1203 getting started manual - rockwell automation1203-gk1 1336-gm1 because of the variety of uses...
TRANSCRIPT
-
GettingStarted Manual
Allen-Bradley
Bulletin 1203 Remote I/OCommunicationsModuleCatalo g Numbers1203-GD11203-GK11336-GM1
-
Because of the variety of uses for the products described in thispublication, those responsible for the application and use of thiscontrol equipment must satisfy themselves that all necessary stepshave been taken to assure that each application and use meets allperformance and safety requirements, including any applicable laws,regulations, codes and standards.
The illustrations shown in this guide are intended solely for purposesof example. Since there are many variables and requirementsassociated with any particular installation, Allen-Bradley does notassume responsibility or liability (to include intellectual propertyliability) for actual use based upon the examples shown in thispublication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for theApplication, Installation, and Maintenance of Solid-State Control(available from your local Allen-Bradley office), describes someimportant differences between solid-state equipment andelectromechanical devices that should be taken into considerationwhen applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, inwhole or in part, without written permission of Allen-BradleyCompany, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safetyconsiderations:
!ATTENTION: Identifies information about practicesor circumstances that can lead to personal injury ordeath, property damage or economic loss.
Attention statements help you to:
• identify a hazard• avoid the hazard• recognize the consequences
Important: Identifies information that is critical for successfulapplication and understanding of the product.
PLC, PLC–2, PLC–3, and PLC–5 are registered trademarks of Allen–Bradley Company, Inc.PLC–2/30, PLC–5/10, PLC–5/15, PLC–5/25, PLC–5/30, PLC–5/40, PLC–5/40L, PLC–5/60L, and PLC–5/250 are trademarksof Allen–Bradley Company, Inc.SCANport is a registered trademark of Allen–Bradley Company, Inc.SLC 500, SLC–5/02, and PLC–5/15 are registered trademarks of Allen–Bradley Company, Inc.DH+ is a registered trademark of Allen–Bradley Company, Inc.
Important UserInformation
-
Summary of Changes
Publication 1203–5.1 – July, 1997
Summary of Changes
We would like to call your attention to the following changes to the1203-5.1 manual which have occurred since the previous versionpublished in April, 1996. All references to page, table, and figurenumbers refer to the December publication. Page, table, and figurenumbers in the July, 1997 publication may not match the page, table,and figure number references mentioned here due to omissions orinclusions and, likewise, text and graphics shifting somewhat frompage to page.
• Page 1–1 was updated to include the 1336 IMPACT and 1397drives.
• Figure 1.1 was changed to reflect a change in LED colors.• Figure 1.2 was changed to reflect a change in LED colors.• Figure 4.1 was changed to reflect a change in LED colors.• Table 4.A was changed to reflect a change in LED colors.• Table 5.A was changed to identify the column headings more
clearly.
-
soc–ii Summary of Changes
Publication 1203–5.1 – July, 1997
-
Preface
Who Should Use this Manual? P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose of this Manual P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents of this Manual P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Firmware Support P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PLC Product Compatibility P–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terms and Abbreviations P–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Common Techniques Used in this Manual P–3. . . . . . . . . . . . . . . . . . . Allen–Bradley Support P–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Product Support P–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Product Assistance P–4. . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Chapter Objectives 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adapter Description 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SCANport Device Compatibility 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Switches 1–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Datalinks 1–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions 1–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Chapter Objectives 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Module Configuration Switches 2–1. . . . . . . . . . . . . . . . . .
Switch SW3 2–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch SW2 2–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch SW1 2–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the Remote I/O Module 2–9. . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Remote I/O Cable 2–12. . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Termination Resistor 2–14. . . . . . . . . . . . . . . . . . . . . . . Connecting the SCANport Link 2–16. . . . . . . . . . . . . . . . . . . . . . . . . . .
1305 Drive 2–16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1336 PLUS (7.5 – 500HP) and 1336 FORCE 2–16. . . . . . . . . . . . . . . SMP 3 2–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SMC Dialog Plus 2–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Power Supply 2–18. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
Chapter Objectives 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Controller Data Table Use 3–1. . . . . . . . . . . . . . . . . . . Data Transfer Through the Communications Module 3–3. . . . . . . . . . . .
Table of Contents
Overview
Installation
Configuration andInterfacing
-
ii
Publication 1203–5.1 – July, 1997
Chapter 4
Chapter Objectives 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting Table 4–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5
Chapter Objectives 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Specifications 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Controller Compatibility 5–2. . . . . . . . . . . . . . . . . . . . .
Troubleshooting
Specifications
-
Preface
Publication 1203–5.1 –– July, 1997
Preface
Read this preface to familiarize yourself with the rest of the manual.This preface covers the following topics:
• who should use this manual• the purpose of this manual• safety precautions• firmware support• product compatibility• terms and abbreviations• conventions used in this manual• Allen–Bradley support
Use this manual if you are responsible for designing, installing,programming, or troubleshooting control systems that use theBulletin 1203 remote I/O communications module. You must haveprevious experience with and a basic understanding of electricalterminology, configuration procedures, required equipment, andsafety precautions.
To efficiently use this communications module, you must be able toprogram and operate an Allen-Bradley programmable controller. Inparticular, you must be familiar with remote I/O concepts andconfiguration and be able to program block transfer instructions.
This manual provides you with the information you need to apply theremote I/O communications module that is available for productsthat include the SCANport� communications port. This manualdescribes the procedures for installing, configuring, andtroubleshooting the remote I/O communications module. Blocktransfer instructions are explained in a separate softwareprogramming manual.
For information on specific product features, refer to the productmanual.
Important: Read this manual in its entirety before installing,operating, servicing, or initializing the remote I/Ocommunications module.
Who Should Use thisManual?
Purpose of this Manual
-
P–2 Preface
Publication 1203–5.1 –– July, 1997
Contents of this Manual
This manual contains the following information:
Chapter: Title: Contents:
PrefaceDescribes the purpose, background, and scope of thismanual as well as an overview of this product.
1 OverviewProvides an overview of the adapter features,configuration information, and diagnostic information.
2 Installation
Provides the procedures you need to mount the Bulletin1203 remote I/O communications module, connect thepower, and configure the switches, as well as providingcabling and hardware information.
3Configuration andInterfacing
Provides information such as addressing, informationtransfer, and sample programs.
4 TroubleshootingProvides information about the LED indications andfault descriptions.
5 SpecificationsProvides the environmental, electrical, andcommunications specifications.
Please read the following safety precautions carefully.
!ATTENTION: Only personnel familiar withSCANport devices and the associated machineryshould plan or implement the installation, start-up,configuration, and subsequent maintenance of thisremote I/O communications module. Failure to complymay result in personal injury and/or equipmentdamage.
!ATTENTION: This module contains ESD(Electrostatic Discharge) sensitive parts andassemblies. Static control precautions are requiredwhen installing, testing, servicing, or repairing thisassembly. Component damage may result if ESDcontrol procedures are not followed. If you are notfamiliar with static control procedures, referenceAllen-Bradley Publication 8000-4.5.2, Guardingagainst Electrostatic Damage, or any other applicableESD protection handbook.
This manual supports communication module firmware versions1.xx and 2.xx (the xx designator may vary). Features that work withspecific firmware versions will be denoted as such.
Safety Precautions
Firmware Support
-
P–3 Preface
Publication 1203–5.1 –– July, 1997
This adapter is designed to be used with the following Allen-Bradleyprogrammable controllers:
• PLC-2/30 with SD2 (communications module version 1.02 orlater)
• PLC-3
• SLC 500� with 1747-SN scanner• PLC-5/10�, PLC-5/15�, PLC-5/25� family• PLC-5/30�, PLC-5/40�, PLC-5/40L�, PLC-5/60�,
PLC-5/60L� family, PLC-5/80�
• PLC5/250�• PLC scanner modules and subscanners.
This adapter was tested with the current revision level of the PLCprocessors listed. Earlier versions of the processors may not becompatible.
The following terms and abbreviations are specific to this product.For a complete listing of Allen–Bradley terminology, refer to theAllen–Bradley Industrial Automation Glossary.
In this manual, we refer to the:
• remote I/O communications module as communications module• variable frequency ac drive (1305, 1336 FORCE, or 1336 PLUS)
as the drive or SCANport device
• The programmable logic controller as the programmablecontroller
• Allen–Bradley remote input/output network as remote I/O• earth ground as Gnd
The following conventions are used throughout this manual:
• Bulleted lists provide information, not procedural steps.• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis and chapter names.
We also use this convention to call attention to helpful information.
PLC Product Compatibility
�
Terms and Abbreviations
Common Techniques Used inthis Manual
�
-
P–4 Preface
Publication 1203–5.1 –– July, 1997
Allen–Bradley offers support services worldwide, with over 75Sales/Support Offices, 512 authorized Distributors and 260authorized Systems Integrators located throughout the United Statesalone, plus Allen–Bradley representatives in every major country inthe world.
Local Product Support
Contact your local Allen–Bradley representative for:
• sales and order support• product technical training• warranty support• support service agreements
Technical Product Assistance
If you need to contact Allen–Bradley for technical assistance, pleasereview the information in the Troubleshooting chapter first. If youare still having problems, then call your local Allen–Bradleyrepresentative.
Allen–Bradley Support
-
Chapter 1
Publication 1203–5.1 –– July, 1997
Overview
Chapter 1 covers the following information:
• a description of the communications module• SCANport device compatibility• configuration switches• datalinks• safety precautions
The remote I/O communications module is an optional interfacedevice designed to provide a direct, digital link between anAllen-Bradley programmable controller and any device that uses theSCANport� communication port. The current list of products thatuse the SCANport communications interface includes: 1305, 1336PLUS, 1336 FORCE, 1336 IMPACT, 1397, and SMP3 and SMCDialog Plus. The board connects to these products through theSCANport peripheral interface.
The adapter is available in both Open style (Figure 1.1) and Enclosed(Figure 1.2) type configurations. The Open style module mountsinside certain drives, depending on drive size (refer to Table 1.A).You can use the Enclosed module with any compatible SCANportdevice that is mounted outside the drive package.
Table 1.A Remote I/O Configurations
Designation Enclosure Power Supply Source Used With
Open Style Open PC board Supplied by drive1336 PLUS➀
1336 FORCE➁
Enclosed IP3024V ac/dc separately supplied or120/240V ac separately supplied
13051336 PLUS1336 FORCESMP3SMC Dialog PlusOther SCANport products
➀ 7.5 hp and higher sizes only➁ 7.5 hp and higher sizes with standard adapter board only
The remote I/O communications module does not support version1.xx (the .xx designator may vary) of the 1305 drive. If you try touse the remote I/O communications module with a version 1.xx1305, the remote I/O communications module will continually resetitself, resulting in the red adapter fault status LED and the amberSCANport status LED both flashing simultaneously indicating anerror condition. Firmware revision 2.xx or higher on the 1305 isrequired to support remote I/O communications and block transfer.
Chapter Objectives
Adapter Description
SCANport DeviceCompatibility
-
1–2 Overview
Publication 1203–5.1 –– July, 1997
Figure 1.1 Open Style Communications Module
SW1
Front View
SW2SW3
Remote I/O Connector
Adapter FaultStatus (Red)
SCANport Status(Green)
Adapter Health(Green)
Remote I/O Status (Green)
Remote I/O Active (Green) J4
181818
Block Transfer EnableLogic Command / Status Enable
Analog Reference / Feedback EnableDatalink A-D enable
Truncate last datalinkStarting Quarter
Baud RateRack Fault
Hold Last StateLast Rack
Rack Address
-
1–3Overview
Publication 1203–5.1 –– July, 1997
Figure 1.2 Enclosed Style Communications Module
Front View
SW1
Remote I/O Status (Green)
Remote I/O Active (Green)
ConnectPower Supply Here
Adapter Health (Green)
SCANport Status (Green)
Adapter Fault Status (Red)
Remote I/OConnector
SCANport CommunicationCable Connector
Bottom View
1
Switch SW3– Block Transfer Enable– Logic Command/ Status Enable– Analog Reference/ Feedback Enable– Datalink A-D enable– Truncate last datalink
Switch SW1– Rack Address
SW28 18SW3 18
Switch SW2– Starting Quarter– Baud Rate– Rack Fault– Hold Last State– Starting Quarter
. . .
-
1–4 Overview
Publication 1203–5.1 –– July, 1997
Figure 1.3 Typical Programmable Controller/SCANport Device Interconnection
SCANport
Communications Module
PLC
...
1305*MicroDrive
1336 PLUS
Open Style RIO Adapter
Remote I/O Link
.
Other Remote I/O Devices
ÁÁÁÁÁÁ
ÀÀÀÀ
Panel View Operator Terminal
*NOTE: Refer to Page 1–1 for compatibilityrequirements of SCANport devices
SCANport
Communications Module
SMP 3
Communications Module
SMC Dialog Plus
-
1–5Overview
Publication 1203–5.1 –– July, 1997
The remote I/O communications module contains three DIP switchesSW1, SW2, and SW3 (Figure 1.1 and Figure 1.2). Switches are setOn or Off as detailed in Figure 1.4. For a detailed explanation ofswitch configuration, refer to Chapter 2, Installation.
Figure 1.4Configuration Switch
Side View of Typical Switches
Open
8
Closed (On)
1234567
OPEN
OpenOpen (Off)
Rocker Switch
Open
Open
Slide Switch
Switch Designation asshown in this manual
OFF (OPEN)
ON
Datalinks are a SCANport mechanism for transferring additionalinformation between a programmable controller and a SCANportdevice. Each datalink switch on the adapter reserves two words ofthe programmable controller I/O image table. The 1305, 1336PLUS, and 1336 FORCE drives support this mechanism. Foradditional details, refer to Chapter 3, Configuration and Interfacing.
Configuration Switches
Datalinks
-
1–6 Overview
Publication 1203–5.1 –– July, 1997
Please read the following safety precautions.
!ATTENTION: This board contains ESD(Electrostatic Discharge) sensitive parts andassemblies. Static control precautions are requiredwhen installing, testing, servicing, or repairing thisassembly. Component damage may result if you do notfollow ESD control procedures. If you are not familiarwith static control procedures, refer to Allen-Bradleypublication 8000-4.5.2, Guarding Against ElectrostaticDamage, or any other applicable ESD ProtectionHandbook.
!ATTENTION: Servicing or configuring the RIOboards on drives larger than 3hp involves opening the1336 drive cabinet which creates the potential to comein contact with other drive components. Energizedindustrial control equipment can be hazardous. Severeinjury or death can result from electrical shock, burn,or unintended actuation of controlled equipment.Recommended practice is to disconnect and lock outall control equipment from power sources, and allowstored energy in any capacitors to dissipate. If youmust work near energized equipment, you must followthe safety related work practices of NFPA 70E,Electrical Safety Requirements for EmployeeWorkplaces.
Safety Precautions
-
Chapter 2
Publication 1203–5.1 –– July, 1997
Installation
Chapter 2 provides information to help you:
• set the module configuration switches• mount the remote I/O module• connect the remote I/O cable• connect the termination resistor• connect the SCANport link• connect the power supply
Read this chapter completely before you attempt to install orconfigure your remote I/O communications module. Double checkall connections and option selections before you apply power.
Important: Switch selections take effect only on power–up. If youchange selections after power is applied, cycle thepower to use the new settings.
This publication describes switches as being either on or off. If theswitch assembly has the word OPEN printed on it, the word OPENcorresponds to OFF (O).
When you change the adapter board configurations, keep in mind theaddressing conventions of the type of processor that you are using. Inall cases, each remote I/O device must have a unique address that theprocessor can recognize.
Important: This adapter is not compatible with complementary I/Oconfigurations because the adapter uses both output andinput image words for proper drive control.
!ATTENTION: When you make changes to the switchsettings, use a blunt, pointed instrument such as a ballpoint pen. Do not use a pencil because the lead(graphite) of the pencil may damage the switchassembly.
ATTENTION: Failure to check connections andswitch settings for compatibility with your applicationwhen configuring the communications module, couldresult in personal injury and/or equipment damage dueto unintended or undesirable operation of the drive orprocess equipment.
Chapter Objectives
Setting the ModuleConfiguration Switches
-
2–2 Installation
Publication 1203–5.1 –– July, 1997
Switch SW3
Set switch SW3 first. The settings on this switch determine how theSCANport device uses the data contained in the programmablecontroller I/O image table. SW3 also establishes the minimum racksize that this communications module requires.
The switches are labeled in the same orientation as they appear onthe board.
Table 2.A, SW3 Image Table Map, and Figure 2.2, SW3 Flowchart,are included to help you set the DIP switches properly. It may alsobe helpful to color in the final switch settings in Figure 2.1 as avisual record of your SW3 settings. Chapter 3 contains severalexamples of how to fill in the worksheet and set these DIP switches.
Figure 2.1 Configuration Switch SW3 Settings
J1
SW3
BlockTransfer
Off
Datalink ATransfers
On
LogicCommand/Status
On
Off
Reference/Feedback
On
Off
On
Off
Datalink BTransfers
Datalink CTransfers
On
Off
On
Off
On
Off
Datalink DTransfers
8 1234567
OPEN
Truncate➀➁
Last Datalink
➀ IMPORTANT: Only available on communications modules with version 1.02 or later firmware.➁ All datalinks are two words, the truncate function will delete the last datalink word. (If “Datalink B” is the last used, “Data in B2” and “Data Out B2” will be truncated.)
Open Style Enclosed Style
Off
On
NotEnabled
Enabled
Off (Open)
On
�
-
2–3Installation
Publication 1203–5.1 –– July, 1997
Table 2.ASW3 Image Table Map
RESERVED FOR: MinimumR i Start AtG pOutput Image Input ImageRequired
Rack Size➀Start AtGroup
R 01/4 Rack 0, 2, 4, or 6
lf R 0Half Rack 0, 2, or 4
R 03/4 Rack 0 or 2
ll R 0 nlyFull Rack 0 only
➀ Use this to select settings for switch SW2, switches 1 and 2
How to use Table 2.A:
1. Use Figure 2.2 to set DIP switch SW3 and fill out Table 2.A.
2. Use minimum rack size shown in Table 2.A to set DIP switchSW2-1 and SW2-2.
Figure 2.2 SW3 Flowchart
Will block transfer or block transfer RIO pass thrube used?
1. Block Transfer
YES
1. Write “Block Transfer” in word 0 of both the inputand the output image2. Set SW 3-1 to on
Will the SCANport device be controlled by (Start/Stopetc.) or will the Logic Status by monitored by the PLC?
2. Logic Command
NO
NO
2. Move to step 2
YES
1. Write “Logic Cmd” in the output image and “LogicStatus” in the input image of the next available word2. Set SW3-2 to on
Will a reference or feedback be provided from/to the programmable controller?
3. Reference/Feedback
NO
YES
1. Write “Reference” in the output image and “Feedback” in the input image of the next availableword2. Set SW3-3 to on
NOTE: For detailed information on block transfermessages refer to the 1203-5.0 Reference Manual.
Step
Step
Step
1. Set SW3-1 to off
2. Move to step 31. Set SW3-2 to off
2. Move to step 41. Set SW3-3 to off
-
2–4 Installation
Publication 1203–5.1 –– July, 1997
Figure 2.2SW3 Flowchart continued
Will Datalink Group B be used?
Step 5. Datalink B Transfer
YES
NO
1. Write “Datalink B“ in the output and input image of the next two available words2. Set SW3-5 to on
Will Datalink Group C be used?
Step 6. Datalink C Transfer
YES
NO
1. Write “Datalink C” in the output and input imageof the next two available words2. Set SW3-6 to on
Will Datalink Group D be used?
Step 7. Datalink D Transfer
YES
NO
1. Write “Datalink D” in the output and input image of the next two available words2. Set SW3-7 to on
Step 9. Calculate minimum rack size
Refer to Table 2.A on page page 2–3.1. Record the minimum rack size in Table 2.A on page 2–3.2. Use the minimum rack size to set Dip switches SW2-1 and SW2-2.
Will the last Datalink be one word(truncate last Datalink) ?
Step 8. Truncate Last Datalink
YES
NO
1. Cross out the last word of the last Datalink groupused in the output and input image table2. Set SW3-8 to on
2. Move to step 61. Set SW3-5 to off
2. Move to step 71. Set SW3-6 to off
2. Move to step 81. Set SW3-7 to off
2. Move to step 91. Set SW3-8 to off
Will Datalink Group A be used?
4. Datalink A Transfer
YES
NO
1. Write “Datalink A” in the output and input imageof the next two available words2. Set SW3-4 to on
Step
2. Move to step 51. Set SW3-4 to off
-
2–5Installation
Publication 1203–5.1 –– July, 1997
Switch SW2
Switch SW2 determines Rack Size, Last State, Rack Fault, and BitRate Selections as shown in Figure 2.3.
The switches are labeled in the same orientation as they appear onthe board.
Figure 2.3 Configuration Switch SW2 Settings
On
J1
SW2
Starting Module Group➁
On
Last RackSetting➃
HoldLastState➄ ➅
ZeroImageon PLCFault
Run atLast State
Communications Loss➅
NoFault
Fault onCommLoss On
RIO Baud Rate
57.6kbps
115.2kbps
230.4kbps
LastRack
Not–LastRack
Off
On
Off
Off Off
On
Off
On
Off
On
Off
Off
Off
On
Off On
0
4
6
➀ If this switch is set to No Fault,the setting of the Hold Last Stateswitch determines the data sent to the SCANport device when thePLC is in Reset/Program/Test.
8 1234567
OPEN
Off
Enclosed StyleOpen Style
2
OFF (OPEN)
ON
NoFault➀
FaultDrive On
Off
➁ The setting of this switch is determinedby the amount of discrete I/O that will bepassed between the PLC and the drive.Refer to Table 2.A for more information.
Reset/Program/Test➂ ➄
➂ This switch is active onFirmware Version 2.xxmodules only. It is not used bymodules containing FirmwareVersion 1.xx.
➃ Set this switch on the lastmodule used for a given rackaddress. It does notelectrically terminate the RIOlink.
➄ Refer to Figure 2.4. ➅ Refer to Figure 2.5and Figure 2.6.
�
-
2–6 Installation
Publication 1203–5.1 –– July, 1997
Figure 2.4 PLC Switched to Program
Fault drive in program set
Off
Hold last state On
On
Off
Send command on to the drive
Send a 0 command tothe drive
Generate a drive communicationsloss fault
Figure 2.5 SCANport Cable Unplugged
Communications loss
Off
Hold last state On
On
Off
Send the last image of the drive status to the PLC
Send a value of 0 to thePLC for the drive status
Stop responding to the PLC. The PLC generates a rack fault
Figure 2.6 RIO Cable Disconnected
Communications loss
Off
Hold last state On
On
Off
Send the last command to the drive
Send zero images tothe drive.
Generate a drive communicationsloss fault
-
2–7Installation
Publication 1203–5.1 –– July, 1997
Switch SW1
Switch SW1 controls starting quarter and rack address options asshown in Figure 2–7.
Note: When using a PLC-2 family processor, you need to offset thevalue of the rack number by one. The PLC-2 cannot have a remoteI/O rack numbered zero. Therefore, add a value of one to the RackNo value in Table 2.B when writing your PLC code.
Figure 2.7 Configuration Switch SW1 Settings
12345678
J1
SW1
Not Used
Rack Addressing (See Table 2.B.)
OPEN
Enclosed StyleOpen Style
Off (Open)
On
�
-
2–8 Installation
Publication 1203–5.1 –– July, 1997
Table 2.BSwitch SW1 SettingsSW1-8 through SW1-1 DIP Switch Definitions, Rack Address
Rack No. SW1-3SW1-4SW1-5SW1-6SW1-8
0001020304050607101112131415161720212223242526273031323334353637
OnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOn
OnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOffOffOffOffOffOffOffOffOff
OnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOffOnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOff
OnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOff
OnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOff
SW1-7
OnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOff
SW1-2 SW1-1
not usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot used
-
2–9Installation
Publication 1203–5.1 –– July, 1997
The remote I/O communications module can be provided in threemounting configurations:
• Open Style board factory installed in a drive (not available for alldrives)
• Open Style board as a separate kit• Enclosed style for panel mount or DIN rail mount
This section provides mounting information for the Enclosed styleand the Open style kit.
Figure 2.8 Open Style Communications Module Mounting Location (1336 Plus7.5–500HP)
1336 PLUS Main Control Board
TB2TB1
L OPTION
J7
J9
Human Interface Module
J4
Open Communications ModuleMounts Here
MemoryModule
U44
J3
J1
U50 U54 U56
Mounting Screws & Standoffs Qty 4
SCANport 6
Install the board with the component side facing you.
Mounting the Remote I/OModule
�
-
2–10 Installation
Publication 1203–5.1 –– July, 1997
Figure 2.9 Open Style Communications Module Mounting Location (1336FORCE Drive)
1336 FORCE Main Control Board
TB2
L OPTION
J4
Open Communications ModuleMounts Here
J1
Mounting Screws & Standoffs Qty 4
1336 FORCE Standard Adapter Board
SCANport 6
Install the board with the component side facing you.�
-
2–11Installation
Publication 1203–5.1 –– July, 1997
Figure 2.10 Enclosed Style Communications Module Dimensions
ÉÉÉÉÉÉÉÉÉÉÉÉDIN RAIL
ÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
45 mm
All dimensions in millimeters and (inches)
(1.8)
Back View(4.8)123 mm
Side View
(1.8)45mm
(1.75)44 mm
Note: The enclosure requires clearance at the top and bottom forproper cooling. Additional space will be required if access to DIPswitches is desired without having to remove the device.
Front ViewTop View
25 mm(1)
DIN rail mounting clip
25 mm(1)
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
70 mm(2.7)
DINRAIL
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
DINRAIL
ÉÉÉÉÉÉÉÉ
76 mm(3.0)
DIN RAIL
-
2–12 Installation
Publication 1203–5.1 –– July, 1997
You must connect remote I/O communications module cables asshown in the example in Figure 2.11. Refer to Table 2.C for cableguidelines.
Figure 2.11 Remote I/O Module Interconnections
Plus
ÉÉÉ
J4
Blue
Shield
Clear
1SH2
ÉÉÉBlue
Shield
Clear
REMI/O
PLC
...
Enclosed Communication Module
1SH
2
1336
Open StyleCommunicationModule
.
ÉÉÉ
J4
Blue
Shield
Clear
1
SH
2
Connecting the Remote I/OCable
-
2–13Installation
Publication 1203–5.1 –– July, 1997
Twinaxial cable used for remote I/O (RIO) and Data Highway+(DH+TM) communications represents a communicationstransmission line in which certain characteristics exist. The followingare some general guidelines that must be adhered to in order toobtain the best results.
Cable Type – Only 1770-CD Belden #9463 is approved for RIO andDH+ installations. All other cable types or manufacturers, no matterhow similar, are untested. Using other cable types is strictly at yourown risk.
Important: The transmission rate determines the maximum cablelength.
Table 2.CTwinaxial Cable Guidelines
Remote I/O link communications rate
Cable lengthcannot exceed:
57.6 kbps
115.2 kbps
230.4 kbps
3,048 m (10,000 ft)
1,524 m (5,000 ft)
762 m (2,500 ft)
Connections – Connect all three conductors, blue, clear, and shield,at each wiring point. No additional ground connections should bemade to the shield.
Important: DO NOT use star type connections. Only two cablesmay be connected at any wiring point on a seriesconnection application.
OK
These are general rules and certain deviations may be warrantedbecause diverse installation and environmental concerns couldchange the requirements.
�
-
2–14 Installation
Publication 1203–5.1 –– July, 1997
You must terminate both ends of a remote I/O link to ensure properoperation. This termination is required only at the ends of thephysical cable. Each remote I/O network should have exactly twotermination resistors installed. Use Table 2.D and Figure 2.12 andFigure 2.13 to determine the proper termination for your particularlink. Termination resistor R3 is located on the board, and the J2jumper selects this resistor.
Table 2.DTermination Resistor Requirements
If this device is an enddevice of a remote I/O link:
Terminate the link by:
Programmable controller Refer to the manual for your model processor.
Open style, single pointremote I/O adapter
Set jumper J2 in position 1–2 for termination and 2–3 forno termination as shown in Figure 2.12. The jumperenables a 150 ohm resistor as the terminator resistor.
Enclosed style single pointremote I/O adapter
Connect a terminator resistor between the remote I/Oterminals labeled 1 and 2 as shown in Figure 2.13.Use either a 150 Ohm or an 82 Ohm terminator.• You must use an 82 Ohm resistor if the remote I/O link is
operating at 230.4 kbps (terminator must be connected at boththe scanner and the adapter).
• You should use an 82 Ohm resistor if the remote I/O link isoperating at 57.6 kbps or 115.2 kbps unless one of the deviceson the link is listed in Table 2.E. If you are using a devicelisted in Table 2.E, then you must use a 150 Ohm terminator.
Important: The following products (Table 2.E) cannot be on a linkusing 82-Ohm termination resistors.
Table 2.EUnsupported Remote I/O Link Devices
Device Type Series
Scanners
Adapters
Miscellaneous
1771-SN1772-SD, -SD21775-SR1775-S4A, -S4B6008-SQH1, -SQH2
All
Catalog Number
1771-AS1772-ASB1771-DCM
1771-AF
AllAAll
All
Connecting theTermination Resistor
-
2–15Installation
Publication 1203–5.1 –– July, 1997
Figure 2.12 Terminating a Remote I/O Link Using the Module Mounted Resistor
ÉÉ
J4
J5
T1
J2123
Blue 1
2
SHShield
Clear
123
123
Not Last Rack(Factory Default)
Last Rack,Termination
Resistor InsertedEnables 150 ohm
Termination Resistor
Figure 2.13 Terminating a Remote I/O Link Using an External Resistor
ToBlue
ShieldClear
Remote I/O Module
Another Remote I/OLink Device
ÉÉ
1
2
I50 Ohmor
82 Ohm
EnclosedRemote I/O Module
Sh
1 watt,± 10%
-
2–16 Installation
Publication 1203–5.1 –– July, 1997
SCANport cables are available in either Male–to– Male orMale–to–Female configuration. You can connect cables of up to 10meters (33 feet) from the master to the SCANport device (A inFigure 2.14). If you use a port expander as shown in Figure 2.14,subtract the cable length from the master to the port expander fromthe cable length used to connect the device to the expander (B1+ C =maximum 10 meters).
1305 Drive
An Allen-Bradley SCANport link cable is used to make theconnection between the communications module and the drive(Figure 2.14).
Figure 2.14 SCANport connection on Remote I/O
1305 Drive
Human Interface Module
Port 1
A
Remote I/O Communication Module
Port 2
OptionalMale–FemaleCable
OptionalMale–Male Cable
B1
2 3 4 5
Port Expander
B2
C
Remote I/O Communication Module
Important: The maximum cable distance between any two masterdevices cannot exceed 10 meters (33 feet) of cable. Forexample, B1 + C = maximum of 10 meters or B1 + B2= maximum of 10 meters.
1336 PLUS (7.5 – 500HP) and 1336 FORCE
Refer to the product manual for connection information. On largerhorsepower 1336 PLUS and 1336 FORCE drives with an openremote I/O module mounted in the drive, you do not need a separateSCANport cable connection.
Connecting the SCANportLink
-
2–17Installation
Publication 1203–5.1 –– July, 1997
SMP 3
An Allen-Bradley SCANport cable is used to connect thecommunications adapter and an SMP 3. See the cable requirementson page 2–16 for details on cable length.
Figure 2.15 SCANport connection on Remote I/O
AB0538A
EnclosedAdapter
SMP 3
RESET
RemoteReset
SCANport
SMC Dialog Plus
An Allen-Bradley Bulletin 1202 SCANport cable is required toconnect the communications adapter and the SMC Dialog Pluscontroller.
Figure 2.16 SCANport connection on Remote I/O
AB0537A
Allen-Bradley SMC Dialog Plus
ESC SEL
EnclosedAdapter
SMC Dialog Plus
SCANport
-
2–18 Installation
Publication 1203–5.1 –– July, 1997
The Enclosed remote I/O is powered from a separate 24V dc or115V ac power supply (Figure 2.17). With the open style remote I/Oboard mounted in the drive, no separate power supply connectionsare required.
Figure 2.17 Typical Power Supply Connection
Enclosed Remote I/O Communication Module
115/230VTypical Connection
LNG
GND
115V AC Hi115V AC Low
Enclosed Remote I/O Communication Module
24V DCTypical Connection
+–G
GND
24V DC +PowerSupply –
Connecting the PowerSupply
-
Chapter 3
Publication 1203–5.1 –– July, 1997
Configuration and Interfacing
Chapter 3 provides information on how the remote I/Ocommunications module and a programmable controllercommunicate. The following topics are covered:
• programmable controller data table use• data transfer through the adapter
Important: Block transfer messaging is covered in a separatepublication.
!ATTENTION: When you configure a system for thefirst time, disconnect the motor from the machine orprocess during the initial testing.
The remote I/O communications module allows a SCANport deviceto look and act like a remote I/O chassis when connected to aprogrammable controller. Data contained in the input/output imagetable is transferred between the programmable controller by theremote I/O scanner, the same as with any remote I/O chassis. Youcontrol the location and amount of data transferred by setting therack address and starting quarter/rack size DIP switches on theremote I/O communication module.
Figure 3.1 shows a typical example of data transfer between aprogrammable controller, the remote I/O communications module,and a 1336 PLUS drive. This same concept works for all SCANportdevices. In this example, assume that you have set the DIP switchesfor rack address 2, a rack size of 1/4 (or greater if larger amounts ofdata are to be transferred), and has enabled (Set) the LogicCommand/Status switch.
Data placed in the output image table area for rack address 2 istransferred to the remote I/O communications module every rackscan. The communications module then transfers the data to the 1336PLUS drive as Logic Command. Logic status data is transferredfrom the drive to the remote I/O communications module and thenpassed to the programmable controller during a rack scan.
!ATTENTION: The RIO to SCANport conversion isasynchronous. Any data sent to the adapter for transferto the drive must be maintained until the drive hasreceived the data.
Chapter Objectives
Programmable ControllerData Table Use
-
3–2 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.1 Typical Example of Data Transfer Through the Communications Module
00
Programmable Controller I/O Image Table
01
02
03
04
05
06
07
11
12
13
14
15
16
17
00
01
02
03
04
05
06
07
11
12
13
14
15
16
17
Rack 2Output Image
Word 0Word 1Word 2Word 3Word 4Word 5Word 6Word 7
Word 0Word 1Word 2Word 3Word 4Word 5Word 6Word 7
Rack 2Input Image
Remote I/O
Logic Command/Status Enabled
SCANport
1336 PLUS Drive
Logic Command
Logic Status
Remote I/OCommunications
Module
Stop
Start
Jog
Clear Faults
Direction
Direction
Local
Mop Increment
Accel Time
Decel Time
Enabled
Running
Cmd Direction
Actual Direction
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local
Local
Local
Accel Time
10
Decel Time
Ref Select
Ref Select
Ref Select
MOP Decrement
10
Ref Select
Ref Select
Ref Select
Ref Select
This is a typical example of data transfer from a PLC to a 1336PLUS drive. Refer to the manual provided with yourSCANport–compatible product for actual Control and Status words.
Important: The communications module does not scale the datathat is transferred. If data in the programmablecontroller is manipulated in units other than deviceunits, the data must first be converted before being sentto the device. Consequently, all scaling of the data mustbe done in the PLC. Refer to the appropriate SCANportdevice manual for details on device units.
�
-
3–3Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
DIP switch SW3 determines how the data contained in theprogrammable controller I/O image table is used in the drive (Figure3.2). The first three switches (1 through 3) select the basic controlfeatures. Switches 4 through 7 support additional capability totransfer selected parameter information between the drive and theprogrammable controller. Products that have this capability have agroup of parameters for adapter I/O. These parameters are identifiedas “Data In” and “Data Out” parameters. Each datalink switch on theadapter consumes two words (unless truncated using SW3–8) in boththe input and output image table of the programmable controller.
The following are the rules for using datalink switches:
1. Normally, each datalink switch reserves two words in both theinput and output image tables of the programmable controller.The starting module group/rack size switch (SW2, 1-2) on theadapter must be set to support this.
2. The truncate last datalink switch truncates the last datalink to oneword in the input and output image table, instead of two. You canuse this to minimize the required rack size consumed by acommunications module.
3. Each set of datalink parameters in the drive can only be used byone remote I/O communications module. If more than onemodule is connected to a single SCANport link, the switchsettings must not conflict.
4. Parameter setting in the drive determine the data passed throughthe datalink mechanism. Refer to the “Adapter I/O” group in thedrive manual for details.
Table 3.ADatalink Switch SW3 Settings
SW3 switch: State: Input and output parameter assignments in the drive:
DatalinkASW3–4
OnOff
Reserves Data In/Out A for this adapterData In/Out A not used by this adapter
Datalink BSW3–5
OnOff
Reserves Data In/Out B for this adapterData In/Out B not used by this adapter
Datalink CSW3–6
OnOff
Reserves Data In/Out C for this adapterData In/Out C not used by this adapter
Datalink DSW3–7
OnOff
Reserves Data In/Out D for this adapterData In/Out D not used by this adapter
TruncateLast DatalinkSW3–8
OnOff
Truncates the last datalink to one wordNo truncation performed
Data Transfer Through theCommunications Module
-
3–4 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.2 Typical Programmable Controller Configuration Using Datalink A
Output Image
Blk Transfer
Logic Command
Reference
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Remote I/O Communications
Module
Data In A1
Input Image SW3
DriveProgrammableController
I/O Image Table
Blk Transfer
Logic Status
Feedback
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Data In A2
Datalink A
Data Out A1Data Out A2
SW3
Parameters
NOTE: This configuration requires a minimumrack size of 3/4 rack.
12
34
56
78
OPEN
Datalink B Off
Datalink C Off
Datalink D Off
Truncate last Datalink Off
Datalink A On
Reference/Feedback On
Logic Command On
Block Transfer On
AB0504B
-
3–5Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.3 Typical Programmable Controller Configuration for 1305 and 1336PLUS/FORCE without Block Transfer
Output Image
Logic Command
Reference
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Remote I/O Communications
Module
Input Image SW3
1336 PLUS/FORCEController
Programmable ControllerI/O Image Table
Logic Status
Feedback
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Data In A1Data In A2
Data In B1Data In B2
Datalink A
Datalink C Data In C1Data In C2
Data Out A1Data Out A2
Data Out B1Data Out B2
Data Out C1Data Out C2
Datalink A
Datalink C
Data Out D1Data Out D2
Data In D1Data In D2
Parameters
NOTE: This configuration requires a minimumrack size of 3/4 rack.
SW3
12
34
56
78
OPEN
Datalink B Off
Datalink C On
Datalink D Off
Truncate Last Datalink Off
Datalink A On
Reference/Feedback On
Logic Cmd/Sts On
Block Transfer Off
AB0505A
-
3–6 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.4 Typical Programmable Controller Configuration for 1305 and 1336PLUS/FORCE with Block Transfer
Block Transfer
Logic Status
Feedback
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Output Image
Block Transfer
Logic Command
Reference
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Remote I/O Communications
Module
Input ImageSW3
1336 PLUS/FORCEController
Programmable ControllerI/O Image Table
Data In A1 DataIn A2
Data In B1 Data In B2
Data Out A1Data Out A2
Data Out B1Data Out B2
Datalink A
Datalink B*
Datalink A
Datalink B*
Parameters
*NOTE: Datalink B has been truncated on a1/4 rack boundary. Only the first word of Datalink B istransferred. This configuration requires aminimum rack size of 3/4 rack. SW3
12
34
56
78
OPEN
Logic Cmd/Sts On
Block Transfer On
Reference/Feedback On
Datalink A On
Datalink B On
Datalink C Off
Datalink D Off
Truncate Last Datalink On
AB0506A
-
3–7Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.5 Typical Programmable Controller Configuration for SMP3
Output Image
Logic Command
WORD 1 REF
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Remote I/O Communications
Module
Input Image SW3
SMP3ProgrammableController I/O Image Table
Logic Status
Feedback
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
SW3
12
34
56
78
OPEN
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
Datalink A Off
Feedback On
Logic Cmd/Sts On
Block Transfer Off
AB0507A
*NOTE: While the reference is sent via the SCANportto the SMP3, the reference is ignored by the SMP3.
-
3–8 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.6 Typical Programmable Controller Configuration for SMC Dialog Plus withoutBlock Transfer
Output Image
Logic Command
Remote I/O Communications
Module
Input Image SW3
SMC Dialog PlusProgrammableController I/O Image Table
Logic Status
Feedback➀
SW3
12
34
56
78
OPEN
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
Datalink A Off
Reference/Feedback Off
Logic Cmd/Sts On
Block Transfer Off
AB0507A
➀ Current Phase A
-
3–9Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.7 Typical Programmable Controller Configuration for SMC Dialog Plus withBlock Transfer
Output Image
Block Transfer
Logic Command
Remote I/O Communications
Module
Input Image SW3
SMC Dialog PlusProgrammableController I/O Image Table
Block Transfer
Logic Status
Feedback➀
SW3
12
34
56
78
OPEN
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
Datalink A Off
Reference/Feedback Off
Logic Cmd/Sts On
Block Transfer On
AB0536A
➀ Current Phase A
-
3–10 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.8SLC 5/02TM Controller Example
Example Information:PLC Type – SLC 5/02Drive Type – 1336 PLUSDrive Rack Address – 2Rack Size – 1/2 Rack MinimumStarting Module Group – 0
When the Machine Start PushButton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sentby the PLC or any other control device. (Start button is a normally open contact in this example.)
MachineSTARTPushbutton I : 1.8
0
DriveSTARTCommand 0 : 1.16
1
When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).
This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zeroto Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)
Drive Frequency Command
MachineSTOPButton I : 1.8
1
DriveSTOPCommand 0 : 1.16
0
0
Drive StopCommand 0 : 1.16
1
Drive Running Bit I : 1.16
N7 : 0160000: 1.1716000
MOV
MOVESource
Dest
PLCWORD
OUTPUTIMAGE
INPUTIMAGE
0
1
2
3
Logic Cmd
Reference
Datalink A
Datalink A
Logic Sts
Feedback
Datalink A
Datalink A
PLC Image Table Map
12
34
56
78
OPEN
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
Datalink A On
Reference/Fdbk On
Logic Cmd/Sts On
Block Transfer Off
AB0508A
-
3–11Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
SLC 5/02 Example continuedWhen the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. (Jog button is a normally open contact in this example.)
When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.
Drive Data In A1(Data to Drive)
N7 : 1500
0: 1.180
MOV
MOVESource
Dest
When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary nor-mally open contact in this example.)
DriveClear FaultsCommand0 : 1.16
Machine ClearFaultsPushbutton I : 1.8
3 3
When the Drive is running, the PLC will receive a Drive Running Status Bit.
MachineRunningIndicator0 : 1.8
DriveRunningStatus Bit I : 1.16
1 1
DriveJOGCommand0 : 1.16
MachineJOGPushbutton I : 1.8
2 2
END OF FILE
MachineFaultedIndicator0 : 1.8
DriveFaultedStatus Bit I : 1.16
7 7
This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.
-
3–12 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
Figure 3.9PLC 5/15 Controller Example
Example Information:PLC Type – PLC 5/15Drive Type – 1336 PLUSDrive Rack Address – 2Rack Size – 1/2 Rack MinimumStarting Module Group – 0
When the Machine Start Pushbutton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sentto the PLC or any other control device. (Start button is a normally open contact in this example.)
MachineSTARTPushbuttonI : 000
00
DriveSTARTCommand0 : 020
01
When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).
This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zeroto Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)
Drive Frequency Command
MachineSTOPButtonI : 000
01
Datalink B OffDatalink C OffDatalink D Off
Truncate Last Datalink Off
Datalink A OnReference/Fdbk On
Logic Cmd/Sts On
Block Transfer Off
DriveSTOPCommand0 : 020
00
00
Drive StopCommand 0 : 020
01
Drive Running Bit I : 020
N7 : 0160000: 02116000
MOV
MOVESource
Dest
PLCWORD
OUTPUTIMAGE
INPUTIMAGE
0
1
2
3
Logic Cmd
Reference
Datalink A
Datalink A
Logic Sts
Feedback
Datalink A
Datalink A
PLC Image Table Map
12
34
56
78
OPE
N
-
3–13Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
PLC 5/15 Example continuedWhen the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. The drive will start and run at the programmed JogFrequency if no STOP command is being sent by the PLC or other control device. (Jog button is a normally open contact in this example.)
When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.
Drive Data In A1(Data to Drive)
N7 : 1500
0: 022500
MOV
MOVESource
Dest
When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary nor-mally open contact in this example.)
DriveClear FaultsCommand0 : 020
Machine ClearFaultsPushbutton I : 000
03 03
When the Drive is running, the PLC will receive a Drive Running Status Bit.
MachineRunningIndicator0 : 000
DriveRunningStatus Bit I : 020
01 00
DriveJOGCommand0 : 020
MachineJOGPushbutton I : 000
02 02
END OF FILE
MachineFaultedIndicator0 : 000
DriveFaultedStatus Bit I : 020
07 01
This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.
-
3–14 Configuration and Interfacing
Publication 1203–5.1 –– July, 1997
This Page Intentionally Left Blank.
-
Chapter 4
Publication 1203–5.1 –– July, 1997
Troubleshooting
Chapter 4 provides information to help you troubleshoot your remoteI/O system using the LED indicators on the front of the device(Figure 4.1). The remote I/O module is a non-serviceable device thatshould be returned to Allen-Bradley for replacement when a majorfault exists that is attributable to the remote I/O communicationsmodule itself.
Figure 4.1 LED Locations
SW1
Front ViewOpen Version
SW2SW3
Adapter Fault Status(Red)
SCANport Status(Green)
Adapter Health(Green)
Remote I/OStatus (Green)
Remote I/OActive (Green) J4
Front ViewEnclosed Version
...Remote I/OStatus (Green)
Remote I/OActive (Green)
Adapter FaultStatus (Red)
SCANport Status (Green)
Adapter Health(Green)
Refer to Table 4.A for details on LED operation.
J3
J2
J1
Chapter Objectives
-
4–2 Troubleshooting
Publication 1203–5.1 –– July, 1997
Table 4.A General Indications
Indicator Color Probably cause Recommended action
Adapter Fault Status Red (Steady) Unrecoverable fault Replace the adapter.
Red (Blinking) Recoverable faultCheck configuration switch setting, check for SCANportcable connection.
Red (Off) Normal operation None
SCANport Status Green (Steady) Normal operation SCANport is active.
Green (Off) No SCANport communication Check SCANport cables, device, cycle power.
Green (Blinking)When blinking in tandem with redfault status, a device incompatibilityexists
Check compatibility of drive on page 1–1 of this manual.
Adapter Health Green (Steady) Normal operation None.
Green (Off) Internal adapter fault Cycle power.
Remote I/O Active Green (Steady) Normal operation None.
Green (Off) No data transfer from PLC/SLCRemote I/O offline, make certain the PLC is in Run Mode,check rack address, check wiring and processor.
Remote I/O Status Green (Steady) Normal Operation None.
Green (Blinking) PLC is in Reset/Program/Test Mode None.
Green (Blinking)PLC has more rack space allocatedthan is being used
Do a PLC auto configuration.
Green (Off) No communication with processorCheck wiring to processor. Check adapter configurationin processor.
Adapter Fault Status Red (Blinking) and Configuration switch setting incorrect Check configuration switch settings.
and Adapter Health Green (Steady) Remote I/O and/or SCANport cablenot wired or connected properly
Check SCANport and remote I/O cable connections.
Troubleshooting Table
-
Chapter 5
Publication 1203–5.1 –– July, 1997
Specifications
Chapter 5 provides you with background information andspecifications that you may need to install, repair, or apply yourremote I/O communications module.
Table 5.A General Indications
Open Style(1336–GM1)
Enclosed Style –– 115V ac(1203–GD1)
Enclosed Style –– 24V dc(1203–GK1)
Environmental
Operating temperature 0–50°C (32–122°F) 0–50°C (32–122°F) 0–50°C (32–122°F)Storage temperature –40–85°C (–40–158°F) –40–85°C (–40–158°F) –40–85°C (–40–158°F)Relative humidity 0–95%, non–condensing 0–95%, non–condensing 0–95%, non–condensing
Electrical
Input voltage Supplied by drive 85–264V ac, 1 ph 24V dc, ±10%Input frequency NA 45–63 Hz NA
Input current NA 35 mA maximum 0.4 amps maximum
SCANport load 60 mA 60 mA 60 mA
Communications
Drive side SCANport peripheral interface
PLC side Allen Bradley remote I/O
Baud rates 57.6K, 115.2K, or 230.4K
Rack size 1/4, 1/2, 3/4, or full
Dimensions
Enclosure type Open (IP00) NEMA 1 (IP30) NEMA 1 (IP30)
Package size Not applicable 45mm x 76mm (1.8 x 3.0 in) 45mm x 76mm (1.8 x 3.0 in)
Chapter Objectives
Product Specifications
-
5–2 Specifications
Publication 1203–5.1 –– July, 1997
This communications module is designed to be used with thefollowing Allen-Bradley programmable controllers:
• PLC-2/30 with SD2 (communications module version 1.02 orlater)
• PLC-3
• SLC500TM with 1747-SN scanner• PLC 5/10TM, 5/15TM, 5/25TM family• PLC 5/30TM, 5/40TM, 5/40LTM, 5/60TM, 5/60LTM family and
PLC-5/80TM
• PLC 5/250TM
• PLC scanner modules and subscanners.
Note: This adapter was tested with the current revision level of thePLC processors listed. Earlier versions of the processors may not becompatible.
Programmable ControllerCompatibility
�
-
You can help! Our manuals must meet the needs of you, the user. This is your opportunity to make sure they do just that.By filling out this form you can help us provide the most useful, thorough, and accurate manuals available. Please take afew minutes to tell us what you think - then mail this form or FAX it.FAX: your local Allen-Bradley Sales Office or 414/512-8579
PUBLICATION NAME ________________________________________________________________________________________________
PUBLICATION NUMBER, DATE AND PART NUMBER (IF PRESENT) _________________________________________________________
✔ CHECK THE FUNCTION THAT MOST CLEARLY DESCRIBES YOUR JOB.
❏ SUGGEST/RESPONSIBLE FOR THE PURCHASE OF EQUIPMENT ❏ MAINTAIN/OPERATE PROGRAMMABLE MACHINERY
❏ DESIGN/IMPLEMENT ELECTRICAL SYSTEMS ❏ TRAIN/EDUCATE MACHINE USERS
❏ SUPERVISE FLOOR OPERATIONS
✔ WHAT LEVEL OF EXPERIENCE DO YOU HAVE WITH EACH OF THE FOLLOWING PRODUCTS?
NONE LITTLE MODERATE EXTENSIVE
PROGRAMMABLE CONTROL ❏ ❏ ❏ ❏
AC/DC DRIVES ❏ ❏ ❏ ❏
PERSONAL COMPUTERS ❏ ❏ ❏ ❏
NC/CNC CONTROLS ❏ ❏ ❏ ❏
DATA COMMUNICATIONS/LAN ❏ ❏ ❏ ❏
✔ RATE THE OVERALL QUALITY OF THIS MANUAL BY CIRCLING YOUR RESPONSE BELOW. (1) = POOR (5) = EXCELLENT
HELPFULNESS OF INDEX/TABLE OF CONTENTS 1 2 3 4 5
CLARITY 1 2 3 4 5
EASE OF USE 1 2 3 4 5
ACCURACY AND COMPLETENESS 1 2 3 4 5
QUALITY COMPARED TO OTHER COMPANIES’ MANUALS 1 2 3 4 5
QUALITY COMPARED TO OTHER ALLEN-BRADLEY MANUALS 1 2 3 4 5
✔ WHAT DID YOU LIKE MOST ABOUT THIS MANUAL?
✔ WHAT DID YOU LIKE LEAST ABOUT THIS MANUAL?
✔ PLEASE LIST ANY ERRORS YOU FOUND IN THIS MANUAL (REFERENCE PAGE, TABLE, OR FIGURE NUMBERS).
✔ DO YOU HAVE ANY ADDITIONAL COMMENTS?
✔ COMPLETE THE FOLLOWING.
NAME __________________________________________________________________________ COMPANY____________________________________________________________________________
TITLE _________________________________________________ DEPARTMENT_______________________________________________
STREET _______________________________________________ CITY _______________________ STATE ______ ZIP ___________________
TELEPHONE ___________________________________________ DATE ______________________________________________________
We Want Our Manuals to be the Best!C
UT
ALO
NG
DO
TTED
LIN
E✁
-
FOLD HERE
FOLD HERE
NO POSTAGENECESSARY
IF MAILEDIN THE
UNITED STATES
BUSINESS REPLY MAILFIRST CLASS PERMIT NO. 413 MEQUON, WI
ALLEN-BRADLEYAttn: Marketing CommunicationsP.O. Box 760Mequon, WI 53092-9907
POSTAGE WILL BE PAID BY ADDRESSEE
-
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for more than 90 years. We design, manufacture and support a broadrange of automation products worldwide. They include logic processors, power and motioncontrol devices, operator interfaces, sensors and a variety of software. Rockwell is one of theworld’s leading technology companies.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic •Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru •Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1203-5.1 – July 1997Supersedes Publication 1203-5.1 – April 1995
PN74001-002-01(F)Copyright 1997 Allen-Bradley Company, Inc. Printed in USA
Front CoverImportant User InformationSummary of ChangesTable of ContentsOverviewInstallationConfiguration and InterfacingTroubleshootingSpecificationsWho Should Use this Manual?Purpose of this ManualSafety PrecautionsFirmware SupportPLC Product CompatibilityTerms and AbbreviationsCommon Techniques Used in this ManualAllen–Bradley Support
Chapter 1Chapter ObjectivesAdapter DescriptionSCANport Device CompatibilityConfiguration SwitchesDatalinksSafety Precautions
Chapter 2Chapter ObjectivesSetting the Module Configuration SwitchesMounting the Remote I/O ModuleConnecting the Remote I/O CableConnecting the Termination ResistorConnecting the SCANport LinkConnecting the Power Supply
Chapter 3Chapter ObjectivesData Table UseData Transfer Through the Communications Module
Chapter 4Chapter ObjectivesTroubleshooting Table
Chapter 5Chapter ObjectivesProduct SpecificationsProgrammable Controller Compatibility
Back Cover