Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house. Tightening the structure with caulking and sealants has several positive impacts. A tight house will have lower heating bills due to less heat loss and fewer drafts to decrease comfort. A tight house reduces the chance of mold and rot because moisture is less likely to enter and become trapped in cavities. Tight homes have better-performing ventilation systems and potentially require smaller heating and cooling equipment capacities. Air leakage is sometimes called infiltration, which is the unintentional or accidental introduction of outside air into a building. To minimize air leakage the energy code requires installation of an air barrier. The code includes a table that details how the air barrier is to be installed. The energy code requires compliance with Table R402.4.1.1 Air Barrier and Insulation Installation. This table is often referred to as the air barrier checklist. The energy code also requires that air barrier effectiveness be tested with a blower door test. Passing a blower door test should help confirm that the air sealing requirements have been met. The energy code requires that the house pass the test with a result of 4 air changes per hour at 50 Pascals of pressure (ACH 50) or less. The blower door test result must be provided to the building code official, who may require that the test be performed by an approved third party. Following are photos and diagrams that illustrate each of the air barrier installation details listed in the air barrier checklist. Table R402.4.1.1 Air Barrier and Insulation Installation includes details for both the air barrier and insulation. In this article the air barrier installation requirements are illustrated. 13. Air Barrier Installation Illustrated Air Barrier Defined The energy code requires that a “continuous air barrier shall be installed in the building envelope.” A Montana amendment to the definition of an air barrier further requires that the air barrier be installed on the warm side of the wall, ceiling, or floor assembly. An air barrier is a material or assembly of materials that reduces air flow through or into the building envelope. A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Air barrier and thermal barrier 1

Upload: others

Post on 24-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

Controlling building envelope air leakage is an important but commonly misunderstood component of the

energy-efficient house. Tightening the structure with caulking and sealants has several positive impacts. A tight

house will have lower heating bills due to less heat loss and fewer drafts to decrease comfort. A tight house

reduces the chance of mold and rot because moisture is less likely to enter and become trapped in cavities. Tight

homes have better-performing ventilation systems and potentially require smaller heating and cooling

equipment capacities. Air leakage is sometimes called infiltration, which is the unintentional or accidental

introduction of outside air into a building. To minimize air leakage the energy code requires installation of an air

barrier. The code includes a table that details how the air barrier is to be installed.

The energy code requires compliance with Table R402.4.1.1 Air Barrier and Insulation Installation. This table is

often referred to as the air barrier checklist. The energy code also requires that air barrier effectiveness be

tested with a blower door test. Passing a blower door test should help confirm that the air sealing requirements

have been met. The energy code requires that the house pass the test with a result of 4 air changes per hour at

50 Pascals of pressure (ACH 50) or less. The blower door test result must be provided to the building code

official, who may require that the test be performed by an approved third party.

Following are photos and diagrams that illustrate each of the air barrier installation details listed in the air

barrier checklist. Table R402.4.1.1 Air Barrier and Insulation Installation includes details for both the air barrier

and insulation. In this article the air barrier installation requirements are illustrated.

13. Air Barrier Installation Illustrated

Air Barrier Defined

The energy code requires that a “continuous air barrier shall be installed in the building envelope.” A

Montana amendment to the definition of an air barrier further requires that the air barrier be installed

on the warm side of the wall, ceiling, or floor assembly. An air barrier is a material or assembly of

materials that reduces air flow through or into the building envelope.

A continuous air barrier shall be installed in the building envelope. Exterior

thermal envelope contains a continuous air barrier. Breaks or joints in the

air barrier shall be sealed. Air-permeable insulation shall not be used as a

sealing material.

Air barrier and

thermal barrier 1

Page 2: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

2

The air barrier in any dropped ceiling/soffit shall be aligned with the

insulation and any gaps in the air barrier sealed. Access openings, drop

down stair or knee wall doors to unconditioned attic spaces shall be sealed. Ceiling/attic

Continuous Sealed Air Barrier on

the Warm Side of the Building

Envelope Assembly

Thermal

Envelope

2

1

Page 3: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

3

Corners and headers shall be insulated and the junction of the foundation

and sill plate shall be sealed. The junction of the top plate and top of

exterior walls shall be sealed. Exterior thermal envelope insulation for

framed walls shall be installed in substantial contact and continuous

alignment with the air barrier. Knee walls shall be sealed.

Walls 3

Source: Northwest ENERGY STAR Homes Program

Source: USDOE Building America

Page 4: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

4

The space between window/door jambs and framing and skylights and

framing shall be sealed. Windows,

skylights and

doors 4

Source: ENERGY STAR New Homes

Source: Sprayfoam.com

Source: USDOE Building Energy Codes University

Page 5: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

5

Rim joists shall be insulated and include the air barrier. Rim Joists 5

Page 6: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

6

Insulation shall be installed to maintain permanent contact with underside

of subfloor decking. The air barrier shall be installed at any exposed edge of

insulation.

Floors (including

above-garage

and cantilevered

floors)

6

Air barrier installed at

any exposed edge of

insulation.

Page 7: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

7

Where provided in lieu of floor insulation, insulation shall be permanently

attached to the crawlspace walls. Exposed earth in unvented crawl spaces

shall be covered with a Class I vapor retarder with overlapping joints taped.

Crawl space

walls 7

Page 8: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

8

Duct shafts, utility penetrations, and flue shafts opening to exterior or

unconditioned space shall be sealed. Shafts,

penetrations 8

Source: ENERGY STAR

Source: Northwest ENERGY STAR Program

Page 9: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

9

Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by

insulation that on installation readily conforms to the available cavity space. Narrow

cavities

Air sealing shall be provided between the garage and conditioned spaces. Garage

separation 10

9

Source: ENERGY STAR New Homes

Source: USDOE Building America

Source: NCAT

Page 10: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

10

Recessed light fixtures installed in the building thermal envelope shall be air

tight, IC rated, and sealed to the drywall. Recessed

lighting 11

Source: Northwest ENERGY STAR Homes

Source: ENERGY STAR

Page 11: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

11

Batt insulation shall be cut neatly to fit around wiring and plumbing in

exterior walls, or insulation that on installation readily conforms to available

space shall extend behind piping and wiring.

Plumbing and

wiring 12

Source: MT DEQ

Source: MT DEQ

Source: MT DEQ

Page 12: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

12

Exterior walls adjacent to showers and tubs shall be insulated and the air

barrier installed separating them from the showers and tubs. Shower/tub on

exterior wall 13

Source: Northwest ENERGY STAR Homes

Source: Northwest ENERGY STAR Homes

Page 13: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

13

The air barrier shall be installed behind electrical or communication boxes

or air sealed boxes shall be installed. Electrical/phone

box on exterior

walls 14

Source: ENERGY STAR New Homes

Page 14: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

14

HVAC register boots that penetrate building thermal envelope shall be

sealed to the subfloor or drywall. HVAC register

boots 15

Source: ENERGY STAR New Homes

Source: ENERGY STAR New Homes

Page 15: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

15

Plan Review

1. Verify that submitted construction documents identify location (warm side of wall) and details of continuous

air barrier installation, including specification of how joints in materials will be sealed. The code required air

barrier installation details are included in Table R402.4.1.1 Air Barrier and Insulation Installation.

2. Verify that the construction documents specify a tested envelope tightness of 4 ACH50 or tighter. The

designer may specify a tighter envelope.

An air barrier shall be installed on fireplace walls. Fireplaces shall have

gasketed doors. Fireplace 16

Source: ENERGY STAR and Building Science Corp

Source: ENERGY STAR New Homes

Page 16: 13. Air Barrier Installation Illustrated · 2018-12-05 · Controlling building envelope air leakage is an important but commonly misunderstood component of the energy-efficient house

16

Field Inspection

1. Verify installation of continuous air barrier in accordance with Table R402.4.1.1 Air Barrier and Insulation

Installation.

2. Verify that all joints and penetrations in the air barrier are sealed.

3. Verify that all air barrier materials are installed per manufacturer’s instructions.

4. Verify that the building envelope has been tested by an approved entity to a tightness of 4 ACH50 or tighter.

Code References

R202 General Definitions

Air Barrier. Material(s) assembled and joined together to provide a barrier to air leakage through or into the

building envelope. An air barrier may be a single material or a combination of materials. (Note: A Montana

amendment added the words “or into.” The intent of the amendment was that an air barrier is to be installed on

the warm side of the exterior thermal envelope assembly and that is the correct interpretation.)

R402.4 Air Leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in

accordance with the requirements of Sections R402.4.1 through R402.4.4.

R402.4.1 Building Thermal Envelope. The building thermal envelope shall comply with Sections R402.4.1.1

and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and

contraction.

R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1

shall be installed in accordance with the manufacturer’s instructions and the criteria listed in Table

R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved

third party shall inspect all components and verify compliance.

Resources

2012 International Energy Conservation Code, Copyright August 2011 by the International Energy Codes Council,

Inc., Falls Church, Virginia.

2012 IECC Code and Commentary, Copyright August 2012 by the International Energy Codes Council, Inc., Falls

Church, Virginia.

Prepared by the National Center for Appropriate Technology with funding from the Northwest Energy Efficiency Alliance.