    AMENDMENTS OVERVIEWEarthing systems diagrams now in part 3

    New numbering system for UK only

    Changes to fuse designations

    Chapter 44 electromagnetic influences added

    Changes to Reg. 522.6 (cables in walls)

    Part 6 now has Electrical Installation Condition Report

    Part 7 changes/additions to Special Installations or Locations

    Appendix 16 surge protective devices added

    Appendices have changes & Appendix 11 & 12 deleted

  • 7/28/2019 17th Edition 2011 Amendments

    3/18

    Regulation Numbering

    612.3.2

    Chapter 61

    Initial

    verification

    Section 612

    Testing

    Group 3

    Insulation

    resistance

    Regulation 2

    Test voltages

    Part 6

    Inspection &

    testing

    First Digit - Part

    Second Digits - Chapter

    Third Digits - Section

    Fourth Digits - Group

    Fifth Digits - Regulation

  • 7/28/2019 17th Edition 2011 Amendments

    4/18

    TABLES

    41.2

    Part 4

    Protection for

    safety

    Chapter 41

    Protection against

    electric shock

    Actual Table Number

    Max. Zs

  • 7/28/2019 17th Edition 2011 Amendments

    5/18

    Regulation Numbering UK

    522.6.100

    Chapter 52

    Selection & erection

    of wiring systems

    Group

    Impact AG

    UK Regulation only 100series used when referring to

    CENELEC documents

    Part 5

    Selection &

    erection of

    equipment

    Section 522

    Selection & erection

    of wiring systems in

    relation to externalinfluences

  • 7/28/2019 17th Edition 2011 Amendments

    6/18

    Removal of BS 1361

    Replaced with BS 88-3 & new ratings (ie: 16A, 32A etc.)

    New time/current characteristic graphs in Appendix 3

    Changes to ratings means new maximum earth fault loop impedance values Tables 41.2 & 41.4

    Original BS 88 fuses now BS 88-2

    Change to fuse designations

  • 7/28/2019 17th Edition 2011 Amendments

    7/18

    New Fuse Designations

    General

    Purpose BS

    88-2 gG

    System E

    (Bolted)

    Colour coded as BS 3036Colour coded as BS 3036BS 88-3

    System C

    old 1361

    BS 3036

    General

    Purpose BS

    88-2 gM

    System G

    (Clip In)

    BS 1362

  • 7/28/2019 17th Edition 2011 Amendments

    8/18

    Changes to cables concealed in a wall

    or a partition

    522.6.100

    Cables to be 50mm deep OR

    i. Incorporate an earthed metal covering i.e. MI

    OR

    ii. Enclosed in earthed metal conduit OR

    iii. Enclosed in earthed trunking or ducting OR

    iv. Mechanically protected (capping not sufficient,

    must withstand penetration by nail, screws

    etc)

    v. ALL to be in safe zones

    vi. Form part of a SELV or PELV circuit (NEW)

    Not allowed unless 50mm

    deep or i,ii,iii,iv are achieved

    Additional protection by RCD shall be provided if i, ii, iii or iv above not complied with. RCD to

    comply with regulation 415.1.1

  • 7/28/2019 17th Edition 2011 Amendments

    9/18

    New section 710 Medical Locations

    Applies to:- hospitals, dentists, private clinics, healthcare centres etc

    Areas grouped (0,1,2) with different requirements for each

    Requirement to assess what procedures take place to be able to determine groups

    Installation of insulation monitoring devicesInstallation of protective conductors of maximum resistance values

    Need to ensure unwanted tripping ofRCDs

    Lower disconnection times

    Emergency safety sources required

  • 7/28/2019 17th Edition 2011 Amendments

    10/18

    New section 729 Operating &

    Maintenance Gangways

    Applies to:- switch rooms etc. where access is restricted to

    skilled/instructed persons

    Minimum access required, measurements given

    Clearly Marked Areas

    Easy access & Egress

  • 7/28/2019 17th Edition 2011 Amendments

    11/18

    Chapter 62 & Appendix 6 Model Forms

    for Certification & Reporting

    New forms for periodic inspection & testing

    Now issue an Electrical Installation Condition Report

    Form for domestic & similar up to 100A

    New scheduleof inspection results & schedule of test results

    New observation codes C1, C2 & C3

    Electrical installation certificate inc schedule of inspection

    results for new work & minor electrical installation works

    certificate NO CHANGE

  • 7/28/2019 17th Edition 2011 Amendments

    12/18

    New Certification Forms

  • 7/28/2019 17th Edition 2011 Amendments

    13/18

    New Forms For Certification

  • 7/28/2019 17th Edition 2011 Amendments

    14/18

    New Forms for Certification

  • 7/28/2019 17th Edition 2011 Amendments

    15/18

    CODES:

    C1 Danger exists, Risk of Injury, rectify Immediately

    C2 Potentially dangerous, remedial action required as a mater of Urgency

    C3 Improvement recommended

    New Codes on ECRs

  • 7/28/2019 17th Edition 2011 Amendments

    16/18

    Appendix 11 - Effects of Harmonic Currents on

    Balanced 3 Phase Systems

    Appendix 12 -Voltage Drop in Consumers Installations

    Deleted by BS 7671:2008 (2011) moved to App.4 para. 5.5 & 5.6

    Deleted by BS 7671:2008 (2011) moved to App.4 para. 6.4

    Changes to Appendices

  • 7/28/2019 17th Edition 2011 Amendments

    17/18

    Appendix 16 (Informative)

    Devices for Protection Against

    Overvoltage

    Examples of connecting Surge Protective Devices to different systems

    Different types of SPD & the locations they are required

  • 7/28/2019 17th Edition 2011 Amendments

    18/18

    Questions...Please feel free to email any questions you

    may have on the changes to BS7671.