Quick Reference 1305 Adjustable Frequency AC Drive Firmware Revision Number 6.01 and Later This publication is designed as a reference tool. The 1305 User Manual, publication 1305-5.2, must be consulted for more detailed information about parameters, faults and hazards of personal injury.

Upload: ledieu

Post on 14-Jul-2019

228 views

Category:

Documents


0 download

TRANSCRIPT

  • Quick Reference

    1305 Adjustable Frequency AC DriveFirmware Revision Number 6.01 and Later

    This publication is designed as a reference tool. The 1305 User Manual, publication 1305-5.2, must be consulted for more detailed information about parameters, faults and hazards of personal injury.

  • 1305 Adjustable Frequency AC Drive

    Power Terminal Block TB1 Designations

    TB1 Terminal Designations

    Input Fusing

    Maximum Recommended AC Input Line Fuse UL Class J, T, CC, or BS88 (or equivalent)

    GRD

    To Motor

    RequiredInput Fusing

    L1R

    L2S

    L3T

    +DC BRK(DC)

    T1U

    T2V

    T3W

    AC Input Line

    To Motor

    Dynamic BrakeOption

    Required BranchCircuit Disconnect

    GRD

    Connection for Dynamic Brake Resistors for all models except the 200-230 Volt, 0.37to 0.75 kW (0.5 to 1 HP) drive. Important: The [DB Enable]parameter must be enabled for proper operation.

    For single phase applications, the AC input line can be connected to any two of thethree input terminals R, S, T (L1, L2, L3).

    1305 drives provide Class 10 motor overload protection according to NEC Article 430.They do not provide speed sensitive overload protection, thermal memory retention and motor over-temperature sensing according to NEC Article 430.126 (A) (2). If such protection is needed in the end-use product, it must be provided by additional means.

    Important: This drive is not intended for use with single-phase motors. Ground from drive to motor frame must be an independent continuous insulated wire

    run.

    Terminals DescriptionGRD Earth ground

    R, S, T (L1, L2, L3) AC input line terminals

    +DC, BRK (or -DC) Dynamic brake option see the instructions included with option

    U, V, W (T1, T2, T3) Motor connections

    ATTENTION: The drive does not provide branch circuit protection. Specifications for the recommended fuse size and type which provide branch circuit protection against short circuits are provided below. Branch circuit breakers or disconnect switches cannot provide this level of protection for drive components.

    Three-Phase Rating kW (HP)

    Single-Phase Rating kW (HP)

    Fuse 200230V Rating

    Fuse 380460V Rating

    0.37 (0.5) 0.19 (0.25) 6 3 (1)

    (1) Must be dual element time delay, Bussmann LPJ or equivalent.

    0.55 (0.75) 0.37 (0.5) 6 3 (1)

    0.75 (1) 0.55 (0.75) 10 6 (2)

    (2) If fuse blowing is a problem, use dual element type fuses.

    1.5 (2) 0.75 (1) 15 10 (2)

    2.2 (3) 1.5 (2) 25 15 (2)

    4.0 (5) 20 (2)

    2 Rockwell Automation Publication 1305-5.2.2 - September 2013

  • 1305 Adjustable Frequency AC Drive

    Terminal Block TB2 Designations

    See footnotes below.

    TB2 Terminal Descriptions

    Required to operate drive. STOP also used to clear a fault. Use HIM Stop button to clear faults. Contact Closure Input. Internal 5V supply. Do not apply external voltage. When the ENABLE signal is lost, the drive output immediately shuts off and the motor will coast to a stop. A Start command will override any Jog command. See 1305 User Manual, publication 1305-5.2, for input configurations based on the setting of parameter 21 - [Input Mode].

    Remote Pot 1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    SourceWiper or 0-10V DC Input

    Common

    4-20mA Input

    0-10V Output

    0-10V

    Common

    Stop

    Start

    Output #1

    24VDC Source(User Supplied)

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    Enable

    Common

    Reverse

    Jog

    Common

    SW2

    SW3

    SW1

    (Sink)Output #2

    User

    Sid

    e

    Remote Pot

    Run Forward

    Run Reverse

    Jumper

    Jumper

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    SourceWiper or 0-10V DC Input

    Common

    4-20mA Input

    0-10V Output

    0-10V

    Common

    Stop

    User

    Sid

    e

    Start

    Output #1

    24VDC Source(User Supplied)

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    Enable

    Common

    Reverse

    Jog

    Common

    SW2

    SW3

    SW1

    (Sink)Output #2

    General Three Wire General Run Fwd/Rev

    Terminals Signal Specification1, 2, 3 External Speed Potentiometer 10 k Potentiometer, 2 watts

    2, 3 010V Analog Input Drive Input Impedance = 100 k

    4, 3 420 mA Analog Input Drive Input Impedance = 250

    5, 3 010V Analog Output Meter Impedance 4 k

    6, 7 Start Contact Closure Input

    8, 7 Stop Contact Closure Input

    9, 10 Programmable Output 1 Resistive Rating = 115V AC/30V DC, 5AInductive Rating = 115V AC/30V DC, 2A

    11, 12 Drive Enable Contact Closure Input

    13, 12 Reverse Contact Closure Input

    14, 15 Jog Contact Closure Input

    16, 15 SW1 Contact Closure Input

    17, 15 SW2 Contact Closure Input

    18, 15 SW3 Contact Closure Input

    19, 20 Programmable Output 2 24V DC 20%, 50 mA max (sink)

    Rockwell Automation Publication 1305-5.2.2 - September 2013 3

  • 1305 Adjustable Frequency AC Drive

    Faults

    Human Interface Module (HIM)

    Name DescriptionDiag C Lim Fault (F36) The drive output current has exceeded the software [Current Limit] and the [Cur Lim Trip En] parameter was enabled.Drive -> HIM The checksum read from the HIMs EEPROM does not match the checksum calculated from the EEPROM data.Drive Reset Fault (F22) Occurs on power-up. Caused by having the START Input (or RUN Input) closed, with the STOP Input open and [Run On Power Up] = DISABLED.EEprom Fault (F32) EEPROM has invalid data or cannot be programmed to valid data.Hz Err Fault (F29) This fault indicates that there is not a valid operating frequency. It can be caused by any of the following:

    1. [Maximum Frequency] is less than [Minimum Freq].2. Skip frequencies and skip bandwidth eliminate all operating frequencies.3. 4-20mA input signal speed reference has been lost or is out of range and [4-20mA Loss Sel] is set for Stop-Fault.

    Hz Sel Fault (F30) An adapter that is not connected has been chosen as the active frequency source.HIM -> Drive Error 1 - The checksum read from the HIMs EEPROM does not match the checksum calculated from the EEPROM data.

    Error 2 - The number of parameters in saved profile does not equal master.Error 3 - Download was attempted to a different type drive (that is, 1336 ->1305).Error 4 - Saved data for parameter not correct for new drive.Error 5 - Drive is running while attempting download.

    IPM Current Fault (F44) The internal power module overcurrent limit has been exceeded.IPM Overtemp Fault (F45) The internal power module thermal limit has been exceeded.Max Retries Fault (F33) Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Reset/Run Tries].Motor Mode Flt (F24) Internal error.Motor Stall Fault (F6) The motor is stalled.Neg Slope Fault (F35) Drive software detected a portion of the volts/Hz curve with a negative slope.Network Error Error 06 SCANport Error; Error 79 Communications ErrorOp Error Fault (F11) [Motor Type] is set to Sync PM and [Stop Mode] is set to DC Brake.Open Pot Fault (F9) An external pot is connected and the ground lead of the pot is disconnected creating a potential drive overspeed hazard.Overcurrent Fault (F12) Overcurrent is detected in overcurrent hardware trip circuit.Overload fault (F7) Internal electronic overload trip.Overspeed Fault (F25) Internal error.Overtemp Fault (F8) Temperature sensor detects excessive heat.Overvolt Fault (F5) DC bus voltage exceeded maximum value.Phase U Fault (F38) A phase to ground fault has been detected between the drive and motor in this phase.Phase V Fault (F39) A phase to ground fault has been detected between the drive and motor in this phase.Phase W Fault (F40) A phase to ground fault has been detected between the drive and motor in this phase.Pin ID Error Communication Hardware problem.Power Loss Fault (F3) DC bus voltage remained below 85% of nominal for longer than 0.500 sec. [Line Loss Fault] parameter is programmed to F03 Enable.Power Mode Fault (F26) Internal error.Power Test Fault (F46) Fault detected during initial start-up sequence.Reprogram Fault (F48) Occurs when drive parameters are reset to defaults.Run Boost Fault (F34) An attempt has been made to set [Run Boost] to a value greater than [Start Boost].Serial Fault (F10) An active local bus adapter is disconnected while it possesses control of a local bus function.Undervolt Fault (F4) DC Bus voltage fell below the minimum value. [Line Loss Fault] is programmed to U Volt Run.UV Short Fault (F41) Excessive current has been detected between these two drive output terminals.UW Short Fault (F42) Excessive current has been detected between these two drive output terminals.VW Short Fault (F43) Excessive current has been detected between these two drive output terminals.

    Digital SpeedControl andIndicator(also availablewith AnalogSpeed Pot.)

    LCD Display

    DisplayPanel

    ControlPanel

    4 Rockwell Automation Publication 1305-5.2.2 - September 2013

  • 1305 Adjustable Frequency AC Drive

    HIM Display Panel Descriptions

    HIM Control Panel Descriptions

    Item Name DescriptionEscape When pressed, the ESCape key will cause the programming system to go back one

    level in the menu structure.

    Select Pressing the SELect key alternately moves the cursor to the next active area. A flashing first character indicates which line is active.

    Increment/Decrement

    These keys are used to increment and decrement a value or scroll through different groups or parameters.

    Enter When pressed, a group or parameter will be selected or a parameter value will be entered into memory. After a parameter has been entered into memory, the top line of the display will automatically become active, allowing another parameter (or group) to be chosen.

    Item Name DescriptionStart The Start key will initiate drive operation if no other control devices are sending a Stop

    command. This key can be disabled by the [Logic Mask] or [Start Mask].

    Stop If the drive is running, pressing the Stop key will cause the drive to stop, using the selected stop mode. See [Stop Select] in the User Manual.If the drive has stopped due to a fault, pressing this key will clear the fault and reset the drive. See [Flt Clear Mode], [Logic Mask], and [Fault Mask].

    Jog When pressed, jog will be initiated at the frequency set by [Jog Frequency], if no other control devices are sending a Stop command. Releasing the key will cause the drive to stop, using the selected stop mode. See [Stop Select], [Logic Mask], and [Jog Mask].Important: If the drive is running prior to issuing a jog command, the jog command will be ignored. A start command from another source will override the jog command.

    Change Direction

    Pressing this key will cause the drive to ramp down to zero Hertz and then ramp up to set speed in the opposite direction. The appropriate Direction LED will illuminate to indicate the direction of motor rotation. See [Logic Mask] and [Direction Mask]. Note that the factory default for control of the reverse function is the reverse input at TB2. To enable the HIM control of the reverse function, change Bit 0 of the [Direction Mask] parameter to 0 to disable the reverse function at TB2.

    Direction LEDs (Indicators)

    These LEDs illuminate to indicate the direction of motor rotation.

    Increment/Decrement Arrows(only available with digital speed control)

    Pressing these keys will increase or decrease the HIM frequency command. An indication of this command will be shown on the visual Speed Indicator LEDs. The drive will run at this command if the HIM is the selected frequency reference. See [Freq Select 1/2].Pressing both keys simultaneously stores the current HIM frequency command in HIM memory. The Speed Indicator LEDs will flash momentarily to indicate a successful save (if speed is above 20 percent). Cycling power or connecting the HIM to the drive will set the frequency command to the value stored in HIM memory.

    Analog Speed Potentiometer

    If the Analog Speed Potentiometer option has been ordered, the Increment/Decrement keys and Speed Indicator will be replaced by the pot.

    Rotating Forward

    Rotating Reverse

    Changing Direction, Decelerating Reverse, will begin to Accelerate Forward.

    Changing Direction, Decelerating Forward, will begin to Accelerate Reverse.

    OFF Steady ON

    Steady ON OFF

    Flashing Steady ON

    Steady ON Flashing

    Rockwell Automation Publication 1305-5.2.2 - September 2013 5

  • 1305 Adjustable Frequency AC Drive

    1305 Series C Parameter List

    Speed Indicator LEDs(only available with digital speed control)

    Illuminates in steps to give an approximate visual indication of the commanded speed.If the Analog Speed Potentiometer option has been ordered, the Increment/Decrement keys and Speed Indicator LEDs will be replaced by the pot.

    Item Name Description

    Group/Parameter No. Units

    Min. Value

    Max. Value

    Default Value

    Group/Parameter No. Units

    Min. Value

    Max. Value

    Default Value

    Metering Analog Invert 84 Text (1) DisabledOutput Current 54 0.01 Amps 0.00 2x Drive Output Current 4-20 mA Loss Sel 81 Text (1) Stop/Fault

    Output Voltage 1 1 Volt 0 Maximum Voltage Stop Select 10 Text (1) Ramp

    Output Power 23 0.01 kW 0.00 2x Rtd. Dr. Output Power DC Hold Time 12 0.1 Sec 0.0 150.0 0.0

    DC Bus Voltage 53 1 Volt 0 410230V Drive DC Hold Volts 13 1 Volt 0 25% of Max DRV 0

    815460V Drive DB Enable 11 Text (1) Disabled

    Output Freq. 66 0.01 Hz 0.00 Maximum Frequency Motor Type 41 Text (1) Induc/Reluc

    Freq. Command 65 0.01 Hz 0.00 +400.00 0.00 Compensation 52 Text (1) Comp

    MOP Hz 42 0.01 Hz 0.00 400.00 Frequency SetDrive Temp 70 1 deg. C 0 100 Freq Select 1 5 Text (1) Adapter 1

    Last Fault 4 Numeric 0 Max. Fault No. Freq Select 2 6 Text (1) Remote Pot

    % Output Power 3 1% 0 200% Drive Rated Power Jog Frequency 24 0.1 Hz 0.0 400.0 10.0

    % Output Curr. 2 1% 0 200% Rtd. Dr. Out. Curr. Prst/2nd Accel 26 Text (1) Preset

    Setup Upper Presets 72 Text (1) DisabledInput Mode 21 Text (1) Three Wire Accel Time 2 30 0.1 sec 0.0 3600.0 5.0

    Freq Select 1 5 Text (1) Adapter 1 Decel Time 2 31 0.1 sec 0.0 3600.0 5.0

    Accel Time 1 7 0.1 sec 0.0 3600.0 10.0 Preset Freq 1 27 0.1 Hz 0.0 400.0 10.0

    Decel Time 1 8 0.1 sec 0.0 3600.0 10.0 Preset Freq 2 28 0.1 Hz 0.0 400.0 20.0

    Base Frequency 17 1 Hz 40 400 60 Preset Freq 3 29 0.1 Hz 0.0 400.0 30.0

    Base Voltage 18 1 Volt 25% of DRV 100% of Max DRV Max DRV Preset Freq 4 73 0.1 Hz 0.0 400.0 40.0

    Maximum Voltage 20 1 Volt 25% of DRV 110% of Max DRV Max DRV Preset Freq 5 74 0.1 Hz 0.0 400.0 50.0

    Minimum Freq 16 1 Hz 0 120 0 Preset Freq 6 75 0.1 Hz 0.0 400.0 60.0

    Maximum Freq 19 1 Hz 40 400 60 Preset Freq 7 76 0.1 Hz 0.0 400.0 0.0

    Stop Select 10 Text (1) Ramp Skip Freq 1 32 1 Hz 0 400 400

    Current Limit 36 1% 20% of DRC 150% of DRC 150% of DRC Skip Freq 2 33 1 Hz 0 400 400

    Overload Mode 37 Text (1) No Derating Skip Freq 3 34 1 Hz 0 400 400

    Overload Current 38 0.1 Amps 20% of DRC 115% of DRC 115% of DRC Skip Freq Band 35 1 Hz 0 15 0

    Sec Curr Limit 141 1% 0% of DRC 150% of DRC 0% of DRC MOP Increment 22 1 Hz/Sec 0.00 255.00 1.00

    Adaptive I Lmt 149 Text (1) Enabled Analog Filter 144 Text (1) 100%

    Advanced Setup Feature SelectMinimum Freq 16 1 Hz 0 120 0 Run On Power Up 14 Text (1) Disabled

    Maximum Freq 19 1 Hz 40 400 60 Reset/Run Tries 85 Numeric 0 9 0

    Base Frequency 17 1 Hz 40 400 60 Reset/Run Time 15 0.1 Sec 0.5 30.0 1.0

    Base Voltage 18 1 Volt 25% of DRV 100% of Max DRV Max DRV S Curve Enable 57 Text (1) Disabled

    Break Frequency 49 1Hz 0 120 30 S Curve Time 56 0.1 Sec 0.0 300.0 0.0

    Break Voltage 50 1 Volt 0 50% of Max DRV Dr. Size Dep. Language 47 Text (1) Approp. Lang.

    Maximum Voltage 20 1 Volt 25% of DRV 110% of Max DRV Max DRV Cable Length 143 Text (1) Short

    DC Boost Select 9 Text (1) Break Point Rated Slip 146 0.1 Hz 0.0 5.0 2.0

    Start Boost 48 1 Volt 0 25% of Max DRV Dr. Size Dep. Slip Comp Adder 148 0.01 Hz 0.00 5.00

    Run Boost 83 1 Volt 0 25% of Max DRV 0 IR Comp % 147 1% 0% 150% Drv. Depend.

    PWM Frequency 45 0.1 kHz 2.0 8.0 4.0 (Table continued on next page.)

    6 Rockwell Automation Publication 1305-5.2.2 - September 2013

  • 1305 Adjustable Frequency AC Drive

    Output Config Local Mask 93 Byte 01111111Output 1 Config 90 Text (1) Faulted OwnersOutput 2 Config 91 Text (1) Running Stop Owner 102 Byte

    Analog Out Sel 25 Text (1) Frequency Direction Owner 103 Byte

    Above Freq Val 77 1 Hz 0 400 0 Start Owner 104 Byte

    Above Curr Val 142 1% 0% of DRC 150% of DRC 0% of DRC Jog Owner 105 Byte

    Faults Reference Owner 106 Byte Fault Buffer 0 86 Numeric Accel Owner 107 Byte

    Fault Buffer 1 87 Numeric Decel Owner 108 Byte

    Fault Buffer 2 88 Numeric Fault Owner 109 Byte

    Fault Buffer 3 89 Numeric MOP Owner 110 Byte

    Clear Fault 51 Text (1) Ready Local Owner 137 Byte

    Cur Lim Trip En 82 Text (1) Default Run Adapter I/OLine Loss Fault 40 Text (1) F03 Enable Data In A1 111 Numeric 0 149 0

    Flt Clear Mode 39 Text (1) Enabled Data In A2 112 Numeric 0 149 0

    Diagnostics Data In B1 113 Numeric 0 149 0Drive Command 58 Byte Data In B2 114 Numeric 0 149 0

    Drive Status 59 Text (1) Data In C1 115 Numeric 0 149 0

    Drive Alarm 60 Byte Data In C2 116 Numeric 0 149 0

    Input Status 55 Byte Data In D1 117 Numeric 0 149 0

    Freq Source 62 Text (1) Data In D2 118 Numeric 0 149 0

    Freq Command 65 0.01 Hz 0.00 400.00 0.00 Data Out A1 119 Numeric 1 149 1

    Drive Direction 69 Text (1) Forward Data Out A2 120 Numeric 1 149 1

    Motor Mode 43 Text (1) Data Out B1 121 Numeric 1 149 1

    Power Mode 44 Text (1) Data Out B2 122 Numeric 1 149 1

    Drive Type 61 Numeric Data Out C1 123 Numeric 1 149 1

    Firmware Ver. 71 Numeric Data Out C2 124 Numeric 1 149 1

    Output Pulses 67 1 Cycle 0 65535 Data Out D1 125 Numeric 1 149 1

    Drive Temp 70 1 deg. C 0 100 Data Out D2 126 Numeric 1 149 1

    Set Defaults 64 Text (1) Ready Process DIsplayMasks Process Par 127 Numeric 1 149 1Logic Mask 92 Byte 01111111 Process Scale 128 Numeric -327.68 +327.67 +1.00

    Direction Mask 94 Byte 01111111 Process Text 1 129 ASCII text ?

    Start Mask 95 Byte 01111111 Process Text 2 130 ASCII text ?

    Jog Mask 96 Byte 01111111 Process Text 3 131 ASCII text ?

    Reference Mask 97 Byte 01111111 Process Text 4 132 ASCII text ?

    Accel Mask 98 Byte 01111111 Process Text 5 133 ASCII text ?

    Decel Mask 99 Byte 01111111 Process Text 6 134 ASCII text ?

    Fault Mask 100 Byte 01111111 Process Text 7 135 ASCII text ?

    MOP Mask 101 Byte 01111111 Process Text 8 136 ASCII text ?

    (1) See the 1305-5.2 User Manual, Appendix B, Table B.5.

    Group/Parameter No. Units

    Min. Value

    Max. Value

    Default Value

    Group/Parameter No. Units

    Min. Value

    Max. Value

    Default Value

    Rockwell Automation Publication 1305-5.2.2 - September 2013 7

  • Programming System

    Access to the Program and EEPROM modes, and the Control Logic and Clear Fault Queue, are disabled if the password is Logged Out. Series A HIM Firmware Revision 3.00 and later or Series B HIM Firmware Revision 1.01 and later only. Series B HIM Firmware Revision 1.01 and later only.

    Power-Up &Status Display

    Login,LogoutModify

    Control Logic ,Fault Queue

    "Choose Mode"

    Process Display

    or or or or

    Parameter Groups(See Parameter List)

    OPERATOR LEVEL

    MODE LEVEL

    GROUP LEVEL

    PARAMETER LEVELParameters

    (See Parameter List)

    Display(Read Only)

    Program (Read/Write)

    PasswordEEPROM Search (Read Only)

    ControlStatus

    Process

    Reset DefaultsRecall ValuesSave Values

    Upload ParametersDownload Parameters

    *PN-219714*PN-219714

    Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Publication 1305-5.2.2 - September 2013Supersedes Publication 1305.2.2 - July 1996 Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: [email protected]: www.ab.com/support/abdrives

    1305 Adjustable Frequency AC Drive Quick ReferencePower Terminal Block TB1 DesignationsTB1 Terminal DesignationsInput FusingTerminal Block TB2 DesignationsTB2 Terminal DescriptionsFaultsHuman Interface Module (HIM)HIM Display Panel DescriptionsHIM Control Panel Descriptions1305 Series C Parameter ListProgramming SystemBack Page / Publication 1305-5.2.2 September 2013Introduction_Category TypesThis tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.Publication Type and Print CategoryPublication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release OptionADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / InternalAPA3D2Application Solution or Customer Success Story5100Presale / ExternalARNANAArticle/Editorial/BylineNANAPresale / Internal(press releases should not be checked into DocMan or printed)ATB3, B4D5Application techniques5100Presale / ExternalBRA2 Primary, A1NABrochures5100Presale / ExternalCAC2 Primary, C1NACatalogue150Presale / ExternalCGNANACatalogue Guide150Presale / ExternalCLNANACollection550Presale / ExternalCOA5, A6, A9D5Company Confidential InformationNANANA / ConfidentialCPE-onlyE-only, D5Competitive Information550NA / ConfidentialDCE-onlyE-onlyDiscount SchedulesNANAPresale / InternalDIA1, A3NADirect Mail5100Presale / InternalDMNANAProduct Demo550Presale / InternalDSB3D5Dimensions Sheet15Post / ExternalDUB3D5Document Update15Post / ExternalGRB2D6Getting Results15Post / ExternalINB3 Primary, B2D5, D6Installation instructions15Post / ExternalLMNANALaunch Materials550Presale / InternalPCB3D5Packaging ContentsPLE-only primary, B3E-onlyPrice List550Presale / InternalPMB2D6Programming Manual15Post / ExternalPPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / ExternalQRB2 primary, B3, B5D5, D6Quick Reference15Post / ExternalQSB2 primary, B3, B5D5, D6Quick Start15Post / ExternalRMB2D5, D6Reference Manual15Post / ExternalRNB3D5Release Notes15Post / ExternalSGB1 Primary, B4D5, D6Selection Guide Colour550Presale / ExternalSGB2D5, D6Selection Guide B/W550Presale / ExternalSPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / InternalSRB2, B3D5, D6Specification Rating Sheet5100Presale / ExternalTDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / ExternalTGB2, B3D6Troubleshooting Guide15Post / ExternalUMB2 Primary, B4D6User Manual B/W15Post / ExternalWDB3D5Wiring Diagrams / Dwgs15Post / InternalWPB3 Primary, B5D5White Paper550Presale / External** Minimum order quantities on all JIT items are based on the publication length. **Publication lengthMinimum Order Quantity77 or more pages1 (no shrink wrap required)33 to 76 pages253 to 32 pages501 or 2 pages100Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or betterCategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper RequirementsA14 color170 gsm 2pp100# gloss cover, 100# gloss textA24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss textA34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss textA42 color170gsm Silk 120gsm Silk80# gloss cover, 80# gloss textA52 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet textA61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet textA74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet textA84 color coverCategory being deleted50# matte sheet text, self cover2 color textSelection GuideA92 color100gsm bond50# matte sheet text, self coverSelection GuideGray shading indicates Obsolete Print CatagoriesPost Sale / Technical CommunicationCategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper RequirementsB14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S2 color text50# matte sheet textB21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet textB31 color100gsm bond50# matte sheet text, self coverB42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet textB52 color100gsm bond50# matte sheet text, self coverCatalogsCategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper RequirementsC14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S4 color text45# Coated SheetC24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S2 color text32#-33# Coated SheetJIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or betterCategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper RequirementsD14 color170gsm white silk80# gloss cover, coated 2 sidesD24 color120gsm white silk80# gloss text, coated 2 sides, self coverD34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sidesD41 color160gsm tab90# indexD51 color80gsm bond20# bond, self coverD61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bondD72 color160gsm tab90# indexD82 color80gsm bond20# bond, self coverD92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bondD10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bondGray shading indicates Obsolete Print CatagoriesJust In Time (JIT) or Off Set (OS)?Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the Either category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.Black & White PrintingColor PrintingColor PrintingPrint Spec SheetJIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013Printing SpecificationYOUR DATA HEREInstructionsNO(required) Publication Number:1305-QR001B-EN-PSample: 2030-SP001B-EN-P11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOPUse Legacy Number:YESYES or NO8.5 x 11PERFECT - Perfect BoundA1LEFTLegacy Number if applicable:1305-5.2.2Sample Legacy Number: 0160-5.338.375 x 10.875SADDLE - Saddle StitchA2RIGHTCORNERPublication Title:1305 Adjustable Frequency AC Drive Quick ReferenceSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25 x 11 (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDEUsed in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25 x 10.875STAPLED1 -1 positionA3Part Number:PN-219714If SAP Part Number, be sure to enter PN- before the number7.385 x 9 (RSI Std)STAPLED1B - bottom 1 positionA5(required) CategoryD5Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6 x 4STAPLED2 - 2 positionsA6Paper Stock Color:White is assumed. For color options contact your vendor5.5 x 8.5 (half-size)THERMAL - Thermal bound (Tape bound)A7Ink Color:One color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8(required) Page Count ofPublication:8Total page count including cover. Enter PAGE count, not SHEET count4.75 x 7 (slightly smaller half-size)A9(required) Finished Trim Size Width:8.5 x 11This is sheet size, before folding4.25" x 5.50"Post Sale / Technical CommunicationFold:Review key below. Leave blank if folded for saddle stitching4 x 6B1Finished Fold Size:This is size after folding is completed3 x 5B2Binding/Stitching:SADDLE - Saddle StitchReview key below9 x 12 (Folder)B3NoneStitching Location:Blank, Corner or SideA4 (8 x 11 ) (210 x 297 mm)B4Half or V or Single FoldDrill Hole (Yes/No):All drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.A5 (5.83 x 8.26) (148 x 210 mm)B5C or Tri-FoldNumber of Tabs Needed:5 tab in stock at RR Donnelley36 x 24 PosterCatalogsDbleParllNumber of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24 x 36 PosterC1SampleGlue Location on Pad:Glue location on pads18 x 24 PosterC2Short (must specify dimensions between folds in Comments)(required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold(required) Cost Center:19134 - Power CIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturingComments:Make as a booklet, printed on 11 x 17 inch paper, folded in half, and saddle stitched.D2Double GateFoldsHalf, V, Single C or TriDble ParllZ or Accordian Microfold or FrenchDouble Gate Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3D4D5D6D7D8D9MBD000B0209.binMBD000B020B.binMBD000B020C.binMBD000B020A.binMBD000B0205.binMBD000B0207.binMBD000B0208.binMBD000B0206.binMBD000B0203.binMBD000B0204.bin

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice