1vap429282-db_kor-20

4
Type KOR-20 Outdoor current transformer Instrument transformers Product features 34.5 kV outdoor 200 kV BIL, 60 Hertz Primary amperes: 5-1200 Electrical clearances: Strike: 15.75" (400 mm) Creep: 36.50" (927 mm) Approximate weight: 110 lbs (50 kg) Application The KOR-20 outdoor current transformer is designed for metering and relaying on outdoor 34.5 kV circuits and is available in single and dual ratio designs. Dual ratio designs are accomplished by tapping the secondary winding. Construction features Primary and secondary windings are assembled around a toroidal core and attached to a support frame. For insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic pressure gelation. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet or humid environments. Terminals Primary terminals are electro-tin plated copper. Clamp-type secondary terminals accommodate #14 through #1 wire. The X2-X3 terminals form the standard tap connections when the transformer is tapped. Junction box The junction box is provided with 1" conduit hubs on each end and a knock-out for fitting a conduit connection from the bottom. It may be detached for ease of installation and changeout procedures. Baseplate The baseplate is constructed of corrosion-resistant aluminum and is secured to the encapsulated base support. Mounting The KOR-20 can be mounted in upright, cantilever, or upside-down positions. Stress relief devices should be used to support cable connections. Test reports Test reports are stored electronically and can be e-mailed in various formats at the time of shipment. Standards This unit can be tested to all applicable IEEE, CSA, or IEC standards as requested.

Upload: capiozzo563535889

Post on 28-Jan-2016

219 views

Category:

Documents


0 download

DESCRIPTION

v

TRANSCRIPT

Page 1: 1VAP429282-DB_KOR-20

Type KOR-20Outdoor current transformer

Instrument transformers

Product features − 34.5 kV outdoor − 200 kV BIL, 60 Hertz − Primary amperes: 5-1200 − Electrical clearances:

Strike: 15.75" (400 mm) Creep: 36.50" (927 mm)

− Approximate weight: 110 lbs (50 kg)

ApplicationThe KOR-20 outdoor current transformer is designed for metering and relaying on outdoor 34.5 kV circuits and is available in single and dual ratio designs. Dual ratio designs are accomplished by tapping the secondary winding.

Construction featuresPrimary and secondary windings are assembled around a toroidal core and attached to a support frame. For insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic pressure gelation. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet or humid environments.

TerminalsPrimary terminals are electro-tin plated copper. Clamp-type secondary terminals accommodate #14 through #1 wire. The X2-X3 terminals form the standard tap connections when the transformer is tapped.

Junction boxThe junction box is provided with 1" conduit hubs on each end and a knock-out for fitting a conduit connection from the bottom. It may be detached for ease of installation and changeout procedures.

BaseplateThe baseplate is constructed of corrosion-resistant aluminum and is secured to the encapsulated base support.

MountingThe KOR-20 can be mounted in upright, cantilever, or upside-down positions. Stress relief devices should be used to support cable connections.

Test reportsTest reports are stored electronically and can be e-mailed in various formats at the time of shipment.

StandardsThis unit can be tested to all applicable IEEE, CSA, or IEC standards as requested.

Page 2: 1VAP429282-DB_KOR-20

2 Type KOR-20 outdoor current transformer | ABB product bulletin

Dimensions

Baseplate dimensions

20.00 [508]

16.30 [414]

.25 [6]

11.19 [284]

5.59 [142]

A

1.31 [33]

1.00 [25]

14.59 [371]

13.00 [330]

.50 [13] 1.00

[25] .75 [19]

3.44 [87]

2.00 [51]

4.00 [101]

H1

1" STD PIPE TAP BOTH SIDES

GROUND LUG WITH Ø.44 [11] HOLE

RATING DECALBOTH SIDES

H2

B

11.25 [286]

10.00 [254]

8.63 [219]

10.50 [267]

.44 [11]

.72 [18]

.63 [16]

.44 X .88[11 X 22]SLOTS4-TOTAL

NAMEPLATE

Bar dimensions

Primary ampere rating

A B

(in) (mm) (in) (mm)

5 - 100 0.25 6 1.5 38

150 - 1200 0.375 10 2.0 51

Type KOR-20

Page 3: 1VAP429282-DB_KOR-20

ABB product bulletin | Type KOR-20 outdoor current transformer 3

Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.

Note: 50 Hz designs available

+ times normal

Selection guidePrimary ampere rating

Rating factor @ 30° C

IEEE metering accuracy

IEEE relay accuracy

Thermal rating*

Mechanical rating+ Style number

Type KOR-20

5 3.0 0.3B-0.9 C100 100 290 E-7524A22G19

10 3.0 0.3B-0.9 C100 100 290 E-7524A22G01

15 3.0 0.3B-0.9 C100 100 290 E-7524A22G02

20 3.0 0.3B-0.9 C100 100 290 E-7524A22G03

25 3.0 0.3B-0.9 C100 100 290 E-7524A22G04

30 3.0 0.3B-0.9 C100 100 290 E-7524A22G05

40 3.0 0.3B-0.9 C100 100 290 E-7524A22G06

50 3.0 0.3B-0.9 C100 100 290 E-7524A22G07

75 3.0 0.3B-0.9 C100 100 290 E-7524A22G08

100 3.0 0.3B-0.9 C100 100 290 E-7524A22G09

150 3.0 0.3B-0.9 C100 100 290 E-7524A22G10

200 3.0 0.3B-0.9 C100 100 290 E-7524A22G11

300 3.0 0.3B-0.9 C100 100 290 E-7524A22G12

400 3.0 0.3B-0.9 C100 100 290 E-7524A22G13

500 3.0 0.3B-0.9 C100 100 290 E-7524A22G14

600 3.0 0.3B-0.9 C100 100 290 E-7524A22G15

800 1.5 0.3B-0.9 C200 100 290 E-7524A22G16

1200 1.0 0.3B-0.9 C200 100 290 E-7524A22G17

Type KOR-20 (dual ratio)

5/10 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G01

10/20 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G02

20/40 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G03

25/50 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G04

50/100 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G05

75/150 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G06

100/200 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G07

150/300 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G08

200/400 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G09

300/600 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G10

400/800 3.0/1.50.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G11

600/1200 2.0/1.00.3B-0.9 0.3B-1.8 C100/C200 100 290/145 E-7524A21G12

* times normal, 1 second

Page 4: 1VAP429282-DB_KOR-20

1VA

P42

9282

-DB

Jun

e 20

14 R

ev.

F

For more information please contact: ABB Inc.Medium Voltage Distribution Components3022 NC 43 NorthPinetops, NC 27864 USA Phone: +1 252 827 3212Fax: +1 252 827 4286

www.abb.com/mediumvoltage

Note:

We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction–in whole or in parts– is forbidden without ABB’s prior written consent.

Copyright 2006 ABB. All rights reserved.