Installation Instructions
ControlLogix ControlNet Bridge Module
Catal og Numbers 1756-CN2, 1756-CN2R
Inside . . .
About This PublicationU se this docum ent as a guide to install the ControlLogix ControlN et
bridge m odule.
For See Page
About This Publ icat ion 1
Important User Informat ion 2
European Hazardous Locat ion Approval 3
North American Hazardous Locat ion Approval 4
Environment and Enclosure 5
Prevent ing Electrostat ic Discharge 6
About the ControlLogix ControlNet Bridge M odule 6
Before You Begin 7Instal l the M odule 11
Troubleshoot the M odules 19
Specif icat ions 25
Addit ional Resources 29
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
-
8/20/2019 1756-CN2
2/32
2 ControlLogix ControlN et Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Important User Information
Solid state equipment has operational characteristics diff ering from those of electromechanicalequipment. Safety Guidelines for the Application, Installation and M aintenance of Solid State Controls(Publication SGI-1.1 available from your local Rockwell Automation sales office or online athttp:/ / l i terature.rockw ellautomation.com/ ) describes some important differences betw een solid stateequipment and hard-wired electromechanical devices. Because of this difference, and also because ofthe w ide variety of uses for solid st ate equipment, all persons responsible f or applying this equipmentmust satisfy t hemselves that each intended application of t his equipment is acceptable.
In no event w ill Rockwel l Autom ation, Inc. be responsible or liable for indirect or consequenti al damagesresulting from the use or application of t his equipment.
The examples and diagrams in this manual are i ncluded solely for ill ustrati ve purposes. Because of the
many variables and requirements associated w ith any particular installation, Rockwell Automat ion, Inc.cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent l iabil i ty is assumed by Rockw ell Aut omation, Inc. w ith respect to use of information, circuits,equipment, or softw are described in this manual.
Reproduction of the contents of this manual, in w hole or in part, w ithout w ritten permission of Rockw ellAutomation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING Identif ies inform ation about pract ices or circumstances that can cause an explosion ina hazardous environment, w hich may lead to personal inj ury or death, property
damage, or economic loss.
IMPORTANT Identifies information t hat is critical for successful application and understanding ofthe product.
ATTENTION Identifies information about practices or circumstances that can lead to personalinjury or death, property damage, or economic loss. Attentions help you identify ahazard, avoid a hazard, and recognize the consequences.
SHOCK HAZARD
Labels may be located on or inside t he equipment (for example, drive or motor) toalert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside t he equipment (for example, drive or motor) toalert people that surfaces may be dangerous temperatures.
-
8/20/2019 1756-CN2
3/32
ControlLogix ControlN et Bridge M odule 3
Publication 1756-IN602A-EN-P - November 2005
European Hazardous Location Approval
European Zone 2 Certification
(The follow ing applies w hen the product bears the EEx M arking.)
This equipm ent is intended for use in potentially explosive
atm ospheres as defined by European U nion D irective 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that
this equipm ent has been found to com ply w ith the Essential H ealth
and Safety Requirem ents relating to the design and construction of
Category 3 equipm ent intended for use in potentially explosive
atm ospheres, given in Annex II to this D irective. The exam ination
and test results are recorded in confidential report N o. 28 682 010.
Com pliance w ith the Essential H ealth and Safety Requirem ents has
been assured by com pliance w ith EN 50021.
IMPORTANT This equipm ent is not resistant to sunlight or other
sources of U V radiation.
The secondary of a current transform er shall not be
open-circuited w hen applied in Class I, Zone 2
environm ents.
Equipm ent of lesser Enclosure Type Rating m ust be
installed in an enclosure providing at least IP54
protection w hen applied in Class I, Zone 2
environm ents.
This equipm ent shall be used w ithin its specified ratings
defined by Allen-Bradley.
Provision shall be m ade to prevent the rated voltage
from being exceeded by transient disturbances of m orethan 40% w hen applied in Class I, Zone 2 environm ents.
-
8/20/2019 1756-CN2
4/32
4 ControlLogix ControlN et Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
North American Hazardous Location Approval
The follow ing information applies w henoperating this equipment in hazardouslocations:
Informations sur l 'uti l isation de cet équipement enenvironnements dangereux:
Products marked “CL I, DIV 2, GP A, B, C, D” aresuitabl e for use i n Class I Division 2 Groups A, B,C, D, Hazardous Locations and nonhazardouslocati ons only. Each product is supplied w ithmarkings on the rating nameplate indicating thehazardous location temperature code. When
combining products wi thin a system, the mostadverse temperature code (low est “ T” number)may be used to help determine the overalltemperature code of the system. Combinationsof equipment in your system are subject t oinvestigation by the local A uthority HavingJurisdiction at the time of installation.
Les produits marqués “CL I, DIV 2, GP A, B, C, D” neconviennent qu'à une utilisation en environnementsde Classe I Division 2 Groupes A, B, C, D dangereuxet non dangereux. Chaque produit est li vré avec desmarquages sur sa plaque d'identification quiindiquent le code de température pour les
environnements dangereux. Lorsque plusieursproduits sont combi nés dans un système, le code detem pérature le plus défavorable (code detempérature le plus faible) peut être ut i l isé pourdéterminer le code de température global dusystème. Les combinaisons d'équipem ents dans lesystème sont sujettes à inspection par les autoritéslocales qualifiées au moment de l ' installation.
EXPLOSION HAZARD
Do not disconnect equipmentunless power has beenremoved or the area isknow n to be nonhazardous.
Do not disconnectconnections to thisequipment unless power hasbeen removed or the area is
know n to be nonhazardous.Secure any externalconnections that mate to t hisequipment by using screws,sliding latches, threadedconnectors, or other meansprovided w ith this product.
Substit ution of componentsmay impair suitabil i ty forClass I, Division 2.
If this product containsbatteries, they must only bechanged in an area know n tobe nonhazardous.
RISQUE D' EXPLOSION
Couper le courant ou s'assurerque l'environnement est classénon dangereux avant dedébrancher l'équipement.
Couper le courant ou s'assurerque l'environnement est classénon dangereux avant dedébrancher les connecteurs.
Fixer t ous les connecteursexternes reliés à cetéquipement à l'aide de vis,loquets coulissants,connecteurs filetés ou autresmoyens fournis avec ce produit .
La substitution de composantspeut rendre cet équipementinadapté à une uti l isation enenvironnement de Classe I,
Division 2.
S'assurer que l'environnementest classé non dangereux avantde changer les piles.
WARNING AVERTISSEMENT
-
8/20/2019 1756-CN2
5/32
ControlLogix ControlN et Bridge M odule 5
Publication 1756-IN602A-EN-P - November 2005
Environment and Enclosure
ATTENTION This equipm ent is intended for use in a Pollution D egree2 industrial environm ent, in overvoltage Category II
applications (as defined in IEC publication 60664-1), at
altitudes up to 2000 m eters w ithout derating.
This equipm ent is considered G roup 1, Class A industrial
equipm ent according to IEC/CISPR Publication 11.
W ithout appropriate precautions, there m ay be potential
difficulties ensuring electrom agnetic com patibility in otherenvironm ents due to conducted as w ell as radiated
disturbance.
This equipm ent is supplied as open-type equipm ent. It
m ust be m ounted w ithin an enclosure that is suitably
designed for those specific environm ental conditions that
w ill be present and appropriately designed to prevent
personal injury resulting from accessibility to live parts.The interior of the enclosure m ust be accessible only by
the use of a tool. Subsequent sections of this publication
m ay contain additional inform ation regarding specific
enclosure type ratings that are required to com ply w ith
certain product safety certifications.
N O TE: See N EM A Standards publication 250 and IEC
publication 60529, as applicable, for explanations of the
degrees of protection provided by different types of
enclosure. Also, see the appropriate sections in this
publication, as w ell as Industrial Autom ation W iring and
G rounding G uidelines, Allen-Bradley publication
1770-4.1, for additional installation requirem ents
pertaining to this equipm ent.
-
8/20/2019 1756-CN2
6/32
6 ControlLogix ControlN et Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Preventing Electrostatic Discharge
For additional inform ation, refer to Industrial Autom ation W iring andG rounding G uidelines, publication 1770-4.1.
About the ControlLogix ControlNet Bridge Module
W e designed the enhanced ControlLogix C ontrolN et m odule for
applications that require higher capacity, and w e recom m end that
you use this m odule w ith ControlLogix controllers to:
• expand system s for tw ice as m uch I/O control.
• effectively double the am ount of Produce/Consum e tags that
can be transferred betw een controllers.
• speed up existing applications to run faster.
U se the 1756-CN 2 ControlLogix ControlN et m odule for stand-alone
applications only. Applications requiring controller redundancy m ust
use the 1756-CN B m odule.
ATTENTION This equipm ent is sensitive to electrostatic discharge,w hich can cause internal dam age and affect norm al
operation. Follow these guidelines w hen you handle this
equipm ent:
• Touch a grounded object to discharge potential static.
• W ear an approved grounding w riststrap.
• D o not touch connectors or pins on com ponent
boards.
• D o not touch circuit com ponents inside the
equipm ent.
• If available, use a static-safe w orkstation.
• W hen not in use, store the equipm ent in appropriate
static-safe packaging.
-
8/20/2019 1756-CN2
7/32
ControlLogix ControlN et Bridge M odule 7
Publication 1756-IN602A-EN-P - November 2005
Before You Begin
Before you install the m odule, m ake sure you:
• know how to handle the m odule (see Preventing Electrostatic
D ischarge).
• know the type of ControlN et netw ork.
There are tw o types of scheduled traffic netw orks for
ControlN et: single-keeper netw orks and m ulti-keeper
netw orks. The 1756-CN 2 and 1756-CN 2R bridges are
m ulti-keeper capable.
You m ust m atch the keeper to the type of netw ork. Refer to
the ControlN et M odules in Logix5000 C ontrol System s U ser
M anual, publication CN ET-U M 001, for m ore inform ation.
Parts List
You need all of the com ponents show n.
1756-CN2 or 1756-CN2R 1756-A4, 1756-A7, 1756-A10,1756-A13, or 1756-A17
1756-PA72/ 75 or 1756-PB72/ 75Power Supply
1786-TPR, -TPS-TPYR, or -TPYS(1)
(1) 1786-TPS or 1786-TPYS taps recommended for net w ork connections.
1786-CP (Temporary
Netw ork Connections) Small Screw driver(Optional)
http://-/?-http://-/?-http://-/?-http://-/?-
-
8/20/2019 1756-CN2
8/32
8 ControlLogix ControlN et Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Identify Module Features
Refer to this figure to identify the hardw are com ponents of the
1756-CN 2 and 1756-CN 2R bridge m odules.
BackplaneConnector
Front View Side View
M odule StatusAlphanumericDisplay
Module
StatusIndicator
ControlNet
Channel Stat usIndicators
NetworkAccess Port(NAP)
Channel BBNC Connector(1756-CN2R
nly)
Channel ABNC ConnectorChannel A
Network AddressSwitches (not show n)See page 9.
-
8/20/2019 1756-CN2
9/32
ControlLogix ControlN et Bridge M odule 9
Publication 1756-IN602A-EN-P - November 2005
Set the Module’s Network Address Switches
U se your fingers or a sm all screw driver to set the m odule’s netw ork
address sw itches. For m odules in a standalone chassis, you m ust
specify a unique ControlN et netw ork address. You can select an
address of 01 to 99 for m odules in a standalone chassis. N ote that 00
is an invalid ControlN et address.
Prepare the Chassis for Module Installation
Before you install the 1756-CN 2 m odule, you m ust install and connect
a ControlLogix chassis and pow er supply. A 4-slot chassis w ith a
pow er supply is show n below .
side of module
f r o n t o f m o d u l e
top of module
This module’s networkaddress is 23.
ChassisPowerSupply
-
8/20/2019 1756-CN2
10/32
10 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
For inform ation about installing these products, refer to the
publications listed in this table.
These m odules are com patible w ith all versions of chassis and pow er
supplies.
Determine Module Slot Location
This figure show s chassis slot num bering in a 4-slot chassis. Slot 0 isthe first slot and is alw ays the leftm ost slot in the rack (the first slot to
the right of the pow er supply). You can use any size ControlLogix
chassis and install the m odule in any slot. You can also install
m ultiple bridge m odules in the sam e chassis. You can install as m any
m odules as your pow er supply can accom m odate (that is, the
num ber for w hich the pow er supply is rated).
Chassis Type
Chassis
Installation
Power Supply
Power Supply
Installation
Series B: 1756-A4, 1756-A7,
1756-A10, 1756-A13, 1756-A17
Publication
1756-IN080
1756-PA72/ C Publicat ion
1756-IN0781756-PB72/C
1756-PA75/ B Publicat ion
1756-IN5961756-PB75/B
Chassis
Power Supply
Slot 0
Slot 1 Slot 3
Slot 2
-
8/20/2019 1756-CN2
11/32
ControlLogix ControlN et Bridge M odule 11
Publication 1756-IN602A-EN-P - November 2005
Install the Module
1 . Align the circuit board w ith top and bottom guides in thechassis.
2. Slide the m odule into the chassis.
M ake sure the m odule backplane connector properly connects
to the chassis backplane.
The m odule is properly installed w hen it is flush w ith the pow er
supply or other installed m odules.
ATTENTION D o not force the m odule into the backplane connector. If
you cannot seat the m odule w ith firm pressure, check the
alignm ent. Forcing the m odule into the chassis can
dam age the backplane connector or the m odule.
1
2
CircuitBoard
-
8/20/2019 1756-CN2
12/32
12 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Connect the Module to the Network
You can connect the m odule to the ControlN et netw ork by using a
tap (1786-TPR, 1786-TPS, 1786-TPY R, 1786-TPY S) or a netw ork
access cable (1786-CP).
This figure show s an exam ple ControlN et netw ork using redundantm edia.
W hen connecting the bridge m odule to a ControlN et netw ork, youshould also refer to this docum entation:
TIP U se the 1786-CP cable for tem porary connections
(for instance, program m ing softw are). For perm anent
connections, use a tap.
Publication Title Publication Number
ControlNet Coax Tap Installat ion Instruct ions 1786-5.7
Cont rolNet Coax M edia Planning and Insta llat ion Guide CNET- IN002
Cont rolNet Fiber M edia Planning and Insta llat ion Guide CNET- IN001
1756-CN2R(In 1756-A4 Chassis)
ControlNetNode
ControlNet Link
ControlNetNode
Redundant M edia(Optional)
-
8/20/2019 1756-CN2
13/32
ControlLogix ControlN et Bridge M odule 13
Publication 1756-IN602A-EN-P - November 2005
Connect to t he Net w ork Using a Tap
Follow these steps to connect the m odule to the netw ork w ith a tap.
1 . Rem ove and save the dust caps from the ControlN et taps.
2. Connect the tap’s straight or right-angle connector to the
m odule’s BN C connector.
TIP For netw ork connections w e recom m end taps w ith a
straight connector (1786-TPS or 1786-TPY S) because of
the location of the B N C connectors on the bottom of them odule.
ATTENTION D o not allow any m etal portions of the tap to contact any
conductive m aterial. If you disconnect the tap from the
m odule, place the dust cap back on the straight or
right-angle connector to prevent the connector from
accidentally contacting a m etallic grounded surface.
If Your Node Supports Connect The Tap’s Connector
non-redundant media (1756-CN2)
to t he channel A connector on the modul e
(channel B on the 1756-CN2R is not used)(1)
(1) W hile both channels are active, we recommend using channel A f or non-redundant media.
redundant media•
from t runkline A to channel A on the 1756-CN2R• from t runkline B to channel B on the 1756-CN2R
Dust Cap
Segment 1 Segment 2
Dust Cap
1756-CN2 - Segme nt 11756-CN2R - Segments 1 and 2
-
8/20/2019 1756-CN2
14/32
14 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
3. Apply pow er to the m odule and check m odule status.
IMPORTANT To prevent inadvertent reversal of the tap connections(resulting in incorrect status displays requiring
troubleshooting), check the tap drop cable for the label
indicating the attached segm ent before m aking your
connection.
Tap
Segment 1
Segment 2
Tap Tap
A AB
-
8/20/2019 1756-CN2
15/32
ControlLogix ControlN et Bridge M odule 15
Publication 1756-IN602A-EN-P - November 2005
U se this flow chart as a guide.
Turn the chassispow er supply on.
Modulestatusindicatorred?
See thetroubleshootingtable on page 20.
M odule performs apow er-on self-testinitialization.
N o
Yes
INIT
No
Yes
Modulestatusindicatorred?
INIT has failed, andthe module displays anerror message (seepages 20 t o 23).
Replace the m odule.
Initialization iscomplete. Thestatus indicatorblinks green.
Channel A and Bindicators alternatelyflash.
Channel A and Bindicato rs display thenetw ork condit io n aslisted on page 23.
ModulestatusdisplaysOK?
NoSee thet roubleshooting tableon page 20.
Yes
M odule is functionaland operating.
OKA#xx
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
-
8/20/2019 1756-CN2
16/32
16 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Connect a Programming Terminal to the Net w ork w ith 1786-CP Cable
To connect a program m ing term inal to the netw ork using a 1786-CP
cable, you have these options:
• U se a 1784-K TC, 1784-K TCx, or 1784-PCC com m unication cardand a 1786-CP cable (pictured)
WARNING If you connect or disconnect the com m unications cablew ith pow er applied to this m odule or any device on the
netw ork, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
IMPORTANT To use redundant m edia, all nodes m ust support
redundant m edia.
If you are using redundant m edia, connect the channel
of each partner to the sam e netw ork segm ent.
1756-CN2R
1786-CP Cable
1784-KTC, KTCx,PCIC, or PCC Card
ControlNet Link
-
8/20/2019 1756-CN2
17/32
ControlLogix ControlN et Bridge M odule 17
Publication 1756-IN602A-EN-P - November 2005
• U se a 1770-K FC com m unication interface, a serial or parallel
connection, and a 1786-CP cable (pictured)
The 1786-CP cable can be plugged into any ControlN et product’s
netw ork access port (N AP) to provide program m ing capability on the
ControlN et netw ork. A program m ing term inal connected through this
cable is counted as a node and m ust have a unique netw ork address.
ATTENTION U se a 1786-CP cable w hen connecting a program m ingterm inal to the netw ork through netw ork access ports.
U sing a com m ercially available RJ-style cable could result
in netw ork failure.
1756-CN2R
1786-CP(1)
ControlNet Link
Cable
1770-KFC
Serial or ParallelConnections
-
8/20/2019 1756-CN2
18/32
18 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Remove the Module
Follow these steps to rem ove the m odule:
1 . Push on the upper and low er tabs to disengage them .
2. Slide the m odule out of the chassis.
IMPORTANT If you are replacing an existing m odule w ith an identical
one, and you w ant to resum e identical system operation,
you m ust install the new m odule w ith the sam e
ControlN et address in the sam e slot.
Upper Tab
-
8/20/2019 1756-CN2
19/32
ControlLogix ControlN et Bridge M odule 19
Publication 1756-IN602A-EN-P - November 2005
Install or Remove the Module Under Power
You can install or rem ove the m odule w hile chassis pow er is applied
if you observe these precautions.
Troubleshoot the Modules
The m odules have these diagnostic indicators:
WARNING W hen you insert or rem ove the m odule w hile backplane
pow er is on, an electrical arc can occur. This could cause
an explosion in hazardous location installations.
Be sure that pow er is rem oved or the area is
nonhazardous before proceeding. Repeated electrical
arcing causes excessive w ear to contacts on both the
m odule and its m ating connector. W orn contacts m ay
create electrical resistance that can affect m odule
operation.
M odule Status DisplaySee Pages 20 t o 22.
M odule Stat us Ind icatorSee Pages 20 t o 22.
1756-CN2 1756-CN2R
Channel A BNC Connector
Channel B BNC Connector
ControlNet Channel Status IndicatorsSee Page 23 .
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
-
8/20/2019 1756-CN2
20/32
20 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Module Status Indicator and Display
The M odule Status Indicator LED and M odule Status D isplay provide
diagnostic inform ation as sum m arized in the D iagnostics table.
Diagnostics
LED Display
Cause Recommended Action
Off None M odule not communicat ing due
to a pow er supply fault orinternal fault.
1. Check the pow er supply.
2. Check the cableconnectors.
3. M ake sure the module is
firmly seated in the
chassis.
4. I f the indicator remains
off, replace the module.
Red M sg
scrolls
(1)
M odule’s netw ork address is set
to 00, an invalid ControlN et
address. See foot note at end of
table.
1. (Optional, see page 9.)
Turn chassis power
supply off.
2. Remove the module from
the chassis.
3. Set the network address
sw itches to a unique
address (01 to 99 ).
4. Install the module in the
chassis.
5. I f off , turn chassis powersupply on.
BPA#
ERR
M odule detected a different slot
address from that latched w hen
you cycled pow er. Excessive
noise on t he backplane causes
this error.
Replace the chassis or mo dule.
BPRX
ERR
Too many CRC errors being
generated by the multicast
backplane receiver, so the
backplane mult icast receivers
have been shut off .
Replace the m odule.
OK
http://-/?-http://-/?-http://-/?-http://-/?-
-
8/20/2019 1756-CN2
21/32
ControlLogix ControlN et Bridge M odule 21
Publication 1756-IN602A-EN-P - November 2005
Red BPIC
ERRHardw are fault
within the module.
Replace the m odule.
CNIC
ERR
DUPL
NODE
The module’s netw ork address is
the same as another modul e’s onthe li nk.
1. (Optional, see page 9.)
Turn off chassis pow ersupply.
2. Remove the module from
the chassis.
3. Set the network address
sw itches to a unique
address (01 to 99 ).
4. Install the module in the
chassis.
5. I f off , turn chassis powersupply on.
RACK
ERR
Cannot read backpl ane EEPROM ,
or rack/slot address incorrect
Replace the chassis.
Flashing
red
BOOT M o dule has inval id f i rmw are. Update module f i rmw are w i th
ControlFlash Updat e Utilit y.
ROM
UPDT
Flash updat e is in progress. N one required.
SNGL
KPR!
M odule detected that it has
been connected t o a ControlN et
1.0 or 1.25 (single-keeper)
network.
Update the firmw are of module at
node address 01 and reschedule
the network.
Diagnostics
LED Display
Cause Recommended ActionOK
http://-/?-http://-/?-
-
8/20/2019 1756-CN2
22/32
22 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Green OK Normal operat ion. There is at least one connect ion to
or through the module. No action
required.
IN IT M odule is ini t ial izing. No act ion required.
BW
>MAX
M odule is receiving too much
netw ork traffic and connections
are timing out. The netw ork
bandw idth has been exceeded.
No act ion required (temporary
condition).
If t his happens frequentl y, add
another bridge module and split
the traffic betw een them.
SW
ERR
Node address sw itch changed
aft er you cycled pow er.
No action required, but w e
recommend that you either return
sw itches to their original settings
or replace the module, since this
could indicate a lat ent hardw are
problem.Flashing
green
OK Normal operat ion. No connect ions to or through the
module. No action required.
CNFG
ERR
ControlNet conf igurat ion error. Recheck conf igurat ion.
NET
ERRNetw ork cabling error or no
other active nodes on netw ork.
Recheck your netw ork cabling and
make sure another node on the
netw ork is acti ve (online).
(1) If sw it ches are set to 0 0, the displ ay scroll s FAULT: ADDRESS SW ITCHES = 00, ILLEGAL
Diagnostics
LED Display
Cause Recommended ActionOK
-
8/20/2019 1756-CN2
23/32
ControlLogix ControlN et Bridge M odule 23
Publication 1756-IN602A-EN-P - November 2005
ControlNet Channel Status Indicators
The ControlN et channel status indicators appear in one of these
states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the tw o indicators alternate betw een the tw o
defined states at the sam e tim e (applies to both indicators
view ed together). The tw o indicators are alw ays in opposite
states, out of phase.
• Flashing - the indicator alternates betw een the tw o defined
states (applies to each indicator view ed independent of the
other). If both indicators are flashing, they m ust flash together,
in phase.
The Indicator States table sum m arizes the m eanings of these states.
Indicator States
Cause Action
Off No pow er None or apply pow er.
Steady red Faulted unit Cycle pow er or reset unit .
If fault persists, contact A-B
representative or dist ributor.
Alternating
red/green
Self -test None.
Alternating
red/off
Inco rrect node conf i gu ra ti on Check network address and othe r
ControlNet configuration
parameters.
Cause Action
Off Channel disabled Program netw ork for redundantmedia, if required.
Steady green Normal operat ion None.
andA B
orA B
http://-/?-http://-/?-
-
8/20/2019 1756-CN2
24/32
24 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Flashing
green/off
Temporary errors None; unit w ill self-correct.
Node is not configured to go
online
M ake sure the configuration
manager node is present and
w orking and selected address is
not greater than selectedUMAX.(1)
Flash ing red/o f f M edia faul t Check media fo r b roken cables,
loose connectors, or missing
terminators.
No ot her nodes present on
network
Add other nodes to the netw ork.
Flashingred/green
Incorrect netw ork conf igurat ion Cycle power or reset uni t .
If fault persists, contact A-B
representative or dist ributor.
(1) The configurat ion manager node is the node responsible for distributi ng ControlN et configurat ion datato all nodes on the netw ork.
Indicator States
Cause Action
andA B
-
8/20/2019 1756-CN2
25/32
ControlLogix ControlN et Bridge M odule 25
Publication 1756-IN602A-EN-P - November 2005
Specifications
ControlLogix ControlNet Bridge Module - 1756-CN2, 1756-CN2R
Attribute Value
Connectors
1756-CN2
1756-CN2R
1 BNC connector for non-redundant medi a operation
1 NA P (RJ-45 8-pin w ith shield)
2 BNC connectors for redundant media operat ion
1 NA P (RJ-45 8-pin w ith shield)
Cable quad shield RG-6 coaxial cable
Ground isolat ion t ransformer
Con trolNet commun ica ti on rate 5 M
Diagnost ics Yes
Weight
1756-CN2
1756-CN2R
0.260 kg (0.57 lb)
0.293 kg (0.64 lb)
M ount ing type Chassis
M ount ing locat ion 1756 Cont rolLogix Chassis
Number of nodes, max 99
Slot w idth 1
Connect ions supported, max 100
Com muni cat ion i nt erf ace t ype Bri dge
Device type Communicat ion interface
Pow er dissipat ion 5.14 W
Thermal dissipat ion 17.5 BTU/ hr
-
8/20/2019 1756-CN2
26/32
26 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Backplane current 970 mA @ 5.1 V
1.7 mA @ 24 V
Isolation voltage
(continuous-voltage withstand
rating)
50V
Tested t o 500V ac for 60 seconds
W iring category(1) 2 - on communications ports
(1) Use this Conductor Category information for planning conductor routing. Refer to IndustrialAutomation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications
Attribute Value
Operat ional temperature IEC 60068-2-1 (Test Ad, Operat ing Cold), IEC 60068-2-2 (Test Bd, Operati ng Dry Heat ),
IEC 60068-2-14 (Test Nb , Operati ng Therma l Shock): 0… 60 °C (32… 140 °F)
Storage tempera tu re IEC 60068-2-1 (Test Ab , Un-packaged Non-operat ing Co ld ), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -40… 85 °C (-40… 185 °F)
Re lat ive hum id it y IEC 60068-2-30 (Test Db, Un-packaged N on -operat ing Damp Heat ): 5… 95% non-condensing
Vibrat ion IEC 60068-2-6 (Test Fc, Operat ing): 2 g @ 10… 500 Hz
Operat ing shock IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Non-opera ting shock IEC 60068-2-27 (Test Ea , Unpackaged Shock): 50 g
Emissions CISPR 11: Group 1, Class A
ESD immunity IEC 61000-4-2: 6 kV contact di scharges 8 kV air di scharges
ControlLogix ControlNet Bridge Module - 1756-CN2, 1756-CN2R
Attribute Value
-
8/20/2019 1756-CN2
27/32
ControlLogix ControlN et Bridge M odule 27
Publication 1756-IN602A-EN-P - November 2005
Radiat ed RF immunity IEC 61000-4-3: 10 V/ m w ith 1 kHz sine-wave 80%AM from 30… 2000 M Hz 10 V/ m w ith 200 Hz 50% Pulse 100% AM at 900 M Hz 10 V/ m w ith 200 Hz 50% Pulse 100% AM at 1890 M Hz 1 V/m w ith 1 kHz sine-wave 80%AM from 2000 M Hz… 2700 M Hz
EFT/ B immunity IEC 61000-4-4: ±2 kV at 5 kHz on communicati ons ports
Surge t ransien t immun it y IEC 61000-4-5 : ±2 kV line-earth(CM ) on communicati ons ports
Conduct ed RF i mmunit y IEC 61000-4-6: 10V rms wit h 1 kHz sine-wave 80%AM from 150 kHz… 80 M Hz
Encl osure type rat ing N one (open-st yle)
Environmental Specifications
Attribute Value
-
8/20/2019 1756-CN2
28/32
28 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Certifications
Certification Value
Agency certification
(w hen product is marked)(1)UL UL Listed Industria l Control Equipment
cULus UL Liste d for Class I,Division 2 Group A,B,C,D
Hazardous Locations, certified for U.S. and Canada
CSA CSA Certif ied Process Control Equipment
CSA CSA Certif ied Process Control Equipment f or Class I,Division 2 Group A ,B,C,D Hazardous Locati ons
FM FM Approved Equipment for use in Class I Division 2
Group A ,B,C,D Hazardous Locatio ns
CE European Union 89/ 336/ EEC EM C Direct ive, compliant
w i th :
EN 50082-2; Industrial Imm unity
EN 61326; M eas./Control/ Lab., IndustrialRequirements
EN 61000-6-2; Industrial Imm unity
EN 61000-6-4; Industrial Emissions
C-TickAustralian Radiocommunications Act, compliant with:
AS/ NZS CISPR 11; Industrial Emissions
EEx European Union 94/ 9/ EC ATEX Directive, compliantw i th :
EN 50021; Potentially Explosive Atmospheres,
Protecti on "n" (Zone 2)
CI Cont rolNet In t 'l conformance tested to Cont rolNet
specifications
(1) See the Product Certif ication li nk at w w w.ab.com for Declarations of Conformity,
Certificates, and other certification details.
-
8/20/2019 1756-CN2
29/32
ControlLogix ControlN et Bridge M odule 29
Publication 1756-IN602A-EN-P - November 2005
Additional Resources
ControlLogix is a tradem ark of Rockw ell Autom ation, Inc.
Tradem arks not belonging to Rockw ell Autom ation are property of their respective com panies.
Publication Title Publication Number
Indust ri al Automat i on W i ri ng and Ground ing Gu idel ines 1770-4 .1
ControlN et M odules in Logix5000 Cont rol Systems CN ET-UM 0 01
ControlLogix Chassis Installat ion Instruct ions 1756-IN080
Cont rol Logi x Pow e r Supp li es Inst al lat ion Inst ruct io ns 1756-IN 07 8
Cont rol Logi x Pow e r Supp li es Inst al lat ion Inst ruct io ns 1756-IN 59 6
ControlNet Coax Tap Installat ion Instruct ions 1786-5.7
Cont rolNet Coax M edia Planning and Insta llat ion Guide CNET- IN002
Cont rolNet Fiber M edia Planning and Insta llat ion Guide CNET- IN001
-
8/20/2019 1756-CN2
30/32
30 ControlLogix ControlNet Bridge M odule
Publication 1756-IN602A-EN-P - N ovember 2005
Notes:
-
8/20/2019 1756-CN2
31/32
ControlLogix ControlN et Bridge M odule 31
Publication 1756-IN602A-EN-P - November 2005
-
8/20/2019 1756-CN2
32/32
ö
Rockwell Automation SupportRockw ell Autom ation provides technical inform ation on the w eb to assist you
in using its products. At http://support.rockw ellautom ation.com , you can findtechnical m anuals, a know ledge base of FAQ s, technical and application
notes, sam ple code and links to softw are service packs, and a M ySupport
feature that you can custom ize to m ake the best use of these tools.
For an additional level of technical phone support for installation,
configuration and troubleshooting, w e offer TechConnect Support program s.
For m ore inform ation, contact your local distributor or Rockw ell Autom ation
representative, or visit http://support.rockw ellautom ation.com .
Installation Assistance
If you experience a problem w ith a hardw are m odule w ithin the first 24 hours
of installation, please review the inform ation that's contained in this m anual.
You can also contact a special Custom er Support num ber for initial help in
getting your m odule up and running:
New Product Satisfaction Return
Rockw ell tests all of its products to ensure that they are fully operational w hen
shipped from the m anufacturing facility. H ow ever, if your product is not
functioning and needs to be returned:
United States 1.440.646.3223 M onday – Friday, 8am – 5pm EST
Outside Uni ted States Please contact your local Rockwel l Automat ion representat ive for anytechnical support issues.
Unit ed St at es Cont act your dist ri but or. You must provide a Cust om er Support case num ber(see phone number above to obtain one) to your distribut or in order to
complete the return process.
Outside Uni ted States Please contact your local Rockwel l Automat ion representat ive for re turnprocedure.