15.1 the power factor at each of the customer’s points of
TRANSCRIPT
![Page 1: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/1.jpg)
![Page 2: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/2.jpg)
15.1 The power factor at each of the CUSTOMER’s Points of Supply shall under all
load conditions not be leading, unless otherwise agreed to by ESKOM.
15.2 The power factor of the load at each of the CUSTOMER’s Points of Supply
shall not be less than 0,9 (naught comma nine) lagging. Should the power
factor be less than 0,9 (naught comma nine) the CUSTOMER shall be required
to install at its own expense suitable apparatus to ensure that this requirement
is complied with.
![Page 3: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/3.jpg)
![Page 4: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/4.jpg)
![Page 5: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/5.jpg)
![Page 6: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/6.jpg)
Real Power or Working Power (kW) - Measured
Reactive Power (kVAr) - Measured
Apparent Power (kVA) - Calculated
Leading Power factor = Dangerous and not easy to manage
Manageable not serious issues
Power Factor = True Power / Apparent Power
Power Factor = Resistance / Impedance
Power Factor = Voltage / Current
Power Factor = Power / 1.73 * Volts * Amps
![Page 7: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/7.jpg)
Never Control to Unity = 1 ( .98 best )
If the Power Factor is 1 you are very close to resonance
![Page 8: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/8.jpg)
Leading Reactive Power:
Produced by Synchronous Capacitors and Capacitor Banks.Consumed by the Capacitive nature of Loads.Leading Reactive power loads are Electric Motors with Capacitor for starting and running, Long TransmissionLines.
The main harmful effect of the leading power factor is, it creates a high voltage in the circuit which can affect theload as well as the power supply circuit.
![Page 9: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/9.jpg)
Charging and discharging capacitors (scienceandmathsrevision.co.uk)
Capacitor Discharging- Explained (learningaboutelectronics.com)
To calculate the time constant of a capacitor, the formula is τ=RC.
This value yields the time (in seconds) that it takes a capacitor to
discharge to 63% of the voltage that is charging it up. After 5 time
constants, the capacitor will discharge to almost 0% of all its
voltage.
Point where you can switch Caps in again at 5T (5 Time Constants) for Industrial caps this time is +_ 7 min.
If this is not done then the voltage will super impose it self. 6.6 -> 12 -> 24-> 48 -> 96 kV. Expect some serious damage to equipment.
![Page 10: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/10.jpg)
Increases heating losses in transformer and distribution equipment.Reduce plant life.Unstable voltage levels.Increase power losses.Upgrades needs == costly equipment.Decreases energy efficiency.Increases electricity cost by paying power factor surcharges.
Causes and Disadvantages of Low Power Factor | Electrical-Technology | All about Electrical Engineering
Why should plant engineers be worried about the power factor? What’s the catch? | EEP (electrical-engineering-portal.com)
![Page 11: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/11.jpg)
Increase in efficiency of system and devices
Low Voltage Drop and cable capacity increases.
Reduction in size of a conductor and cable which reduces cost of the Cooper
An Increase in available power on cables and equipment
Line Losses (Copper Losses) I2R is reduced
Appropriate Size of Electrical Machines (Transformer, Generators etc.)
Saving in the power bill
Back-to-Basics: On Power Factor And Why We Correct It | Power Electronics
![Page 12: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/12.jpg)
Advantages
Reduces the tariff penalties for excessive consumption of Reactive Power
Reduces the apparent power kVA demand, on which standing charges are
usually based
Relieves the supply transformer, which is then able to accept more load if
necessary
Reactive current still flows in all conductors of cables leaving (i.e.
downstream of) the main LV distribution board
For the above reason, the sizing of these cables, and power losses in them, are not improved by the global mode of compensation.
Down side
5 Types of Power Factor Correction | Capacitor bank locations - TheElectricalGuy
![Page 13: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/13.jpg)
Advantages
Reduces the tariff penalties for excessive consumption of kVArs
Reduces the apparent power kVA demand, on which standing charges are usually
based
Relieves the supply transformer, which is then able to accept more load if necessary
The size of the cables supplying the local distribution boards may be reduced, or will
have additional capacity for possible load increases
Losses in the same cables will be reduced
Down side
Reactive current still flows in all cables downstream of the local distribution boards
For the above reason, the sizing of these cables, and the power losses in them, are not improved by
compensation by sector
Where large changes in loads occur, there is always a risk of overcompensation and consequent
overvoltage problems
![Page 14: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/14.jpg)
Advantages
Reduces the tariff penalties for excessive consumption of kVArs
Reduces the apparent power kVA demand
Improve the Power Factor of the piece of Equipment.
Reduces the size of all cables as well as the cable losses (in design)
Significant reactive currents no longer exist in the installation
HUGE ADVANTAGE
![Page 15: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/15.jpg)
![Page 16: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/16.jpg)
Never install PFC equipment where the concrete is reinforced with steel
The steel will be a path for induced circulating current.
Rather reinforce the concrete with Fibre or Kevlar
![Page 17: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/17.jpg)
Good is not always Good or the Best
![Page 18: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/18.jpg)
![Page 19: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/19.jpg)
The voltage across the inductor is equal to the voltage across the capacitor.
The voltage across the resistor is equal to the applied voltage.
The impedance (Z)of the circuit has its lowest value and is equal to (R). Z=R
Circuit current assumes its maximum value because the impedance is minimum.
The power factor for the circuit becomes equal to 1, and the phase angle is zero.
Apparent power has its lowest value and becomes equal to the active power because the powerfactor is 1.
Resonance occurs because the collapsing magnetic field of the inductor generates an electric current in its windings that charges the capacitor,the discharging capacitor provides an electric current that builds the magnetic field in the inductor, and the
process is repeated
![Page 20: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/20.jpg)
A serious concern arising from the use of capacitors in an electrical power system is the possibility of system resonance.
This effect imposes voltages and currents that are substantially higher than would be the case without resonance.
Effect on the circuit is the same as though neither inductance nor capacitance is present. So NO Impedance only Resistance
Harmonic resonance in a power system may be classified as parallel or series resonance, and both types are present in a harmonic-rich environment.
Parallel resonance causes current multiplication, whereas Series resonance produces Voltage magnification.
Substantial damage to capacitor banks would occur when resonance is present
A high probability that other electrical devices / Equipment in the system would also be damaged.
Difference Between Series Resonance and Parallel Resonance i
What are Series RLC Circuit and Parallel RLC Circuit? (apogeeweb.net)
![Page 21: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/21.jpg)
![Page 22: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/22.jpg)
Overloads on distribution systems due to the increase in the RMS current,
overloads on neutral conductors due to the summing of third-order
harmonics
Overloads, vibrations and premature ageing of generators, transformers,
motors, etc., transformer hum,
Overloading and premature ageing of capacitors in power factor correction
equipment,
Distortion of the supply voltage, capable of disturbing sensitive loads,
Disturbances on communications networks and telephone lines.
The Presence of Harmonics can result in increased equipment and
conductor heating, misfiring in variable speed drives, and torque
pulsations in motors and generators.
Harmonics and It’s Effects | Electrical Notes & Articles (wordpress.com)
Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (byjus.com)
![Page 23: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/23.jpg)
Harmonics that causes serious problems
3rd = Motor = Zero Sequence = Current in Neutral / Star Point5th = Motor = Negative Sequence = Negative Torque / Overheating, Motors, Cables7th = Motor = Positive Sequence = Over exited Positive Torque
Harmonic Current and Voltage Distortion | EC&M (ecmweb.com)
Harmonic distortion: causes and mitigation (capacitorfaks.com)
![Page 24: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/24.jpg)
Harmonics measured at a shaft causing Resonance
EFFECTS OF HARMONICS ON CAPACITORS | Power Quality In Electrical Systems (powerqualityworld.com)
![Page 25: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/25.jpg)
Switching of a capacitor bank in the presence of already energized banks on the same bus.
The transients mainly consist of interchange of current between the banks.
These transient currents can be extremely high in amplitude and frequency and may exceed
the capability of the circuit breaker. Causing a serious failure
![Page 26: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/26.jpg)
Where the capacitor bank is already energized and operating in the steady state and a fault
occurs on the bus, the capacitor bank would discharge into the fault.
It`s magnitude and frequency depend on inductance between the capacitor bank and the fault
location.
Outrush transient can be very severe causing stress in the circuit breaker causing failure and an
explosion.
![Page 27: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/27.jpg)
The voltage magnification is due to the interaction between a distribution-level capacitor bank and
another nearby bank on the transmission system.
Voltage magnification transients can be experienced at the distribution level capacitor.
This could lead to severe over voltages, which could ultimately lead to the failure of the capacitor
bank or Equipment
Arc, Restriking and Recovery Voltages | chakarvyuh (wordpress.com)
![Page 28: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/28.jpg)
Restriking Voltage Transient in a Circuit Breaker - Explanation & Calculation of Restriking Voltage - Circuit Globe
As soon as the contacts separate out an arc is formed. The voltage across the contacts during the arcing period is known as the arc voltage and is relatively low with heavy current arcs of short length.
At current zero it rises rapidly to the peak value since a short circuit current is almost 90° lagging.The translate voltage appearing across the contacts at current zero during arc period is called the restriking voltage. This voltage will probably restrike the arc so that it persists for another half cycle.
![Page 29: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/29.jpg)
SF6 Rotating Arc
Modern Vacuum Bottle
![Page 30: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/30.jpg)
ION 8240 Custom Control ModuleION 7550
Custom Stage Control Module
![Page 31: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/31.jpg)
Doing Power Factor Correction is in evadable == doing it correctly is a choice
Do your home work before you jump into the exercise.
Most important step is Start of by doing an study of your electrical system
Decide what benefit you want out of the exercise
Check your equipment if it is suited for the added capacitance
Make sure that the interlocking is done properly and that the control is relevant
No sophisticated control equipment is necessary, do it with your power quality equipment
installed.
![Page 32: 15.1 The power factor at each of the CUSTOMER’s Points of](https://reader031.vdocuments.us/reader031/viewer/2022012213/61df4b5ecffa70272f3e7fb3/html5/thumbnails/32.jpg)