Smart Energy Management1 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Smart Energy Management

1Measure2Detect3Control

Benefits of IT in Power Plants

Presented by: R Bhatia, GM Conzerv Systems

Page 2: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management2 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Requirement of Energy Management in Utilities

Improvement in PLFReduction in APCReduction in T&D losses

> Improvement in Accountabilty> Improvement in Power Quality

>> Power Factor>> Harmonics

Page 3: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management3 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Requirement of Energy Management in Utilities – Ways to Improve

Energy Audit followed by implementation of recommendations.Energy Management System: By taking action on shortcomings indicated and reports generated.

Page 4: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management4 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

On Line Monitoring System

Page 5: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management5 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Instrumentation for Measurement

Page 6: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management6 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Stand-Alone Meters are not enough

Generally provide only Raw Data

Readings cannot be correlated on-line, in Real-Time

Difficult to relate Energy Consumption in Auxiliaries to Generation

Optimisation requires On-Line Data. Difficult to achieve with Stand-Alone Instruments.

Page 7: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management7 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

EMS SYSTEM

EM 6000 Series RS 485-RS232

CONVERTORDATA

CONVERTOR

LAN NETWORK HUB

ETHERNET

CONVERTOREM 3000 Series

DATA CONVERTOR

CONZERV eLAN®

Page 8: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management8 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Energy Management System Applications

Predictive MaintenanceRoot Cause AnalysisPower QualityMeasurement and VerificationCost AllocationSmart Power ManagementEnergy Resource PlanningEnergy BalancingBreaker Status – remote monitoringAutomated Energy Billing System for Townships

Page 9: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management9 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Conzerv in NTPC & GencosOn Line Systems>> Singrauli, Tanda, Dadri, Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu

NTPC corporate has made On Line Monitoring standard in new power plants alsoEnergy Audits>> Dadri (twice), Talcher, Faridabad, Kayamkulam,Auraiya,Singrauli, WBWDC plants Bakreshwar and Santaldih

Page 10: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management10 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

About Ourselves

l Incorporated in February 1988l HQ and Unit I at Electronic City, Bangalore,

India. Unit-II at Daman, l Specialized in Electrical Energy Management

& Conservation for Industrial and Commercial Complexes

l A Total Electrical solution providerl To help our customers improve their

performance through reducing energy costs

Page 11: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management11 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Spectrum of Activities

MetersMetersIndustrial, Industrial, RevenueRevenue

SoftwareSoftware NetNet--workingworking

Training On Training On Energy Energy

EfficiencyEfficiency

Sales & Sales & Support Support NetworkNetwork

PF PF ControlControl

Demand Demand ControlControl

Energy Energy AuditsAudits

Generator Generator SynchSynch

Remote Remote MonitoringMonitoring

Harmonic Harmonic Analysis, Analysis, Reactors, Reactors,

FiltersFilters

Generator Generator AMFAMF

Page 12: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management12 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential12 25-Dec-08 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Page 13: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management13 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential13 25-Dec-08

Outsource the Energy Management and Energy Accounting function

On-line Energy Audits

Periodic reports with recommendations for energy cost reduction

The Conzerv Way2SaveThe Conzerv Way2SaveTM–– Energy Improvement ProgramEnergy Improvement Program

Page 14: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management14 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

How EIP works….

14 25-Dec-08 © Copyright 1986-2005, ConZerv Proprietary & Confidential

User EMS PC Conzerv Server

Broadband

Online Analysis of Plant Data

Page 15: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management15 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential15 25-Dec-08 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CONZERV HO

ISP(Internet Service Provider)

GSM/CDMA TOWER

GSM/CDMA MODEM

GSM /CDMA MODEM

DSL CONNECTION

EMS PC

EMS PC

EMS PC

Fig: Schematic diagram EIP (Way to Save)Fig: Schematic diagram EIP (Way to Save)

Online DataAnalysis

Page 16: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management16 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL POWER STATIONS

ENERGY CONSUMPTION IN AUXILIARY EQUIPMENT

Page 17: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management17 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL STATIONSAUXILIARIES MAY CONSUME 6%TO 14% OF TOTAL GENERATIONEACH ONE PERCENT REDUCTION CAN RESULT IN SAVINGS OF CRORES ANNUALLY AND RELEASE A FEW MEGAWATTS OF GENERATIONNO REDUCTION POSSIBLE UNLESS CONSUMPTION IN EACH MEASURED

Page 18: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management18 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL AUXILIARIESNO EXISTING SYSTEM OF MEASUREMENT OF ENERGY CONSUMPTION IN AUXILIARIESAUXILIARY CONSUMPTION CALCULATED FROM DIFFERENCE OF POWER GENERATED AND POWER TRANSMITTED

Page 19: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management19 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL AUXILIARIESAS NO DIRECT MEASUREMENT IS BEING DONE

APC CALCULATION IS APPROXIMATEEFFICIENCY OF EACH EQUIPMENT IS UNAVAILABLELOSS OF EFFICIENCY DUE TO TECHNICAL / MAINTENANCE REASON CANNOT BE ASCERTAINED

Page 20: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management20 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL AUXILIARIES

•FOR A TYPICAL 210 MW UNIT

•HT MOTORS 6.6 KV - 43 NO’S

•LT MOTORS 415 V - 510 NO’S

TOTAL CONNECTED LOAD - 36.5 MW

= 17.5%

Page 21: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management21 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL AUXILIARIES

PROPOSED ENERGY MONITORING

•HT MOTORS - 43 NO’S

•LT MOTORS > 50 KW - 44 NO’S

Page 22: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management22 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

THERMAL AUXILIARIES

FOR MOTORS < 50 KW

USE OF PORTABLE ANALYSER ON

AS REQD. BASIS

Page 23: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management23 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

RELEVANCE OF ENERGY CONSERVATION

MAXIMISE DESPATCH OF ENERGY BY MINIMISING INTERNAL USAGEENERGY USAGE CAN BE MINIMISED BY OBTAINING OPTIMUM EFFICENCY

Page 24: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management24 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

ADVANTAGES OF ON LINE MONITORING

ENERGY CONSUMPTION OF MAJOR AUXILIARIES WILL BE AVAILABLEPROPER ACCOUNTING AND ENERGY BALANCE POSSIBLELOSSES CAN BE DETERMINEDDETERIORATION OF EFFIENCY CAN BE IDENTIFIED AND CORRECTED AT FIRST OPPORTUNITY

Page 25: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management25 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

ADVANTAGES …PROPER COSTING OF ENERGY GENERATION ACCURATE ON LINE DATA ELIMINATING HUMAN ERRORSBENCHMARKS CAN BE SET FOR PLANT COMPARISON WITHIN AND WITHOUT POSSIBLE

Page 26: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management26 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Requirement of Energy Management System in Utilities

Improvement in PLFReduction in APCReduction in T&D losses

> Improvement in Accountabilty> Improvement in Power Quality

>> Power Factor>> Harmonics

Page 27: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management27 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CASE STUDYBOILER FEED PUMP

Page 28: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management28 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

NTPC Unit ( 210 MW ) ITEM KWH KWH / DAYBFP-1B 2085 55938BFP-1C 2312 62285FD Fan-1A 380 10797FD Fan-1B 383 10879ID Fan-1A 770 21280ID Fan-1B 800 22820PA Fan-1A 780 18210PA Fan-1B 780 18135

Page 29: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management29 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study – Boiler Feed PumpBoiler feed pump 1C showed higher energy consumption.This pump was overhauled in recent past by manufacturer.The pump internals ( cartridge ) was also replaced recently.New technology valve was also fitted in this pump.

Page 30: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management30 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study contd.All factors stated should have resulted in lower energy consumption .Obvious conclusion was that measurements were incorrect.Meter was rechecked and recalibrated.Software for on line monitoring was also checked but no fault could be located.Pump continued to show higher consumption.

Page 31: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management31 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study contd.As running 210 MW unit could not be shut down, checks were carried out on motor as well as the pump in operation.Results were inconclusive as no defects could be ascertained.Plant authorities decided to wait till next scheduled shut down.For over two months pump operated with excess consumption of 6500 units per day.

Page 32: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management32 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study - ConclusionDuring shut down, the pump was dismantled.Observed that on the recirculating valve side there was excess clearance or gap resulting in higher energy for same pumping requirement.On line monitoring system could payback in less than two months.Analogue ammeter of say 500 Amp full scale may not show noticeable difference between 228 and 252 Amps

Page 33: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management33 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case StudyCoal Mill

Page 34: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management34 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

COAL MILLIn the Coal mills power consumption increases with wear of grind rolls. Thus it should be possible to establish a relation between run hours and power consumption.Actual spot readings taken with energy meters in a coal mill are shown in the next slide with attempt to establish some pattern in the next two slides.

Page 35: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management35 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

COAL MILL

Page 36: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management36 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Coal Mill

Page 37: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management37 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Coal MillRun Hours Vs Power Consumpt ion and Speci f ic Power Consumpt ion

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

1 A 1 B 1 C 1 D 1 E 1 F 2 A 2 B 2 C 2 D 2 E 2 F 3 A 3 B 3 C 3 D 3 E 3 F 4 A 4 B 4 C 4 D 4 E0.00

2.00

4.00

6.00

8.00

10.00

12.00

Run Hours

Power Consumption

Specific Power Consumption

Page 38: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management38 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Coal Mill - AnalysisFrom energy meter readings it is not possible to establish any relationship .Noting Specific Power Consumption trend on line from 0 to 2500 hrs can enable extrapolation to say 3500 hrs or even 4000 hrs.Prediction of Specific power consumption at 4000 hrs and consequently extra power consumption vs cost can provide an optimum replacement point in no of hours for each mill as characterstics for each are different.

Page 39: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management39 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Coal Mill - AnalysisWhen Bullring replacement is done it is necessary to know whether Specific power consumption has changed as compared to original state.If not, there could be other causes also which contribute to higher consumption.Actual power consumption of a coal mill is shown in next slide. Mill E is showing unusually high consumption.

Page 40: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management40 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

DAILY POWER CONSUMPTION & AVG.KW

EQUIPMENT NAME

UNIT-1 UNIT-2 UNIT-3 UNIT-4

AVG. KW AVG. KW AVG. KW AVG. KW

MILL-A 139 160 161 153

MILL-B 135 147 166 148

MILL-C 148 141 163 151

MILL-D 131 144 158 157

MILL-E 173 0 159 142

MILL-F 148 139 138 145

Av.Kw 146 146 158 149

Case : 1

Page 41: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management41 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Coal MillLooking at high consumption mill E is attended to for necessary repair and maintenance.Results of correct operation can be seen in the next slide – a reduction of over 50 KW in one mill.

Page 42: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management42 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

DAILY POWER CONSUMPTION & AVG.KW

UNIT-1 UNIT-2 UNIT-3 UNIT-4

EQUIPMENT NAME AVG. KW AVG. KW AVG. KW AVG. KW

MILL-A 134 139 142 149

MILL-B 119 124 133 131

MILL-C 138 117 159 149

MILL-D 0 130 153 138

MILL-E 121 119 0 120

MILL-F 124 0 102 0

Av.KW 127 126 138 137

Page 43: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management43 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CASE STUDYCOAL HANDLING PLANT

Page 44: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management44 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study – Coal Handling PlantNTPC had taken over Thermal Station from Electricity Board against dues.Station had low PLF and high auxiliary power consumption.NTPC made substantial improvements on both achieving PLF better than 85 % and auxiliary consumption at approx 12 %.Station has 4 x 210 MW units

Page 45: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management45 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study contd.Plateauing of further gains in Auxiliary Power consumption occurred.Unit auxiliaries were in focus for reduction but station auxiliaries not given adequate attention.Coal Handling plant tended to be neglected being out of sight.Plant authorities decided to focus on CHP.

Page 46: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management46 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study contd.Energy meters were installed in CHP.Consumption was measured in conveyors and crushers.No opportunity for reduction could be established.Use of power analyser also could not result in substantial reduction.It was decided to have a demo energy management system.

Page 47: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management47 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study - ConclusionEMS provided on line data of consumption with relation to time.Conveyor was observed to be consistently underloaded.Crusher was actually operating for only a few hours per day but remained on all the time.With improvements in operation indicated by EMS the station has achieved further gains.

Page 48: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management48 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Operation of CrusherNext slide shows from actual coal crusher the trend of energy consumption on a particular day.On line data shows crusher operation is proper in the beginning and towards the later part.In the middle portion for considerable period the crusher is not optimally loaded

Page 49: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management49 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case : 2

Page 50: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management50 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Ash Slurry PumpsCase Study

Page 51: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management51 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Case Study - NTPC PlantAfter On line monitoring system was operated for 2-3

months, the plant managers one key finding was that there were huge number of START & STOPS in their Ash slurry pumps. After analysis it was found that there are a lot of leakages at the pumps on the output side. After sealing of these leakages the requirement of running the Ash slurry pump for the same process drastically came down from 6 pumps to 3 pumps. Each pump consumes a total of 120-130kw/hrNet Saving = 120*3=360kw/hr*24hr = 8640kwh.

Page 52: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management52 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Earlier

Page 53: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management53 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

After

Page 54: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management54 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CW PumpsCase Study

Page 55: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management55 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CW System – Observations in Power plants

Specific Cooling water consumption cubic meters per MW higher than norm.Specific energy consumption (pumping efficiency) KWH per cubic meter higher.Ash water consumption higher.DM water make up pumps running even if there is no demand – energy savings possibility with VFD.High back pressure in condenser – can be improved by condenser tube cleaning. High TTD indicates low heat transfer efficiency.

Page 56: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management56 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

CW System – Some Audit Observations

Low efficiency of CW pumpsHead higher than requiredWastage of water in auxiliary heatingRecovery of waste water from clarifier etc

Page 57: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management57 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Page 58: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management58 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Page 59: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management59 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

Page 60: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in

Smart Energy Management60 Apr 1, 2005 © Copyright 1986-2005, ConZerv Proprietary & Confidential

SPECIFIC ENERGY CONSUMPTION REPORT

System Fan Unit -1 Unit-2 Unit-3 Unit-4

ID Fans

Fan-A 1.61 1.86 1.75

Fan-B 1.57 1.81 1.64

Fan-C 1.92 1.67

FD FansFan-A 1.45 1.35 1.14 1.42

Fan-B 1.25 1.24 1.12 1.50

PA FansFan-A 9.69 9.21 10.52 8.77

Fan-B 9.55 9.48 10.10 8.85

BFPs

Pump-A 7.91 8.07 9.0 7.15

Pump-B

Page 61: 1Measure 2Detect 3Control - India Core...Vindhyachal,Ramagundam,Kawas, Jhanor, Kahalgaon, OPGC (Jharsugada), Reliance Dahanu NTPC corporate has made On Line Monitoring standard in