  • 8/2/2019 2008_ac0458en_LD

    1/20

    Sepam 100 LD

    Electrical network protection

    High impedance differential protection

    Catalogue2008

  • 8/2/2019 2008_ac0458en_LD

    2/20

    A new path for achieving your electrical installations

    A comprehensive offer

    The Sepam 100 LD range is part of a comprehensive offer of products that are perfectly

    coordinated to meet all medium and low voltage electrical distribution requirements.

    All of these products have been designed to work together: electrical, mechanical

    and communication compatibility.

    The electrical installation is thus both optimised and has improved performance:

    @ better service continuity,

    @ increased personnel and equipment safety,

    @ guaranteed upgradeability,

    @ efcient monitoring and control.

    You therefore have all the advantages at hand in terms of know-how and creativity

    for achieving optimised, safe, upgradeable and compliant installations.

    Tools for facilitating the design and installation

    With Schneider Electric, you have a complete range of tools to help you get to know and

    install the products whilst complying with current standards and good working practices.

    These tools, technical sheets and guides, design software, training courses, etc are

    regularly updated.

    For a real partnership with you

    A universal solution doesnt exist because each electrical installation is specic.

    The variety of combinations on offer allows you to truly customise the technical solutions.

    You are able to express your creativity and put your know-how to best advantage

    when designing, manufacturing and exploiting an electrical installation.

    Schneider Electric is associating itself with

    your know-how and your creativity to produce

    optimised, safe, upgradeable and compliant

    installations

  • 8/2/2019 2008_ac0458en_LD

    3/20

    Presentation 2

    Highimpedancedifferentialprotection 3Specifyingthesensors 4

    Surgelimiter 6

    Descriptionandconnection 7

    Connectiondiagramsoftheaccessories 8

    Exampleofapplications 9

    Characteristics 10

    Installation 11

    Commissioning 13

    Orderfrom 14

    ContentsSepam 100 LDSepam 100 LD

    AC0458EN.indd 1

  • 8/2/2019 2008_ac0458en_LD

    4/20

    Sepam 100Sepam100isagroupofmodulesthatmaybeused:

    separatelytoperformafunction

    incombinationwithaSepamprotectionrelay.Eachmodulehasbeendesignedtoperformacompletefunction.

    Itincludesalltheelementsrequired,suchas:

    trippingoutputrelays

    annunciation,settings

    connections.

    Sepam 100 LDSepam100LDisahighimpedancedifferentialrelay.

    Itprovidesrestrictedearthfault,busbarandmachineprotection.

    Advantagesstabilitywithrespecttoexternalfaults

    sensitivitytointernalfaultsspeed(typicalresponsetime:15msto5Is)

    outputswithorwithoutlatching

    localandremoteacknowledgment

    highlevelofimmunitytoelectromagneticinterference.

    DescriptionSepam100LDisavailablein4versions:

    single-phaseforrestrictedearthprotection

    three-phaseforbusbarandmachineprotection

    50or60Hz

    50Hzsingle-phase:100LDX51

    50Hzthree-phase:100LDX53

    60Hzsingle-phase:100LDX61

    60Hzthree-phase:100LDX63.

    ThefrontofSepam100LDincludes:

    2signallamps:

    poweronindicator

    latchingtripindicatorindicatingoutputrelaytripping

    protectionsettingdial

    resetbuttonforacknowledgingoutputrelaysandthetripindicator.

    Whenthebuttonisactivated,thetripindicatorundergoesalamptest.

    ThebackofSepam100LDincludes:

    input/outputconnectors:

    an8-pinconnectorfortoroidinputsandremoteacknowledgment

    an8-pinconnectorfortrippingoutputsandpowersupply

    a4-pinconnectorfortrippingoutputs

    a microswitch used to congure the relay with or without latching.

    Sepam100LDhas:

    1or3currentinputswithacommonpointaccordingtowhetheritisasingle-phase

    orthree-phaseversion

    alogicinput(isolated)forremoteacknowledgment

    trippingoutputrelaywith5contacts

    3normallyopencontactsand2normallyclosedcontacts).

    Sepam100LDoperatesin5voltageranges(pleasespecifywhenordering):

    24-30Vdc

    48-125Vdc

    220-250Vdc

    100-127Vac

    220-240Vac.

    Sepam100LDisassociatedwithastabilizationplate(or3plates)withvariable

    resistance,enablingoperationwith1Aor5Atransformers.

    b

    b

    b

    b

    b

    b

    b

    b

    bb

    b

    b

    b

    b

    b

    b

    b

    v

    v

    b

    b

    b

    v

    v

    v

    b

    b

    b

    b

    b

    b

    b

    b

    b

    PE41200

    Sepam 100 LD

    DE40950

    Sepam 100 LD: front panel

    PE41200

    Sepam 100 LD

    DE40950

    Sepam 100 LD: front panel

    PresentationSepam 100 LDSepam 100 LD

    AC0458EN.indd2

  • 8/2/2019 2008_ac0458en_LD

    5/20

    Operation curve

    DE

    40949

    SettingsSettings Setting values

    SettingcurrentIs 5to40%Inbystepsof5%In

    40to80%Inbystepsof10%In

    Thedialonthefrontofthedeviceisusedforsetting

    Stabilizingresistorplate Rs=0to68 P=280W

    Rs=0to150 P=280W

    Rs=0to270 P=280W

    Rs=0to470 P=180W

    Rs=0 to680 P=180W

    Accuracy / performance

    Setting 5%

    Pickup(%) 93%5%

    Responsetime y10msforIu10Isy16msforIu5Is

    y25msforIu2Is

    Memorytime y30ms

    Parameter settingMicroswitchSW1,accessibleonthebackofSepam100LD,isusedtochoosewithorwithoutlatching.

    Without latching:

    With latching:

    High impedance differentialprotection

    Sepam 100 LDSepam 100 LD

    AC0458EN.indd 3

  • 8/2/2019 2008_ac0458en_LD

    6/20

    Specifying the sensorsSepam 100 LDSepam 100 LD

    Current transformersToensurethestabilityandsensitivityofSepam100LD,thestabilizationresistorand

    characteristicsofthecurrenttransformers(CTs)arecalculatedasfollows.

    Choice of current transformersalltheCTsmusthavethesametransformationration

    theknee-pointvoltagesarechosensothat:

    Vk > 2 x (R + Rf) x isc

    Choice of stabilizing resistor

    Surge limiterTheapproximatevoltagedevelopedbyaCTintheeventofaninternalfaultis:

    V = 2 2 x Vk x (isc x (R + Rf + Rs) - Vk)Ifthevalueexceeds3kV,itisnecessarytoaddanRlsurgelimiterinparallelwiththe

    relayandstabilizingresistorinordertoprotecttheCTs(see:surgelimiter).

    Protection sensitivityTheCTsconsumemagnetizingcurrentandthesurgelimiter,wheninstalled,creates

    faultcurrent.Theminimumresidualprimarycurrentdetectedbytheprotectionis

    therefore:

    Id = n x (im1 + i

    mp + if + is)

    with

    im

    1,im

    parereadontheCTmagnetizationcurvesatV=Rsxis

    ifisthetotalearthleakagecurrentofthesurgelimiterforVs=Rsxis,i.e.thesum

    oftheearthleakagecurrentsoftheNlimiterunitsinstalledinparallel:if=Nxib

    (see:surgelimiter).

    Example 1: Restricted earth (single-phase relay)Data:

    Iscprimary=8kA

    n:400/1A

    R=2,4CTssituated60mfromtherelays

    connectedby6mm2wiring(copper)

    numberofsensorsinparallel:4(same)

    setting:Is=20%In,is=0.2A.

    CT knee-point voltageisc=8000/400=20A

    (R+Rf)xisc=(2,4+0,4)x20=56V

    Vk>2x56=112V

    e.g.:Vk=140V.

    Stabilizing resistor

    280 < Rs 350

    Theresistanceisadjustablefrom0to470 .Itissetto300.

    Surge limiter ?V = 2 2 x 140 (20 (2.4 + 0.4 + 300) - 140)

    V = 2574 V < 3 kV

    Itsnotnecessarytoinstallasurgelimiterinparallel.

    Minimum primary default current detected by the protectionForV=Rsxis=60V

    TheCTmagnetizationcurveindicatesim=10mA

    Id = 400 (4 x 0.01 + 0.2) = 96 A

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    b

    DE40947

    n: CT transformation ratio

    p: Number of CTs

    Rf1, Rf2: Wiring resistance on either side of Rs

    Rf = max (Rf1, Rf2)

    R1, ...Rp: CT secondary resistances

    R = max (R1, ...Rp)

    Rs: Stabilizing resistor

    Rl: Surge limiter

    isc: Maximum external short-circuit

    current in CT secondary winding

    is : Protection setting (A)

    if: Current in Rl

    im1, i

    mp: CT magnetizing currents

    Vk1, Vkp: CT knee-point voltages

    Vk = min (Vk1,...Vkp)

    DE40947

    n: CT transformation ratio

    p: Number of CTs

    Rf1, Rf2: Wiring resistance on either side of Rs

    Rf = max (Rf1, Rf2)

    R1, ...Rp: CT secondary resistances

    R = max (R1, ...Rp)

    Rs: Stabilizing resistor

    Rl: Surge limiter

    isc: Maximum external short-circuit

    current in CT secondary winding

    is : Protection setting (A)

    if: Current in Rl

    im1, i

    mp: CT magnetizing currents

    Vk1, Vkp: CT knee-point voltages

    Vk = min (Vk1,...Vkp)

    R + Rfis

    x isc < Rs Vk2 x is

    Rf=0,020 x ( 2x 60 )6

    =0,4

    560,2

    < Rs 140

    (2 x 0,2)

    AC0458EN.indd4

  • 8/2/2019 2008_ac0458en_LD

    7/20

    Specifying the sensorsSepam 100 LDSepam 100 LD

    Example 2: Busbar differential protection (three-

    phase relay)

    Data:switchboardwith10cubiclesincomerandfeeder,withoutcoupling

    Isc=30kA

    n:2000/5A

    R=1.76

    CTssituated15mfromtherelays

    connectedby2.5mm 2wiring(copper):

    numberofsensorsinparallel:10(same)

    setting:is=50%In,is=2.5A.

    CT knee-point voltage

    isc=30000x5/2000=75A(R+Rf)xisc=(1.76+0.24)x75=150V

    Vk>2x150=300V

    e.g.:Vk=320V.

    Stabilizing resistor

    60 < Rs 64 Theresistanceisadjustablefrom0to68 .Itissetto64.

    Surge limiter ?V = 2 2 x 320 (75 (1.76 + 0.24 + 64) - 320)V = 3443 V > 3 kV

    Itsnotnecessarytoinstallasurgelimiterinparallel.

    Minimum primary default current detected by the protection

    ForV=Rsxis=160V

    TheCTmagnetizationcurveindicatesim=20mA.

    Theleakagecurrentcurveofthesurgelimiterindicatesil=4mA.

    Thenumberofsurgelimitersis:

    b

    b

    b

    b

    b

    b

    b

    b

    1502,5

    < Rs 320

    (2 x 2,5)

    Rf=0,02 x ( 2x 15 )2,5

    =0,24

    N 7540

    =2,hence

    Id =2000

    5(10 x 0,02 + 0,004 + 2,5) = 1083 A

    AC0458EN.indd 5

  • 8/2/2019 2008_ac0458en_LD

    8/20

    Surge limiterSepam 100 LDSepam 100 LD

    Ifthecalculationshaveshownthatitisnecessarytoinstallasurgelimiterinparallel

    withtherelayandRstoprotecttheCTs,itisdeterminedasfollows..

    Choice

    Standard referencesthesurgelimitersonofferconsistoflimiterblockswhichareindependentofeach

    other.Eachblockacceptsamaximumcurrentof40ARMSfor1s.Byinstallingthe

    blocksinparallel,itispossibletoobtaintheappropriatelimiterfortheapplication.

    therearetwostandardreferences:

    asinglemodule,comprisingoneblock

    atriplemodule,comprisingthreeindependentblockswhicharealigned.

    Calculation of the number of blocks per phaseAccordingtoi,max.RMSshort-circuitcurrentinthesecondarywindingofaCT,the

    numberofblocksrequiredperphaseiscalculated:

    forathree-phaserelay,Ntriplemodulesshouldbeordered

    forasingle-phaserelay,Nblocks,madeupoftripleandsinglemodules.

    Example 1max.RMSshort-circuitcurrentintheprimarywindingofaCT

    witharatioof1000:60kA

    calculationofthenumberofblocksperphase:

    modulestobeordered:

    2triplemodulesforathree-phaserelay

    2singlemodulesforasingle-phaserelay.

    Example 2max.RMSshort-circuitcurrentintheprimarywindingofaCTwitharatioof400:50kA

    single-phaserelay.

    calculationofthenumberofblocksperphase:

    modulestobeordered:

    1triplemodule+1singlemoduletohave4blocksinall.

    Earth leakage currentAlimiterblockacceptsamax.steadystatevoltageof325VRMSandpresentsan

    earthfaultcurrentlb:

    b

    b

    v

    v

    b

    b

    b

    b

    b

    v

    v

    b

    b

    b

    b

    DE40946

    DE40946

    N

    l

    40

    N 60000

    (1000 x 40)= 1,5 ,henceN = 2

    N 50000

    (400 x 40)= 3,1 , hence N = 4

    AC0458EN.indd6

  • 8/2/2019 2008_ac0458en_LD

    9/20

    Description and connectionSepam 100 LDSepam 100 LD

    Rear panel Functional and connection diagram

    DE40945

    DE

    40944

    0A : 8-pin CCA608 connector(torold and remote reloading inputs); screw terminal wiringwith 0.6 to 2.5 mm2 wires, each terminal being capable ofreceiving two 1.5 mm2 wires.

    Note: only 0A1 and 0A2 terminals are available in the single-phase version.

    Terminal identifcationEach terminal is identied by 3 characters.

    DE40943

    1A : 8-pin CCA608 connector(power supply and annunciation and tripping outputs);screw terminal wiring with 0.6 to 2.5 mm2 wires, each terminalbeing capable of receivingtwo 1.5 mm2 wires.

    1B : CCA604 connector ("annuciation" outputs);screw terminal wiring with 0.6 to 2.5 mm2 wires, each terminal

    being capable of receiving two 1.5 mm2 wires.t

    :groundterminal

    1 A 4

    Boardslotnumber(0to1)

    Connectorterminalnumber

    Connectoridentificationletter(AorB)

    1 A 4

    Boardslotnumber(0to1)

    Connectorterminalnumber

    Connectoridentificationletter(AorB)

    AC0458EN.indd 7

  • 8/2/2019 2008_ac0458en_LD

    10/20

    Stabilization plateConnectionofCTsandsurgelimiters:

    5Arating:betweenterminals1-2and3-4

    1Arating:betweenterminals1-2and5-6

    DE10418

    items1to6:clampscrewconnectionsfor6mm 2wire

    items1,2:secondaryofCSH30corebalanceCT,connectedto0A

    Wiretobeused:

    sheathed,shieldedwire

    min.cross-section0.93mm2(AWG18)(max.2.5mm2)

    resistanceloadperunitlength

  • 8/2/2019 2008_ac0458en_LD

    11/20

    Example of applicationsSepam 100 LDSepam 100 LD

    Restricted earth protection (single-phase)

    1A CTDE40942

    Busbar protection (three-phase)

    5 A CT - with surge limiters

    DE40941

    Note: = correspondence between primary and secondary connections (e.g. P1, S1).

    AC0458EN.indd 9

  • 8/2/2019 2008_ac0458en_LD

    12/20

    CharacteristicsSepam 100 LDSepam 100 LD

    Electrical characteristicsAnalog inputs ( with plate)

    Constantcurrent 10ln

    3sec.current 500ln

    Logic input ( remote reset)

    Voltage 24/250Vdc 127/240VacMaximumpowerconsumption 3.5W 3.7VA

    Logic outputs

    Constantcurrent 8A

    Voltage 24/30Vdc 48Vdc 127Vdc/Vac 220Vdc/Vac

    Breakingcapacity(contact01) Resistivedcload 7A 4A 0.7A 0.3A

    Resistivedcload 8A 8A

    Resistivedcload 3.4A 2A 0.3A 0.15A

    Resistivedcload 4A 4A

    Power supply

    Range Consumption when inactive Max. consumption Inrush current24/30Vdc 20% 2.5W 6W

  • 8/2/2019 2008_ac0458en_LD

    13/20

    InstallationSepam 100 LDSepam 100 LD

    Sepam 100 LD

    Relay Cutout

    DE4094

    0

    Weight:1.9kg

    Stabilization plate

    DE40939

    Weight:1.7kg

    AC0458EN.indd 11

  • 8/2/2019 2008_ac0458en_LD

    14/20

    InstallationSepam 100 LDSepam 100 LD

    Surge limiter

    Single unit

    DE4093

    8

    Weight:1.2kgmax.

    Triple unit

    DE40937

    Weight:3.1kgmax.

    AC0458EN.indd12

  • 8/2/2019 2008_ac0458en_LD

    15/20

    Platebeforeinstallingtheplate,settherequiredresistanceusingtheohmmeter

    wirethecurrenttransformerstotheterminalsthatcorrespondtotheircurrentrating,inparallelwithsurgelimiters:

    between1-2and3-4for5A

    between1-2and5-6for1A.

    RelaysetmicroswitchSW1,locatedontheback,towithorwithoutlatching(seepage

    3)

    adjustthefrontdialtotherequiredsetting.

    b

    b

    v

    v

    b

    b

    DE40936

    Testing

    Usingatemporaryconnection(1turn),injectacurrent20%abovethesetting(5Arating)intothetoroidprimaryandcheckthattherelaytrips.

    Example:Is=40%In.

    I=0.4x5Ax1.2=2.4A.

    Thetestiscarriedoutoneachofthethreeplatesifathree-phaserelayisbeing

    used.

    CommissioningSepam 100 LDSepam 100 LD

    AC0458EN.indd 13

  • 8/2/2019 2008_ac0458en_LD

    16/20

    WhenorderingSepam100LD,stabilizationplate

    and/orsurgelimiters,pleaseencloseaphotocopyof

    this page with your order, lling in the requestedquantitiesinthespacesprovidedand

    tickingofftheboxestoindicateyourchoices.

    Sepam 100 S01 LD (suppliedwithconnectionsandmountinglugs)

    Quantity

    Ratedfrequency 50H z

    60Hz

    Version Single-phase

    Three-phase

    Auxiliarypowersupply 24to30Vdc

    48to125Vdc

    220to250Vdc

    100to127Vac

    220to240Vac

    Stabilization plate

    Resistance 68 - 280 W

    150 - 280 W

    270 - 280 W

    470 - 180 W

    680 - 180 W

    Surge limiters

    Singleunit

    Tripleunit

    Order formSepam 100 LDSepam 100 LD

    AC0458EN.indd14

  • 8/2/2019 2008_ac0458en_LD

    17/20

    NotesSepam 100 LDSepam 100 LD

    AC0458EN.indd 15

  • 8/2/2019 2008_ac0458en_LD

    18/20

    NotesSepam 100 LDSepam 100 LD

    AC0458EN.indd16

  • 8/2/2019 2008_ac0458en_LD

    19/20

  • 8/2/2019 2008_ac0458en_LD

    20/20

    ART.6

    3979

    SchneiderElectricIndus

    triesSAS-Allrightsreserved

    As standards, specications and designs change from time to time, please ask for conrmationof the information given in this publication.