is needed
between the dwelling and attached garage although a door is not specifically required that would allow direct access between the dwelling and the attached garage. Access to the garage could be obtained through the overhead door, or an exterior nonfire resistance rated service door that opens directly to the exterior.
193Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
Garages and CarportsGarages and Carports1. Is the service door between a garage and dwelling
required to be labeled, and does it need a self-closing device?
The code does not specifically require a labeled fire door when using the solid wood door or honeycomb steel door. Self-closers are required for these doors.
Latching devices are not needed for these doors. The door frame can be a simple wood frame, as it is
not required to be a rated assembly.
194Page 84
2012 IRC Townhouse Fire and Life Safety Provisions
Garages and CarportsGarages and Carports2. Is the service door required in the wall that
separates the dwelling from the garages?
No. No door is required.
2. Is a service door required into the garage directly from the exterior?
No. No door is required.
195Page 84
2012 IRC Townhouse Fire and Life Safety Provisions
Means of Egress—R311Means of Egress—R311Module 4
2012 IRC Townhouse Fire and Life Safety Provisions 196
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 50
R311 – Means of EgressR311 – Means of Egress Each dwelling unit in a townhouse is considered
a separate building. Scoping provisions in Section R101.2 remind us
that each dwelling unit in the townhouse needs to have its own separate means of egress.
The provisions for means of egress in the IRC apply the same for single dwellings, two-family dwellings and townhouses.
197Page 85
2012 IRC Townhouse Fire and Life Safety Provisions
R311 – Means of EgressR311 – Means of Egress
In the IRC, there are no provisions and no requirements that address: An occupant load factor per square foot. A maximum number of occupants. In other
words, the code does not limit the maximum number of occupants that can live in a single family dwelling.
198Page 85
2012 IRC Townhouse Fire and Life Safety Provisions
R311 – Means of EgressR311 – Means of Egress A maximum overall square footage. The
means of egress requirements in the code are not affected by the square footage of the dwelling or townhouse. Travel distance to an exit. The code does not
require a second exit no matter how long the travel distance, or number of stories.
199Page 85
2012 IRC Townhouse Fire and Life Safety Provisions
R311 – Means of EgressR311 – Means of Egress
Discuss the bullets on workbook pages 85-86 Each dwelling unit is to have it’s own
means of egress to the exterior. Means of egress cannot travel through a
garage.
2012 IRC Townhouse Fire and Life Safety Provisions 200Page 85 86
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 51
Means of EgressMeans of Egress
1. Does the code require doors for sleeping rooms?
No. No doors are required for sleeping rooms.
201Workbook Page 80
2012 IRC Townhouse Fire and Life Safety Provisions
Means of EgressMeans of Egress
2. Can a spiral stair be used to service the main exit required by Section R311.4.1?
Yes. There are no provisions that would prohibit the use of a spiral stair to serve as the main exit or egress door, or any
other exit in the dwelling.
202Page 87
2012 IRC Townhouse Fire and Life Safety Provisions
Means of EgressMeans of Egress3. Does the means of egress system in a dwelling
or townhouse need to extend to the public way?
No. The IRC provides for a means-of-egress to get the occupants safely out of the building to grade. Generally speaking, the means-of-egress ends
where the occupant walks out the required egress door and down any step or stairs to
grade. Exit discharge is not regulated beyond that point.
203Page 87
2012 IRC Townhouse Fire and Life Safety Provisions
Means of EgressMeans of Egress4. A townhouse project was
constructed. The occupants can exit the front door of their dwelling units at grade level. A sidewalk leads towards a parking lot and also towards a set of steps on an embankment that leads down to the public way.
204Page 87
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 52
Means of EgressMeans of Egress4. Are the embankment
steps/stairs regulated by the code?
No. As they are not a required element of the
means-of-egress system in this situation, they are
not regulated by the provisions of the code.
205Page 87
2012 IRC Townhouse Fire and Life Safety Provisions
Smoke AlarmsSmoke AlarmsModule 5
2012 IRC Townhouse Fire and Life Safety Provisions 206
R314 – Smoke AlarmsR314 – Smoke Alarms Smoke alarms must be: Listed in accordance with UL 217. Installed in accordance with the IRC and NFPA 72. Receive their primary power from the building wiring. Interconnected within each individual dwelling unit
such that the actuation of one alarms activates all alarms within the dwelling unit.
207Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
R314 – Smoke AlarmsR314 – Smoke Alarms Smoke alarms must be: Located in each sleeping room. Located outside each separate sleeping area in the
immediate vicinity of the bedrooms. On each story of the dwelling, including basements.
208Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 53
R314 – Smoke AlarmsR314 – Smoke Alarms
Smoke alarms are not required in crawl spaces, uninhabitable attics, or garages. Fire alarms systems, monitored or not, are
not required for townhouses.
209Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
R313—Automatic Fire Sprinkler SystemsR313—Automatic Fire Sprinkler Systems
Installed in townhouses in accordance with Section R313, except for additions to existing townhouses that do not contain a residential fire sprinkler system.
Designed and installed in accordance with Section P2904, which is the same as NFPA 13D.
210Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
R315–Carbon Monoxide Alarms R315–Carbon Monoxide Alarms
Installed outside of each separate sleeping area in dwellings that contain fuel-fired appliances and in dwellings with attached garages. To be installed and maintained in
accordance with NFPA 720.
211Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
R315–Carbon Monoxide Alarms R315–Carbon Monoxide Alarms
To be listed as complying with UL 2075. The carbon monoxide alarm does not need to be hard-wired or interconnected. It can be a plug-in wall unit (into a wall receptacle), a battery-powered unit or a hard-wired unit. The alarm is required to comply with UL 2075. The information that needs to be either on the alarm or the alarm package is a UL listing logo and a category or class listing identification.
212Page 89
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 54
2009 IRC Townhouse Fire and Life Safety Provisions2009 IRC Townhouse Fire and Life Safety Provisions
The IBC contains provisions for multiple unit-dwelling structures classified as Group R-2 where the level of fire resistance of the structure may need to be increased from nonrated construction (Type V-B) to 1-hour fire-resistive construction (Type V-A) throughout based on the square footage of the structure.
213Page 90
2012 IRC Townhouse Fire and Life Safety Provisions
2009 IRC Townhouse Fire and Life Safety Provisions2009 IRC Townhouse Fire and Life Safety Provisions
Include 1-hour fire-resistive floor/ceilings and roof assemblies along with rated penetrations for all of the plumbing, HVAC and electrical materials passing in or through those assemblies.
214Page 90
2012 IRC Townhouse Fire and Life Safety Provisions
AccessibilityAccessibilityModule 6
2012 IRC Townhouse Fire and Life Safety Provisions 215
R320 – AccessibilityR320 – Accessibility Code contains provisions for accessibility that
are applicable to townhouses and congregate residences (e.g., group homes, boarding houses) constructed using the IRC. The determination is generally based on number of dwelling and sleeping units in the structure and the number of stories in the unit.
216Page 91
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 55
R320 – AccessibilityR320 – Accessibility FHA is enforced by the Department of Housing and Urban
Development (HUD). HUD has determined that the 2003 IBC with the 1998 A117.1
is ‘safe harbor’ documents for compliance with the FHA. In other words, if a designer uses the IBC to design for
accessibility, they will meet or exceed the FHA requirements. HUD is currently reviewing the 2009 and 2012 IBC and the
2009 ICC A117.1. ICC anticipates that these editions will be certified in the
future. The IRC references the IBC for accessibility requirements.
2012 IRC Townhouse Fire and Life Safety Provisions 217Page 91
R320.1 – ScopeR320.1 – Scope Four or more dwelling units or sleeping units in a
single structure, the provisions of Chapter 11 of the IBC for Group R-3 shall apply.
Requirements in the IBC for accessibility are based on a per structure basis.
Legal property lines or separation walls do not change the requirements for accessibility.
2182012 IRC Townhouse Fire and Life Safety Provisions Page 91
R320.1 – ScopeR320.1 – Scope There are three levels or accessibility for
dwelling units and sleeping units in the IBC. The three types are described below Accessible Units Type A Unit Type B Unit
2192012 IRC Townhouse Fire and Life Safety Provisions Page 91-92
Assisted Living
Type B unit requirementsType B unit requirements Four or more dwelling units are provided in a
single structure, the assumption is that Type B units are required unless exempted under Section 1107.7 of the IBC.
If the individual dwelling units are multistory and do not provide an elevator, Type B dwelling units are not required in accordance with Section 1107.7.2 of the IBC. This exempts most IRC townhouse configurations.
220Page 92
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 56
Type B unit requirementsType B unit requirements Elevators are not required, however, if a private
residence elevator is installed voluntarily in a multi-story unit, that unit must meet Type B units requirements.
221Page 92
2012 IRC Townhouse Fire and Life Safety Provisions
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of ICC A117.1-2003 edition. A basic description includes the following: An accessible route must be provided from the
parking to the front door of the unit. All doors within the unit that you are expected to walk
through must be a minimum of 2feet 10inches (864 mm) wide (i.e. yes for walk-in closets, but no for reach-in closets).
222Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of the ICC A117.1-2003 edition. A basic description includes the following: An accessible route is required throughout the unit,
however, turning spaces are not required in each room. There are exceptions for mezzanines and allowances for a step down at patios/balconies.
Ramps, elevators or platform lifts can be part of the accessible route.
223Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of the ICC A117.1-2003 edition. A basic description includes the following: Light switches, fan switches, furnace/air conditioning
controls and electrical outlets are required be located between 15 inches and 48inches (381 mm and 1219 mm) above the floor. There are exceptions for some of these items. In addition, there are no accessibility requirements for appliance controls, plumbing controls or door hardware on doors within the unit.
224Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 57
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of the ICC A117.1-2003 edition. A basic description includes the following: If laundry is provided in the unit, a person using a
wheelchair must be able to get to the washer and dryer.
225Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of the ICC A117.1-2003 edition. A basic description includes the following: There are two choices for bathrooms – Option A and
Option B. Option A is required in all bathrooms in a unit. Option B, which provides better access for a person using a wheelchair, is required in only one bathroom. A person using a wheelchair must be able to get into a bathroom, close the door, and get at each fixture. All bathrooms must provide blocking in the walls for the future installation of grab bars.
226Page 93
2012 IRC Townhouse Fire and Life Safety Provisions
Unit RequirementsUnit Requirements Specific requirements can be found in Section
1004 of the ICC A117.1. A basic description includes the following: A person using a wheelchair must be able to get to
each appliance in the kitchen and a minimum clearance is required between cabinets based on the configuration.
227Page 94
2012 IRC Townhouse Fire and Life Safety Provisions
Site RequirementsSite Requirements If the site is required to include Type B units, 2
percent of the parking for those units are required to be accessible spaces as noted in Section 1106.2 of the IBC and, A117.1 502.
If covered parking is provided, at least two percent but not less than one of each type including the covered parking must be accessible.
228Page 94
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 58
Site RequirementsSite Requirements An accessible route must be provided from site
arrival points (e.g. parking spaces, public sidewalks) to the accessible unit entrance in accordance with Section 1107.4.
If there are shared facilities, such as a living room in a group home or a community building in a townhouse complex, an accessible route must connect each unit to those shared facilities.
229Page 94
2012 IRC Townhouse Fire and Life Safety Provisions
ConclusionConclusion
Any questions?
2302012 IRC Townhouse Fire and Life Safety Provisions
231
International Code Council is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-AIA members are available on request.
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
2012 IRC Townhouse Fire and Life Safety Provisions 232
Copyright Materials
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is
prohibited.
© International Code Council 2006
2012 IRC Townhouse Fire and Life Safety Provisions
2012 IRC Townhouse Fire and Life Safety Provisions
Copyright 2012 International Code Council 59
Thank you for participatingThank you for participating