1500 series - dmgenerator.com

20

Upload: others

Post on 25-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1500 Series - dmgenerator.com
Page 2: 1500 Series - dmgenerator.com

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN3090B/12/15 Produced in England ©2015 Perkins Engines Company Limited

1500 Series 1506A-E88TAG5 ElectropaKU.S. EPA Tier 3 Emergency Stationary Engines 333 kWm standby net power @ 1800 rpm

Building upon Perkins proven reputation within the power generation industry the Perkins® 1500 Series Electropak engines now fit even closer to our customer’s needs.

The 1506A-E88TAG5 ElectropaK is a 6 cylinder, fully electronic, turbocharged, air-to-air charge cooled diesel engine. It is economical, quiet and reliable and provides the high performance that is demanded by our customers for their power generation needs.

Focusing on the Perkins common platform theme, changes to engine envelope dimensions and connection points have been kept to a minimum, making for easy installation across the ratings.

Specification

Number of cylinders 6 vertical in-line

Bore and stroke 112 x 149 mm 4.5 x 5.8 in

Displacement 8.8 litres 537 cubic in

Aspiration Turbocharged aftercooled

Cycle 4 stroke

Combustion system Direct injection

Compression ratio 16.1:1

Rotation Anti-clockwise, viewed on flywheel

Total lubricating capacity 41 litres 9.01 US gal

Cooling system Liquid

Page 3: 1500 Series - dmgenerator.com

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN3090B/12/15 Produced in England ©2015 Perkins Engines Company Limited

1500 Series 1506A-E88TAG5 ElectropaKU.S. EPA Tier 3 Emergency Stationary Engines 333 kWm standby net power @ 1800 rpm

Features and benefits

Dependable powerl The 1506A-E88TAG5 delivers greater productivity through an improved power to weight ratiol The world-class power density has been achieved from an 8.8 litre turbocharged engine using a hydraulic actuated

unit injection (HEUI) fuel system; making this engine robust for all markets due to its ability to cope with the variation of fuel quality around the world

l In its class, the 1506A-E88TAG5 has been designed to provide dependable power even in extreme ambient climates

Low operating costsl Oil change service intervals are set at 500 hours as standardl Designed to provide low cost of ownerhsip, simple maintenance and reduced downtime l Perkins provides warranty coverage commencing on the date of delivery of new engines to the first user for

12 months, with 24 months on major core engine components. Consult Perkins Engines Company for detailed information

Flexibilityl The 1506-E88TAG5 has been designed to hit the power node requirements of our customers l Switchability functionality from 50 Hz/1500 rpm to 60 Hz/1800 rpm and vice versa is available to provide greater

flexibility for frequency selection

World class product support l Perkins experienced global network of distributors and dealers, fully trained engine experts deliver total service

support around the clock, 365 days a year. They have a comprehensive suite of web based tools at their disposal, covering technical information, parts identification and ordering systems, all dedicated to maximising the productivity of your engine

l Perkins actively pursues product support excellence by insisting our distribution network invest in their territory to provide customers with a consistent quality of support across the globe

l Throughout the entire life of a Perkins engine, we provide access to genuine OE specification parts giving 100% reassurance that you receive the very best in terms of quality for lowest possible cost, wherever your Perkins powered machine is operating in the world

l To find your local distributor: www.perkins.com/distributor

Page 4: 1500 Series - dmgenerator.com

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN3090B/12/15 Produced in England ©2015 Perkins Engines Company Limited

1500 Series 1506A-E88TAG5 ElectropaKU.S. EPA Tier 3 Emergency Stationary Engines 333 kWm standby net power @ 1800 rpm

Technical information

Air inlet systemlMounted air filter and turbocharger

Fuel systemlHEUI fuel system with full authority electronic controll Electronic governing to ISO 8528-5 with stand-alone isochronous and load-sharing capabilitiesl Fuel filter, fuel transfer pump, fuel priming pumpl Spin on primary, secondary and water filter separator

Lubrication systemlWet full aluminium sump with filler and dipstickl Full-flow spin-on filterslOil pump, gear driven

Cooling systeml Thermostatically controlled with belt driven, circulating pump and belt-drive fanlMounted belt driven pusher fanlRadiator supplied loose with all guards and pipesl Air-to-air charge cooler incorporated in radiator

Electrical equipmentl 24V starter motor and 24V, 45 amp alternator with DC outputl Electronic Control Module (ECM) mounted on engine with wiring looms and sensors

Flywheel and housinglHigh inertia flywheel to SAE 1 J620 Size 355.6 mm (14 in)l Aluminium SAE 1 flywheel housing

Mountingsl Front engine mounting bracket

Page 5: 1500 Series - dmgenerator.com

1129 mm

2180 mm

1725

mm

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN3090B/12/15 Produced in England ©2015 Perkins Engines Company Limited

1500 Series 1506A-E88TAG5 ElectropaKU.S. EPA Tier 3 Emergency Stationary Engines 333 kWm standby net power @ 1800 rpm

Engine package weights and dimensions

Length (including air cleaner) 2180 mm 86 in

Width 1129 mm 45 in

Height 1725 mm 68 in

Weight (dry) 1175 kg 2590 lb

Page 6: 1500 Series - dmgenerator.com

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN3090B/12/15 Produced in England ©2015 Perkins Engines Company Limited

1500 Series 1506A-E88TAG5 ElectropaKU.S. EPA Tier 3 Emergency Stationary Engines 333 kWm standby net power @ 1800 rpm

Percent of prime powerFuel consumption at 1800 rpm

g/kWhFuel consumption at 1800 rpm

l/hr

Standby power ? ?

Prime power ? ?

75% ? ?

50% ? ?

Speed rpm

Type of operation

Typical generator output Engine power (Net)

kVA kWe kWm hp

1800Prime power 352 282 300 402

Standby power 386 309 333 446

Page 7: 1500 Series - dmgenerator.com

LSA 46.3

Low Voltage Alternator - 4 pole230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Electrical and mechanical data

Page 8: 1500 Series - dmgenerator.com

2 Electric Power Generation

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Specially adapted to applicationsThe LSA 46.3 alternator is designed to be suitable for typical generator applications, such as: backup, prime power, cogeneration, marine applications, rental, telecommunications, etc.

Compliant with international standardsThe LSA 46.3 alternator conforms to the main international standards and regulations:IEC 60034, NEMA MG 1.32-33, ISO 8528-3, CSA C22.2 n°100-14, UL 1446 (UL 1004 on request), marine regulations, etc.It can be integrated into a EC marked generator.The LSA 46.3 is designed, manufactured and marketed in an ISO 9001 and ISO 14001 environment.

Top of the range electrical performance ● Class H insulation ● Standard 12-wire re-connectable winding, 2/3 pitch, type no. 6 ● Voltage range 50 Hz: 220 V - 240 V and 380 V - 415 V (440 V) ● Voltage range 60 Hz: 208 V - 240 V and 380 V - 480 V ● High efficiency and motor starting capacity ● Other voltages are possible with optional adapted windings:

- 50 Hz: 440 V (no. 7), 500 V (no. 9), 550 V (no. 22), 600 V (no. 23), 690 V (no. 10 or 52)- 60 Hz: 380 V and 416 V (no. 8), 600 V (no. 9)

● R 791 interference suppression conforming to standard EN 61000-6-3, EN 61000-6-2, EN 55011 group 1 class B standard forEuropean zone (EC marking)

Excitation and regulation system suited to the applicationExcitation system Regulation options

Volageregulator

SHUNT AREP (option)

PMG(option)

C.T.Current transformer

for paralleling

Mainsparalleling

3-phasesensing

Remote voltagepotentiometer

R250 Standard - - - - - √D350 - Standard Standard C.T. - √ √D550 Option Option Option C.T. √ √ √

√ : Possible option

Protection system suited to the environment ● The LSA 46.3 is IP 23 ● Standard winding protection for clean environments with relative humidity ≤ 95 %, including indoor marine environments ● Options:

- Filters on air inlet : derating 5%- Filters on air inlet and air outlet (IP 44) : derating 10%- Winding protections for harsh environments and relative humidity greater than 95%- Space heaters- Thermal protection for winding and shields

Reinforced mechanical structure using finite element modelling ● Compact and rigid assembly to better withstand generator vibrations ● Steel frame ● Cast iron flanges and shields ● Twin-bearing and single-bearing versions designed to be suitable for engines on the market ● Half-key balancing ● Sealed for life ball bearings, regreasable bearings (optional) ● Direction of rotation: clockwise and anti-clockwise (without derating)

Accessible terminal box proportioned for optional equipment ● Easy access to the voltage regulator and to the connections ● Possible inclusion of accessories for paralleling, protection and measurement ● 9-way terminal block for voltage reconnection

Page 9: 1500 Series - dmgenerator.com

3Electric Power Generation

Phase 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph.Y 380V 400V 415V 440V ∆∆ 380V 400V 415V 440V ∆∆ 380V 400V 415V 440V ∆∆ 380V 400V 415V 440V ∆∆∆ 220V 230V 240V 230V 220V 230V 240V 230V 220V 230V 240V 230V 220V 230V 240V 230V

YY 220V 220V 220V 220V46.3 S4 kVA 230 230 230 219 138 209 209 209 200 126 244 244 244 232 146 253 253 253 240 152

kW 184 184 184 175 110 167 167 167 160 101 195 195 195 186 117 202 202 202 192 12246.3 S5 kVA 240 250 250 238 150 218 228 228 216 137 254 265 265 252 159 264 275 275 261 165

kW 192 200 200 190 120 174 182 182 173 110 204 212 212 202 127 211 220 220 209 13246.3 M7 kVA 275 275 275 261 165 250 250 250 238 150 292 292 292 277 175 303 303 303 287 182

kW 220 220 220 209 132 200 200 200 190 120 234 234 234 222 140 242 242 242 230 14646.3 M8 kVA 290 300 300 285 180 264 273 273 259 164 307 318 318 302 191 319 330 330 313 200

kW 232 240 240 228 144 211 218 218 207 131 246 254 254 242 153 255 264 264 250 16046.3 L10 kVA 325 325 325 309 195 300 300 300 281 177 345 345 345 327 207 358 358 358 340 215

kW 260 260 260 247 156 240 240 240 225 142 276 276 276 262 166 286 286 286 272 17246.3 L11 kVA 350 365 365 347 210 319 332 332 316 191 371 387 387 368 225 385 400 400 380 231

kW 280 292 292 277 168 255 266 266 253 153 297 310 310 294 180 308 320 320 304 185

Phase 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph.Y 380V 416V 440V 480V ∆∆ 380V 416V 440V 480V ∆∆ 380V 416V 440V 480V ∆∆ 380V 416V 440V 480V ∆∆∆ 220V 240V 240V 240V 220V 240V 240V 240V 220V 240V 240V 240V 220V 240V 240V 240V

YY 208V 220V 240V 208V 220V 240V 208V 220V 240V 208V 220V 240V46.3 S4 kVA 226 250 262 288 152 206 227 238 262 138 240 264 278 305 161 250 274 288 316 167

kW 181 200 210 230 122 165 182 190 210 110 192 211 222 244 129 200 219 230 253 13446.3 S5 kVA 245 265 280 313 165 223 241 255 284 150 260 281 297 331 175 270 292 308 344 182

kW 196 212 224 250 132 178 193 204 227 120 208 225 238 265 140 216 234 246 275 14646.3 M7 kVA 275 300 315 344 182 250 273 287 313 165 292 318 334 364 192 303 330 347 378 200

kW 220 240 252 275 146 200 218 230 250 132 234 254 267 291 154 242 264 278 302 16046.3 M8 kVA 290 315 340 375 200 264 287 309 337 180 307 334 360 395 210 319 347 375 412 218

kW 232 252 272 300 160 211 230 247 270 144 246 267 288 316 168 255 278 300 330 17446.3 L10 kVA 315 345 365 406 215 287 314 332 370 195 334 366 387 431 227 347 380 402 447 236

kW 252 276 292 325 172 230 251 266 296 156 267 293 310 345 182 278 304 322 358 18946.3 L11 kVA 360 393 419 456 231 328 358 381 415 210 382 417 444 483 250 396 432 461 502 254

kW 288 314 335 365 185 262 286 305 332 168 305 333 355 386 200 317 346 369 402 203

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

General characteristicsInsulation class H Excitation system SHUNT AREP / PMGWinding pitch 2/3 (winding 6) AVR type R250 D350Number of wires 12 Voltage regulation (*) ± 0.5% ± 0.25%Protection IP 23 Short-circuit current - 300% (3 IN) : 10sAltitude ≤ 1000 m Total Harmonic Distortion THD (**) no load < 2.5% - on load < 2.5%Overspeed 2250 min-1 Waveform: NEMA = TIF (**) < 50Air flow 0.48 m3/s (50Hz) / 0.58 m3/s (60Hz) Waveform: I.E.C. = THF (**) < 2%(*) Steady state. (**) Total harmonic distortion between phases, no-load or on-load (non-distorting).

kVA / kW - P.F. = 0.8Duty/T°C Continuous duty/40°C Continuous duty/40°C Stand-by/40°C Stand-by/27°CClass/T°K H/125°K F/105°K H/150°K H/163°K

kVA / kW - P.F. = 0.8Duty/T°C Continuous duty/40°C Continuous duty/40°C Stand-by/40°C Stand-by/27°CClass/T°K H/125°K F/105°K H/150°K H/163°K

Ratings 60 Hz - 1800 R.P.M.

Ratings 50 Hz - 1500 R.P.M.

Page 10: 1500 Series - dmgenerator.com

4 Electric Power Generation

93.1

93.493.893.6

91.3

95.395.495.4

94.9

92.1

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350

93.693.8

94.494.4

92.7

95.695.795.995.6

93.5

92.0

93.0

94.0

95.0

96.0

97.0

0 50 100 150 200 250 300 350 400 450

93.994.194.5

94.3

92.1

95.8

95.895.995.4

92.9

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350 400

92.893.1

93.793.7

91.7

95.295.395.595.1

92.6

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350

92.793.0

93.593.5

91.4

95.095.195.294.8

92.2

91.0

92.0

93.0

94.0

95.0

96.0

0 25 50 75 100 125 150 175 200 225 250 275

92.492.7

93.493.6

91.8

94.895.095.295.0

92.7

91.0

92.0

93.0

94.0

95.0

96.0

0 25 50 75 100 125 150 175 200 225 250 275 300

LSA 46.3 M7

LSA 46.3 M8LSA 46.3 S4

LSA 46.3 L10LSA 46.3 S5

LSA 46.3 L11

S4 S5 M7 M8 L10 L11Kcc 0.4 0.36 0.49 0.44 0.44 0.39Xd 339 369 316 344 316 355Xq 173 188 161 175 161 181

T’do 2452 2452 2543 2543 2686 2686X’d 13.8 15 12.4 13.5 11.7 13.2T’d 100 100 100 100 100 100X”d 11 12 9.9 10.8 9.4 10.5T”d 10 10 10 10 10 10X”q 14.6 15.9 13.1 14.3 12.6 14.1Xo 0.57 0.62 0.51 0.56 0.49 0.55X2 12.86 13.98 11.57 12.62 11.01 12.37Ta 15 15 15 15 15 15

io (A) 0.75 0.75 0.9 0.9 0.78 0.78ic (A) 2.75 2.97 2.86 3.08 2.64 2.92uc (V) 38.3 41.1 43 46.2 39.6 43.7

ms 500 500 500 500 500 500kVA 580 581 667 664 791 790kVA 638 639 740 741 873 877% 13.2 14 13.6 14.4 13.6 14.7% 11 11.6 11.2 11.9 11.2 12.1W 3658 3658 4443 4443 4767 4767W 13811 15593 15499 17516 16145 19014

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Efficiencies 400V - 50 Hz (..... P.F.: 1) (— P.F.: 0.8)

Reactances (%). Time constants (ms) - Class H / 400 V

Short-circuit ratioDirect-axis synchro. reactance unsaturatedQuadrature-axis synchro. reactance unsaturatedNo-load transient time constantDirect-axis transient reactance saturatedShort-circuit transient time constantDirect-axis subtransient reactance saturatedSubtransient time constantQuadrature-axis subtransient reactance saturatedZero sequence reactance unsaturatedNegative sequence reactance saturatedArmature time constant

Other class H / 400 V dataNo-load excitation current (SHUNT/AREP)On-load excitation current (SHUNT/AREP)On-load excitation voltage (SHUNT/AREP)Response time (∆U = 20% transient)Start (∆U = 20% cont. or 30% trans.) SHUNTStart (∆U = 20% cont. or 30% trans.) AREPTransient ∆U (on-load 4/4) SHUNT - P.F.: 0.8LAG

Transient ∆U (on-load 4/4) AREP - P.F.: 0.8LAG

No-load lossesHeat dissipation

Page 11: 1500 Series - dmgenerator.com

5Electric Power Generation

0%

5%

10%

15%

20%

25%

30%

0 100 200 300 400 500 600 700 800 900

0%

5%

10%

15%

20%

25%

0 50 100 150 200 250 300 350 400 450

0%

5%

10%

15%

20%

25%

0 50 100 150 200 250 300 350 400 450

0%

5%

10%

15%

20%

25%

30%

0 100 200 300 400 500 600 700 800

0%

5%

10%

15%

20%

25%

0 50 100 150 200 250 300 350 400 450

0%

5%

10%

15%

20%

25%

0 50 100 150 200 250 300 350 400 450

L10-L11

L10-L11 L10-L11

M7-M8

M7-M8 M7-M8

S4-S5

S4-S5 S4-S5

S4-S5 S4-S5M7-M8 M7-M8L10-L11 L10-L11

L10-L11

M7-M8

S4-S5

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Transient voltage variation 400V - 50 Hz

SHUNT system AREP/PMG system

1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.82) For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.

Load application Load application

kVA at 0.8 P.F. kVA at 0.8 P.F.

kVA at 0.8 P.F. kVA at 0.8 P.F.

Locked rotor kVA at 0.6 P.F. Locked rotor kVA at 0.6 P.F.

Load rejection Load rejection

Motor starting Motor starting

Volta

ge d

rop

Volta

ge d

rop

Volta

ge ri

se

Page 12: 1500 Series - dmgenerator.com

6 Electric Power Generation

S4 S5 M7 M8 L10 L11Kcc 0.38 0.35 0.47 0.43 0.42 0.37Xd 354 385 329 359 329 370Xq 180 196 168 183 168 188

T’do 2452 2452 2543 2543 2686 2686X’d 14.4 15.7 12.9 14.1 12.2 13.7T’d 100 100 100 100 100 100X”d 11.5 12.5 10.3 11.2 9.8 11T”d 10 10 10 10 10 10X”q 15.2 16.6 13.7 14.9 13.1 14.1Xo 0.6 0.65 0.53 0.58 0.51 0.57X2 13.42 14.58 12.06 13.14 11.46 12.87Ta 15 15 15 15 15 15

io (A) 0.75 0.75 0.9 0.9 0.78 0.78ic (A) 2.78 2.99 2.88 3.09 2.67 2.94uc (V) 39 41.9 43.7 46.8 40.3 44.4

ms 500 500 500 500 500 500kVA 699 695 799 800 947 945kVA 764 765 891 887 1051 1050% 13.6 14.4 14 14.9 13.9 15.1% 11.3 12 11.5 12.2 11.5 12.4W 5546 5546 6611 6611 7107 7107W 16841 18838 18880 21116 19764 23002

92.993.193.5

93.1

90.3

94.995.095.0

94.3

91.0

90.0

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350

92.793.0

93.493.3

90.8

94.8

95.095.094.5

91.6

90.0

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350

93.493.593.8

93.3

90.3

95.395.395.2

94.4

91.0

90.0

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350 400

93.1

93.493.793.5

90.9

95.295.395.3

94.6

91.6

90.0

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350 400 450

94.194.294.494.0

91.2

95.795.895.794.9

91.8

90.0

91.0

92.0

93.0

94.0

95.0

96.0

0 50 100 150 200 250 300 350 400 450 500

93.894.094.494.2

91.9

95.695.795.7

95.2

92.5

91.0

92.0

93.0

94.0

95.0

96.0

97.0

0 50 100 150 200 250 300 350 400 450 500 550

LSA 46.3 M7

LSA 46.3 M8LSA 46.3 S4

LSA 46.3 L10LSA 46.3 S5

LSA 46.3 L11

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Efficiencies 480V - 60 Hz (..... P.F.: 1) (— P.F.: 0.8)

Reactances (%). Time constants (ms) - Class H / 480 V

Short-circuit ratioDirect-axis synchro. reactance unsaturatedQuadrature-axis synchro. reactance unsaturatedNo-load transient time constantDirect-axis transient reactance saturatedShort-circuit transient time constantDirect-axis subtransient reactance saturatedSubtransient time constantQuadrature-axis subtransient reactance saturatedZero sequence reactance unsaturatedNegative sequence reactance saturatedArmature time constant

Other class H / 480 V dataNo-load excitation current (SHUNT/AREP)On-load excitation current (SHUNT/AREP)On-load excitation voltage (SHUNT/AREP)Response time (∆U = 20% transient)Start (∆U = 20% cont. or 30% trans.) SHUNTStart (∆U = 20% cont. or 30% trans.) AREPTransient ∆U (on-load 4/4) SHUNT - P.F.: 0.8LAG

Transient ∆U (on-load 4/4) AREP - P.F.: 0.8LAG

No-load lossesHeat dissipation

Page 13: 1500 Series - dmgenerator.com

7Electric Power Generation

0%

5%

10%

15%

20%

25%

0 100 200 300 400 500

0%

5%

10%

15%

20%

25%

0 100 200 300 400 500

0%

5%

10%

15%

20%

25%

0 100 200 300 400 500

0%

5%

10%

15%

20%

25%

0 100 200 300 400 500

0%

5%

10%

15%

20%

25%

30%

0 200 400 600 800 10000%

5%

10%

15%

20%

25%

30%

0 200 400 600 800 1000

L10-L11

M7-M8

S4-S5

L10-L11

M7-M8

S4-S5

L10-L11L10-L11

L10-L11

M7-M8M7-M8

S4-S5S4-S5

S4-S5 S4-S5M7-M8 M7-M8L10-L11

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.82) For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.

Transient voltage variation 480V - 60 Hz

SHUNT system AREP/PMG system

Load application Load application

kVA at 0.8 P.F. kVA at 0.8 P.F.

kVA at 0.8 P.F. kVA at 0.8 P.F.

Locked rotor kVA at 0.6 P.F. Locked rotor kVA at 0.6 P.F.

Load rejection Load rejection

Volta

ge d

rop

Volta

ge d

rop

Volta

ge ri

se

Motor starting Motor starting

Page 14: 1500 Series - dmgenerator.com

8 Electric Power Generation

10

100

1000

10000

1 10 100 1000 10000

10

100

1000

10000

1 10 100 1000 1000010

100

1000

10000

1 10 100 1000 10000

LSA 46.3 S4 - SHUNT

10

100

1000

10000

1 10 100 1000 10000

LSA 46.3 S5 - SHUNT

10

100

1000

10000

1 10 100 1000 1000010

100

1000

10000

1 10 100 1000 10000

LSA 46.3 M7 - SHUNT LSA 46.3 M7 - AREP

LSA 46.3 S4 - AREP

LSA 46.3 S5 - AREP

In

In

In

In

In

In

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

Influence due to connectionCurves shown are for star (Y) connection.For other connections, use the following multiplication factors: - Series delta : current value x 1.732 - Parallel star : current value x 2

Symmetrical

Asymmetrical

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Time (ms)

Time (ms)

Time (ms)

Page 15: 1500 Series - dmgenerator.com

9Electric Power Generation

10

100

1000

10000

1 10 100 1000 10000

LSA 46.3 M8 - SHUNT

10

100

1000

10000

1 10 100 1000 10000

LSA 46.3 M8 - AREP

10

100

1000

10000

1 10 100 1000 10000

LSA 46.3 L10 - SHUNT LSA 46.3 L10 - AREP

10

100

1000

10000

1 10 100 1000 1000010

100

1000

10000

1 10 100 1000 10000

LSA 46.3 L11 - SHUNT LSA 46.3 L11 - AREP

10

100

1000

10000

1 10 100 1000 100001 10 100 1000 10000

In

In

In

In

In

In

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

Influence due to short-circuitCurves are based on a three-phaseshort-circuit.For other types of short-circuit, use the following multiplication factors.

3-phase 2-phase L/L 1-phase L/NInstantaneous (max.) 1 0.87 1.3Continuous 1 1.5 2.2Maximum duration (AREP/PMG) 10 sec. 5 sec. 2 sec.

Symmetrical

Asymmetrical

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Cur

rent

(A)

Time (ms)

Time (ms)

Time (ms)

Page 16: 1500 Series - dmgenerator.com

10 Electric Power Generation

Ø 7

5

Ø 1

00

Ø 1

10

Ø 1

14.8

Ø 1

15

Ø 1

20

Ø 1

15

Ø 1

10

Ø 8

75

Lr

Xr

Xr Lr M J Xr Lr M J LSA 46.3 S4 431 928 277 2.93 416 928 277 3.09LSA 46.3 S5 431 928 277 2.93 416 928 277 3.09LSA 46.3 M7 459 973 307 3.23 444 973 307 3.39LSA 46.3 M8 459 973 307 3.32 444 973 307 3.39LSA 46.3 L10 507 1068 362 3.96 493 1068 362 4.12LSA 46.3 L11 507 1068 362 3.96 493 1068 362 4.12

Type L L (SAE 11 ½) LB Xg C 11 ½ 14 18LSA 46.3 S4 935 944 892 423 429 674 XLSA 46.3 S5 935 944 892 423 429 682 XLSA 46.3 M7 980 989 937 445 429 754 X XLSA 46.3 M8 980 989 937 445 429 754 XLSA 46.3 L10* 1075 1084 1032 493 525 888 X XLSA 46.3 L11* 1075 1084 1032 493 525 888

S.A.E. P N M XBG S β° S.A.E. BX U X Y AH3 600**/641 409.575 428.625 12 11 15° 11 ½ 352.42 333.38 8 11 39.62 600**/641 447.675 466.725 12 11 15° 14 466.72 438.15 8 14 25.41 600**/641 511.175 530.225 12 12 15° 18*** 571.5 542.92 6 17 15.7½ 713 584.2 619.125 12 14 15° *** Option0 713 647.7 679.45 16 14 11° 15’

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Single bearing dimensions

NOTE : Dimensions are for information only and may be subject to modifications. Contractual 2D drawings can be downloaded from the Leroy-Somer site, 3D drawing files are available upon request.The torsional analysis of the transmission is imperative. All values are available upon request.

Dimensions (mm) and weight

Flange (mm) Flex plate (mm)

Weight (kg)

Flange S.A.E 2Flange S.A.E 3

CouplingFlex plate

Torsional analysis data

Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)Flex plate S.A.E. 11 1/2 S.A.E. 14Type

Flange S.A.E 1/2Flange S.A.E 0

Flange S.A.E 1

* Shaft height = 355 mm optional - ** Specific dimension LSA 46.3 S4

Ø 2

35

PMG optional

L LB

Xg

AIR OUTLET

Ø B

XØ P

Ø N

AH568

457 21

527

485.

5

280

765.

5

12

S DIA. Qty XBG as shown on Ø M

Access to rotating diodes

0 - 0.1

27

- 0.0

50- 0

.100

6198

6

506

AIR INLET

C

4094.3

170

68

Access to regulator

Access to terminals

80

Ø 206

0 - 2

Y DIA, Qty X Eq. Sp. on Ø U.

Standard cableoutput

Optional cableoutputß

Page 17: 1500 Series - dmgenerator.com

11Electric Power Generation

Type L LB C BB B P XgLSA 46.3 S4 997 892 389 368 318 600 427 674LSA 46.3 S5 997 892 389 368 318 640 427 682LSA 46.3 M7 1042 937 389 368 318 640 449 754LSA 46.3 M8 1042 937 389 368 318 640 449 754LSA 46.3 L10 1137 1032 485 424 374 640 496 888LSA 46.3 L11 1137 1032 485 424 374 640 496 888

Xr Lr M J LSA 46.3 S4 430 990 250 2.76LSA 46.3 S5 430 990 250 2.76LSA 46.3 M7 456 1035 280 3.09LSA 46.3 M8 456 1035 280 3.09LSA 46.3 L10 503 1130 336 3.79LSA 46.3 L11 503 1130 336 3.79

Ø 1

20

Ø 1

10

Ø 1

15

Ø 1

15

Ø 1

10Ø

88

Ø 7

5

Ø 7

5

Ø 8

92

Ø 1

05.8

Lr

Xr

LSA 46.3 - 230 to 365 kVA - 50 Hz / 288 to 456 kVA - 60 Hz

Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)Type

Two bearing dimensions

Torsional analysis data

Dimensions (mm) and weightWeight (kg)

NOTE : Dimensions are for information only and may be subject to modifications. Contractual 2D drawings can be downloaded from the Leroy-Somer site, 3D drawing files are available upon request.The torsional analysis of the transmission is imperative. All values are available upon request.

Ø 2

35

PMG optional

L LB

Xg

AIR OUTLET

Ø 7

5 m

6

Ø P

Ø 5

11.1

75568

457 527

485.

5

280

765.

5

17

M10 DIA. Qty 12as shown onØ 530.225

Ø 21 x 6Access to rotating diodes

0 - 0.1

27

198

105

6

506

AIR INLET

C

4094.3

B 25

BB182

Access to regulator

Access to terminals

80

0 - 2

Cable output

Cable output15°

20

79.5 12

Page 18: 1500 Series - dmgenerator.com

www.leroy-somer.com/epgwww.leroy-somer.com/epg

- 2019.09 / g

© Nidec 2018. The information contained in this brochure is for guidance only and does not form part of any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development and reserve the right to change the specification of their products without notice.

Moteurs Leroy-Somer SAS. Siège : Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9, France. Capital social : 65 800 512 €, RCS Angoulême 338 567 258.

5273 en

Linkedin.com/company/leroy-somerTwitter.com/Leroy_Somer_enFacebook.com/LeroySomer.Nidec.enYouTube.com/LeroySomerOfficiel

Page 19: 1500 Series - dmgenerator.com

DSE7310/20AUTO START & AUTO MAINS FAILURE CONTROL MODULES

DSEGenset

®

FEATURES

ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn

HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS

DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.

8 4

PC

4

USBPORT

DC OUTPUTS ANALOGUESENDERS

EMERGENCY STOP

DC POWER SUPPLY 8-35V

DSE2130DSE2157DSE2548DSE2510/20

232 485

MODBUSMODEM

RS232 ANDRS485

+

1ph2ph3phN

1ph2ph3phEN

1ph2ph3phN

VOLTS

1 1

+

DEUTZISUZUPERKINSCATERPILLARMTUVOLVOCUMMINSSCANIA

D +W/L

GENERATOR SENSING

VOLTSCURRENT

ELECTRONICENGINES &MAGNETIC PICK-UP

FUEL & CRANKOUTPUTS(Flexible with CAN)

CHARGEALTERNATOR

N/O VOLTFREE OUTPUT

N/C VOLT FREEOUTPUT

MAINS (UTILITY) SENSINGDSE7320 ONLY

ISSUE 6

COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS

7

OTHER

DSE7310/20

CONFIGURABLEINPUTS

DSENET®

EXPANSION

The DSE7310 is an Auto StartControl Module and the DSE7320 isan Auto Mains (Utility) FailureControl Module suitable for a widevariety of single, diesel or gas, gen-set applications.

Monitoring an extensive number ofengine parameters, the modules willdisplay warnings, shutdown andengine status information on theback-lit LCD screen, illuminatedLEDs, remote PC and via SMS textalerts (with external modem).

The DSE7320 will also monitor themains (utility) supply. The modulesinclude USB, RS232 and RS485ports as well as dedicated DSENet®terminals for system expansion.

Both modules are compatible withelectronic (CAN) and non-electronic(magnetic pick-up/alternatorsensing) engines and offer anextensive number of flexible inputs,outputs and extensive engineprotections so the system can beeasily adapted to meet the mostdemanding industry requirements.

The extensive list of featuresincludes enhanced event andperformance monitoring, remotecommunications, PLC functionalityand dual mutual standby (DSE7310only) to reduce engine wear.

The modules can be easilyconfigured using the DSEConfiguration Suite PC software.Selected front panel editing is alsoavailable.

Page 20: 1500 Series - dmgenerator.com

DSE7310/20AUTO START & AUTO MAINS FAILURE CONTROL MODULES

®

DSEGenset

FEATURES

SPECIFICATION

DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous

CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE0 V to 35 V

MAINS (UTILITY) DSE7320 ONLYVOLTAGE RANGE15 V - 333 V AC (L-N)

FREQUENCY RANGE3.5 Hz to 75 Hz

OUTPUTSOUTPUT A (FUEL)15 A DC at supply voltage

OUTPUT B (START)15 A DC at supply voltage

OUTPUTS C & D8 A 250 V (Volt free)

AUXILIARY OUTPUTS E,F,G,H2 A DC at supply voltage

GENERATORVOLTAGE RANGE 15 V - 333 V AC (L-N)

FREQUENCY RANGE3.5 Hz to 75 Hz

MAGNETIC PICK UPVOLTAGE RANGE+/- 0.5 V to 70 V

FREQUENCY RANGE10,000 Hz (max)

DIMENSIONSOVERALL240 mm x 181 mm x 42 mm 9.4” x 7.1” x 1.6”

PANEL CUT-OUT220 mm x 160 mm8.7” x 6.3”

MAXIMUM PANEL THICKNESS8 mm0.3”

DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

RELATED MATERIALSTITLE PART NO’SDSE7310 Installation Instructions 053-028DSE7320 Installation Instructions 053-029DSE7200/7300 Quick Start Guide 057-101DSE7200/7300 Operator Manual 057-074DSE7200/7300 Configuration Suite PC Manual 057-077

055-051/10/11 (11) USRegistered in England & Wales No.01319649VAT No.316923457

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.

DSE7310

DSE7320

KEY FEATURES• 4-Line back-lit LCD text display• Five key menu navigation• Front panel editing with PIN

protection• Customisable status screens• Power save mode• Support for up to three remote

display units• 9 configurable inputs• 8 configurable outputs• Flexible sender inputs• Configurable timers and alarms• 3 configurable maintenance

alarms• Multiple date and time scheduler• Configurable event log (250)• Tier 4 CAN engine support• Integral PLC editor• Easy access diagnostic page• CAN and Magnetic Pick-up/Alt.

sensing• Fuel usage monitor and low fuel

alarms• Charge alternator failure alarm• Manual speed control (on

compatible CAN engines)• Manual fuel pump control • Engine exerciser• “Protections disabled” feature• kW & kV Ar protection

• Reverse power (kW & kV Ar)protection

• LED and LCD alarm indication• Power monitoring (kW h, kV Ar, kV

A h, kV Ar h)• Load switching (load shedding and

dummy load outputs)• Automatic load transfer (DSE7320)• Unbalanced load protection• Independent Earth Fault trip• True dual mutual standby with load

balancing timer (DSE7310 only)• USB connectivity• Backed up real time clock• Fully configurable via DSE

Configuration Suite PC software• Configurable display languages• Remote SCADA monitoring via

DSE Configuration Suite PCsoftware

• User selectable RS232 and RS485communications

• Configurable Gencomm pages• Advanced SMS messaging

(additional external modemrequired)

• Start & stop capability via SMSmessaging

• Additional display screens to helpwith modem diagnostics

• Idle control for starting & stopping.• DSENet® expansion compatible

KEY BENEFITS• 132 x 64 pixel ratio display for

clarity• Real-time clock provides accurate

event logging• Multiple date and time scheduler• Set maintenance periods can be

configured to maintain optimumengine performance

• Ethernet communications (viaDSE860/865 modules), providesadvanced remote monitoring atlow cost

• Modules can be integrated intobuilding management systems(BMS)

• Increased input and outputexpansion capability via DSENet®

• Licence-free PC software• IP65 rating (with supplied gasket)

offers increased resistance towater ingress

• PLC editor allows userconfigurable functions to meetspecific application requirements