1203 getting started manual - rockwell automation1203-gk1 1336-gm1 because of the variety of uses...

55
Getting Started Manual Allen-Bradley Bulletin 1203 Remote I/O Communications Module Catalog Numbers 1203-GD1 1203-GK1 1336-GM1

Upload: others

Post on 26-Jan-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • GettingStarted Manual

    Allen-Bradley

    Bulletin 1203 Remote I/OCommunicationsModuleCatalo g Numbers1203-GD11203-GK11336-GM1

  • Because of the variety of uses for the products described in thispublication, those responsible for the application and use of thiscontrol equipment must satisfy themselves that all necessary stepshave been taken to assure that each application and use meets allperformance and safety requirements, including any applicable laws,regulations, codes and standards.

    The illustrations shown in this guide are intended solely for purposesof example. Since there are many variables and requirementsassociated with any particular installation, Allen-Bradley does notassume responsibility or liability (to include intellectual propertyliability) for actual use based upon the examples shown in thispublication.

    Allen-Bradley publication SGI-1.1, Safety Guidelines for theApplication, Installation, and Maintenance of Solid-State Control(available from your local Allen-Bradley office), describes someimportant differences between solid-state equipment andelectromechanical devices that should be taken into considerationwhen applying products such as those described in this publication.

    Reproduction of the contents of this copyrighted publication, inwhole or in part, without written permission of Allen-BradleyCompany, Inc., is prohibited.

    Throughout this manual we use notes to make you aware of safetyconsiderations:

    !ATTENTION: Identifies information about practicesor circumstances that can lead to personal injury ordeath, property damage or economic loss.

    Attention statements help you to:

    • identify a hazard• avoid the hazard• recognize the consequences

    Important: Identifies information that is critical for successfulapplication and understanding of the product.

    PLC, PLC–2, PLC–3, and PLC–5 are registered trademarks of Allen–Bradley Company, Inc.PLC–2/30, PLC–5/10, PLC–5/15, PLC–5/25, PLC–5/30, PLC–5/40, PLC–5/40L, PLC–5/60L, and PLC–5/250 are trademarksof Allen–Bradley Company, Inc.SCANport is a registered trademark of Allen–Bradley Company, Inc.SLC 500, SLC–5/02, and PLC–5/15 are registered trademarks of Allen–Bradley Company, Inc.DH+ is a registered trademark of Allen–Bradley Company, Inc.

    Important UserInformation

  • Summary of Changes

    Publication 1203–5.1 – July, 1997

    Summary of Changes

    We would like to call your attention to the following changes to the1203-5.1 manual which have occurred since the previous versionpublished in April, 1996. All references to page, table, and figurenumbers refer to the December publication. Page, table, and figurenumbers in the July, 1997 publication may not match the page, table,and figure number references mentioned here due to omissions orinclusions and, likewise, text and graphics shifting somewhat frompage to page.

    • Page 1–1 was updated to include the 1336 IMPACT and 1397drives.

    • Figure 1.1 was changed to reflect a change in LED colors.• Figure 1.2 was changed to reflect a change in LED colors.• Figure 4.1 was changed to reflect a change in LED colors.• Table 4.A was changed to reflect a change in LED colors.• Table 5.A was changed to identify the column headings more

    clearly.

  • soc–ii Summary of Changes

    Publication 1203–5.1 – July, 1997

  • Preface

    Who Should Use this Manual? P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose of this Manual P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Contents of this Manual P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Firmware Support P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PLC Product Compatibility P–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terms and Abbreviations P–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Common Techniques Used in this Manual P–3. . . . . . . . . . . . . . . . . . . Allen–Bradley Support P–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Local Product Support P–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Product Assistance P–4. . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 1

    Chapter Objectives 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adapter Description 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SCANport Device Compatibility 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Switches 1–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Datalinks 1–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions 1–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2

    Chapter Objectives 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Module Configuration Switches 2–1. . . . . . . . . . . . . . . . . .

    Switch SW3 2–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch SW2 2–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch SW1 2–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Mounting the Remote I/O Module 2–9. . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Remote I/O Cable 2–12. . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Termination Resistor 2–14. . . . . . . . . . . . . . . . . . . . . . . Connecting the SCANport Link 2–16. . . . . . . . . . . . . . . . . . . . . . . . . . .

    1305 Drive 2–16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1336 PLUS (7.5 – 500HP) and 1336 FORCE 2–16. . . . . . . . . . . . . . . SMP 3 2–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SMC Dialog Plus 2–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Connecting the Power Supply 2–18. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 3

    Chapter Objectives 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Controller Data Table Use 3–1. . . . . . . . . . . . . . . . . . . Data Transfer Through the Communications Module 3–3. . . . . . . . . . . .

    Table of Contents

    Overview

    Installation

    Configuration andInterfacing

  • ii

    Publication 1203–5.1 – July, 1997

    Chapter 4

    Chapter Objectives 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting Table 4–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 5

    Chapter Objectives 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Specifications 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Controller Compatibility 5–2. . . . . . . . . . . . . . . . . . . . .

    Troubleshooting

    Specifications

  • Preface

    Publication 1203–5.1 –– July, 1997

    Preface

    Read this preface to familiarize yourself with the rest of the manual.This preface covers the following topics:

    • who should use this manual• the purpose of this manual• safety precautions• firmware support• product compatibility• terms and abbreviations• conventions used in this manual• Allen–Bradley support

    Use this manual if you are responsible for designing, installing,programming, or troubleshooting control systems that use theBulletin 1203 remote I/O communications module. You must haveprevious experience with and a basic understanding of electricalterminology, configuration procedures, required equipment, andsafety precautions.

    To efficiently use this communications module, you must be able toprogram and operate an Allen-Bradley programmable controller. Inparticular, you must be familiar with remote I/O concepts andconfiguration and be able to program block transfer instructions.

    This manual provides you with the information you need to apply theremote I/O communications module that is available for productsthat include the SCANport� communications port. This manualdescribes the procedures for installing, configuring, andtroubleshooting the remote I/O communications module. Blocktransfer instructions are explained in a separate softwareprogramming manual.

    For information on specific product features, refer to the productmanual.

    Important: Read this manual in its entirety before installing,operating, servicing, or initializing the remote I/Ocommunications module.

    Who Should Use thisManual?

    Purpose of this Manual

  • P–2 Preface

    Publication 1203–5.1 –– July, 1997

    Contents of this Manual

    This manual contains the following information:

    Chapter: Title: Contents:

    PrefaceDescribes the purpose, background, and scope of thismanual as well as an overview of this product.

    1 OverviewProvides an overview of the adapter features,configuration information, and diagnostic information.

    2 Installation

    Provides the procedures you need to mount the Bulletin1203 remote I/O communications module, connect thepower, and configure the switches, as well as providingcabling and hardware information.

    3Configuration andInterfacing

    Provides information such as addressing, informationtransfer, and sample programs.

    4 TroubleshootingProvides information about the LED indications andfault descriptions.

    5 SpecificationsProvides the environmental, electrical, andcommunications specifications.

    Please read the following safety precautions carefully.

    !ATTENTION: Only personnel familiar withSCANport devices and the associated machineryshould plan or implement the installation, start-up,configuration, and subsequent maintenance of thisremote I/O communications module. Failure to complymay result in personal injury and/or equipmentdamage.

    !ATTENTION: This module contains ESD(Electrostatic Discharge) sensitive parts andassemblies. Static control precautions are requiredwhen installing, testing, servicing, or repairing thisassembly. Component damage may result if ESDcontrol procedures are not followed. If you are notfamiliar with static control procedures, referenceAllen-Bradley Publication 8000-4.5.2, Guardingagainst Electrostatic Damage, or any other applicableESD protection handbook.

    This manual supports communication module firmware versions1.xx and 2.xx (the xx designator may vary). Features that work withspecific firmware versions will be denoted as such.

    Safety Precautions

    Firmware Support

  • P–3 Preface

    Publication 1203–5.1 –– July, 1997

    This adapter is designed to be used with the following Allen-Bradleyprogrammable controllers:

    • PLC-2/30 with SD2 (communications module version 1.02 orlater)

    • PLC-3

    • SLC 500� with 1747-SN scanner• PLC-5/10�, PLC-5/15�, PLC-5/25� family• PLC-5/30�, PLC-5/40�, PLC-5/40L�, PLC-5/60�,

    PLC-5/60L� family, PLC-5/80�

    • PLC5/250�• PLC scanner modules and subscanners.

    This adapter was tested with the current revision level of the PLCprocessors listed. Earlier versions of the processors may not becompatible.

    The following terms and abbreviations are specific to this product.For a complete listing of Allen–Bradley terminology, refer to theAllen–Bradley Industrial Automation Glossary.

    In this manual, we refer to the:

    • remote I/O communications module as communications module• variable frequency ac drive (1305, 1336 FORCE, or 1336 PLUS)

    as the drive or SCANport device

    • The programmable logic controller as the programmablecontroller

    • Allen–Bradley remote input/output network as remote I/O• earth ground as Gnd

    The following conventions are used throughout this manual:

    • Bulleted lists provide information, not procedural steps.• Numbered lists provide sequential steps or hierarchical

    information.

    • Italic type is used for emphasis and chapter names.

    We also use this convention to call attention to helpful information.

    PLC Product Compatibility

    Terms and Abbreviations

    Common Techniques Used inthis Manual

  • P–4 Preface

    Publication 1203–5.1 –– July, 1997

    Allen–Bradley offers support services worldwide, with over 75Sales/Support Offices, 512 authorized Distributors and 260authorized Systems Integrators located throughout the United Statesalone, plus Allen–Bradley representatives in every major country inthe world.

    Local Product Support

    Contact your local Allen–Bradley representative for:

    • sales and order support• product technical training• warranty support• support service agreements

    Technical Product Assistance

    If you need to contact Allen–Bradley for technical assistance, pleasereview the information in the Troubleshooting chapter first. If youare still having problems, then call your local Allen–Bradleyrepresentative.

    Allen–Bradley Support

  • Chapter 1

    Publication 1203–5.1 –– July, 1997

    Overview

    Chapter 1 covers the following information:

    • a description of the communications module• SCANport device compatibility• configuration switches• datalinks• safety precautions

    The remote I/O communications module is an optional interfacedevice designed to provide a direct, digital link between anAllen-Bradley programmable controller and any device that uses theSCANport� communication port. The current list of products thatuse the SCANport communications interface includes: 1305, 1336PLUS, 1336 FORCE, 1336 IMPACT, 1397, and SMP3 and SMCDialog Plus. The board connects to these products through theSCANport peripheral interface.

    The adapter is available in both Open style (Figure 1.1) and Enclosed(Figure 1.2) type configurations. The Open style module mountsinside certain drives, depending on drive size (refer to Table 1.A).You can use the Enclosed module with any compatible SCANportdevice that is mounted outside the drive package.

    Table 1.A Remote I/O Configurations

    Designation Enclosure Power Supply Source Used With

    Open Style Open PC board Supplied by drive1336 PLUS➀

    1336 FORCE➁

    Enclosed IP3024V ac/dc separately supplied or120/240V ac separately supplied

    13051336 PLUS1336 FORCESMP3SMC Dialog PlusOther SCANport products

    ➀ 7.5 hp and higher sizes only➁ 7.5 hp and higher sizes with standard adapter board only

    The remote I/O communications module does not support version1.xx (the .xx designator may vary) of the 1305 drive. If you try touse the remote I/O communications module with a version 1.xx1305, the remote I/O communications module will continually resetitself, resulting in the red adapter fault status LED and the amberSCANport status LED both flashing simultaneously indicating anerror condition. Firmware revision 2.xx or higher on the 1305 isrequired to support remote I/O communications and block transfer.

    Chapter Objectives

    Adapter Description

    SCANport DeviceCompatibility

  • 1–2 Overview

    Publication 1203–5.1 –– July, 1997

    Figure 1.1 Open Style Communications Module

    SW1

    Front View

    SW2SW3

    Remote I/O Connector

    Adapter FaultStatus (Red)

    SCANport Status(Green)

    Adapter Health(Green)

    Remote I/O Status (Green)

    Remote I/O Active (Green) J4

    181818

    Block Transfer EnableLogic Command / Status Enable

    Analog Reference / Feedback EnableDatalink A-D enable

    Truncate last datalinkStarting Quarter

    Baud RateRack Fault

    Hold Last StateLast Rack

    Rack Address

  • 1–3Overview

    Publication 1203–5.1 –– July, 1997

    Figure 1.2 Enclosed Style Communications Module

    Front View

    SW1

    Remote I/O Status (Green)

    Remote I/O Active (Green)

    ConnectPower Supply Here

    Adapter Health (Green)

    SCANport Status (Green)

    Adapter Fault Status (Red)

    Remote I/OConnector

    SCANport CommunicationCable Connector

    Bottom View

    1

    Switch SW3– Block Transfer Enable– Logic Command/ Status Enable– Analog Reference/ Feedback Enable– Datalink A-D enable– Truncate last datalink

    Switch SW1– Rack Address

    SW28 18SW3 18

    Switch SW2– Starting Quarter– Baud Rate– Rack Fault– Hold Last State– Starting Quarter

    . . .

  • 1–4 Overview

    Publication 1203–5.1 –– July, 1997

    Figure 1.3 Typical Programmable Controller/SCANport Device Interconnection

    SCANport

    Communications Module

    PLC

    ...

    1305*MicroDrive

    1336 PLUS

    Open Style RIO Adapter

    Remote I/O Link

    .

    Other Remote I/O Devices

    ÁÁÁÁÁÁ

    ÀÀÀÀ

    Panel View Operator Terminal

    *NOTE: Refer to Page 1–1 for compatibilityrequirements of SCANport devices

    SCANport

    Communications Module

    SMP 3

    Communications Module

    SMC Dialog Plus

  • 1–5Overview

    Publication 1203–5.1 –– July, 1997

    The remote I/O communications module contains three DIP switchesSW1, SW2, and SW3 (Figure 1.1 and Figure 1.2). Switches are setOn or Off as detailed in Figure 1.4. For a detailed explanation ofswitch configuration, refer to Chapter 2, Installation.

    Figure 1.4Configuration Switch

    Side View of Typical Switches

    Open

    8

    Closed (On)

    1234567

    OPEN

    OpenOpen (Off)

    Rocker Switch

    Open

    Open

    Slide Switch

    Switch Designation asshown in this manual

    OFF (OPEN)

    ON

    Datalinks are a SCANport mechanism for transferring additionalinformation between a programmable controller and a SCANportdevice. Each datalink switch on the adapter reserves two words ofthe programmable controller I/O image table. The 1305, 1336PLUS, and 1336 FORCE drives support this mechanism. Foradditional details, refer to Chapter 3, Configuration and Interfacing.

    Configuration Switches

    Datalinks

  • 1–6 Overview

    Publication 1203–5.1 –– July, 1997

    Please read the following safety precautions.

    !ATTENTION: This board contains ESD(Electrostatic Discharge) sensitive parts andassemblies. Static control precautions are requiredwhen installing, testing, servicing, or repairing thisassembly. Component damage may result if you do notfollow ESD control procedures. If you are not familiarwith static control procedures, refer to Allen-Bradleypublication 8000-4.5.2, Guarding Against ElectrostaticDamage, or any other applicable ESD ProtectionHandbook.

    !ATTENTION: Servicing or configuring the RIOboards on drives larger than 3hp involves opening the1336 drive cabinet which creates the potential to comein contact with other drive components. Energizedindustrial control equipment can be hazardous. Severeinjury or death can result from electrical shock, burn,or unintended actuation of controlled equipment.Recommended practice is to disconnect and lock outall control equipment from power sources, and allowstored energy in any capacitors to dissipate. If youmust work near energized equipment, you must followthe safety related work practices of NFPA 70E,Electrical Safety Requirements for EmployeeWorkplaces.

    Safety Precautions

  • Chapter 2

    Publication 1203–5.1 –– July, 1997

    Installation

    Chapter 2 provides information to help you:

    • set the module configuration switches• mount the remote I/O module• connect the remote I/O cable• connect the termination resistor• connect the SCANport link• connect the power supply

    Read this chapter completely before you attempt to install orconfigure your remote I/O communications module. Double checkall connections and option selections before you apply power.

    Important: Switch selections take effect only on power–up. If youchange selections after power is applied, cycle thepower to use the new settings.

    This publication describes switches as being either on or off. If theswitch assembly has the word OPEN printed on it, the word OPENcorresponds to OFF (O).

    When you change the adapter board configurations, keep in mind theaddressing conventions of the type of processor that you are using. Inall cases, each remote I/O device must have a unique address that theprocessor can recognize.

    Important: This adapter is not compatible with complementary I/Oconfigurations because the adapter uses both output andinput image words for proper drive control.

    !ATTENTION: When you make changes to the switchsettings, use a blunt, pointed instrument such as a ballpoint pen. Do not use a pencil because the lead(graphite) of the pencil may damage the switchassembly.

    ATTENTION: Failure to check connections andswitch settings for compatibility with your applicationwhen configuring the communications module, couldresult in personal injury and/or equipment damage dueto unintended or undesirable operation of the drive orprocess equipment.

    Chapter Objectives

    Setting the ModuleConfiguration Switches

  • 2–2 Installation

    Publication 1203–5.1 –– July, 1997

    Switch SW3

    Set switch SW3 first. The settings on this switch determine how theSCANport device uses the data contained in the programmablecontroller I/O image table. SW3 also establishes the minimum racksize that this communications module requires.

    The switches are labeled in the same orientation as they appear onthe board.

    Table 2.A, SW3 Image Table Map, and Figure 2.2, SW3 Flowchart,are included to help you set the DIP switches properly. It may alsobe helpful to color in the final switch settings in Figure 2.1 as avisual record of your SW3 settings. Chapter 3 contains severalexamples of how to fill in the worksheet and set these DIP switches.

    Figure 2.1 Configuration Switch SW3 Settings

    J1

    SW3

    BlockTransfer

    Off

    Datalink ATransfers

    On

    LogicCommand/Status

    On

    Off

    Reference/Feedback

    On

    Off

    On

    Off

    Datalink BTransfers

    Datalink CTransfers

    On

    Off

    On

    Off

    On

    Off

    Datalink DTransfers

    8 1234567

    OPEN

    Truncate➀➁

    Last Datalink

    ➀ IMPORTANT: Only available on communications modules with version 1.02 or later firmware.➁ All datalinks are two words, the truncate function will delete the last datalink word. (If “Datalink B” is the last used, “Data in B2” and “Data Out B2” will be truncated.)

    Open Style Enclosed Style

    Off

    On

    NotEnabled

    Enabled

    Off (Open)

    On

  • 2–3Installation

    Publication 1203–5.1 –– July, 1997

    Table 2.ASW3 Image Table Map

    RESERVED FOR: MinimumR i Start AtG pOutput Image Input ImageRequired

    Rack Size➀Start AtGroup

    R 01/4 Rack 0, 2, 4, or 6

    lf R 0Half Rack 0, 2, or 4

    R 03/4 Rack 0 or 2

    ll R 0 nlyFull Rack 0 only

    ➀ Use this to select settings for switch SW2, switches 1 and 2

    How to use Table 2.A:

    1. Use Figure 2.2 to set DIP switch SW3 and fill out Table 2.A.

    2. Use minimum rack size shown in Table 2.A to set DIP switchSW2-1 and SW2-2.

    Figure 2.2 SW3 Flowchart

    Will block transfer or block transfer RIO pass thrube used?

    1. Block Transfer

    YES

    1. Write “Block Transfer” in word 0 of both the inputand the output image2. Set SW 3-1 to on

    Will the SCANport device be controlled by (Start/Stopetc.) or will the Logic Status by monitored by the PLC?

    2. Logic Command

    NO

    NO

    2. Move to step 2

    YES

    1. Write “Logic Cmd” in the output image and “LogicStatus” in the input image of the next available word2. Set SW3-2 to on

    Will a reference or feedback be provided from/to the programmable controller?

    3. Reference/Feedback

    NO

    YES

    1. Write “Reference” in the output image and “Feedback” in the input image of the next availableword2. Set SW3-3 to on

    NOTE: For detailed information on block transfermessages refer to the 1203-5.0 Reference Manual.

    Step

    Step

    Step

    1. Set SW3-1 to off

    2. Move to step 31. Set SW3-2 to off

    2. Move to step 41. Set SW3-3 to off

  • 2–4 Installation

    Publication 1203–5.1 –– July, 1997

    Figure 2.2SW3 Flowchart continued

    Will Datalink Group B be used?

    Step 5. Datalink B Transfer

    YES

    NO

    1. Write “Datalink B“ in the output and input image of the next two available words2. Set SW3-5 to on

    Will Datalink Group C be used?

    Step 6. Datalink C Transfer

    YES

    NO

    1. Write “Datalink C” in the output and input imageof the next two available words2. Set SW3-6 to on

    Will Datalink Group D be used?

    Step 7. Datalink D Transfer

    YES

    NO

    1. Write “Datalink D” in the output and input image of the next two available words2. Set SW3-7 to on

    Step 9. Calculate minimum rack size

    Refer to Table 2.A on page page 2–3.1. Record the minimum rack size in Table 2.A on page 2–3.2. Use the minimum rack size to set Dip switches SW2-1 and SW2-2.

    Will the last Datalink be one word(truncate last Datalink) ?

    Step 8. Truncate Last Datalink

    YES

    NO

    1. Cross out the last word of the last Datalink groupused in the output and input image table2. Set SW3-8 to on

    2. Move to step 61. Set SW3-5 to off

    2. Move to step 71. Set SW3-6 to off

    2. Move to step 81. Set SW3-7 to off

    2. Move to step 91. Set SW3-8 to off

    Will Datalink Group A be used?

    4. Datalink A Transfer

    YES

    NO

    1. Write “Datalink A” in the output and input imageof the next two available words2. Set SW3-4 to on

    Step

    2. Move to step 51. Set SW3-4 to off

  • 2–5Installation

    Publication 1203–5.1 –– July, 1997

    Switch SW2

    Switch SW2 determines Rack Size, Last State, Rack Fault, and BitRate Selections as shown in Figure 2.3.

    The switches are labeled in the same orientation as they appear onthe board.

    Figure 2.3 Configuration Switch SW2 Settings

    On

    J1

    SW2

    Starting Module Group➁

    On

    Last RackSetting➃

    HoldLastState➄ ➅

    ZeroImageon PLCFault

    Run atLast State

    Communications Loss➅

    NoFault

    Fault onCommLoss On

    RIO Baud Rate

    57.6kbps

    115.2kbps

    230.4kbps

    LastRack

    Not–LastRack

    Off

    On

    Off

    Off Off

    On

    Off

    On

    Off

    On

    Off

    Off

    Off

    On

    Off On

    0

    4

    6

    ➀ If this switch is set to No Fault,the setting of the Hold Last Stateswitch determines the data sent to the SCANport device when thePLC is in Reset/Program/Test.

    8 1234567

    OPEN

    Off

    Enclosed StyleOpen Style

    2

    OFF (OPEN)

    ON

    NoFault➀

    FaultDrive On

    Off

    ➁ The setting of this switch is determinedby the amount of discrete I/O that will bepassed between the PLC and the drive.Refer to Table 2.A for more information.

    Reset/Program/Test➂ ➄

    ➂ This switch is active onFirmware Version 2.xxmodules only. It is not used bymodules containing FirmwareVersion 1.xx.

    ➃ Set this switch on the lastmodule used for a given rackaddress. It does notelectrically terminate the RIOlink.

    ➄ Refer to Figure 2.4. ➅ Refer to Figure 2.5and Figure 2.6.

  • 2–6 Installation

    Publication 1203–5.1 –– July, 1997

    Figure 2.4 PLC Switched to Program

    Fault drive in program set

    Off

    Hold last state On

    On

    Off

    Send command on to the drive

    Send a 0 command tothe drive

    Generate a drive communicationsloss fault

    Figure 2.5 SCANport Cable Unplugged

    Communications loss

    Off

    Hold last state On

    On

    Off

    Send the last image of the drive status to the PLC

    Send a value of 0 to thePLC for the drive status

    Stop responding to the PLC. The PLC generates a rack fault

    Figure 2.6 RIO Cable Disconnected

    Communications loss

    Off

    Hold last state On

    On

    Off

    Send the last command to the drive

    Send zero images tothe drive.

    Generate a drive communicationsloss fault

  • 2–7Installation

    Publication 1203–5.1 –– July, 1997

    Switch SW1

    Switch SW1 controls starting quarter and rack address options asshown in Figure 2–7.

    Note: When using a PLC-2 family processor, you need to offset thevalue of the rack number by one. The PLC-2 cannot have a remoteI/O rack numbered zero. Therefore, add a value of one to the RackNo value in Table 2.B when writing your PLC code.

    Figure 2.7 Configuration Switch SW1 Settings

    12345678

    J1

    SW1

    Not Used

    Rack Addressing (See Table 2.B.)

    OPEN

    Enclosed StyleOpen Style

    Off (Open)

    On

  • 2–8 Installation

    Publication 1203–5.1 –– July, 1997

    Table 2.BSwitch SW1 SettingsSW1-8 through SW1-1 DIP Switch Definitions, Rack Address

    Rack No. SW1-3SW1-4SW1-5SW1-6SW1-8

    0001020304050607101112131415161720212223242526273031323334353637

    OnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOn

    OnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOffOffOffOffOffOffOffOffOff

    OnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOffOnOnOnOnOnOnOnOnOffOffOffOffOffOffOffOff

    OnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOffOnOnOnOnOffOffOffOff

    OnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOffOnOff

    SW1-7

    OnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOffOnOnOffOff

    SW1-2 SW1-1

    not usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot usednot used

  • 2–9Installation

    Publication 1203–5.1 –– July, 1997

    The remote I/O communications module can be provided in threemounting configurations:

    • Open Style board factory installed in a drive (not available for alldrives)

    • Open Style board as a separate kit• Enclosed style for panel mount or DIN rail mount

    This section provides mounting information for the Enclosed styleand the Open style kit.

    Figure 2.8 Open Style Communications Module Mounting Location (1336 Plus7.5–500HP)

    1336 PLUS Main Control Board

    TB2TB1

    L OPTION

    J7

    J9

    Human Interface Module

    J4

    Open Communications ModuleMounts Here

    MemoryModule

    U44

    J3

    J1

    U50 U54 U56

    Mounting Screws & Standoffs Qty 4

    SCANport 6

    Install the board with the component side facing you.

    Mounting the Remote I/OModule

  • 2–10 Installation

    Publication 1203–5.1 –– July, 1997

    Figure 2.9 Open Style Communications Module Mounting Location (1336FORCE Drive)

    1336 FORCE Main Control Board

    TB2

    L OPTION

    J4

    Open Communications ModuleMounts Here

    J1

    Mounting Screws & Standoffs Qty 4

    1336 FORCE Standard Adapter Board

    SCANport 6

    Install the board with the component side facing you.�

  • 2–11Installation

    Publication 1203–5.1 –– July, 1997

    Figure 2.10 Enclosed Style Communications Module Dimensions

    ÉÉÉÉÉÉÉÉÉÉÉÉDIN RAIL

    ÉÉÉÉÉÉÉÉÉÉ

    ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

    ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ

    45 mm

    All dimensions in millimeters and (inches)

    (1.8)

    Back View(4.8)123 mm

    Side View

    (1.8)45mm

    (1.75)44 mm

    Note: The enclosure requires clearance at the top and bottom forproper cooling. Additional space will be required if access to DIPswitches is desired without having to remove the device.

    Front ViewTop View

    25 mm(1)

    DIN rail mounting clip

    25 mm(1)

    ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

    70 mm(2.7)

    DINRAIL

    ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

    DINRAIL

    ÉÉÉÉÉÉÉÉ

    76 mm(3.0)

    DIN RAIL

  • 2–12 Installation

    Publication 1203–5.1 –– July, 1997

    You must connect remote I/O communications module cables asshown in the example in Figure 2.11. Refer to Table 2.C for cableguidelines.

    Figure 2.11 Remote I/O Module Interconnections

    Plus

    ÉÉÉ

    J4

    Blue

    Shield

    Clear

    1SH2

    ÉÉÉBlue

    Shield

    Clear

    REMI/O

    PLC

    ...

    Enclosed Communication Module

    1SH

    2

    1336

    Open StyleCommunicationModule

    .

    ÉÉÉ

    J4

    Blue

    Shield

    Clear

    1

    SH

    2

    Connecting the Remote I/OCable

  • 2–13Installation

    Publication 1203–5.1 –– July, 1997

    Twinaxial cable used for remote I/O (RIO) and Data Highway+(DH+TM) communications represents a communicationstransmission line in which certain characteristics exist. The followingare some general guidelines that must be adhered to in order toobtain the best results.

    Cable Type – Only 1770-CD Belden #9463 is approved for RIO andDH+ installations. All other cable types or manufacturers, no matterhow similar, are untested. Using other cable types is strictly at yourown risk.

    Important: The transmission rate determines the maximum cablelength.

    Table 2.CTwinaxial Cable Guidelines

    Remote I/O link communications rate

    Cable lengthcannot exceed:

    57.6 kbps

    115.2 kbps

    230.4 kbps

    3,048 m (10,000 ft)

    1,524 m (5,000 ft)

    762 m (2,500 ft)

    Connections – Connect all three conductors, blue, clear, and shield,at each wiring point. No additional ground connections should bemade to the shield.

    Important: DO NOT use star type connections. Only two cablesmay be connected at any wiring point on a seriesconnection application.

    OK

    These are general rules and certain deviations may be warrantedbecause diverse installation and environmental concerns couldchange the requirements.

  • 2–14 Installation

    Publication 1203–5.1 –– July, 1997

    You must terminate both ends of a remote I/O link to ensure properoperation. This termination is required only at the ends of thephysical cable. Each remote I/O network should have exactly twotermination resistors installed. Use Table 2.D and Figure 2.12 andFigure 2.13 to determine the proper termination for your particularlink. Termination resistor R3 is located on the board, and the J2jumper selects this resistor.

    Table 2.DTermination Resistor Requirements

    If this device is an enddevice of a remote I/O link:

    Terminate the link by:

    Programmable controller Refer to the manual for your model processor.

    Open style, single pointremote I/O adapter

    Set jumper J2 in position 1–2 for termination and 2–3 forno termination as shown in Figure 2.12. The jumperenables a 150 ohm resistor as the terminator resistor.

    Enclosed style single pointremote I/O adapter

    Connect a terminator resistor between the remote I/Oterminals labeled 1 and 2 as shown in Figure 2.13.Use either a 150 Ohm or an 82 Ohm terminator.• You must use an 82 Ohm resistor if the remote I/O link is

    operating at 230.4 kbps (terminator must be connected at boththe scanner and the adapter).

    • You should use an 82 Ohm resistor if the remote I/O link isoperating at 57.6 kbps or 115.2 kbps unless one of the deviceson the link is listed in Table 2.E. If you are using a devicelisted in Table 2.E, then you must use a 150 Ohm terminator.

    Important: The following products (Table 2.E) cannot be on a linkusing 82-Ohm termination resistors.

    Table 2.EUnsupported Remote I/O Link Devices

    Device Type Series

    Scanners

    Adapters

    Miscellaneous

    1771-SN1772-SD, -SD21775-SR1775-S4A, -S4B6008-SQH1, -SQH2

    All

    Catalog Number

    1771-AS1772-ASB1771-DCM

    1771-AF

    AllAAll

    All

    Connecting theTermination Resistor

  • 2–15Installation

    Publication 1203–5.1 –– July, 1997

    Figure 2.12 Terminating a Remote I/O Link Using the Module Mounted Resistor

    ÉÉ

    J4

    J5

    T1

    J2123

    Blue 1

    2

    SHShield

    Clear

    123

    123

    Not Last Rack(Factory Default)

    Last Rack,Termination

    Resistor InsertedEnables 150 ohm

    Termination Resistor

    Figure 2.13 Terminating a Remote I/O Link Using an External Resistor

    ToBlue

    ShieldClear

    Remote I/O Module

    Another Remote I/OLink Device

    ÉÉ

    1

    2

    I50 Ohmor

    82 Ohm

    EnclosedRemote I/O Module

    Sh

    1 watt,± 10%

  • 2–16 Installation

    Publication 1203–5.1 –– July, 1997

    SCANport cables are available in either Male–to– Male orMale–to–Female configuration. You can connect cables of up to 10meters (33 feet) from the master to the SCANport device (A inFigure 2.14). If you use a port expander as shown in Figure 2.14,subtract the cable length from the master to the port expander fromthe cable length used to connect the device to the expander (B1+ C =maximum 10 meters).

    1305 Drive

    An Allen-Bradley SCANport link cable is used to make theconnection between the communications module and the drive(Figure 2.14).

    Figure 2.14 SCANport connection on Remote I/O

    1305 Drive

    Human Interface Module

    Port 1

    A

    Remote I/O Communication Module

    Port 2

    OptionalMale–FemaleCable

    OptionalMale–Male Cable

    B1

    2 3 4 5

    Port Expander

    B2

    C

    Remote I/O Communication Module

    Important: The maximum cable distance between any two masterdevices cannot exceed 10 meters (33 feet) of cable. Forexample, B1 + C = maximum of 10 meters or B1 + B2= maximum of 10 meters.

    1336 PLUS (7.5 – 500HP) and 1336 FORCE

    Refer to the product manual for connection information. On largerhorsepower 1336 PLUS and 1336 FORCE drives with an openremote I/O module mounted in the drive, you do not need a separateSCANport cable connection.

    Connecting the SCANportLink

  • 2–17Installation

    Publication 1203–5.1 –– July, 1997

    SMP 3

    An Allen-Bradley SCANport cable is used to connect thecommunications adapter and an SMP 3. See the cable requirementson page 2–16 for details on cable length.

    Figure 2.15 SCANport connection on Remote I/O

    AB0538A

    EnclosedAdapter

    SMP 3

    RESET

    RemoteReset

    SCANport

    SMC Dialog Plus

    An Allen-Bradley Bulletin 1202 SCANport cable is required toconnect the communications adapter and the SMC Dialog Pluscontroller.

    Figure 2.16 SCANport connection on Remote I/O

    AB0537A

    Allen-Bradley SMC Dialog Plus

    ESC SEL

    EnclosedAdapter

    SMC Dialog Plus

    SCANport

  • 2–18 Installation

    Publication 1203–5.1 –– July, 1997

    The Enclosed remote I/O is powered from a separate 24V dc or115V ac power supply (Figure 2.17). With the open style remote I/Oboard mounted in the drive, no separate power supply connectionsare required.

    Figure 2.17 Typical Power Supply Connection

    Enclosed Remote I/O Communication Module

    115/230VTypical Connection

    LNG

    GND

    115V AC Hi115V AC Low

    Enclosed Remote I/O Communication Module

    24V DCTypical Connection

    +–G

    GND

    24V DC +PowerSupply –

    Connecting the PowerSupply

  • Chapter 3

    Publication 1203–5.1 –– July, 1997

    Configuration and Interfacing

    Chapter 3 provides information on how the remote I/Ocommunications module and a programmable controllercommunicate. The following topics are covered:

    • programmable controller data table use• data transfer through the adapter

    Important: Block transfer messaging is covered in a separatepublication.

    !ATTENTION: When you configure a system for thefirst time, disconnect the motor from the machine orprocess during the initial testing.

    The remote I/O communications module allows a SCANport deviceto look and act like a remote I/O chassis when connected to aprogrammable controller. Data contained in the input/output imagetable is transferred between the programmable controller by theremote I/O scanner, the same as with any remote I/O chassis. Youcontrol the location and amount of data transferred by setting therack address and starting quarter/rack size DIP switches on theremote I/O communication module.

    Figure 3.1 shows a typical example of data transfer between aprogrammable controller, the remote I/O communications module,and a 1336 PLUS drive. This same concept works for all SCANportdevices. In this example, assume that you have set the DIP switchesfor rack address 2, a rack size of 1/4 (or greater if larger amounts ofdata are to be transferred), and has enabled (Set) the LogicCommand/Status switch.

    Data placed in the output image table area for rack address 2 istransferred to the remote I/O communications module every rackscan. The communications module then transfers the data to the 1336PLUS drive as Logic Command. Logic status data is transferredfrom the drive to the remote I/O communications module and thenpassed to the programmable controller during a rack scan.

    !ATTENTION: The RIO to SCANport conversion isasynchronous. Any data sent to the adapter for transferto the drive must be maintained until the drive hasreceived the data.

    Chapter Objectives

    Programmable ControllerData Table Use

  • 3–2 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.1 Typical Example of Data Transfer Through the Communications Module

    00

    Programmable Controller I/O Image Table

    01

    02

    03

    04

    05

    06

    07

    11

    12

    13

    14

    15

    16

    17

    00

    01

    02

    03

    04

    05

    06

    07

    11

    12

    13

    14

    15

    16

    17

    Rack 2Output Image

    Word 0Word 1Word 2Word 3Word 4Word 5Word 6Word 7

    Word 0Word 1Word 2Word 3Word 4Word 5Word 6Word 7

    Rack 2Input Image

    Remote I/O

    Logic Command/Status Enabled

    SCANport

    1336 PLUS Drive

    Logic Command

    Logic Status

    Remote I/OCommunications

    Module

    Stop

    Start

    Jog

    Clear Faults

    Direction

    Direction

    Local

    Mop Increment

    Accel Time

    Decel Time

    Enabled

    Running

    Cmd Direction

    Actual Direction

    Accelerating

    Decelerating

    Alarm

    Faulted

    At Speed

    Local

    Local

    Local

    Accel Time

    10

    Decel Time

    Ref Select

    Ref Select

    Ref Select

    MOP Decrement

    10

    Ref Select

    Ref Select

    Ref Select

    Ref Select

    This is a typical example of data transfer from a PLC to a 1336PLUS drive. Refer to the manual provided with yourSCANport–compatible product for actual Control and Status words.

    Important: The communications module does not scale the datathat is transferred. If data in the programmablecontroller is manipulated in units other than deviceunits, the data must first be converted before being sentto the device. Consequently, all scaling of the data mustbe done in the PLC. Refer to the appropriate SCANportdevice manual for details on device units.

  • 3–3Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    DIP switch SW3 determines how the data contained in theprogrammable controller I/O image table is used in the drive (Figure3.2). The first three switches (1 through 3) select the basic controlfeatures. Switches 4 through 7 support additional capability totransfer selected parameter information between the drive and theprogrammable controller. Products that have this capability have agroup of parameters for adapter I/O. These parameters are identifiedas “Data In” and “Data Out” parameters. Each datalink switch on theadapter consumes two words (unless truncated using SW3–8) in boththe input and output image table of the programmable controller.

    The following are the rules for using datalink switches:

    1. Normally, each datalink switch reserves two words in both theinput and output image tables of the programmable controller.The starting module group/rack size switch (SW2, 1-2) on theadapter must be set to support this.

    2. The truncate last datalink switch truncates the last datalink to oneword in the input and output image table, instead of two. You canuse this to minimize the required rack size consumed by acommunications module.

    3. Each set of datalink parameters in the drive can only be used byone remote I/O communications module. If more than onemodule is connected to a single SCANport link, the switchsettings must not conflict.

    4. Parameter setting in the drive determine the data passed throughthe datalink mechanism. Refer to the “Adapter I/O” group in thedrive manual for details.

    Table 3.ADatalink Switch SW3 Settings

    SW3 switch: State: Input and output parameter assignments in the drive:

    DatalinkASW3–4

    OnOff

    Reserves Data In/Out A for this adapterData In/Out A not used by this adapter

    Datalink BSW3–5

    OnOff

    Reserves Data In/Out B for this adapterData In/Out B not used by this adapter

    Datalink CSW3–6

    OnOff

    Reserves Data In/Out C for this adapterData In/Out C not used by this adapter

    Datalink DSW3–7

    OnOff

    Reserves Data In/Out D for this adapterData In/Out D not used by this adapter

    TruncateLast DatalinkSW3–8

    OnOff

    Truncates the last datalink to one wordNo truncation performed

    Data Transfer Through theCommunications Module

  • 3–4 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.2 Typical Programmable Controller Configuration Using Datalink A

    Output Image

    Blk Transfer

    Logic Command

    Reference

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Remote I/O Communications

    Module

    Data In A1

    Input Image SW3

    DriveProgrammableController

    I/O Image Table

    Blk Transfer

    Logic Status

    Feedback

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Data In A2

    Datalink A

    Data Out A1Data Out A2

    SW3

    Parameters

    NOTE: This configuration requires a minimumrack size of 3/4 rack.

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C Off

    Datalink D Off

    Truncate last Datalink Off

    Datalink A On

    Reference/Feedback On

    Logic Command On

    Block Transfer On

    AB0504B

  • 3–5Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.3 Typical Programmable Controller Configuration for 1305 and 1336PLUS/FORCE without Block Transfer

    Output Image

    Logic Command

    Reference

    WORD 2

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Remote I/O Communications

    Module

    Input Image SW3

    1336 PLUS/FORCEController

    Programmable ControllerI/O Image Table

    Logic Status

    Feedback

    WORD 2

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Data In A1Data In A2

    Data In B1Data In B2

    Datalink A

    Datalink C Data In C1Data In C2

    Data Out A1Data Out A2

    Data Out B1Data Out B2

    Data Out C1Data Out C2

    Datalink A

    Datalink C

    Data Out D1Data Out D2

    Data In D1Data In D2

    Parameters

    NOTE: This configuration requires a minimumrack size of 3/4 rack.

    SW3

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C On

    Datalink D Off

    Truncate Last Datalink Off

    Datalink A On

    Reference/Feedback On

    Logic Cmd/Sts On

    Block Transfer Off

    AB0505A

  • 3–6 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.4 Typical Programmable Controller Configuration for 1305 and 1336PLUS/FORCE with Block Transfer

    Block Transfer

    Logic Status

    Feedback

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Output Image

    Block Transfer

    Logic Command

    Reference

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Remote I/O Communications

    Module

    Input ImageSW3

    1336 PLUS/FORCEController

    Programmable ControllerI/O Image Table

    Data In A1 DataIn A2

    Data In B1 Data In B2

    Data Out A1Data Out A2

    Data Out B1Data Out B2

    Datalink A

    Datalink B*

    Datalink A

    Datalink B*

    Parameters

    *NOTE: Datalink B has been truncated on a1/4 rack boundary. Only the first word of Datalink B istransferred. This configuration requires aminimum rack size of 3/4 rack. SW3

    12

    34

    56

    78

    OPEN

    Logic Cmd/Sts On

    Block Transfer On

    Reference/Feedback On

    Datalink A On

    Datalink B On

    Datalink C Off

    Datalink D Off

    Truncate Last Datalink On

    AB0506A

  • 3–7Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.5 Typical Programmable Controller Configuration for SMP3

    Output Image

    Logic Command

    WORD 1 REF

    WORD 2

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    Remote I/O Communications

    Module

    Input Image SW3

    SMP3ProgrammableController I/O Image Table

    Logic Status

    Feedback

    WORD 2

    WORD 3

    WORD 4

    WORD 5

    WORD 6

    WORD 7

    SW3

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C Off

    Datalink D Off

    Truncate Last Datalink Off

    Datalink A Off

    Feedback On

    Logic Cmd/Sts On

    Block Transfer Off

    AB0507A

    *NOTE: While the reference is sent via the SCANportto the SMP3, the reference is ignored by the SMP3.

  • 3–8 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.6 Typical Programmable Controller Configuration for SMC Dialog Plus withoutBlock Transfer

    Output Image

    Logic Command

    Remote I/O Communications

    Module

    Input Image SW3

    SMC Dialog PlusProgrammableController I/O Image Table

    Logic Status

    Feedback➀

    SW3

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C Off

    Datalink D Off

    Truncate Last Datalink Off

    Datalink A Off

    Reference/Feedback Off

    Logic Cmd/Sts On

    Block Transfer Off

    AB0507A

    ➀ Current Phase A

  • 3–9Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.7 Typical Programmable Controller Configuration for SMC Dialog Plus withBlock Transfer

    Output Image

    Block Transfer

    Logic Command

    Remote I/O Communications

    Module

    Input Image SW3

    SMC Dialog PlusProgrammableController I/O Image Table

    Block Transfer

    Logic Status

    Feedback➀

    SW3

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C Off

    Datalink D Off

    Truncate Last Datalink Off

    Datalink A Off

    Reference/Feedback Off

    Logic Cmd/Sts On

    Block Transfer On

    AB0536A

    ➀ Current Phase A

  • 3–10 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.8SLC 5/02TM Controller Example

    Example Information:PLC Type – SLC 5/02Drive Type – 1336 PLUSDrive Rack Address – 2Rack Size – 1/2 Rack MinimumStarting Module Group – 0

    When the Machine Start PushButton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sentby the PLC or any other control device. (Start button is a normally open contact in this example.)

    MachineSTARTPushbutton I : 1.8

    0

    DriveSTARTCommand 0 : 1.16

    1

    When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).

    This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zeroto Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)

    Drive Frequency Command

    MachineSTOPButton I : 1.8

    1

    DriveSTOPCommand 0 : 1.16

    0

    0

    Drive StopCommand 0 : 1.16

    1

    Drive Running Bit I : 1.16

    N7 : 0160000: 1.1716000

    MOV

    MOVESource

    Dest

    PLCWORD

    OUTPUTIMAGE

    INPUTIMAGE

    0

    1

    2

    3

    Logic Cmd

    Reference

    Datalink A

    Datalink A

    Logic Sts

    Feedback

    Datalink A

    Datalink A

    PLC Image Table Map

    12

    34

    56

    78

    OPEN

    Datalink B Off

    Datalink C Off

    Datalink D Off

    Truncate Last Datalink Off

    Datalink A On

    Reference/Fdbk On

    Logic Cmd/Sts On

    Block Transfer Off

    AB0508A

  • 3–11Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    SLC 5/02 Example continuedWhen the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. (Jog button is a normally open contact in this example.)

    When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.

    Drive Data In A1(Data to Drive)

    N7 : 1500

    0: 1.180

    MOV

    MOVESource

    Dest

    When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary nor-mally open contact in this example.)

    DriveClear FaultsCommand0 : 1.16

    Machine ClearFaultsPushbutton I : 1.8

    3 3

    When the Drive is running, the PLC will receive a Drive Running Status Bit.

    MachineRunningIndicator0 : 1.8

    DriveRunningStatus Bit I : 1.16

    1 1

    DriveJOGCommand0 : 1.16

    MachineJOGPushbutton I : 1.8

    2 2

    END OF FILE

    MachineFaultedIndicator0 : 1.8

    DriveFaultedStatus Bit I : 1.16

    7 7

    This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.

  • 3–12 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    Figure 3.9PLC 5/15 Controller Example

    Example Information:PLC Type – PLC 5/15Drive Type – 1336 PLUSDrive Rack Address – 2Rack Size – 1/2 Rack MinimumStarting Module Group – 0

    When the Machine Start Pushbutton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sentto the PLC or any other control device. (Start button is a normally open contact in this example.)

    MachineSTARTPushbuttonI : 000

    00

    DriveSTARTCommand0 : 020

    01

    When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).

    This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zeroto Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)

    Drive Frequency Command

    MachineSTOPButtonI : 000

    01

    Datalink B OffDatalink C OffDatalink D Off

    Truncate Last Datalink Off

    Datalink A OnReference/Fdbk On

    Logic Cmd/Sts On

    Block Transfer Off

    DriveSTOPCommand0 : 020

    00

    00

    Drive StopCommand 0 : 020

    01

    Drive Running Bit I : 020

    N7 : 0160000: 02116000

    MOV

    MOVESource

    Dest

    PLCWORD

    OUTPUTIMAGE

    INPUTIMAGE

    0

    1

    2

    3

    Logic Cmd

    Reference

    Datalink A

    Datalink A

    Logic Sts

    Feedback

    Datalink A

    Datalink A

    PLC Image Table Map

    12

    34

    56

    78

    OPE

    N

  • 3–13Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    PLC 5/15 Example continuedWhen the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. The drive will start and run at the programmed JogFrequency if no STOP command is being sent by the PLC or other control device. (Jog button is a normally open contact in this example.)

    When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.

    Drive Data In A1(Data to Drive)

    N7 : 1500

    0: 022500

    MOV

    MOVESource

    Dest

    When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary nor-mally open contact in this example.)

    DriveClear FaultsCommand0 : 020

    Machine ClearFaultsPushbutton I : 000

    03 03

    When the Drive is running, the PLC will receive a Drive Running Status Bit.

    MachineRunningIndicator0 : 000

    DriveRunningStatus Bit I : 020

    01 00

    DriveJOGCommand0 : 020

    MachineJOGPushbutton I : 000

    02 02

    END OF FILE

    MachineFaultedIndicator0 : 000

    DriveFaultedStatus Bit I : 020

    07 01

    This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.

  • 3–14 Configuration and Interfacing

    Publication 1203–5.1 –– July, 1997

    This Page Intentionally Left Blank.

  • Chapter 4

    Publication 1203–5.1 –– July, 1997

    Troubleshooting

    Chapter 4 provides information to help you troubleshoot your remoteI/O system using the LED indicators on the front of the device(Figure 4.1). The remote I/O module is a non-serviceable device thatshould be returned to Allen-Bradley for replacement when a majorfault exists that is attributable to the remote I/O communicationsmodule itself.

    Figure 4.1 LED Locations

    SW1

    Front ViewOpen Version

    SW2SW3

    Adapter Fault Status(Red)

    SCANport Status(Green)

    Adapter Health(Green)

    Remote I/OStatus (Green)

    Remote I/OActive (Green) J4

    Front ViewEnclosed Version

    ...Remote I/OStatus (Green)

    Remote I/OActive (Green)

    Adapter FaultStatus (Red)

    SCANport Status (Green)

    Adapter Health(Green)

    Refer to Table 4.A for details on LED operation.

    J3

    J2

    J1

    Chapter Objectives

  • 4–2 Troubleshooting

    Publication 1203–5.1 –– July, 1997

    Table 4.A General Indications

    Indicator Color Probably cause Recommended action

    Adapter Fault Status Red (Steady) Unrecoverable fault Replace the adapter.

    Red (Blinking) Recoverable faultCheck configuration switch setting, check for SCANportcable connection.

    Red (Off) Normal operation None

    SCANport Status Green (Steady) Normal operation SCANport is active.

    Green (Off) No SCANport communication Check SCANport cables, device, cycle power.

    Green (Blinking)When blinking in tandem with redfault status, a device incompatibilityexists

    Check compatibility of drive on page 1–1 of this manual.

    Adapter Health Green (Steady) Normal operation None.

    Green (Off) Internal adapter fault Cycle power.

    Remote I/O Active Green (Steady) Normal operation None.

    Green (Off) No data transfer from PLC/SLCRemote I/O offline, make certain the PLC is in Run Mode,check rack address, check wiring and processor.

    Remote I/O Status Green (Steady) Normal Operation None.

    Green (Blinking) PLC is in Reset/Program/Test Mode None.

    Green (Blinking)PLC has more rack space allocatedthan is being used

    Do a PLC auto configuration.

    Green (Off) No communication with processorCheck wiring to processor. Check adapter configurationin processor.

    Adapter Fault Status Red (Blinking) and Configuration switch setting incorrect Check configuration switch settings.

    and Adapter Health Green (Steady) Remote I/O and/or SCANport cablenot wired or connected properly

    Check SCANport and remote I/O cable connections.

    Troubleshooting Table

  • Chapter 5

    Publication 1203–5.1 –– July, 1997

    Specifications

    Chapter 5 provides you with background information andspecifications that you may need to install, repair, or apply yourremote I/O communications module.

    Table 5.A General Indications

    Open Style(1336–GM1)

    Enclosed Style –– 115V ac(1203–GD1)

    Enclosed Style –– 24V dc(1203–GK1)

    Environmental

    Operating temperature 0–50°C (32–122°F) 0–50°C (32–122°F) 0–50°C (32–122°F)Storage temperature –40–85°C (–40–158°F) –40–85°C (–40–158°F) –40–85°C (–40–158°F)Relative humidity 0–95%, non–condensing 0–95%, non–condensing 0–95%, non–condensing

    Electrical

    Input voltage Supplied by drive 85–264V ac, 1 ph 24V dc, ±10%Input frequency NA 45–63 Hz NA

    Input current NA 35 mA maximum 0.4 amps maximum

    SCANport load 60 mA 60 mA 60 mA

    Communications

    Drive side SCANport peripheral interface

    PLC side Allen Bradley remote I/O

    Baud rates 57.6K, 115.2K, or 230.4K

    Rack size 1/4, 1/2, 3/4, or full

    Dimensions

    Enclosure type Open (IP00) NEMA 1 (IP30) NEMA 1 (IP30)

    Package size Not applicable 45mm x 76mm (1.8 x 3.0 in) 45mm x 76mm (1.8 x 3.0 in)

    Chapter Objectives

    Product Specifications

  • 5–2 Specifications

    Publication 1203–5.1 –– July, 1997

    This communications module is designed to be used with thefollowing Allen-Bradley programmable controllers:

    • PLC-2/30 with SD2 (communications module version 1.02 orlater)

    • PLC-3

    • SLC500TM with 1747-SN scanner• PLC 5/10TM, 5/15TM, 5/25TM family• PLC 5/30TM, 5/40TM, 5/40LTM, 5/60TM, 5/60LTM family and

    PLC-5/80TM

    • PLC 5/250TM

    • PLC scanner modules and subscanners.

    Note: This adapter was tested with the current revision level of thePLC processors listed. Earlier versions of the processors may not becompatible.

    Programmable ControllerCompatibility

  • You can help! Our manuals must meet the needs of you, the user. This is your opportunity to make sure they do just that.By filling out this form you can help us provide the most useful, thorough, and accurate manuals available. Please take afew minutes to tell us what you think - then mail this form or FAX it.FAX: your local Allen-Bradley Sales Office or 414/512-8579

    PUBLICATION NAME ________________________________________________________________________________________________

    PUBLICATION NUMBER, DATE AND PART NUMBER (IF PRESENT) _________________________________________________________

    ✔ CHECK THE FUNCTION THAT MOST CLEARLY DESCRIBES YOUR JOB.

    ❏ SUGGEST/RESPONSIBLE FOR THE PURCHASE OF EQUIPMENT ❏ MAINTAIN/OPERATE PROGRAMMABLE MACHINERY

    ❏ DESIGN/IMPLEMENT ELECTRICAL SYSTEMS ❏ TRAIN/EDUCATE MACHINE USERS

    ❏ SUPERVISE FLOOR OPERATIONS

    ✔ WHAT LEVEL OF EXPERIENCE DO YOU HAVE WITH EACH OF THE FOLLOWING PRODUCTS?

    NONE LITTLE MODERATE EXTENSIVE

    PROGRAMMABLE CONTROL ❏ ❏ ❏ ❏

    AC/DC DRIVES ❏ ❏ ❏ ❏

    PERSONAL COMPUTERS ❏ ❏ ❏ ❏

    NC/CNC CONTROLS ❏ ❏ ❏ ❏

    DATA COMMUNICATIONS/LAN ❏ ❏ ❏ ❏

    ✔ RATE THE OVERALL QUALITY OF THIS MANUAL BY CIRCLING YOUR RESPONSE BELOW. (1) = POOR (5) = EXCELLENT

    HELPFULNESS OF INDEX/TABLE OF CONTENTS 1 2 3 4 5

    CLARITY 1 2 3 4 5

    EASE OF USE 1 2 3 4 5

    ACCURACY AND COMPLETENESS 1 2 3 4 5

    QUALITY COMPARED TO OTHER COMPANIES’ MANUALS 1 2 3 4 5

    QUALITY COMPARED TO OTHER ALLEN-BRADLEY MANUALS 1 2 3 4 5

    ✔ WHAT DID YOU LIKE MOST ABOUT THIS MANUAL?

    ✔ WHAT DID YOU LIKE LEAST ABOUT THIS MANUAL?

    ✔ PLEASE LIST ANY ERRORS YOU FOUND IN THIS MANUAL (REFERENCE PAGE, TABLE, OR FIGURE NUMBERS).

    ✔ DO YOU HAVE ANY ADDITIONAL COMMENTS?

    ✔ COMPLETE THE FOLLOWING.

    NAME __________________________________________________________________________ COMPANY____________________________________________________________________________

    TITLE _________________________________________________ DEPARTMENT_______________________________________________

    STREET _______________________________________________ CITY _______________________ STATE ______ ZIP ___________________

    TELEPHONE ___________________________________________ DATE ______________________________________________________

    We Want Our Manuals to be the Best!C

    UT

    ALO

    NG

    DO

    TTED

    LIN

    E✁

  • FOLD HERE

    FOLD HERE

    NO POSTAGENECESSARY

    IF MAILEDIN THE

    UNITED STATES

    BUSINESS REPLY MAILFIRST CLASS PERMIT NO. 413 MEQUON, WI

    ALLEN-BRADLEYAttn: Marketing CommunicationsP.O. Box 760Mequon, WI 53092-9907

    POSTAGE WILL BE PAID BY ADDRESSEE

  • Allen-Bradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for more than 90 years. We design, manufacture and support a broadrange of automation products worldwide. They include logic processors, power and motioncontrol devices, operator interfaces, sensors and a variety of software. Rockwell is one of theworld’s leading technology companies.

    Worldwide representation.

    Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic •Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru •Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

    Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

    Publication 1203-5.1 – July 1997Supersedes Publication 1203-5.1 – April 1995

    PN74001-002-01(F)Copyright 1997 Allen-Bradley Company, Inc. Printed in USA

    Front CoverImportant User InformationSummary of ChangesTable of ContentsOverviewInstallationConfiguration and InterfacingTroubleshootingSpecificationsWho Should Use this Manual?Purpose of this ManualSafety PrecautionsFirmware SupportPLC Product CompatibilityTerms and AbbreviationsCommon Techniques Used in this ManualAllen–Bradley Support

    Chapter 1Chapter ObjectivesAdapter DescriptionSCANport Device CompatibilityConfiguration SwitchesDatalinksSafety Precautions

    Chapter 2Chapter ObjectivesSetting the Module Configuration SwitchesMounting the Remote I/O ModuleConnecting the Remote I/O CableConnecting the Termination ResistorConnecting the SCANport LinkConnecting the Power Supply

    Chapter 3Chapter ObjectivesData Table UseData Transfer Through the Communications Module

    Chapter 4Chapter ObjectivesTroubleshooting Table

    Chapter 5Chapter ObjectivesProduct SpecificationsProgrammable Controller Compatibility

    Back Cover