    Publication 1756-IN602A-EN-P - N ovember 2005

    Installation Instructions 

    ControlLogix ControlNet Bridge Module

    Catal og Numbers 1756-CN2, 1756-CN2R

    Inside . . .

    About This PublicationU se this docum ent as a guide to install the ControlLogix ControlN et

    bridge m odule.

    For See Page

    About This Publ icat ion 1

    Important User Informat ion 2

    European Hazardous Locat ion Approval 3

    North American Hazardous Locat ion Approval 4

    Environment and Enclosure 5

    Prevent ing Electrostat ic Discharge 6

    About the ControlLogix ControlNet Bridge M odule 6

    Before You Begin 7Instal l the M odule 11

    Troubleshoot the M odules 19

    Specif icat ions 25

    Addit ional Resources 29

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    2/32

    2  ControlLogix ControlN et Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Important User Information

    Solid state equipment has operational characteristics diff ering from those of electromechanicalequipment. Safety Guidelines for the Application, Installation and M aintenance of Solid State Controls(Publication SGI-1.1 available from your local Rockwell Automation sales office or online athttp:/ / l i terature.rockw ellautomation.com/ ) describes some important differences betw een solid stateequipment and hard-wired electromechanical devices. Because of this difference, and also because ofthe w ide variety of uses for solid st ate equipment, all persons responsible f or applying this equipmentmust satisfy t hemselves that each intended application of t his equipment is acceptable.

    In no event w ill Rockwel l Autom ation, Inc. be responsible or liable for indirect or consequenti al damagesresulting from the use or application of t his equipment.

    The examples and diagrams in this manual are i ncluded solely for ill ustrati ve purposes. Because of the

    many variables and requirements associated w ith any particular installation, Rockwell Automat ion, Inc.cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent l iabil i ty is assumed by Rockw ell Aut omation, Inc. w ith respect to use of information, circuits,equipment, or softw are described in this manual.

    Reproduction of the contents of this manual, in w hole or in part, w ithout w ritten permission of Rockw ellAutomation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING Identif ies inform ation about pract ices or circumstances that can cause an explosion ina hazardous environment, w hich may lead to personal inj ury or death, property

    damage, or economic loss.

    IMPORTANT Identifies information t hat is critical for successful application and understanding ofthe product.

    ATTENTION Identifies information about practices or circumstances that can lead to personalinjury or death, property damage, or economic loss. Attentions help you identify ahazard, avoid a hazard, and recognize the consequences.

    SHOCK HAZARD

    Labels may be located on or inside t he equipment (for example, drive or motor) toalert people that dangerous voltage may be present.

    BURN HAZARD

    Labels may be located on or inside t he equipment (for example, drive or motor) toalert people that surfaces may be dangerous temperatures.

  • 8/20/2019 1756-CN2

    3/32

    ControlLogix ControlN et Bridge M odule 3

    Publication  1756-IN602A-EN-P - November 2005

    European Hazardous Location Approval

    European Zone 2 Certification

    (The follow ing applies w hen the product bears the EEx M arking.)

    This equipm ent is intended for use in potentially explosive

    atm ospheres as defined by European U nion D irective 94/9/EC.

    The LCIE (Laboratoire Central des Industries Electriques) certifies that

    this equipm ent has been found to com ply w ith the Essential H ealth

    and Safety Requirem ents relating to the design and construction of

    Category 3 equipm ent intended for use in potentially explosive

    atm ospheres, given in Annex II to this D irective. The exam ination

    and test results are recorded in confidential report N o. 28 682 010.

    Com pliance w ith the Essential H ealth and Safety Requirem ents has

    been assured by com pliance w ith EN 50021.

    IMPORTANT This equipm ent is not resistant to sunlight or other

    sources of U V radiation.

    The secondary of a current transform er shall not be

    open-circuited w hen applied in Class I, Zone 2

    environm ents.

    Equipm ent of lesser Enclosure Type Rating m ust be

    installed in an enclosure providing at least IP54

    protection w hen applied in Class I, Zone 2

    environm ents.

    This equipm ent shall be used w ithin its specified ratings

    defined by Allen-Bradley.

    Provision shall be m ade to prevent the rated voltage

    from being exceeded by transient disturbances of m orethan 40% w hen applied in Class I, Zone 2 environm ents.

  • 8/20/2019 1756-CN2

    4/32

    4  ControlLogix ControlN et Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    North American Hazardous Location Approval

    The follow ing information applies w henoperating this equipment in hazardouslocations:

    Informations sur l 'uti l isation de cet équipement enenvironnements dangereux:

    Products marked “CL I, DIV 2, GP A, B, C, D” aresuitabl e for use i n Class I Division 2 Groups A, B,C, D, Hazardous Locations and nonhazardouslocati ons only. Each product is supplied w ithmarkings on the rating nameplate indicating thehazardous location temperature code. When

    combining products wi thin a system, the mostadverse temperature code (low est “ T” number)may be used to help determine the overalltemperature code of the system. Combinationsof equipment in your system are subject t oinvestigation by the local A uthority HavingJurisdiction at the time of installation.

    Les produits marqués “CL I, DIV 2, GP A, B, C, D” neconviennent qu'à une utilisation en environnementsde Classe I Division 2 Groupes A, B, C, D dangereuxet non dangereux. Chaque produit est li vré avec desmarquages sur sa plaque d'identification quiindiquent le code de température pour les

    environnements dangereux. Lorsque plusieursproduits sont combi nés dans un système, le code detem pérature le plus défavorable (code detempérature le plus faible) peut être ut i l isé pourdéterminer le code de température global dusystème. Les combinaisons d'équipem ents dans lesystème sont sujettes à inspection par les autoritéslocales qualifiées au moment de l ' installation.

    EXPLOSION HAZARD

    Do not disconnect equipmentunless power has beenremoved or the area isknow n to be nonhazardous.

    Do not disconnectconnections to thisequipment unless power hasbeen removed or the area is

    know n to be nonhazardous.Secure any externalconnections that mate to t hisequipment by using screws,sliding latches, threadedconnectors, or other meansprovided w ith this product.

    Substit ution of componentsmay impair suitabil i ty forClass I, Division 2.

    If this product containsbatteries, they must only bechanged in an area know n tobe nonhazardous.

    RISQUE D' EXPLOSION

    Couper le courant ou s'assurerque l'environnement est classénon dangereux avant dedébrancher l'équipement.

    Couper le courant ou s'assurerque l'environnement est classénon dangereux avant dedébrancher les connecteurs.

    Fixer t ous les connecteursexternes reliés à cetéquipement à l'aide de vis,loquets coulissants,connecteurs filetés ou autresmoyens fournis avec ce produit .

    La substitution de composantspeut rendre cet équipementinadapté à une uti l isation enenvironnement de Classe I,

    Division 2.

    S'assurer que l'environnementest classé non dangereux avantde changer les piles.

    WARNING   AVERTISSEMENT

  • 8/20/2019 1756-CN2

    5/32

    ControlLogix ControlN et Bridge M odule 5

    Publication  1756-IN602A-EN-P - November 2005

    Environment and Enclosure

    ATTENTION This equipm ent is intended for use in a Pollution D egree2 industrial environm ent, in overvoltage Category II

    applications (as defined in IEC publication 60664-1), at

    altitudes up to 2000 m eters w ithout derating.

    This equipm ent is considered G roup 1, Class A industrial

    equipm ent according to IEC/CISPR Publication 11.

    W ithout appropriate precautions, there m ay be potential

    difficulties ensuring electrom agnetic com patibility in otherenvironm ents due to conducted as w ell as radiated

    disturbance.

    This equipm ent is supplied as open-type equipm ent. It

    m ust be m ounted w ithin an enclosure that is suitably

    designed for those specific environm ental conditions that

    w ill be present and appropriately designed to prevent

    personal injury resulting from accessibility to live parts.The interior of the enclosure m ust be accessible only by

    the use of a tool. Subsequent sections of this publication

    m ay contain additional inform ation regarding specific

    enclosure type ratings that are required to com ply w ith

    certain product safety certifications.

    N O TE: See N EM A Standards publication 250 and IEC

    publication 60529, as applicable, for explanations of the

    degrees of protection provided by different types of

    enclosure. Also, see the appropriate sections in this

    publication, as w ell as Industrial Autom ation W iring and

    G rounding G uidelines, Allen-Bradley publication

    1770-4.1, for additional installation requirem ents

    pertaining to this equipm ent.

  • 8/20/2019 1756-CN2

    6/32

    6  ControlLogix ControlN et Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Preventing Electrostatic Discharge

    For additional inform ation, refer to Industrial Autom ation W iring andG rounding G uidelines, publication 1770-4.1.

    About the ControlLogix ControlNet Bridge Module

    W e designed the enhanced ControlLogix C ontrolN et m odule for

    applications that require higher capacity, and w e recom m end that

    you use this m odule w ith ControlLogix controllers to:

    • expand system s for tw ice as m uch I/O control.

    • effectively double the am ount of Produce/Consum e tags that

    can be transferred betw een controllers.

    • speed up existing applications to run faster.

    U se the 1756-CN 2 ControlLogix ControlN et m odule for stand-alone

    applications only. Applications requiring controller redundancy m ust

    use the 1756-CN B m odule.

    ATTENTION This equipm ent is sensitive to electrostatic discharge,w hich can cause internal dam age and affect norm al

    operation. Follow these guidelines w hen you handle this

    equipm ent:

    • Touch a grounded object to discharge potential static.

    • W ear an approved grounding w riststrap.

    • D o not touch connectors or pins on com ponent

    boards.

    • D o not touch circuit com ponents inside the

    equipm ent.

    • If available, use a static-safe w orkstation.

    • W hen not in use, store the equipm ent in appropriate

    static-safe packaging.

  • 8/20/2019 1756-CN2

    7/32

    ControlLogix ControlN et Bridge M odule 7

    Publication  1756-IN602A-EN-P - November 2005

    Before You Begin

    Before you install the m odule, m ake sure you:

    • know how to handle the m odule (see Preventing Electrostatic

    D ischarge).

    • know the type of ControlN et netw ork.

    There are tw o types of scheduled traffic netw orks for

    ControlN et: single-keeper netw orks and m ulti-keeper

    netw orks. The 1756-CN 2 and 1756-CN 2R bridges are

    m ulti-keeper capable.

    You m ust m atch the keeper to the type of netw ork. Refer to

    the ControlN et M odules in Logix5000 C ontrol System s U ser

    M anual, publication CN ET-U M 001, for m ore inform ation.

    Parts List

    You need all of the com ponents show n.

    1756-CN2 or 1756-CN2R 1756-A4, 1756-A7, 1756-A10,1756-A13, or 1756-A17

    1756-PA72/ 75 or 1756-PB72/ 75Power Supply

    1786-TPR, -TPS-TPYR, or -TPYS(1)

    (1) 1786-TPS or 1786-TPYS taps recommended for net w ork connections.

    1786-CP (Temporary

    Netw ork Connections) Small Screw driver(Optional)

    http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    8/32

    8  ControlLogix ControlN et Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Identify Module Features

    Refer to this figure to identify the hardw are com ponents of the

    1756-CN 2 and 1756-CN 2R bridge m odules.

    BackplaneConnector

    Front View Side View

    M odule StatusAlphanumericDisplay

    Module

    StatusIndicator

    ControlNet

    Channel Stat usIndicators

    NetworkAccess Port(NAP)

    Channel BBNC Connector(1756-CN2R

    nly)

    Channel ABNC ConnectorChannel A

    Network AddressSwitches (not show n)See page 9.

  • 8/20/2019 1756-CN2

    9/32

    ControlLogix ControlN et Bridge M odule 9

    Publication  1756-IN602A-EN-P - November 2005

    Set the Module’s Network Address Switches

    U se your fingers or a sm all screw driver to set the m odule’s netw ork

    address sw itches. For m odules in a standalone chassis, you m ust

    specify a unique ControlN et netw ork address. You can select an

    address of 01 to 99 for m odules in a standalone chassis. N ote that 00

    is an invalid ControlN et address.

    Prepare the Chassis for Module Installation

    Before you install the 1756-CN 2 m odule, you m ust install and connect

    a ControlLogix chassis and pow er supply. A 4-slot chassis w ith a

    pow er supply is show n below .

    side of module

        f   r   o   n    t   o    f   m   o    d   u    l   e

    top of module

    This module’s networkaddress is 23.

    ChassisPowerSupply

  • 8/20/2019 1756-CN2

    10/32

    10  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    For inform ation about installing these products, refer to the

    publications listed in this table.

    These m odules are com patible w ith all versions of chassis and pow er

    supplies.

    Determine Module Slot Location

    This figure show s chassis slot num bering in a 4-slot chassis. Slot 0 isthe first slot and is alw ays the leftm ost slot in the rack (the first slot to

    the right of the pow er supply). You can use any size ControlLogix

    chassis and install the m odule in any slot. You can also install

    m ultiple bridge m odules in the sam e chassis. You can install as m any

    m odules as your pow er supply can accom m odate (that is, the

    num ber for w hich the pow er supply is rated).

     

    Chassis Type

    Chassis

    Installation

     

    Power Supply

    Power Supply

    Installation

    Series B: 1756-A4, 1756-A7,

    1756-A10, 1756-A13, 1756-A17

    Publication

    1756-IN080

    1756-PA72/ C Publicat ion

    1756-IN0781756-PB72/C

    1756-PA75/ B Publicat ion

    1756-IN5961756-PB75/B

    Chassis

    Power Supply

    Slot 0

    Slot 1 Slot 3

    Slot 2

  • 8/20/2019 1756-CN2

    11/32

    ControlLogix ControlN et Bridge M odule 11

    Publication  1756-IN602A-EN-P - November 2005

     Install the Module

    1 . Align the circuit board w ith top and bottom guides in thechassis.

    2. Slide the m odule into the chassis.

    M ake sure the m odule backplane connector properly connects

    to the chassis backplane.

    The m odule is properly installed w hen it is flush w ith the pow er

    supply or other installed m odules.

    ATTENTION D o not force the m odule into the backplane connector. If

    you cannot seat the m odule w ith firm pressure, check the

    alignm ent. Forcing the m odule into the chassis can

    dam age the backplane connector or the m odule.

    1

    2

    CircuitBoard

  • 8/20/2019 1756-CN2

    12/32

    12  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Connect the Module to the Network 

    You can connect the m odule to the ControlN et netw ork by using a

    tap (1786-TPR, 1786-TPS, 1786-TPY R, 1786-TPY S) or a netw ork

    access cable (1786-CP).

    This figure show s an exam ple ControlN et netw ork using redundantm edia.

    W hen connecting the bridge m odule to a ControlN et netw ork, youshould also refer to this docum entation:

    TIP U se the 1786-CP cable for tem porary connections

    (for instance, program m ing softw are). For perm anent

    connections, use a tap.

    Publication Title Publication Number

    ControlNet Coax Tap Installat ion Instruct ions 1786-5.7

    Cont rolNet Coax M edia Planning and Insta llat ion Guide CNET- IN002

    Cont rolNet Fiber M edia Planning and Insta llat ion Guide CNET- IN001

    1756-CN2R(In 1756-A4 Chassis)

    ControlNetNode

    ControlNet Link

    ControlNetNode

    Redundant M edia(Optional)

  • 8/20/2019 1756-CN2

    13/32

    ControlLogix ControlN et Bridge M odule 13

    Publication  1756-IN602A-EN-P - November 2005

    Connect to t he Net w ork Using a Tap 

    Follow these steps to connect the m odule to the netw ork w ith a tap.

    1 . Rem ove and save the dust caps from the ControlN et taps.

    2. Connect the tap’s straight or right-angle connector to the

    m odule’s BN C connector.

    TIP For netw ork connections w e recom m end taps w ith a

    straight connector (1786-TPS or 1786-TPY S) because of

    the location of the B N C connectors on the bottom of them odule.

    ATTENTION D o not allow any m etal portions of the tap to contact any

    conductive m aterial. If you disconnect the tap from the

    m odule, place the dust cap back on the straight or

    right-angle connector to prevent the connector from

    accidentally contacting a m etallic grounded surface.

    If Your Node Supports Connect The Tap’s Connector

    non-redundant media (1756-CN2)

    to t he channel A connector on the modul e

    (channel B on the 1756-CN2R is not used)(1)

    (1) W hile both channels are active, we recommend using channel A f or non-redundant media.

    redundant media•

    from t runkline A to channel A on the 1756-CN2R• from t runkline B to channel B on the 1756-CN2R

    Dust Cap

    Segment 1 Segment 2

    Dust Cap

    1756-CN2 - Segme nt 11756-CN2R - Segments 1 and 2

  • 8/20/2019 1756-CN2

    14/32

    14  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    3. Apply pow er to the m odule and check m odule status.

    IMPORTANT To prevent inadvertent reversal of the tap connections(resulting in incorrect status displays requiring

    troubleshooting), check the tap drop cable for the label

    indicating the attached segm ent before m aking your

    connection.

    Tap

    Segment 1

    Segment 2

    Tap Tap

    A AB

  • 8/20/2019 1756-CN2

    15/32

    ControlLogix ControlN et Bridge M odule 15

    Publication  1756-IN602A-EN-P - November 2005

    U se this flow chart as a guide.

    Turn the chassispow er supply on.

    Modulestatusindicatorred?

    See thetroubleshootingtable on page 20.

    M odule performs apow er-on self-testinitialization.

    N o

    Yes

    INIT

    No

    Yes

    Modulestatusindicatorred?

    INIT has failed, andthe module displays anerror message (seepages 20 t o 23).

    Replace the m odule.

    Initialization iscomplete. Thestatus indicatorblinks green.

    Channel A and Bindicators alternatelyflash.

    Channel A and Bindicato rs display thenetw ork condit io n aslisted on page 23.

    ModulestatusdisplaysOK?

    NoSee thet roubleshooting tableon page 20.

    Yes

    M odule is functionaland operating.

    OKA#xx

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    16/32

    16  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Connect a Programming Terminal to the Net w ork w ith 1786-CP Cable 

    To connect a program m ing term inal to the netw ork using a 1786-CP

    cable, you have these options:

    • U se a 1784-K TC, 1784-K TCx, or 1784-PCC com m unication cardand a 1786-CP cable (pictured)

     

    WARNING If you connect or disconnect the com m unications cablew ith pow er applied to this m odule or any device on the

    netw ork, an electrical arc can occur. This could cause an

    explosion in hazardous location installations.

    IMPORTANT To use redundant m edia, all nodes m ust support

    redundant m edia.

    If you are using redundant m edia, connect the channel

    of each partner to the sam e netw ork segm ent.

    1756-CN2R

    1786-CP Cable

    1784-KTC, KTCx,PCIC, or PCC Card

    ControlNet Link

  • 8/20/2019 1756-CN2

    17/32

    ControlLogix ControlN et Bridge M odule 17

    Publication  1756-IN602A-EN-P - November 2005

    • U se a 1770-K FC com m unication interface, a serial or parallel

    connection, and a 1786-CP cable (pictured)

    The 1786-CP cable can be plugged into any ControlN et product’s

    netw ork access port (N AP) to provide program m ing capability on the

    ControlN et netw ork. A program m ing term inal connected through this

    cable is counted as a node and m ust have a unique netw ork address.

    ATTENTION U se a 1786-CP cable w hen connecting a program m ingterm inal to the netw ork through netw ork access ports.

    U sing a com m ercially available RJ-style cable could result

    in netw ork failure.

    1756-CN2R

    1786-CP(1) 

    ControlNet Link

    Cable

    1770-KFC

    Serial or ParallelConnections

  • 8/20/2019 1756-CN2

    18/32

    18  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Remove the Module

    Follow these steps to rem ove the m odule:

    1 . Push on the upper and low er tabs to disengage them .

    2. Slide the m odule out of the chassis.

     

    IMPORTANT If you are replacing an existing m odule w ith an identical

    one, and you w ant to resum e identical system operation,

    you m ust install the new m odule w ith the sam e

    ControlN et address in the sam e slot.

    Upper Tab

  • 8/20/2019 1756-CN2

    19/32

    ControlLogix ControlN et Bridge M odule 19

    Publication  1756-IN602A-EN-P - November 2005

    Install or Remove the Module Under Power

    You can install or rem ove the m odule w hile chassis pow er is applied

    if you observe these precautions.

    Troubleshoot the Modules

    The m odules have these diagnostic indicators:

    WARNING W hen you insert or rem ove the m odule w hile backplane

    pow er is on, an electrical arc can occur. This could cause

    an explosion in hazardous location installations.

    Be sure that pow er is rem oved or the area is

    nonhazardous before proceeding. Repeated electrical

    arcing causes excessive w ear to contacts on both the

    m odule and its m ating connector. W orn contacts m ay

    create electrical resistance that can affect m odule

    operation.

    M odule Status DisplaySee Pages 20 t o 22.

    M odule Stat us Ind icatorSee Pages 20 t o 22.

    1756-CN2 1756-CN2R

    Channel A BNC Connector

    Channel B BNC Connector

    ControlNet Channel Status IndicatorsSee Page 23 .

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    20/32

    20  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Module Status Indicator and Display

    The M odule Status Indicator LED and M odule Status D isplay provide

    diagnostic inform ation as sum m arized in the D iagnostics table.

    Diagnostics

    LED Display

    Cause Recommended Action

    Off None M odule not communicat ing due

    to a pow er supply fault orinternal fault.

    1. Check the pow er supply.

    2. Check the cableconnectors.

    3. M ake sure the module is

    firmly seated in the

    chassis.

    4. I f the indicator remains

    off, replace the module.

    Red M sg

    scrolls

    (1)

    M odule’s netw ork address is set

    to 00, an invalid ControlN et

    address. See foot note at end of

    table.

    1. (Optional, see page 9.) 

    Turn chassis power

    supply off.

    2. Remove the module from

    the chassis.

    3. Set the network address

    sw itches to a unique

    address (01 to 99 ).

    4. Install the module in the

    chassis.

    5. I f off , turn chassis powersupply on.

    BPA#

    ERR

    M odule detected a different slot

    address from that latched w hen

    you cycled pow er. Excessive

    noise on t he backplane causes

    this error.

    Replace the chassis or mo dule.

    BPRX

    ERR

    Too many CRC errors being

    generated by the multicast

    backplane receiver, so the

    backplane mult icast receivers

    have been shut off .

    Replace the m odule.

    OK 

    http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    21/32

    ControlLogix ControlN et Bridge M odule 21

    Publication  1756-IN602A-EN-P - November 2005

    Red BPIC 

    ERRHardw are fault 

    within the module.

    Replace the m odule.

    CNIC 

    ERR

    DUPL

    NODE

    The module’s netw ork address is

    the same as another modul e’s onthe li nk.

    1. (Optional, see page 9.) 

    Turn off chassis pow ersupply.

    2. Remove the module from

    the chassis.

    3. Set the network address

    sw itches to a unique

    address (01 to 99 ).

    4. Install the module in the

    chassis.

    5. I f off , turn chassis powersupply on.

    RACK

    ERR

    Cannot read backpl ane EEPROM ,

    or rack/slot address incorrect

    Replace the chassis.

    Flashing

    red

    BOOT M o dule has inval id f i rmw are. Update module f i rmw are w i th

    ControlFlash Updat e Utilit y.

    ROM

    UPDT

    Flash updat e is in progress. N one required.

    SNGL

    KPR!

    M odule detected that it has

    been connected t o a ControlN et

    1.0 or 1.25 (single-keeper)

    network.

    Update the firmw are of module at

    node address 01 and reschedule

    the network.

    Diagnostics

    LED Display

    Cause Recommended ActionOK 

    http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    22/32

    22  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Green OK Normal operat ion. There is at least one connect ion to

    or through the module. No action

    required.

    IN IT M odule is ini t ial izing. No act ion required.

    BW

    >MAX

    M odule is receiving too much

    netw ork traffic and connections

    are timing out. The netw ork

    bandw idth has been exceeded.

    No act ion required (temporary

    condition). 

    If t his happens frequentl y, add

    another bridge module and split

    the traffic betw een them.

    SW  

    ERR

    Node address sw itch changed

    aft er you cycled pow er.

    No action required, but w e

    recommend that you either return

    sw itches to their original settings

    or replace the module, since this

    could indicate a lat ent hardw are

    problem.Flashing

    green

    OK Normal operat ion. No connect ions to or through the

    module. No action required.

    CNFG

    ERR

    ControlNet conf igurat ion error. Recheck conf igurat ion.

    NET 

    ERRNetw ork cabling error or no

    other active nodes on netw ork.

    Recheck your netw ork cabling and

    make sure another node on the

    netw ork is acti ve (online).

    (1) If sw it ches are set to 0 0, the displ ay scroll s FAULT: ADDRESS SW ITCHES = 00, ILLEGAL

    Diagnostics

    LED Display

    Cause Recommended ActionOK 

  • 8/20/2019 1756-CN2

    23/32

    ControlLogix ControlN et Bridge M odule 23

    Publication  1756-IN602A-EN-P - November 2005

    ControlNet Channel Status Indicators

    The ControlN et channel status indicators appear in one of these

    states:

    • Steady - indicator is on continuously in the defined state.

    • Alternating - the tw o indicators alternate betw een the tw o

    defined states at the sam e tim e (applies to both indicators

    view ed together). The tw o indicators are alw ays in opposite

    states, out of phase.

    • Flashing - the indicator alternates betw een the tw o defined

    states (applies to each indicator view ed independent of the

    other). If both indicators are flashing, they m ust flash together,

    in phase.

    The Indicator States table sum m arizes the m eanings of these states.

    Indicator States

    Cause Action

    Off No pow er None or apply pow er.

    Steady red Faulted unit Cycle pow er or reset unit . 

    If fault persists, contact A-B

    representative or dist ributor.

    Alternating

    red/green

    Self -test None.

    Alternating

    red/off

    Inco rrect node conf i gu ra ti on Check network address and othe r

    ControlNet configuration

    parameters.

    Cause Action

    Off Channel disabled Program netw ork for redundantmedia, if required.

    Steady green Normal operat ion None.

    andA B

    orA B

    http://-/?-http://-/?-

  • 8/20/2019 1756-CN2

    24/32

    24  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Flashing

    green/off

    Temporary errors None; unit w ill self-correct.

    Node is not configured to go

    online

    M ake sure the configuration

    manager node is present and

    w orking and selected address is

    not greater than selectedUMAX.(1)

    Flash ing red/o f f M edia faul t Check media fo r b roken cables,

    loose connectors, or missing

    terminators.

    No ot her nodes present on

    network

    Add other nodes to the netw ork.

    Flashingred/green

    Incorrect netw ork conf igurat ion Cycle power or reset uni t . 

    If fault persists, contact A-B

    representative or dist ributor.

    (1) The configurat ion manager node is the node responsible for distributi ng ControlN et configurat ion datato all nodes on the netw ork.

    Indicator States

    Cause Action

    andA B

  • 8/20/2019 1756-CN2

    25/32

    ControlLogix ControlN et Bridge M odule 25

    Publication  1756-IN602A-EN-P - November 2005

    Specifications

    ControlLogix ControlNet Bridge Module - 1756-CN2, 1756-CN2R

    Attribute Value

    Connectors 

    1756-CN2 

    1756-CN2R

     

    1 BNC connector for non-redundant medi a operation 

    1 NA P (RJ-45 8-pin w ith shield) 

    2 BNC connectors for redundant media operat ion 

    1 NA P (RJ-45 8-pin w ith shield)

    Cable quad shield RG-6 coaxial cable

    Ground isolat ion t ransformer

    Con trolNet commun ica ti on rate 5 M

    Diagnost ics Yes

    Weight  

    1756-CN2 

    1756-CN2R

     

    0.260 kg (0.57 lb) 

    0.293 kg (0.64 lb)

    M ount ing type Chassis

    M ount ing locat ion 1756 Cont rolLogix Chassis

    Number of nodes, max 99

    Slot w idth 1

    Connect ions supported, max 100

    Com muni cat ion i nt erf ace t ype Bri dge

    Device type Communicat ion interface

    Pow er dissipat ion 5.14 W

    Thermal dissipat ion 17.5 BTU/ hr

  • 8/20/2019 1756-CN2

    26/32

    26  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Backplane current 970 mA @ 5.1 V 

    1.7 mA @ 24 V

    Isolation voltage

    (continuous-voltage withstand

    rating)

    50V 

    Tested t o 500V ac for 60 seconds

    W iring category(1) 2 - on communications ports

    (1) Use this Conductor Category information for planning conductor routing. Refer to IndustrialAutomation Wiring and Grounding Guidelines, publication 1770-4.1.

    Environmental Specifications

    Attribute Value

    Operat ional temperature IEC 60068-2-1 (Test Ad, Operat ing Cold), IEC 60068-2-2 (Test Bd, Operati ng Dry Heat ), 

    IEC 60068-2-14 (Test Nb , Operati ng Therma l Shock): 0… 60 °C (32… 140 °F)

    Storage tempera tu re IEC 60068-2-1 (Test Ab , Un-packaged Non-operat ing Co ld ), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -40… 85 °C (-40… 185 °F)

    Re lat ive hum id it y IEC 60068-2-30 (Test Db, Un-packaged N on -operat ing Damp Heat ): 5… 95% non-condensing

    Vibrat ion IEC 60068-2-6 (Test Fc, Operat ing): 2 g @ 10… 500 Hz

    Operat ing shock IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

    Non-opera ting shock IEC 60068-2-27 (Test Ea , Unpackaged Shock): 50 g

    Emissions CISPR 11: Group 1, Class A

    ESD immunity IEC 61000-4-2: 6 kV contact di scharges 8 kV air di scharges

    ControlLogix ControlNet Bridge Module - 1756-CN2, 1756-CN2R

    Attribute Value

  • 8/20/2019 1756-CN2

    27/32

    ControlLogix ControlN et Bridge M odule 27

    Publication  1756-IN602A-EN-P - November 2005

    Radiat ed RF immunity IEC 61000-4-3: 10 V/ m w ith 1 kHz sine-wave 80%AM from 30… 2000 M Hz 10 V/ m w ith 200 Hz 50% Pulse 100% AM at 900 M Hz 10 V/ m w ith 200 Hz 50% Pulse 100% AM at 1890 M Hz 1 V/m w ith 1 kHz sine-wave 80%AM from 2000 M Hz… 2700 M Hz

    EFT/ B immunity IEC 61000-4-4: ±2 kV at 5 kHz on communicati ons ports

    Surge t ransien t immun it y IEC 61000-4-5 : ±2 kV line-earth(CM ) on communicati ons ports

    Conduct ed RF i mmunit y IEC 61000-4-6: 10V rms wit h 1 kHz sine-wave 80%AM from 150 kHz… 80 M Hz

    Encl osure type rat ing N one (open-st yle)

    Environmental Specifications

    Attribute Value

  • 8/20/2019 1756-CN2

    28/32

    28  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Certifications

    Certification Value

    Agency certification 

    (w hen product is marked)(1)UL UL Listed Industria l Control Equipment

    cULus UL Liste d for Class I,Division 2 Group A,B,C,D

    Hazardous Locations, certified for U.S. and Canada

    CSA CSA Certif ied Process Control Equipment

    CSA CSA Certif ied Process Control Equipment f or Class I,Division 2 Group A ,B,C,D Hazardous Locati ons

    FM FM Approved Equipment for use in Class I Division 2

    Group A ,B,C,D Hazardous Locatio ns

    CE European Union 89/ 336/ EEC EM C Direct ive, compliant

    w i th : 

    EN 50082-2; Industrial Imm unity 

    EN 61326; M eas./Control/ Lab., IndustrialRequirements 

    EN 61000-6-2; Industrial Imm unity  

    EN 61000-6-4; Industrial Emissions

    C-TickAustralian Radiocommunications Act, compliant with: 

    AS/ NZS CISPR 11; Industrial Emissions

    EEx European Union 94/ 9/ EC ATEX Directive, compliantw i th : 

    EN 50021; Potentially Explosive Atmospheres,

    Protecti on "n" (Zone 2)

    CI Cont rolNet In t 'l conformance tested to Cont rolNet

    specifications

    (1) See the Product Certif ication li nk at w w w.ab.com for Declarations of Conformity,

    Certificates, and other certification details.

  • 8/20/2019 1756-CN2

    29/32

    ControlLogix ControlN et Bridge M odule 29

    Publication  1756-IN602A-EN-P - November 2005

    Additional Resources

    ControlLogix is a tradem ark of Rockw ell Autom ation, Inc.

    Tradem arks not belonging to Rockw ell Autom ation are property of their respective com panies.

    Publication Title Publication Number

    Indust ri al Automat i on W i ri ng and Ground ing Gu idel ines 1770-4 .1

    ControlN et M odules in Logix5000 Cont rol Systems CN ET-UM 0 01

    ControlLogix Chassis Installat ion Instruct ions 1756-IN080

    Cont rol Logi x Pow e r Supp li es Inst al lat ion Inst ruct io ns 1756-IN 07 8

    Cont rol Logi x Pow e r Supp li es Inst al lat ion Inst ruct io ns 1756-IN 59 6

    ControlNet Coax Tap Installat ion Instruct ions 1786-5.7

    Cont rolNet Coax M edia Planning and Insta llat ion Guide CNET- IN002

    Cont rolNet Fiber M edia Planning and Insta llat ion Guide CNET- IN001

  • 8/20/2019 1756-CN2

    30/32

    30  ControlLogix ControlNet Bridge M odule

    Publication 1756-IN602A-EN-P - N ovember 2005

    Notes:

  • 8/20/2019 1756-CN2

    31/32

    ControlLogix ControlN et Bridge M odule 31

    Publication  1756-IN602A-EN-P - November 2005

  • 8/20/2019 1756-CN2

    32/32

     

    ö

    Rockwell Automation SupportRockw ell Autom ation provides technical inform ation on the w eb to assist you

    in using its products. At http://support.rockw ellautom ation.com , you can findtechnical m anuals, a know ledge base of FAQ s, technical and application

    notes, sam ple code and links to softw are service packs, and a M ySupport

    feature that you can custom ize to m ake the best use of these tools.

    For an additional level of technical phone support for installation,

    configuration and troubleshooting, w e offer TechConnect Support program s.

    For m ore inform ation, contact your local distributor or Rockw ell Autom ation

    representative, or visit http://support.rockw ellautom ation.com .

    Installation Assistance

    If you experience a problem w ith a hardw are m odule w ithin the first 24 hours

    of installation, please review the inform ation that's contained in this m anual.

    You can also contact a special Custom er Support num ber for initial help in

    getting your m odule up and running:

    New Product Satisfaction Return

    Rockw ell tests all of its products to ensure that they are fully operational w hen

    shipped from the m anufacturing facility. H ow ever, if your product is not

    functioning and needs to be returned:

    United States 1.440.646.3223 M onday – Friday, 8am – 5pm EST

    Outside Uni ted States Please contact your local Rockwel l Automat ion representat ive for anytechnical support issues.

    Unit ed St at es Cont act your dist ri but or. You must provide a Cust om er Support case num ber(see phone number above to obtain one) to your distribut or in order to

    complete the return process.

    Outside Uni ted States Please contact your local Rockwel l Automat ion representat ive for re turnprocedure.