4UcSbY`dY_^The Auto-Zone Basic control system converts a
single zone HVAC unit into a variable air vol-ume/variable air temperature multiple zone system.The microprocessor based Zone Manager calculatesthe heating and cooling requirements for each zone
based on real time information received from eachZone Controller. The Zone Manager then directs theHVAC unit to provide the appropriate amount of heat-ing, cooling, and ventilation to satisfy each zone's re-quirements. A static pressure sensor, which modulatesa bypass damper, maintains a constant system ductpressure.
Substantial savings can be realized using theAuto-Zone Basic system instead of installing multipleHVAC units to accommodate multiple zones. The
Auto-Zone Basic system is versatile and can be usedwith any 3-40 ton HVAC unit. It controls a variety oterminal unit functions including single duct pressuredependent or pressure independent systems.
User friendly, menu driven, fill in the blank pro-gramming, makes the Auto-Zone Basic easy to set upand operate without the need for specialized training.
ZoneView AZ, a Windows based color graphicsoftware package is available at no additional chargeThe optional CommLink II must be ordered and con-nected to a PC in order to use the software for on-sitecontrol and monitoring. If remote monitoring and con-trol is required, an optional modem must be ordered osupplied.
1ed_J_^U2QcYS
3_^db_\CicdU]
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
2/8 WattMaster Controls
DQR\U_V3_^dU^dc
TYPICAL APPLICATION........................................................................................................................3
TYPICAL SYSTEM................................................................................................................................. 4
SYSTEM OVERVIEW.............................................................................................................................5
TECHNICAL DATA................................................................................................................................. 6
ORDERING INFORMATION ..................................................................................................................7
NOTES................................................................................................................................................... 8
GXQd9c1ed_J_^U/
Auto-Zone is a new approach to providing simple, cost effective, control solutions to many standard unitary HVACsystems. Auto-Zone provides a very competitive controls solution for buildings which require more control than aprogrammable room thermostat will provide yet are not budgeted for full building automation systems.
These systems come pre-engineered, pre-programmed, and fully documented. This provides two main benefitsfor the contractor, engineer, and end user:
1. Advanced direct digital control technology for comfort and energy savings at up to 50% lowercost than traditional direct digital control systems.
2. A system that is simple to use allowing almost any HVAC technician to install and start-up thesystem without the need for specialized training.
The following pages are designed to give you a perspective of what Auto-Zone can do for your HVAC control ap-plications. Please contact us for more information or a list of distributorsin your area.
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
3/8
WattMaster Controls
Di`YSQ\1``\YSQdY_^
1ed_J_^U2QcYS1``\YSQdY_^
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
4/8 WattMaster Controls
Di`YSQ\9^cdQ\\QdY_^
1ed_J_^U2QcYSCicdU]
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
5/8
WattMaster Controls
CicdU]?fUbfYUg
CicdU]6UQdebUc EcUb@QbQ]UdUbc
Multizone comfort from a single zone AHU
Controls up to 16 individual zones
User friendly, menu driven programming
Backlighted LCD display provides complete sys-tem status
LEDs on Zone Manager show status for fan,cooling, heating, bypass, communications andalarms.
Seven day scheduling program
365 day holiday program
Programmable local or global zone overrides
Pressure dependent or independent zone opera-tion
Password protection prevents unauthorized access
Use of gas or electric heat
Selectable, continuous or cycling fan operation
Change filter alarm Energy saving economizer control available
Trend Logging to PC (requires optional communi-cations interface and software)
Windows based color graphic software for on-siteor remote monitoring when using optional commu-nications interface
Seven day scheduling
Holiday scheduling
Static pressure setpoint
Mechanical heating & cooling lockouts Minimum heating/cooling run time
Minimum heating/cooling off time
Heating/cooling change over delay
Supply air setpoint for economizer control
Economizer enable setpoint
Minimum economizer damper position
Occupied/unoccupied - heating/cooling setpoints
MIN/MAX zone damper position(pressure dependent only)
MIN/MAX zone CFM(pressure independent only)
Zone sensor setpoint adjustment offset limit
Zone sensor setpoint adjustment Range
6e^SdY_^
The Zone Manager monitors each zone and inturn controls the HVAC unit to satisfy the requirements
for each individual zone while maintaining efficient op-eration and comfort.
Data entry is accomplished through a keypad andbacklighted 4 line by 20 character Liquid Crystal Dis-play. User friendly, menu driven programming makesthe Auto-Zone system easy to set up and operatewithout the need for specialized training.
The Zone Controller monitors the space tem-perature and allocates the proper air flow into its as-signed space to achieve the desired comfort and ven-tilation levels. If the supply air temperature is near thezone temperature setpoint, the zone damper modu-lates to reduce or increase air flow as needed. If sup-ply air will not benefit the local zone, the controller willdirect the damper actuator to a minimum position andwait for a change in supply air temperature.
For pressure independent applications, an optionalairflow sensor can be added. The airflow sensor iseasily installed by plugging into a jack located on thecontroller board. The controller automatically recog-nizes the presence of the sensor on system power upand configures for pressure independent operation.
Drybulb economizer control is available via ananalog 0-10 VDC output from the Zone Manager. An
optional Wetbulb Module (OE782) is available to provide wetbulb calculations for maximum economizeefficiency.
An optional auxiliary relay board is available focontrol of auxiliary heat, series fan and parallel fancontrol. The relay board connects to the zone controllevia a plug-in modular connector.
The Zone Sensor is a patented design, flush walmounted sensor. A special plate on the face of thesensor accurately samples space conditions, yet re
jects the influence of internal wall temperatures. Thesensor comes in four models:
Sensor only Sensor w/ push button override Sensor w setpoint adjustment Sensor w/ override and setpoint adjustment
Each Zone Sensor setpoint adjustment is programmable from 0 to 5 via the Zone Manager.
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
6/8 WattMaster Controls
DUSX^YSQ\4QdQ
ZONE MANAGERPower........................................24 VAC
25 VA MaximumDimensions......... 7.75"W x 9H x 2.5"DOperating Temp...............10F - 149 FOperating Humidity.......... Max 90% RH
non-condensingDisplay................................Backlighted
4 Line by 20 CharacterKeypad. ................................... 16 Keys
I/O Configuration:Inputs-Thermistor (Type III)Outside Air Sensor ........-30 F - 180 FSupply Air Sensor..........-30 F - 180 FReturn Air Sensor..........-30 F - 180 FInputs-AnalogPressure Sensor .................0 to 5 WCBypass Actuator
Feedback Range ........... 500 to 7300 Inputs-Digital
Economizer Disable........... Dry ContactChange Filter Alarm........... Dry ContactForced OccupiedMode.................................. Dry ContactOutputs-Digital (2 amp @ 24 VAC)*Fan ......................................N.O. RelayCooling Stage #1.................N.O. RelayCooling Stage #2.................N.O. RelayHeating Stage #1.................N.O. RelayHeating Stage #2.................N.O. RelayBypass Actuator ......................Tri-stateExhaust Fan.........................N.O. RelayOutput-Analog
(1k min. load)Economizer Actuator .............0-10 VDC
Communication.........................RS-4859600 Baud
Weight .............................. Approx. 4 lb.
ZONE CONTROLLERPower .......................................24 VAC
10 VA Max.Including Actuator
Dimensions............. 7"W x 4H x 1.5" DOperating Temp............ 10 F to 149 F
Operating Humidity.......... Max 90% RHnon-condensing
I/O Configuration:InputsRoom Sensor................ 40 F to 120 FAir Flow Sensor* ........................Range
0-5000 CFM* For Pressure Independent operationonlyOutputsDamper Actuator .......... Tri-State Relay
Modular JackConnection
Expansion Port ..................Relay Board
-Optional-Modular Jack
Connection.
ACTUATORPower .........24VAC 50/60HZ or 24VDC
3.0 VA MaximumDimensions....4.53H x 2.56"W x 2.32"DOperating Temp.............-22 F - 122 F
Mounting........................Direct CoupledRotation .................0 to 95 AdjustableWiring .................. RJ11 - Modular JackRunning Torque........................35 in-lb.Run Time........................80 to 110 Sec
0 to 35 in-lbFeedback Resistance ..................... 0 to
10K/95Weight .........................................1.2 lb.
BYPASS PRESSURE SENSORPower .........................................5 VDC
Powered from Zone ManagerRange.................................0 to 5 WC
Accuracy................................... . 0.5%
Operating Temp.............. 57F to 284FDimensions...............Approx. 2.25 x 3Weight ........................................2.5 oz.
SENSORSSensor Element ........................ Type III
Thermistor
10k @ 77 F
Accuracy................... . 0.4 F between30 F to 150 F
DimensionsRoom Sensor............ Std. Single Gang
Flush Mount - White PlasticTamper Resistant
2.75W x 4.5H x 1.25DSensor Options............ Override Button
Setpoint Adjust SlideDuct Sensor........................... 6 LengthOutside AirSensor .............Weather Protective Box
2.75W x 4.5H x 1.25D
COMM LINK II (Optional)Power .......................................24 VAC
14 VA MaximumDimensions.............................1-5/8H x
5.25"W x 7"DOperating Temp.............. 10 F - 140 FCommunications:Computer................RS-232/9600 BaudNetwork ...............RS-485/19,200 Baud
Protocol .................. HSI Open ProtocolToken Passing
Connections:Power ....................... Quick Disconnect
TerminalsRS-485 ..................... Quick Disconnect
TerminalsComputer......................9 Pin/DB9 MaleModem..........................9 Pin/DB9 Male
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
7/8
WattMaster Controls
?bTUbY^W9^V_b]QdY_^
Zone Manager Package
OE710...............................................Zone Manager Package
Includes Zone Manager with Keypad and Display,Mounted in Enclosure, Supply and Return Air Temp.Sensors, Bypass Pressure Sensor.
Room Sensors - One required for each zone.
OE210.................................................... Room Sensor - Plain
OE211..........................................Room Sensor - w/ Override
OE212................................Room Sensor - w/ Setpoint Adjust
OE213............. Room Sensor - w/ Override & Setpoint Adjust
Bypass Damper Assemblies
Includes Damper Actuator mounted on Round AirDamper with Cable, Wiring Interface and SheetMetal Enclosure.
OE512-10 .............................Bypass Damper Assembly - 10
OE512-12 .............................Bypass Damper Assembly - 12
OE512-14 .............................Bypass Damper Assembly - 14
OE512-16 .............................Bypass Damper Assembly - 16
Zone Damper AssembliesPressure Dependent
Includes Damper Actuator and Zone Controllermounted on Round Air Damper with sheet metal en-closure.
OE510-06 ...................................Zone Damper Assembly - 6
OE510-08 ...................................Zone Damper Assembly - 8
OE510-10 .................................Zone Damper Assembly - 10
OE510-12 .................................Zone Damper Assembly - 12
OE510-14 .................................Zone Damper Assembly - 14
OE510-16 .................................Zone Damper Assembly - 16
Zone Damper Assemblies
Pressure Independent
Includes Damper Actuator, Zone Controller and AirFlow Sensor mounted on Round Air Damper withSheet Metal Enclosure.
OE511-06 ...................................Zone Damper Assembly - 6
OE511-08 ...................................Zone Damper Assembly - 8
OE511-10 .................................Zone Damper Assembly - 10
OE511-12 .................................Zone Damper Assembly - 12
OE511-14 .................................Zone Damper Assembly - 14
OE511-16 .................................Zone Damper Assembly - 16
Slaved-Zone Damper Assemblies
Includes Damper Actuator, Wiring Interface andmounted on Round Air Damper with sheet metal en-
closure. Also Includes OE267 Slave Wiring Adapter.OE513-06 ...................... Slaved-Zone Damper Assembly - 6
OE513-08 ...................... Slaved-Zone Damper Assembly - 8
OE513-10 .................... Slaved-Zone Damper Assembly - 10
OE513-12 .................... Slaved-Zone Damper Assembly - 12
OE513-14 .................... Slaved-Zone Damper Assembly - 14
OE513-16 .................... Slaved-Zone Damper Assembly - 16
Accessories
OE782........................................................... Wetbulb Modul
Provides Wetbulb Temp. Monitoring for Control ofAll Economizer Equipped Units on the System. In-cludes: Wetbulb Module, Outside Air Humidity Sen-sor.
OE330-21-AZGPC.......................................... GPC Controlle
General Purpose Controller with (5) Control Relays,(5) Analog Inputs and (1) Analog Output. Used forAuxiliary Control Functions such as Boiler Control,Humidity Control Etc..
OE310-21-AZOSS ............................ Optimal Start Schedule
Provides Expanded Scheduling Capabilities beyondthose incorporated into the PLUS System. Sched-uler Provides for Optimal Start/Stop and up to (7)Independent Schedules.
OE310-21-AZLP ........................................ Lighting Controlle
Provides Lighting Control Capability to the PLUSSystem. Lighting Controller Provides for (7) Inde-
pendent Schedules for Lighting Control.OE281-01 ............................. Economizer Actuator -133 in/lb
Belimo AF24SR - 133 in/lb. torque rated actuator.For use when HVAC unit actuator is not compatiblewith 0-10VDC signal.
OE281-02 .............................. Economizer Actuator - 60 in/lb
Belimo NF24SR - 60 in/lb. torque rated actuator. Foruse when HVAC unit actuator is not compatible with0-10VDC signal.
OE266-01 ................................. Actuator Interface Module K
Converts Honeywell M7415 & M7405 Actuators foruse with 0-10VDC signal. Includes Adapter and24VAC Isolation Transformer
OE321............... Relay Expansion Board for Zone Controller
Provides for Control of Auxiliary Heat, Series andParallel Fan Terminal Units.
OE340-10-AGSTG......................... Staging Expansion Board
Allows for Addition of 4 Stages of Heating and 4Stages of Cooling
OE740......................................Rectangular Zone Damper K
Damper Kit (Damper Not Included). IncludesDamper Actuator and Zone Controller FactoryMounted in an Enclosure
OE741.................................. Rectangular Bypass Damper K
Damper Kit (Damper Not Included). IncludesDamper Actuator and Wiring Interface FactoryMounted in an Enclosure
OE739..........................Rectangular Slaved-Zone Damper K
Damper Kit (Damper Not Included). IncludesDamper Actuator and Wiring Interface FactoryMounted in an Enclosure. Also Includes OE267Slave Wiring Adapter.
.
-
8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]
8/8
Form: WM-AZB-DS-01D Printed in the USA April 1999