Installation Instructions EtherNet/IP Fiber Tap Catalog Numbers 1783-ETAP1F, 1783-ETAP2F Topic Page Important User Information 2 North American Hazardous Location Approval 3 European Hazardous Location Approval 4 Environment and Enclosure 5 Prevent Electrostatic Discharge 5 About the EtherNet/IPEtherNet/IP Fiber Tap 6 Module Components 9 Software Requirements 10 Install the Tap 11 Mount the Tap 11 Wire the Tap 13 Connect the EtherNet RJ45 Ports 15 Connect the Fiber EtherNet Ports 16 Download the Tap Add-on Profile 17 Download the EDS File 18 Configure Internet Protocol Settings 19 Set the DIP Switches 22 Use the Web Interface 25 Status Indicators 26 Specifications 28 Additional Resources 32

Upload: zacrias

Post on 28-Apr-2015

95 views

Category:

Documents


11 download

DESCRIPTION

Allen Bradley

TRANSCRIPT

Page 1: 1783-in008_-en-p

Installation Instructions

EtherNet/IP Fiber TapCatalog Numbers 1783-ETAP1F, 1783-ETAP2F

Topic Page

Important User Information 2

North American Hazardous Location Approval 3

European Hazardous Location Approval 4

Environment and Enclosure 5

Prevent Electrostatic Discharge 5

About the EtherNet/IPEtherNet/IP Fiber Tap 6

Module Components 9

Software Requirements 10

Install the Tap 11

Mount the Tap 11

Wire the Tap 13

Connect the EtherNet RJ45 Ports 15

Connect the Fiber EtherNet Ports 16

Download the Tap Add-on Profile 17

Download the EDS File 18

Configure Internet Protocol Settings 19

Set the DIP Switches 22

Use the Web Interface 25

Status Indicators 26

Specifications 28

Additional Resources 32

Page 2: 1783-in008_-en-p

2 EtherNet/IP Fiber Tap

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 3: 1783-in008_-en-p

EtherNet/IP Fiber Tap 3

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

WARNING:Explosion Hazard•Do not disconnect equipment

unless power has been removed or the area is known to be nonhazardous.

•Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

•Substitution of components may impair suitability for Class I, Division 2.

• If this product contains batteries, they must only be changed in an area known to be nonhazardous.

AVERTISSEMENT:Risque d’Explosion•Couper le courant ou s'assurer que

l'environnement est classé non dangereux avant de débrancher l'équipement.

•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

•S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 4: 1783-in008_-en-p

4 EtherNet/IP Fiber Tap

European Hazardous Location ApprovalThe following applies when the product bears the Ex Marking.

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.1.

WARNING:

• This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.

• This equipment shall be used within its specified ratings defined by Rockwell Automation.

• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.

• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 5: 1783-in008_-en-p

EtherNet/IP Fiber Tap 5

Environment and Enclosure

Prevent Electrostatic Discharge

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.In addition to this publication, see:

• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements.

• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures.

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 6: 1783-in008_-en-p

6 EtherNet/IP Fiber Tap

About the EtherNet/IPEtherNet/IP Fiber Tap

The EtherNet/IP fiber tap provides EtherNet/IP connectivity. Use the tap to support these network topologies:

• Linear• Star• Device-level ring (DLR)

The tap is configured by default to support linear, star, and ring (as a non-supervisor ring node) topologies.

Refer to the EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005, for information on setting up EtherNet/IP network topologies.

Linear and Star Network ConsiderationsWhen using the tap in a linear or star network, be sure that Ring Supervisor mode is not enabled. By default, the tap is configured to be a non-supervisor ring node.

IMPORTANT When setting up a DLR, refer to Device-level Ring (DLR) Network Considerations on page 7 to avoid adversely impacting your network.

IMPORTANT DIP switch 3 is used for making the tap a ring supervisor in a DLR network. To avoid adversely impacting communication in a linear or star network, take these precautions:

• Make sure switch 3 remains in the Off position. If switch 3 is in the On position, the tap will be automatically enabled as a ring supervisor.

• Make sure the Ring Supervisor mode is not enabled in RSLinx Classic communication software or RSLogix 5000 programming software. When switch 3 is in the Off position, the programming software controls whether the tap is a ring supervisor.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 7: 1783-in008_-en-p

EtherNet/IP Fiber Tap 7

Device-level Ring (DLR) Network ConsiderationsWhen using the tap in a DLR network, consider whether the tap will be a ring supervisor. By default, the tap is configured to be a non-supervisor ring node. Use one of these methods for controlling supervisor functionality:

• Use RSLinx Classic communication software or RSLogix 5000 programming software to set the Ring Supervisor mode and other supervisor-related parameters. This is the default method. If you choose this option, follow the procedures outlined in the online help that accompanies the software to enable Ring Supervisor mode.

• Use the DIP switches to automatically enable Ring Supervisor mode with the current supervisor-related parameters stored in the tap’s memory. Refer to Set the DIP Switches on page 22 for additional information.

IMPORTANT Use these precautions when setting up a DLR network:

• Make sure at least one node is acting as supervisor before connecting the last link of a DLR network and physically closing the ring.

• Do not connect nodes that do not support a DLR network as members of the ring.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 8: 1783-in008_-en-p

8 EtherNet/IP Fiber Tap

Grounding ConsiderationsThis product is intended to be mounted to a well-grounded mounting surface, such as a metal pane or DIN rail.

Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure the DIN rail to the mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 9: 1783-in008_-en-p

EtherNet/IP Fiber Tap 9

Module Components

Item Description Item Description

1 DIP switches 6 MAC ID label

2 Top view 7 Bottom view, 1783-ETAP1F

3 Status indicators 8 Bottom view, 1783-ETAP2F

4 Device port on front panel 9 Ports for connection to linear or ring network(1)

(1) The 1783-ETAP2F tap has two fiber-optic ports. The 1783-ETAP1F tap has one fiber-optic port.

5 Side view 10 DC connector

1

3

4

6

5

2

9

87

10

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 10: 1783-in008_-en-p

10 EtherNet/IP Fiber Tap

By default, the 10BASE-T and 100BASE-TX ports on the tap autonegotiate link speeds (10 Mbps or 100 Mbps) and duplex (full or half ). The 100BASE-FX fiber interfaces provide 100 Mbps, full duplex operation.

Software RequirementsYou must have these versions of software.

IMPORTANT Configure the Ethernet port on the device you connect to a tap so that it matches the tap’s speed and duplex settings.

Failure to make the speed and duplex settings of directly connected devices match may result in higher error rates or loss of network connectivity.

Software Version

RSLinx Classic 2.56 or later

RSLogix 5000 17.01 or laterIf you are using version 17.01, you need version 2.x of the add-on profile. Download it from http://www.rockwellautomation.com/support/downloads.html.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 11: 1783-in008_-en-p

EtherNet/IP Fiber Tap 11

Install the Tap

Follow these procedures to install the tap.

1. Mount the tap in one of these configurations:• Panel mount• DIN rail mount

2. Wire the tap.

3. Connect the Ethernet RJ45 ports.

4. Connect the fiber Ethernet ports.

5. Download the tap Add-on Profile (AOP) if you are using RSLogix 5000 programming software version 17.01.

6. Download the EDS file for the tap.

7. Configure Internet Protocol settings.

8. Set the DIP switches.

This publication describes these steps in detail.

Mount the TapInstall the tap on a DIN rail or panel mount the tap.

ATTENTION: Class 1 laser product. Laser radiation is present when the system is open and interlocks bypassed. Only trained and qualified personnel should be allowed to install, replace, or service this equipment.

IMPORTANT • When mounting the tap, be sure to provide 7.62 cm (3 in.) of space on the bottom side of the tap and 2.54 cm (1 in.) of space on the remaining sides of the tap.

• Allow at least 5.08 cm (2 in.) for the fiber cable bend radius. Contact the cable manufacturer for more information on recommended cable bend radii.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 12: 1783-in008_-en-p

12 EtherNet/IP Fiber Tap

DIN Rail Mounting To install the tap on a DIN rail, proceed as follows.

1. Mount your DIN rail.

2. Use a screwdriver to open the latch at the bottom of the tap.

3. Hook the latch over the DIN rail while holding the latch open with your screwdriver.

4. Remove the screwdriver and push the latch to close.

The top figure shows the latch at the bottom of the tap in the closed position. The bottom figure shows the use of a screwdriver to open the latch so that you can remove the tap from the DIN rail.

Panel MountingTo panel mount a tap, proceed as follows.

1. Use the tap as a template and mark pilot holes on your panel.

2. Drill the pilot holes for M4 or #8 screws.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 13: 1783-in008_-en-p

EtherNet/IP Fiber Tap 13

Wire the Tap

Provide DC power to the tap by using the DC connector at the bottom of the tap.

WARNING: An electrical arc can occur if you connect or disconnect the following:

• Communication cable with power applied to this module or any device on the network

• Wiring while the field-side power is onThis could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with safety extra low voltage (SELV) or protected extra low voltage (PELV).

To comply with UL restrictions, this equipment must be powered from a source compliant with Class 2.

WARNING: For hazardous location applications, use the supplied Phoenix MSTB 2.5/2-ST-5.08 power terminal block.

ATTENTION: Do not wire more than two conductors on any single terminal.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 14: 1783-in008_-en-p

14 EtherNet/IP Fiber Tap

EtherNet/IP Fiber Tap Terminals Description

Item Description

1 Tap bottom

2 DC- (0V DC) terminal

3 DC+ (24V DC nom) terminal

1

23

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 15: 1783-in008_-en-p

EtherNet/IP Fiber Tap 15

Connect the Ethernet RJ45 PortsFollow these steps to connect the Ethernet RJ45 ports on the tap.

1. Locate the Ethernet RJ45 ports on the front and bottom of the tap, as shown in the figure (1783-ETAP1F tap shown).

2. Connect one end of an Ethernet cable to the front panel port that is used as a device port.

3. Connect the other end of the Ethernet cable to the appropriate device (typically a non-DLR device) in your network.

4. Connect one end of a twisted-pair Ethernet cable to a port at the bottom of the tap and connect the other end of the twisted-pair Ethernet cable to the linear or ring network.

5. Repeat with the other port at the bottom of the tap if the port is used by your network.

Item Description

1 Device port on tap front panel

2 RJ45 port on tap bottom for connection to a linear, star, or ring network

1

2

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 16: 1783-in008_-en-p

16 EtherNet/IP Fiber Tap

Connect the Fiber Ethernet PortsFollow these steps to connect the fiber Ethernet ports on the tap.

1. Locate the fiber Ethernet ports on the bottom of the tap, as shown in the figure (1783-ETAP2F tap shown).

2. Connect the duplex LC connector end of the fiber-optic cable, in the proper orientation, to the fiber-optic Ethernet port on the bottom of the tap.

IMPORTANT When setting up a DLR, refer to Device-level Ring (DLR) Network Considerations on page 7 to avoid adversely impacting your network.

ATTENTION: Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed under some conditions, the optical port may expose the eye beyond the maximum permissible exposure recommendations.

Item Description

1 Fiber ports on tap bottom for connection to the ring network

+

TxRx

TxRx

-

1

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 17: 1783-in008_-en-p

EtherNet/IP Fiber Tap 17

3. Connect the other end of the fiber-optic cable to the linear or ring network.

4. Repeat step 2 and step 3 with the remaining fiber-optic Ethernet port at the bottom of the tap, if used by your network.

Download the Tap Add-on Profile, RSLogix 5000 Software Version 17.01 OnlyIf you are using RSLogix 5000 programming software, version 17.01, you need version 2.x of the Add-on Profile (AOP). Follow these steps to download the AOP.

1. Locate the tap AOP at http://www.rockwellautomation.com/support/downloads.html.

2. Click the desired file to download it.

3. Enter your RSLogix 5000 programming software serial number and click Qualify for Update.

4. Download and extract the zipped files to a temporary directory.

5. Shut down any instances of RSLogix 5000 programming software that are currently running.

6. In the temporary directory, double-click the MPSetup.exe file and follow the on-screen instructions to install the AOP.

IMPORTANT You need a Rockwell Automation MySupport account to download the AOP. If you do not have one, follow the steps on the MySupport website to obtain an account.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 18: 1783-in008_-en-p

18 EtherNet/IP Fiber Tap

Download the EDS FileTo use RSLinx Classic software to configure the tap, follow these steps to download the EDS file for the tap.

1. Obtain the EDS file from http://www.rockwellautomation.com/resources/eds/.

2. From the Network pull-down menu, choose the EtherNet/IP network.

3. From the Device Type pull-down, choose Communication Adapter.

4. In the Bulletin/catalog number field, type 1783-ETAP1F or 1783-ETAP2F.

5. Click Search.

6. Click Download to download the EDS file for the tap.

7. Save the file to an appropriate location on your computer.

8. Use your configuration software to register the downloaded file. a. If you are using RSLinx Classic communication software, use the

EDS Hardware Installation Tool. b. Choose Start>All Programs>Rockwell Software>RSLinx>Tools.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 19: 1783-in008_-en-p

EtherNet/IP Fiber Tap 19

Configure Internet Protocol SettingsConfigure Internet Protocol (IP) settings, such as the IP address, in one of these ways:

• Use the tap’s default IP address of 169.254.1.1 by connecting the tap directly to a computer. To establish communication between a computer and the tap’s default IP address, you have the following options:– Enter a unique IP address in the local area connection properties for

your computer. The computer’s IP address must be on the same subnet as the tap’s default IP address, such as 169.254.1.2.

– Set up your computer to obtain its IP address automatically.

• Use IP settings configured in RSLinx Classic communication software or RSLogix 5000 programming software.

• Acquire IP settings from a DHCP server.

• Acquire IP settings from a BOOTP server.

IMPORTANT If the port on your computer that is connected to the tap is configured to obtain its IP address automatically, expect a wait time of up to two minutes before communication is established after connecting the tap to a computer.

If two or more taps are connected to one another, and each tap is using the default IP address, the computer is only able to communicate with the tap to which it is directly connected.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 20: 1783-in008_-en-p

20 EtherNet/IP Fiber Tap

Use the DIP switches on the tap to select the configuration method to use for IP settings. Refer to Set the DIP Switches on page 22.

Use the DHCP/BOOTP ServerIf your network infrastructure does not provide DHCP/BOOT functionality, you may download our DHCP/BOOTP server software to a personal computer running a Microsoft Windows operating system. You can use this computer as the DHCP/BOOTP server.

To set the network address by using the Rockwell Automation DHCP/BOOTP server, follow these steps.

1. Access the DHCP/BOOTP utility at http://www.ab.com/networks/ethernet/bootp.html.

2. Download the latest version of the DHCP/BOOTP utility.

3. Extract the zipped files to a temporary directory.

4. In the temporary directory, double-click setup.exe to install the DHCP/BOOTP utility.

5. Run the utility.

TIP After connecting with the out-of-box IP address or an address obtained by using a DHCP server or a BOOTP server, RSLinx Classic communication software or RSLogix 5000 programming software may be used to configure a static IP address that will be stored in nonvolatile memory.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 21: 1783-in008_-en-p

EtherNet/IP Fiber Tap 21

6. Refer to the following chart, which describes what happens next, depending on whether DHCP/BOOTP is enabled on the tap.

If DHCP/BOOTP is The tap

Enabled Requests an IP address from a DHCP/BOOTP server. Consult the online help available in the BOOTP/DHCP application to configure the server to provide the desired IP address for your tap.Your network topology must be constructed so that the requests sent by the tap will be received by the computer running the DHCP/BOOTP server.

Not enabled Uses the IP settings stored in nonvolatile memory. The default IP address stored in memory is 169.254.1.1.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 22: 1783-in008_-en-p

22 EtherNet/IP Fiber Tap

Set the DIP SwitchesUse the DIP switches on the tap to do the following:

• Specify the method for configuring Internet Protocol (IP) settings, such as the IP address.

• Enable the Ring Supervisor mode with its current parameters.

• Restore the factory default settings.

Refer to the illustration to understand DIP switch On and Off positions.

Switch 1

Switch 2

Switch 3Off On

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 23: 1783-in008_-en-p

EtherNet/IP Fiber Tap 23

Use this procedure to set the DIP switches.

1. Move the switches to the desired position, and then cycle power to the tap.

IMPORTANT The switch settings take effect only at powerup. The tap's behavior will not be modified by switch changes until the tap is power cycled.

Power-up Behavior Switch 1 Switch 2 Switch 3

Internet Protocol settings

Uses the IP settings configured by software(1)

orUses the default IP address of 169.254.1.1 if settings have not been configured by software

(1) RSLinx Classic communication software or RSLogix 5000 programming software is required.

Off Off The position of switch 3 does not affect IP settings

Uses the IP settings acquired by a BOOTP server

On Off

Uses the IP settings acquired by a DHCP server

Off On

Ring Supervisor mode

Enables Ring Supervisor mode with the current supervisor-related parameters(2)

(2) For information about supervisor-related parameters, refer to the EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005.

The positions of switches 1 and 2 do not affect Ring Supervisor mode

On

Allows Ring Supervisor mode and supervisor-related parameters to be enabled and configured by software

Off

Restores the factory default settings and then suspends operation

On On On or Off

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 24: 1783-in008_-en-p

24 EtherNet/IP Fiber Tap

2. Observe these guidelines on use of the DIP switches:• Out of the box, all three switches are in the Off position. In this

state, the tap is configured to be a non-supervisor ring node and will respond to the default IP address of 169.254.1.1.If your application does not require access to the tap’s diagnostic information or configuration, no further action is required. Otherwise, select alternate DIP switch settings or configure the tap by using RSLinx Classic communication software or RSLogix 5000 programming software.

• When a switch is pushed to the left, it is in the Off position.• When a switch is pushed to the right, it is in the On position. • To select BOOTP, move switch 1 to the On position and switch 2 to

the Off position.• To select DHCP, move switch 1 to the Off position and switch 2 to

the On position.• To enable Ring Supervisor mode with the current supervisor-related

parameters, move switch 3 to the On position.• To restore the factory default settings and suspend operation, move

both switch 1 and 2 to the On position. When both switch 1 and 2 are in the On position, the position of switch 3 is ignored.

• When operation is suspended, the OK status indicator blinks red. To resume normal operation, move the switches to the desired positions and then cycle power to the tap.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 25: 1783-in008_-en-p

EtherNet/IP Fiber Tap 25

Use the Web InterfaceThe tap supports a Web interface that provides diagnostic read-only information. Follow these steps to access the Web interface.

1. Connect a computer to any of the tap’s Ethernet ports.

2. Browse to the tap by entering the tap’s IP address (the out-of-the-box default is 169.254.1.1) in your web browser’s address bar.

3. Press Enter.

You see the 1783-ETAP1F or 1783-ETAP2F tap page, which provides general information about the tap.

4. In the left pane, click Diagnostics.

You see links to these pages:• Diagnostic Overview • Network Settings • Ethernet Statistics • Ring Statistics

TIP If you configure the tap with an IP address, you can also access the tap Web interface from any computer connected to the network.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 26: 1783-in008_-en-p

26 EtherNet/IP Fiber Tap

Status Indicators

This web page Contains information about

Diagnostic Overview • Module resource utilization• Web server read and write hits• Module settings• Ring status• Network management features

Network Settings • Network interface details, such as IP address and subnet mask

• Ethernet interface configuration method• Ethernet port details

Ethernet Statistics • Ethernet counters• Ethernet port details• Error information

Ring Statistics Ring supervisor, configuration, and fault details

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 27: 1783-in008_-en-p

EtherNet/IP Fiber Tap 27

Indicator Description

Indicator Status Description

OK Off Tap is not powered.

Flashing green Tap is not configured.

Solid green Tap is powered, configured, and operating correctly.

Flashing red Recoverable fault, such as duplicate IP address detected, or an update in progress, is detected.

Solid red Unrecoverable fault detected.

LINK 1, LINK 2

Off One of these conditions exists:• No link.• Port administratively disabled.• Ring network has encountered a rare, partial network

fault, or rapid ring fault condition, and this tap is the active supervisor (LINK 2).

Solid green One of these conditions exists:• RJ45 port: a 100 Mbps (full or half duplex) link exists,

and there is no activity.• Fiber port: a 100 Mbps (full duplex) link exists, and

there is no activity.• Ring network is operating normally, and this tap is the

active supervisor (LINK 2).

Flashing green A 100 Mbps link exists and there is activity.

Solid yellow RJ45 port only. One of these conditions exists:• A 10 Mbps (full or half duplex) link exists.• Ring network is operating normally, and this tap is the

active supervisor (LINK 2).

Flashing yellow RJ45 port only. A 10 Mbps link exists and there is activity.

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 28: 1783-in008_-en-p

28 EtherNet/IP Fiber Tap

Specifications

Technical Specifications - 1783-ETAP1F, 1783-ETAP2F

Attribute 1783-ETAP1F, 1783-ETAP2F

Enclosure type rating None (open-style)

Current consumption, max 1783-ETAP1F: 200 mA @ 24V DC1783-ETAP2F: 260 mA @ 24V DC

Voltage variationIEC 61000-4-29

10 ms interruption on DC supply ports

DC power supply voltage rating 24V DC (20.4...27.6V DC)

Isolation voltage 30V (continuous), Basic Insulation Type, Network channels to Power and Network channels to Network channelsType tested at 1250V DC for 60 s

Power consumption, max 1783-ETAP1F: 4.8 W1783-ETAP2F: 6.24 W

Power dissipation 1783-ETAP1F: 4.8 W1783-ETAP2F: 6.24 W

Wire size Ethernet connections:RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1, or Category 5 cable according to ISO/IEC 24702

DC power connections:One 0.33... 3.3 mm2 (22...12 AWG) or two 0.33...1.3 mm2 (22.....16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

Torque 0.6...0.8 N•m (5...7 lb•in) on power connectors

Dimensions (HxWxD), approx. 132 x 35 x 105 mm (5.16 x 1.36 x 4.13 in)

Wiring category(1) 1 - on power ports2 - on communication ports

North American temp code 1783-ETAP1F: T4A1783-ETAP2F: T4

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 29: 1783-in008_-en-p

EtherNet/IP Fiber Tap 29

IEC temp code T4

Fiber transceiver type 100Base-FX IEEE802.3u

Optical wavelength 1310 nm no cap

Transmitter launch power at Beginning of Life (BOL), minAllow -1 dB at End of Life (EOL)

-19 dBm into 62.5/125 µm fiber, N/A = 0.275-22.5 dBm into 50/125 µm fiber, N/A = 0.20

Receiver sensitivity, min -31.8 dBm

Receiver sensitivity, max -14 dBm

Fiber channel power budget at rated BER (2 connected taps, either 1783-ETAP1F or 1783-ETAP2F)

12.8 dB for 62.5/125 µm multimode fiber9.3 dB for 50/125 µm multimode fiber

Fiber type Glass62.5/125 µm and 50/125 µm multimode fiberSimplex or duplexJacket type and jacket diameter is dependent on connector selectionGraded Index (GI) fiberPer IEC 60794-1-1, IEC 60793-2-10 category A1 fibers

Connector type IEC 61754-20 LC connector, maximum insertion loss 0.75 dB per connection

Channel length, max 2 km (1.24 mi) (2)

(1) Use this Conductor Category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

(2) The channel, that is, connectors and cable, must not exceed the allowable power budget.

Technical Specifications - 1783-ETAP1F, 1783-ETAP2F

Attribute 1783-ETAP1F, 1783-ETAP2F

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 30: 1783-in008_-en-p

30 EtherNet/IP Fiber Tap

Environmental Specifications - 1783-ETAP1F, 1783-ETAP2F

Attribute 1783-ETAP1F, 1783-ETAP2F

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…60 °C (-13…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 31: 1783-in008_-en-p

EtherNet/IP Fiber Tap 31

EFT/B immunityIEC 61000-4-4

±4 kV at 5 kHz on power ports±3 kV at 5 kHz on communication ports

Surge transient immunityEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports±2 kV line-earth (CM) on communication ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1783-ETAP1F, 1783-ETAP2F

Certification(1) 1783-ETAP1F, 1783-ETAP2F

c-UL-us • UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

• UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/EC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A and B)

C-tick Australian Radiocommunications Act, compliant with:• AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with:• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"• EN 60079-0; General Requirements• II 3 G Ex nA IIC T4 X

EtherNet/IP ODVA conformance tested to EtherNet/IP specifications

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Environmental Specifications - 1783-ETAP1F, 1783-ETAP2F

Attribute 1783-ETAP1F, 1783-ETAP2F

Rockwell Automation Publication 1783-IN008C-EN-P - April 2011

Page 32: 1783-in008_-en-p

Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

Resource Description

EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001

Provides details about how to configure your module.

EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005

Provides information about using products with embedded switch technology to construct networks with linear and ring topologies.

EtherNet/IP Industrial Protocol White Paper, publication ENET-WP001

Describes how to implement services and data objects on a TCP/UDP/IP based Ethernet network.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

Publication 1783-IN008C-EN-P - April 2011 PN-100149Supersedes Publication 1783-IN008B-EN-P - January 2011 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Allen-Bradley, Rockwell Software, Rockwell Automation, CompactLogix, Compact I/O, Logix5000, RSLinx Classic, RSLogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400