1794-in064e-en-p flex i/o 4-channel pulse counter module … · 2017. 12. 6. · throughout this...

2
Publication 1794-IN064E-EN-P - August 2015 Installation Instructions FLEX I/O 4-Channel Pulse Counter Module Catalog Numbers 1794-IP4 Series B Environment and Enclosure Preventing Electrostatic Discharge North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1794-IP4 Series B. Install Your Digital Module The module mounts on a 1794 terminal base. 1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 1 as required for this type of module. 2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot install the module unless the connector is fully extended. 3. Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base. 4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base. 5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (7) is locked into the module. Connecting Wiring for the 1794-IP4 Module (using a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base unit) 1. Connect individual input wiring (N, N ) or (D, D ) for each channel to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for I794-IP4 table. 2. Connect the associated input common to the corresponding terminal on the 16-33 row (B) for each input as indicated in the Wiring Connections for I794-IP4 table. 3. Connect +V DC power to terminal 34 on the 34-51 row (C). 4. Connect DC return to terminal 16 on the 16-33 row (B). 5. If daisychaining power to the next terminal base, connect a jumper from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit. 6. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit. Connecting Wiring for the 1794-IP4 Module (using a 1794-TBN terminal base unit) 1. Connect individual input wiring (N, N ) or (D, D ) for each channel to the even-numbered terminals on the 16-33 row (B) as indicated in the Wiring Connections for I794-IP4 table. 2. Connect the associated input common to the corresponding odd-numbered terminal on the 34-51 row (C) for each input as indicated in the Wiring Connections for I794-IP4 table. 3. Connect +V DC power to terminal 34 on the 34-51 row (C). 4. Connect DC return to terminal 16 on the 16-33 row (B). 5. If daisychaining power to the next terminal base, connect a jumper from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit. 6. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit. Wiring Connections for I794-IP4 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com ) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences. IMPORTANT Identifies information that is critical for successful application and understanding of the product. ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see: Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1 . NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static-safe workstation. ATTENTION: FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation. WARNING: EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Substitution of components may impair suitability for Class I, Division 2. If this product contains batteries, they must only be changed in an area known to be nonhazardous. WARNING: RISQUE D’EXPLOSION Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement. Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2. S’assurer que l’environnement est classé non dangereux avant de changer les piles. Description Description 1 Keyswitch 5 Alignment bar 2 Terminal base 6 Groove 3 Flexbus connector 7 Latching mechanism 4 Module ATTENTION: During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up. WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 1 2 3 4 5 6 7 ATTENTION: Do not connect maximum input voltage simultaneously to all inputs if the module ambient temperature is expected to exceed 40 °C. If the ambient temperature is expected to continuously exceed 40 °C, you must limit the input voltage using an external resistor on each input. A 1kΩ resistor effectively limits a 24V sensor signal to about 15V at the input. Do not limit the input to less than 6V. ATTENTION: Do not connect maximum input voltage simultaneously to all inputs if the module ambient temperature is expected to exceed 40 °C. If the ambient temperature is expected to continuously exceed 40 °C, you must limit the input voltage using an external resistor on each input. A 1kΩ resistor effectively limits a 24V sensor signal to about 15V at the input. Do not limit the input to less than 6V. Channel Signal Name (1) (1) Any unused signals have to be connected to the associated common. 1794-TB2, 1794-TB3, 1794-TB3S 1794-TBN (2) (2) Auxiliary terminal blocks are required when using these terminal base units. Signal 0V DC COM 12...24V DC Signal 16-bit Period Time Measurement 0 N A-0 B-17 C-35 B-0 N A-1 B-18 C-36 B-1 1 N A-2 B-19 C-37 B-2 N A-3 B-20 C-38 B-3 2 N A-4 B-21 C-39 B-4 N A-5 B-22 C-40 B-5 3 N A-6 B-23 C-41 B-6 N A-7 B-24 C-42 B-7 32-bit Period Time Measurement 0 D A-8 B-25 C-43 B-8 D A-9 B-26 C-44 B-9 1 D A-10 B-27 C-45 B-10 D A-11 B-28 C-46 B-11 2 D A-12 B-29 C-47 B-12 D A-13 B-30 C-48 B-13 3 D A-14 B-31 C-49 B-14 D A-15 B-32 C-50 B-15 0V DC Terminals 16...33 (1794-TB2, 1794-TB3, 1794-TB3S) Terminals 16 and 33 12/24V DC Terminals 34 and 51 (1794-TB2) Terminals 34...51 (1794-TB3, 1794-TB3S) Terminals 34 and 51 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 34 Inputs Commons (1794-TB3 shown) -V (Supply Common) = Terminals B16 and B33 +V (Supply +Voltage) = Terminals C34 and C51 -V Voltage In +V Voltage Out +V Voltage A B C Common -V Common (Use B33 and C51 for daisy-chaining to next terminal base unit.) 16 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 51 33 34 +V COM +V COM B C Even Numbered I/O Terminals 0 thru 14 Odd Numbered I/O Terminals 1 thru 15 +V = Terminals C34 and C51 COM (-V) = Terminals B16 and B33

Upload: others

Post on 06-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • Installation Instructions

    FLEX I/O 4-Channel Pulse Counter ModuleCatalog Numbers 1794-IP4 Series B

    Environment and Enclosure

    Preventing Electrostatic Discharge

    North American Hazardous Location ApprovalThe following modules are North American Hazardous Location approved: 1794-IP4 Series B.

    Install Your Digital Module

    The module mounts on a 1794 terminal base.

    1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 1 as required for this type of module.

    2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot install the module unless the connector is fully extended.

    3. Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base.

    4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.

    5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (7) is locked into the module.

    Connecting Wiring for the 1794-IP4 Module (using a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base unit)

    1. Connect individual input wiring (N, N) or (D, D) for each channel to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for I794-IP4 table.

    2. Connect the associated input common to the corresponding terminal on the 16-33 row (B) for each input as indicated in the Wiring Connections for I794-IP4 table.

    3. Connect +V DC power to terminal 34 on the 34-51 row (C).4. Connect DC return to terminal 16 on the 16-33 row (B).5. If daisychaining power to the next terminal base, connect a jumper

    from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.

    6. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit.

    Connecting Wiring for the 1794-IP4 Module (using a 1794-TBN terminal base unit)

    1. Connect individual input wiring (N, N) or (D, D) for each channel to the even-numbered terminals on the 16-33 row (B) as indicated in the Wiring Connections for I794-IP4 table.

    2. Connect the associated input common to the corresponding odd-numbered terminal on the 34-51 row (C) for each input as indicated in the Wiring Connections for I794-IP4 table.

    3. Connect +V DC power to terminal 34 on the 34-51 row (C).4. Connect DC return to terminal 16 on the 16-33 row (B).5. If daisychaining power to the next terminal base, connect a jumper

    from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.

    6. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit.

    Wiring Connections for I794-IP4

    Important User Information

    Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations.

    WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.In addition to this publication, see:

    • Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1.

    • NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

    ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

    • Touch a grounded object to discharge potential static.• Wear an approved grounding wriststrap.• Do not touch connectors or pins on component boards.• Do not touch circuit components inside the equipment.• If available, use a static-safe workstation.

    ATTENTION: FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.

    WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

    WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    The following information applies when operating this equipment in hazardous locations:

    Informations sur l’utilisation de cet équipement en environnements dangereux:

    Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.

    WARNING: EXPLOSION HAZARD• Do not disconnect

    equipment unless power has been removed or the area is known to be nonhazardous.

    • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    • Substitution of components may impair suitability for Class I, Division 2.

    • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    WARNING: RISQUE D’EXPLOSION• Couper le courant ou

    s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.

    • Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

    • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

    • S’assurer que l’environnement est classé non dangereux avant de changer les piles.

    Description Description

    1 Keyswitch 5 Alignment bar

    2 Terminal base 6 Groove

    3 Flexbus connector 7 Latching mechanism

    4 Module

    ATTENTION: During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.

    WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    1

    2

    3

    4 5

    6

    7

    ATTENTION: Do not connect maximum input voltage simultaneously to all inputs if the module ambient temperature is expected to exceed 40 °C. If the ambient temperature is expected to continuously exceed 40 °C, you must limit the input voltage using an external resistor on each input. A 1kΩ resistor effectively limits a 24V sensor signal to about 15V at the input. Do not limit the input to less than 6V.

    ATTENTION: Do not connect maximum input voltage simultaneously to all inputs if the module ambient temperature is expected to exceed 40 °C. If the ambient temperature is expected to continuously exceed 40 °C, you must limit the input voltage using an external resistor on each input. A 1kΩ resistor effectively limits a 24V sensor signal to about 15V at the input. Do not limit the input to less than 6V.

    Channel Signal Name(1)

    (1) Any unused signals have to be connected to the associated common.

    1794-TB2, 1794-TB3, 1794-TB3S 1794-TBN(2)

    (2) Auxiliary terminal blocks are required when using these terminal base units.

    Signal 0V DC COM 12...24V DC Signal

    16-bit Period Time Measurement

    0 N A-0 B-17 C-35 B-0

    N A-1 B-18 C-36 B-1

    1 N A-2 B-19 C-37 B-2

    N A-3 B-20 C-38 B-3

    2 N A-4 B-21 C-39 B-4

    N A-5 B-22 C-40 B-5

    3 N A-6 B-23 C-41 B-6

    N A-7 B-24 C-42 B-7

    32-bit Period Time Measurement

    0 D A-8 B-25 C-43 B-8

    D A-9 B-26 C-44 B-9

    1 D A-10 B-27 C-45 B-10

    D A-11 B-28 C-46 B-11

    2 D A-12 B-29 C-47 B-12

    D A-13 B-30 C-48 B-13

    3 D A-14 B-31 C-49 B-14

    D A-15 B-32 C-50 B-15

    0V DC Terminals 16...33 (1794-TB2, 1794-TB3, 1794-TB3S)

    Terminals 16 and 33

    12/24V DC Terminals 34 and 51 (1794-TB2) Terminals 34...51 (1794-TB3, 1794-TB3S)

    Terminals 34 and 51

    17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    16

    35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 5134

    Inputs

    Commons

    (1794-TB3 shown)-V (Supply Common) = Terminals B16 and B33+V (Supply +Voltage) = Terminals C34 and C51

    -V

    VoltageIn +V

    VoltageOut +V

    Voltage

    A

    B

    C

    Common-V

    Common

    (Use B33 and C51 for daisy-chaining to next terminal base unit.)

    16 0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15 51

    33

    34

    +V

    COM

    +V

    COM

    B

    C

    Even Numbered I/O Terminals 0 thru 14

    Odd Numbered I/O Terminals 1 thru 15

    +V = Terminals C34 and C51COM (-V) = Terminals B16 and B33

    Publication 1794-IN064E-EN-P - August 2015

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://literature.rockwellautomation.com/http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • Example of 16-bit Period Time Measurement and 16-bit Accumulating Pulse Counter Wiring (4-channels)

    Example of 32-bit Period Time Measurement Wiring (4-channels)

    Configure Your Module

    Filter Function DescriptionUse the filter in either 16-bit or 32-bit mode. Enable filter to use a triangular shape waveform of frequencies as low as 1 Hz. If the filter is not enabled, the module will only function properly with input waveform of square shape.

    Specifications – FLEX I/O 4-channel Pulse Counter Module

    Environmental Specifications

    Certifications

    Input (Read) Image

    Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

    0 Reserved

    1 Counter 00 – 16-bit period measurement for channel 0

    2 Counter 01 – pulse counter for channel 0 – 16-bit pulse counting

    1 32-bit period measurement for channel 0

    2 32-bit period measurement for channel 0

    3 Counter 10 – 16-bit period measurement for channel 1

    4 Counter 11 – pulse counter for channel 1 – 16-bit pulse counting

    3 32-bit period measurement for channel 1

    4 32-bit period measurement for channel 1

    5 Counter 20 – 16-bit period measurement for channel 2

    6 Counter 21 – pulse counter for channel 2 – 16-bit pulse counting

    5 32-bit period measurement for channel 2

    6 32-bit period measurement for channel 2

    7 Counter 30 – 16-bit period measurement for channel 3

    8 Counter 31 – pulse counter for channel 3 – 16-bit pulse counting

    7 32-bit period measurement for channel 3

    8 32-bit period measurement for channel 3

    9 Readback of Control Word 2

    Reserved RD3 RD2 RD1 RD0 M3 M2 M1 M0

    10 Revision Read - software version code

    Where M = Measurement ready bit – positive edge measurement ready for the respective channel RD = Reset done

    Output/Configuration Image

    Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

    0 Control Word 0 – selects the measure function

    1 Control Word 1 – sets the clock frequency and period multiple

    2 Control Word 2 – sets the start of a new measurement

    3 Not used

    N

    N

    17 18 19 20 21 22 23 24 25 33

    0 1 2 3 4 5 6 7 8

    16

    35 36 37 38 39 40 41 42

    15

    51340V DC

    12/24V DC

    ExternalPower Supply

    12/24V DC

    Signal Inputs

    Channel 0

    Channel 3

    Channel 2

    Channel 1

    0

    AB

    C

    1

    N

    N

    N

    N

    N

    N

    Accumulating Pulse Counter

    6 73 4 52

    16

    0

    340V DC

    12/24V DC

    ExternalPower Supply

    12/24V DC

    32-bit period time measurement

    Signal Inputs A

    BC

    24 25 26 27 28 29 30 31 32

    8 9 10 11 12 13 14 15

    42 43 44 45 46 47 48 49 50

    33

    51

    10 11 12 13

    D

    D

    Channel 0

    Channel 3

    Channel 2

    Channel 1

    D

    D

    D

    D

    D

    D

    8 9 14 15

    NOTE: To reduce noise, attach N to 0V DC.

    Description of Control Word 0

    Bit Description

    00 Pulse Counting and period time measurement selection, Channel 0 0 = pulse counting and period time measurement selected – 16-bit 1 = period time measurement selected – 32-bit

    01 Pulse Counting and period time measurement selection, Channel 1 0 = pulse counting and period time measurement selected – 16-bit 1 = period time measurement selected – 32-bit

    02 Pulse Counting and period time measurement selection, Channel 2 0 = pulse counting and period time measurement selected – 16-bit 1 = period time measurement selected – 32-bit

    03 Pulse Counting and period time measurement selection, Channel 3 0 = pulse counting and period time measurement selected – 16-bit 1 = period time measurement selected – 32-bit

    04 Channel 0 – 0 = filter disabled; 1 = filter enabled(1)

    (1) Use filter when the input waveform has slow rise/fall time or has high frequency noise on the input waveform.

    05 Channel 1 – 0 = filter disabled; 1 = filter enabled(1)

    06 Channel 2 – 0 = filter disabled; 1 = filter enabled(1)

    07 Channel 3 – 0 = filter disabled; 1 = filter enabled(1)

    08...09 09 08 Filter sample clock frequency and period (common to all channels)

    0 0 625 kHz 1.6 μs

    0 1 312.5 kHz 3.2 μs

    1 0 104.17 kHz 9.6 μs

    1 1 7.8125 kHz 128 μs

    10...15 Reserved

    ATTENTION: Do not enable the filter with frequencies greater than 90 kHz. A loss of counts may result.

    Description of Control Word 1

    Bit Description

    00 Clock Frequency for period time measurement, Channel 0 0 = period time measurement with 10 MHz internal clock selected 1 = period time measurement with 1 MHz internal clock selected

    01...03 03 02 01 Number of periods for measurement – Channel 0

    0 0 0 1 period

    0 0 1 2 periods

    0 1 0 4 periods

    0 1 1 8 periods

    1 0 0 16 periods

    1 0 1 32 periods

    1 1 0 64 periods

    1 1 1 128 periods

    04 Clock frequency for period time measurement, Channel 1 – refer to bit 00

    05...07 Selection of number of periods for measurement, Channel 1 – see bits 01...03

    08 Clock frequency for period time measurement, Channel 2 – refer to bit 00

    09...11 Selection of number of periods for measurement, Channel 2 – see bits 01...03

    12 Clock frequency for period time measurement, Channel 3 – refer to bit 00

    13...15 Selection of number of periods for measurement, Channel 3 – see bits 01...03

    Description of Control Word 2

    Bit Description

    00 Start new measurement, Channel 0 – when set, start new measurement on positive edge

    01 Start new measurement, Channel 1 – when set, start new measurement on positive edge

    02 Start new measurement, Channel 2 – when set, start new measurement on positive edge

    03 Start new measurement, Channel 3 – when set, start new measurement on positive edge

    04 Reset Counter, Channel 0 – a positive edge on this bit resets counter 01

    05 Reset Counter, Channel 1– a positive edge on this bit resets counter 11

    06 Reset Counter, Channel 2 – a positive edge on this bit resets counter 21

    07 Reset Counter, Channel 3 – a positive edge on this bit resets counter 31

    08...15 Reserved for factory use

    Description of Control Word 2 Readback

    Bit Description

    00 Positive edge, Channel 0 – measurement ready

    01 Positive edge, Channel 1 – measurement ready

    02 Positive edge, Channel 2 – measurement ready

    03 Positive edge, Channel 3 – measurement ready

    04 Reset Counter, Channel 0 – a positive edge on this bit indicates counter 01 reset done

    05 Reset Counter, Channel 1 – a positive edge on this bit indicates counter 11 reset done

    06 Reset Counter, Channel 2 – a positive edge on this bit indicates counter 21 reset done

    07 Reset Counter, Channel 3 – a positive edge on this bit indicates counter 31 reset done

    08...15 Reserved for factory use

    Attribute Value

    Number of inputs 4

    Number of inputs per counter

    2 groups of 2

    Recommended terminal base unit

    1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TBKD

    Input pulse width Each signal condition must be stable for at least 2 μs to be recognized

    Counting frequency, max 100 kHz

    On-state voltage, min 6V DC

    On-state voltage, max 26.4V DC (24V DC +10%)

    On-state current, min 3 mA @ 6V DC

    On-state current, nom 9 mA @ 12V DC

    On-state current, max 15 mA @ 24V DC

    Off-state voltage, min -26.4V DC

    Off-state voltage, max 3V DC

    Isolation voltage Tested @ 500V AC for 60 s

    FlexBus current 5 mA @ 5V DC

    Power dissipation, max 5 W @ 26.4V DC

    Thermal dissipation, max 17.1 BTU/hr @ 26.4V DC

    Terminal base screw torque

    Determined by installed terminal base

    Dimensions, approx. (H x W x D)

    46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in.)

    Indicators (field side) 1 green/red power/status indicator 8 yellow status indicators

    External power supply voltage range

    12…24V DC (+10%)

    Current consumption from external power supply

    150 mA @ 12V DC 75 mA @ 24V DC

    North American temp code T4

    Keyswitch position 1

    Enclosure type rating None (open-style)

    Wire size Belden 8761, 304.8 m (1000 ft.)

    Wiring category(1)

    (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

    2 - on signal ports

    Attribute Value

    Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…55 °C (32…131 °F)

    Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock): -40…85 °C (-40…185 °F)

    Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% non-condensing

    Vibration IEC60068-2-6 (Test Fc, Operating): 5 g @ 10...500 Hz

    Shock IEC60068-2-27 (Test Ea, Unpackaged shock): Operating 30 g Non-operating 50 g

    Emissions CISPR 11: Group 1, Class A (with appropriate enclosure)

    ESD immunity IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges

    Radiated RF immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 30...1000 MHz

    EFT/B immunity IEC 61000-4-4: ±2 kV @ 5 kHz on signal ports

    Surge transient immunity IEC 61000-4-5: ±1 kV line-earth(CM) on shielded ports

    Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

    Certifications (when product is marked)(1)

    (1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

    Value

    c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

    UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E193170.

    CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

    KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

    EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation

    RCM Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

    Publication 1794-IN064E-EN-P - August 2015 2 PN-315547Supersedes Publication 1794-IN064D-EN-P - March 2005 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    Allen-Bradley, Rockwell Automation, FLEX I/O, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

    FLEX I/O 4-Channel Pulse Counter Module

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice

    Introduction_Catagory Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3 Primary, B2D5, D6Installation instructions15Post / External

    LMNANALaunch Materials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    ** Minimum order quantities on all JIT items are based on the publication length. **

    Publication lengthMinimum Order Quantity

    77 or more pages1 (no shrink wrap required)

    33 to 76 pages25

    3 to 32 pages50

    1 or 2 pages100

    Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170 gsm 2pp100# gloss cover, 100# gloss text

    A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color170gsm Silk – 120gsm Silk80# gloss cover, 80# gloss text

    A52 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Gray shading indicates Obsolete Print Catagories

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B31 color100gsm bond50# matte sheet text, self cover

    B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B52 color100gsm bond50# matte sheet text, self cover

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Gray shading indicates Obsolete Print Catagories

    Just In Time (JIT) or Off Set (OS)?

    Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the “Either” category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

    Black & White Printing

    Color Printing

    Color Printing

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005G-EN-P - 3/29/2010

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Category:JIT / PODSelect Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11” x 17”LOOSE -Loose LeafYESPre-sale / MarketingTOP

    (required) Finished Trim Size Width:11” x 17”8.5” x 11”PERFECT - Perfect BoundA1LEFT

    (required) Publication Number :1794-IN0064E-EN-PSample: 2030-SP001B-EN-P3” x 5”SADDLE - Saddle StitchA2RIGHTCORNER

    Use Legacy NumberNOYES or NO18” x 24” PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Legacy Number if applicable:Sample Legacy Number: 0160-5.3324” x 36” PosterSTAPLED1 -1 positionA3

    Publication Title:FLEX I/O 4 Channel Pulse Counter Module Installation InstructionsSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title36” x 24” PosterSTAPLED1B - bottom 1 positionA5

    (required) Business Group:Marketing CommercialAs entered in DocMan4” x 6”STAPLED2 - 2 positionsA6

    (required) Cost Center:19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75” x 7” (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7

    Binding/Stitching:Review key on right...Saddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch - no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

    Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

    Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

    Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)4.75” x 7.75”THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count of Publication:2Total page count including cover5.5” x 8.5” (half-size)A9

    Paper Stock Color:WhiteWhite is assumed. For color options contact your vendor.6” x 4”Post Sale / Technical Communication

    Number of Tabs Needed:5 tab in stock at RR Donnelley7.385” x 9” (RSI Std)B1

    Stitching Location:Blank, Corner or Side8.25” x 10.875”B2

    Drill Hole YES/NONOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of ¼ inch from the inner page border.8.25” x 11” (RA product profile std)B3None

    Glue Location on Pad:Glue location on pads8.375” x 10.875B4Half or V or Single Fold

    Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9” x 12” (Folder)B5C or Tri-Fold

    Ink ColorBlackOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number here…A4 (8 ¼” x 11 ¾”) (210 x 297 mm)CatalogsDbleParll

    Used in Manufacturing:YESA5 (5.83” x 8.26”) (148 x 210 mm)C1Sample

    Fold:Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturingReview key on right...Short (must specify dimensions between folds in Comments)

    Comments:65gsm artpaper (45# matte text k/k)6 FOLDSFinished folded size = 2.75 (w) x 1.75 (h) inches

    See folding instructions below.C2Z or Accordian Fold

    Part Number:PN-315547JIT / PODMicrofold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

    D1Double Gate

    D2

    FoldsHalf, V, Single C or Tri

    Dble Parll

    Z or Accordian Microfold or French

    Double Gate

    Short FoldD3

    D4

    D5

    D6

    D7

    D8

    D9

    Folding Instructions

    Sheet1

    MBD000CCD74.bin

    MBD000D141F.bin

    MBD000E357A.bin

    MBD000D05AE.bin

    MBD000B37AA.bin

    MBD000C2CF0.bin

    MBD000CBFEF.bin

    MBD000B71E5.bin

    MBD000AB9B4.bin

    MBD000AF7AA.bin