    4UcSbY`dY_^The Auto-Zone Basic control system converts a

    single zone HVAC unit into a variable air vol-ume/variable air temperature multiple zone system.The microprocessor based Zone Manager calculatesthe heating and cooling requirements for each zone

    based on real time information received from eachZone Controller. The Zone Manager then directs theHVAC unit to provide the appropriate amount of heat-ing, cooling, and ventilation to satisfy each zone's re-quirements. A static pressure sensor, which modulatesa bypass damper, maintains a constant system ductpressure.

    Substantial savings can be realized using theAuto-Zone Basic system instead of installing multipleHVAC units to accommodate multiple zones. The

    Auto-Zone Basic system is versatile and can be usedwith any 3-40 ton HVAC unit. It controls a variety oterminal unit functions including single duct pressuredependent or pressure independent systems.

    User friendly, menu driven, fill in the blank pro-gramming, makes the Auto-Zone Basic easy to set upand operate without the need for specialized training.

    ZoneView AZ, a Windows based color graphicsoftware package is available at no additional chargeThe optional CommLink II must be ordered and con-nected to a PC in order to use the software for on-sitecontrol and monitoring. If remote monitoring and con-trol is required, an optional modem must be ordered osupplied.

    1ed_J_^U2QcYS

    3_^db_\CicdU]

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    2/8 WattMaster Controls

    DQR\U_V3_^dU^dc

    TYPICAL APPLICATION........................................................................................................................3

    TYPICAL SYSTEM................................................................................................................................. 4

    SYSTEM OVERVIEW.............................................................................................................................5

    TECHNICAL DATA................................................................................................................................. 6

    ORDERING INFORMATION ..................................................................................................................7

    NOTES................................................................................................................................................... 8

    GXQd9c1ed_J_^U/

    Auto-Zone is a new approach to providing simple, cost effective, control solutions to many standard unitary HVACsystems. Auto-Zone provides a very competitive controls solution for buildings which require more control than aprogrammable room thermostat will provide yet are not budgeted for full building automation systems.

    These systems come pre-engineered, pre-programmed, and fully documented. This provides two main benefitsfor the contractor, engineer, and end user:

    1. Advanced direct digital control technology for comfort and energy savings at up to 50% lowercost than traditional direct digital control systems.

    2. A system that is simple to use allowing almost any HVAC technician to install and start-up thesystem without the need for specialized training.

    The following pages are designed to give you a perspective of what Auto-Zone can do for your HVAC control ap-plications. Please contact us for more information or a list of distributorsin your area.

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    3/8

    WattMaster Controls

    Di`YSQ\1``\YSQdY_^

    1ed_J_^U2QcYS1``\YSQdY_^

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    4/8 WattMaster Controls

    Di`YSQ\9^cdQ\\QdY_^

    1ed_J_^U2QcYSCicdU]

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    5/8

    WattMaster Controls

    CicdU]?fUbfYUg

    CicdU]6UQdebUc EcUb@QbQ]UdUbc

    Multizone comfort from a single zone AHU

    Controls up to 16 individual zones

    User friendly, menu driven programming

    Backlighted LCD display provides complete sys-tem status

    LEDs on Zone Manager show status for fan,cooling, heating, bypass, communications andalarms.

    Seven day scheduling program

    365 day holiday program

    Programmable local or global zone overrides

    Pressure dependent or independent zone opera-tion

    Password protection prevents unauthorized access

    Use of gas or electric heat

    Selectable, continuous or cycling fan operation

    Change filter alarm Energy saving economizer control available

    Trend Logging to PC (requires optional communi-cations interface and software)

    Windows based color graphic software for on-siteor remote monitoring when using optional commu-nications interface

    Seven day scheduling

    Holiday scheduling

    Static pressure setpoint

    Mechanical heating & cooling lockouts Minimum heating/cooling run time

    Minimum heating/cooling off time

    Heating/cooling change over delay

    Supply air setpoint for economizer control

    Economizer enable setpoint

    Minimum economizer damper position

    Occupied/unoccupied - heating/cooling setpoints

    MIN/MAX zone damper position(pressure dependent only)

    MIN/MAX zone CFM(pressure independent only)

    Zone sensor setpoint adjustment offset limit

    Zone sensor setpoint adjustment Range

    6e^SdY_^

    The Zone Manager monitors each zone and inturn controls the HVAC unit to satisfy the requirements

    for each individual zone while maintaining efficient op-eration and comfort.

    Data entry is accomplished through a keypad andbacklighted 4 line by 20 character Liquid Crystal Dis-play. User friendly, menu driven programming makesthe Auto-Zone system easy to set up and operatewithout the need for specialized training.

    The Zone Controller monitors the space tem-perature and allocates the proper air flow into its as-signed space to achieve the desired comfort and ven-tilation levels. If the supply air temperature is near thezone temperature setpoint, the zone damper modu-lates to reduce or increase air flow as needed. If sup-ply air will not benefit the local zone, the controller willdirect the damper actuator to a minimum position andwait for a change in supply air temperature.

    For pressure independent applications, an optionalairflow sensor can be added. The airflow sensor iseasily installed by plugging into a jack located on thecontroller board. The controller automatically recog-nizes the presence of the sensor on system power upand configures for pressure independent operation.

    Drybulb economizer control is available via ananalog 0-10 VDC output from the Zone Manager. An

    optional Wetbulb Module (OE782) is available to provide wetbulb calculations for maximum economizeefficiency.

    An optional auxiliary relay board is available focontrol of auxiliary heat, series fan and parallel fancontrol. The relay board connects to the zone controllevia a plug-in modular connector.

    The Zone Sensor is a patented design, flush walmounted sensor. A special plate on the face of thesensor accurately samples space conditions, yet re

    jects the influence of internal wall temperatures. Thesensor comes in four models:

    Sensor only Sensor w/ push button override Sensor w setpoint adjustment Sensor w/ override and setpoint adjustment

    Each Zone Sensor setpoint adjustment is programmable from 0 to 5 via the Zone Manager.

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    6/8 WattMaster Controls

    DUSX^YSQ\4QdQ

    ZONE MANAGERPower........................................24 VAC

    25 VA MaximumDimensions......... 7.75"W x 9H x 2.5"DOperating Temp...............10F - 149 FOperating Humidity.......... Max 90% RH

    non-condensingDisplay................................Backlighted

    4 Line by 20 CharacterKeypad. ................................... 16 Keys

    I/O Configuration:Inputs-Thermistor (Type III)Outside Air Sensor ........-30 F - 180 FSupply Air Sensor..........-30 F - 180 FReturn Air Sensor..........-30 F - 180 FInputs-AnalogPressure Sensor .................0 to 5 WCBypass Actuator

    Feedback Range ........... 500 to 7300 Inputs-Digital

    Economizer Disable........... Dry ContactChange Filter Alarm........... Dry ContactForced OccupiedMode.................................. Dry ContactOutputs-Digital (2 amp @ 24 VAC)*Fan ......................................N.O. RelayCooling Stage #1.................N.O. RelayCooling Stage #2.................N.O. RelayHeating Stage #1.................N.O. RelayHeating Stage #2.................N.O. RelayBypass Actuator ......................Tri-stateExhaust Fan.........................N.O. RelayOutput-Analog

    (1k min. load)Economizer Actuator .............0-10 VDC

    Communication.........................RS-4859600 Baud

    Weight .............................. Approx. 4 lb.

    ZONE CONTROLLERPower .......................................24 VAC

    10 VA Max.Including Actuator

    Dimensions............. 7"W x 4H x 1.5" DOperating Temp............ 10 F to 149 F

    Operating Humidity.......... Max 90% RHnon-condensing

    I/O Configuration:InputsRoom Sensor................ 40 F to 120 FAir Flow Sensor* ........................Range

    0-5000 CFM* For Pressure Independent operationonlyOutputsDamper Actuator .......... Tri-State Relay

    Modular JackConnection

    Expansion Port ..................Relay Board

    -Optional-Modular Jack

    Connection.

    ACTUATORPower .........24VAC 50/60HZ or 24VDC

    3.0 VA MaximumDimensions....4.53H x 2.56"W x 2.32"DOperating Temp.............-22 F - 122 F

    Mounting........................Direct CoupledRotation .................0 to 95 AdjustableWiring .................. RJ11 - Modular JackRunning Torque........................35 in-lb.Run Time........................80 to 110 Sec

    0 to 35 in-lbFeedback Resistance ..................... 0 to

    10K/95Weight .........................................1.2 lb.

    BYPASS PRESSURE SENSORPower .........................................5 VDC

    Powered from Zone ManagerRange.................................0 to 5 WC

    Accuracy................................... . 0.5%

    Operating Temp.............. 57F to 284FDimensions...............Approx. 2.25 x 3Weight ........................................2.5 oz.

    SENSORSSensor Element ........................ Type III

    Thermistor

    10k @ 77 F

    Accuracy................... . 0.4 F between30 F to 150 F

    DimensionsRoom Sensor............ Std. Single Gang

    Flush Mount - White PlasticTamper Resistant

    2.75W x 4.5H x 1.25DSensor Options............ Override Button

    Setpoint Adjust SlideDuct Sensor........................... 6 LengthOutside AirSensor .............Weather Protective Box

    2.75W x 4.5H x 1.25D

    COMM LINK II (Optional)Power .......................................24 VAC

    14 VA MaximumDimensions.............................1-5/8H x

    5.25"W x 7"DOperating Temp.............. 10 F - 140 FCommunications:Computer................RS-232/9600 BaudNetwork ...............RS-485/19,200 Baud

    Protocol .................. HSI Open ProtocolToken Passing

    Connections:Power ....................... Quick Disconnect

    TerminalsRS-485 ..................... Quick Disconnect

    TerminalsComputer......................9 Pin/DB9 MaleModem..........................9 Pin/DB9 Male

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    7/8

    WattMaster Controls

    ?bTUbY^W9^V_b]QdY_^

    Zone Manager Package

    OE710...............................................Zone Manager Package

    Includes Zone Manager with Keypad and Display,Mounted in Enclosure, Supply and Return Air Temp.Sensors, Bypass Pressure Sensor.

    Room Sensors - One required for each zone.

    OE210.................................................... Room Sensor - Plain

    OE211..........................................Room Sensor - w/ Override

    OE212................................Room Sensor - w/ Setpoint Adjust

    OE213............. Room Sensor - w/ Override & Setpoint Adjust

    Bypass Damper Assemblies

    Includes Damper Actuator mounted on Round AirDamper with Cable, Wiring Interface and SheetMetal Enclosure.

    OE512-10 .............................Bypass Damper Assembly - 10

    OE512-12 .............................Bypass Damper Assembly - 12

    OE512-14 .............................Bypass Damper Assembly - 14

    OE512-16 .............................Bypass Damper Assembly - 16

    Zone Damper AssembliesPressure Dependent

    Includes Damper Actuator and Zone Controllermounted on Round Air Damper with sheet metal en-closure.

    OE510-06 ...................................Zone Damper Assembly - 6

    OE510-08 ...................................Zone Damper Assembly - 8

    OE510-10 .................................Zone Damper Assembly - 10

    OE510-12 .................................Zone Damper Assembly - 12

    OE510-14 .................................Zone Damper Assembly - 14

    OE510-16 .................................Zone Damper Assembly - 16

    Zone Damper Assemblies

    Pressure Independent

    Includes Damper Actuator, Zone Controller and AirFlow Sensor mounted on Round Air Damper withSheet Metal Enclosure.

    OE511-06 ...................................Zone Damper Assembly - 6

    OE511-08 ...................................Zone Damper Assembly - 8

    OE511-10 .................................Zone Damper Assembly - 10

    OE511-12 .................................Zone Damper Assembly - 12

    OE511-14 .................................Zone Damper Assembly - 14

    OE511-16 .................................Zone Damper Assembly - 16

    Slaved-Zone Damper Assemblies

    Includes Damper Actuator, Wiring Interface andmounted on Round Air Damper with sheet metal en-

    closure. Also Includes OE267 Slave Wiring Adapter.OE513-06 ...................... Slaved-Zone Damper Assembly - 6

    OE513-08 ...................... Slaved-Zone Damper Assembly - 8

    OE513-10 .................... Slaved-Zone Damper Assembly - 10

    OE513-12 .................... Slaved-Zone Damper Assembly - 12

    OE513-14 .................... Slaved-Zone Damper Assembly - 14

    OE513-16 .................... Slaved-Zone Damper Assembly - 16

    Accessories

    OE782........................................................... Wetbulb Modul

    Provides Wetbulb Temp. Monitoring for Control ofAll Economizer Equipped Units on the System. In-cludes: Wetbulb Module, Outside Air Humidity Sen-sor.

    OE330-21-AZGPC.......................................... GPC Controlle

    General Purpose Controller with (5) Control Relays,(5) Analog Inputs and (1) Analog Output. Used forAuxiliary Control Functions such as Boiler Control,Humidity Control Etc..

    OE310-21-AZOSS ............................ Optimal Start Schedule

    Provides Expanded Scheduling Capabilities beyondthose incorporated into the PLUS System. Sched-uler Provides for Optimal Start/Stop and up to (7)Independent Schedules.

    OE310-21-AZLP ........................................ Lighting Controlle

    Provides Lighting Control Capability to the PLUSSystem. Lighting Controller Provides for (7) Inde-

    pendent Schedules for Lighting Control.OE281-01 ............................. Economizer Actuator -133 in/lb

    Belimo AF24SR - 133 in/lb. torque rated actuator.For use when HVAC unit actuator is not compatiblewith 0-10VDC signal.

    OE281-02 .............................. Economizer Actuator - 60 in/lb

    Belimo NF24SR - 60 in/lb. torque rated actuator. Foruse when HVAC unit actuator is not compatible with0-10VDC signal.

    OE266-01 ................................. Actuator Interface Module K

    Converts Honeywell M7415 & M7405 Actuators foruse with 0-10VDC signal. Includes Adapter and24VAC Isolation Transformer

    OE321............... Relay Expansion Board for Zone Controller

    Provides for Control of Auxiliary Heat, Series andParallel Fan Terminal Units.

    OE340-10-AGSTG......................... Staging Expansion Board

    Allows for Addition of 4 Stages of Heating and 4Stages of Cooling

    OE740......................................Rectangular Zone Damper K

    Damper Kit (Damper Not Included). IncludesDamper Actuator and Zone Controller FactoryMounted in an Enclosure

    OE741.................................. Rectangular Bypass Damper K

    Damper Kit (Damper Not Included). IncludesDamper Actuator and Wiring Interface FactoryMounted in an Enclosure

    OE739..........................Rectangular Slaved-Zone Damper K

    Damper Kit (Damper Not Included). IncludesDamper Actuator and Wiring Interface FactoryMounted in an Enclosure. Also Includes OE267Slave Wiring Adapter.

    .

  • 8/14/2019 1ed J ^U 2QcYS 3 ^Db \ CicdU]

    8/8

    Form: WM-AZB-DS-01D Printed in the USA April 1999

    All rights reserved Copyright 1999

    WattMaster Controls Inc. 8500 NW River Park Drive Parkville, Mo. 64152Phone (816) 505-1100 website: wattmaster.com Fax (816) 505-1101