GENERAL REPLACEMENTS GUIDERSL
CFC R12 R502
HCFC R401A (MP39) R402A (HP80) R22 R402B (MP66) R402B (HP81) R409A (FX56) R403B (69L) R414B (HOT SHOT) R408A (FX10)
HFC R426A (RS-24) R428A (RS-52) R424A (RS-44) R434A (RS-45)
R22 REPLACEMENTS
RSL
DESIRABLE PROPERTIES FOR R22 REPLACEMENT
NON-OZONE DEPLETING NON-OZONE DEPLETING
LOW TOXICITY LOW TOXICITY
ENERGY EFFICIENTENERGY EFFICIENT
NON-FLAMMABLENON-FLAMMABLE
COMPATIBLE WITH ALL OILS (MO/AB/POE)COMPATIBLE WITH ALL OILS (MO/AB/POE)
SIMILAR TEMPERATURES & PRESSURES AS R22SIMILAR TEMPERATURES & PRESSURES AS R22
ZERO GLOBAL WARMING POTENTIALZERO GLOBAL WARMING POTENTIAL
SINGLE FLUID OR AZEOTROPESINGLE FLUID OR AZEOTROPE
STABLESTABLE
LOW /NO COSTLOW /NO COST
RSL
DOES ANYONE KNOW OF SUCH A PRODUCT?
IF YOU DO, LET ME KNOW………..
RSL
“RS” SERIES OF REFRIGERANTS
NO SINGLE REPLACEMENT FOR R22NO SINGLE REPLACEMENT FOR R22
NOTHING WHICH IS NEAR AZEOTROPIC, NOTHING WHICH IS NEAR AZEOTROPIC, SIMILAR FLOW RATE, PRESSURE, COP, SIMILAR FLOW RATE, PRESSURE, COP, COMPATIBLE WITH MO, NON FLAMMABLE ETCCOMPATIBLE WITH MO, NON FLAMMABLE ETC
APPLICATIONS BASED APPROACH TO APPLICATIONS BASED APPROACH TO ALTERNATIVESALTERNATIVES
RSL
KEY BENEFITS OF USING RS SERIES OF REFRIGERANTS
FACILITATES REPLACING OZONE DEPLETING FACILITATES REPLACING OZONE DEPLETING SUBSTANCESSUBSTANCES
COMPATIBLE WITH MO/ABCOMPATIBLE WITH MO/AB
LOW COST RETROFITLOW COST RETROFIT
AVOIDS USING EXPENSIVE & HYGROSCOPIC POE OILSAVOIDS USING EXPENSIVE & HYGROSCOPIC POE OILS
SIMILAR PERFORMANCE TO PRODUCTS BEING SIMILAR PERFORMANCE TO PRODUCTS BEING REPLACED IE R12, R22 & R502REPLACED IE R12, R22 & R502
ZERO OZONE DEPLETION POTENTIALZERO OZONE DEPLETION POTENTIAL
RSL
APPROVALS* ASHRAE NUMBERS CLASSIFICATION
RS-24 R426AR426A A1A1RS-44 R424A A1RS-45 R434A A1RS-52 R428A A1
* US EPA SNAP LIST
RS-24 RS-44RS-45 RS-52
RSL
OIL COMPATIBILTYMINERAL OIL (MO)MINERAL OIL (MO)
ALKYLBENZENE OIL (AB)ALKYLBENZENE OIL (AB)
POLYOLESTER OIL (POE)POLYOLESTER OIL (POE)
POLYALKYLENE GLYCOL OIL (PAG)POLYALKYLENE GLYCOL OIL (PAG)
** ** ** ** ** ** ** **RS-24, RS-44, RS-45, RS-52 & RS-25RS-24, RS-44, RS-45, RS-52 & RS-25 ARE ARE COMPATIBLE WITH ALL OF THESE COMPATIBLE WITH ALL OF THESE REFRIGERATION OILSREFRIGERATION OILS
RSL
R22 REPLACEMENTS %
R424A R434A RS-44 RS-45 R407C R410A
HFC 134a 47 16 52 HFC 125 50 .5 63.2 25 50
R143A 18
R32 23 50
Butane 1
Isopentane 0.6
Isobutane 0.9 2.8
GLIDE 3 1.5 5 0.3
RSL
R22 REPLACEMENTS
%
R424A R417A R434A R422D MO99 FX100 RS-44 M059 RS-45 MO 29 R438A R427A
HFC 134a 47 50 16.2 31.5 44.2 50 HFC 125 50 .5 46.5 63 65.1 45 25
R143A 18 10
R32 8.5 15
Butane 1 3.5 1.7
Isopentane 0.6 0.6
Isobutane 0.9 2.8 3.4
GLIDE 3 3 1.5 3 5 5
RSL
RS-44 (R424A)
RSL
RS-44RSL
* R22 REPLACEMENT PRIMARILY FOR A/C
* SUITABLE IN SYSTEMS WITH FIXED ORIFICES & EXPANSIONS DEVICES
* LOWER DISCHARGE PRESSURES
* LOWER DISCHARGE TEMPERATURES
* HIGHER CAPACITY THAN R417A
RS-44 TRIALSRELATIVE COPs
APPLICATION % REDUCTIONENERGY INPUT
* HEAT PUMP 15
* WINDOW A/C 3-12
* WALK-IN COOLER 11 * LOBLAWS SUPERMARKET 8
RSL*
LOBLAWS SUPERMARKET, CANADA
* 5 tonne walk in cooler converted from R22 to RS-44 in May 2001 * 40m suction line & 7m total lift
* Design temp 5oC
* Changed from AB to MO
* 8% lower energy usage
* Oil return good despite long suction line
* 8 years operating on RS-44 with no reported problems
RSI
RS-44 RETROFIT IN CANADARSL
York 5 tonne roof topat Kincore Holdings retrofitted by Neil Glenn of contractorG T Air Systems from R22 toRS-44 in Kingston,Ontario.
Conversion wascompleted in 2 hours& the system has been operatingsatisfactorily
2005
RS-44 RETROFIT IN MALAYSIA
RSL
Dunham Bush unitary A/C unit at ISO 14001 registered company Iriichi, Malaysia, converted from R22 to RS-44.Mr Arumgam, Production Manager, (third from left) said:“We are very happy with RS-44 & plan tochange all our systems
to RS-44 “
2004
CABLE & WIRELESS REPLACES R22 WITH RS-44
RSL
Over 100 Cable & Wireless DX AHU units (6-12 KW) have been converted to RS-44 at Bristol. Simple and straightforward procedure. Lower discharge pressure and discharge temperature produced significant operating benefits. Previous problems of trip out at high pressure with R407C avoided. Ran with no problems through hot summer with high ambient temperatures.
*
CARRIER SPLITS CONVERTED FROM R22 TO RS-44
RSL
Carrier Commercial converted twelve year old Carrier 25 to 30 ton split systems used for process cooling at Pratt and Whitney manufacturing facilities in Connecticut, USA.
The systems had reciprocating compressors manufactured by Carlyle. The conversion went smoothly according to Carrier Commercial’s service supervisor, who said:
“Not having to change the oil, valves or dealing with leaking seals was a big plus”.
HAIER CONVERTS HEAT PUMP FROM R22 TO RS-44
RSL
1.5 te heat pump in South Carolina, USA
R22 RS-44Ambient Temperature - 75F Ambient temperature - 80FStart Amps - 5.59 Start Amps - 5.60Run Amps - 5.70 Run Amps - 5.40Suction Pressure - 75 Suction Pressure - 65Head Pressure - 175 Head Pressure - 190 (Higher Ambient Temp) RS-44Ambient Temperature - 70FStart Amps - 5.6Run Amps - 5.25Suction Pressure - 70Head Pressure - 160
RSL
KRAFT, PHILIPPINESKRAFT, PHILIPPINESSplit type a/c unit at Paranaque, Metro Manila
August 2004
R22 Before RS-44 After
Low side psi 60 55Expansion line side psi 63 57Amount kgs 3.5 3.5Ambient temp 0C 30 30Current amps 14 12
RSL
VALEO, CHINAVALEO, CHINA
Recently converted a new Trane chiller from R22 to RS-44
HEAT PUMP CONVERSION TO RS-44RSL
RS-45 (R434A)
RSL
RS-45 (R434A)RSL
* SAME CAPACITY AS R22
* REPLACES R22 ACROSS TEMP RANGE
* 1.5 DEG GLIDE
* POTENTIAL USE IN FLOODED SYSTEMS
* LOWER DISCHARGE TEMPERATURE
* UNSUITABLE FOR RETROFIT IN FIXED ORIFICE SYSTEMS
* OEM PRODUCT
* NOTHING COMPARABLE: (1) Capacity to match R22 (2) Use with MO/AB/POE (3) Pressures similar to R22
RSLWHY USE RS-45?
* COMPATIBLE WITH TRADITIONAL LUBRICANTS (AB & MO)
* SAME CAPACITY AS R22 AT HIGH & LOW TEMPERATURES * AVOIDS COSTLY RE-TOOLING TO HIGH PRESSURE R410A
* NOTHING SIMILAR FOR S&T EVAPS
* SIMILAR PRESSURES TO R22
* SIMILAR COEFFICIENT OF PERFORMANCE TO R22
* CONSIDERABLY LOWER DISCHARGE TEMPERATURE THAN R22
* NEAR AZEOTROPIC - LOW TEMPERATURE GLIDE 1.50C
* SAME COMPRESSION RATIO AS R22
* AVOIDS PROBLEMS OF FRACTIONATION
* A SINGLE REFRIGERANT REPLACEMENT FOR R22 ACROSS THE RANGE OF APPLICATIONS WHERE R22 IS COMMONLY FOUND
R22 ALTERNATIVES
RSL
+7 deg C evap RS-45
+45 deg C cond R22 R434A R407C R410A
Discharge pressure ` 17.91 19.81 19.3 28.2
Discharge temp Deg C 111 81 98 105
Capacity kJ/m3 3062 3115 3189 4467
Capacity % R22 102 104 145
COP System 3.20 3.12 3.19 3
Compression ratio 3.02 3.02 3.2 2.98
Glide Deg C 0 1.5 5 0.2
R22 ALTERNATIVES
RSL
-35 deg C evap RS-45
+35 deg C cond R22 R434A
Discharge pressure Bar 14.07 15.55
Discharge temp Deg C 197 120
Capacity kJ/m3 619 632
Capacity % R22 102
COP System 1.27 1.28
Compression ratio 11.4 11.4
Glide Deg C 0 1.5
RSLRS-45 CHILLER CONVERSION
* BRITISH ENERGY, GLOUCESTER
* DUNHAM-BUSH CHILLER
* FLOODED SHELL & TUBE
* R22 CHARGE 1,200 KGS
* CONVERSION ATTENDED BY DB ENGINEER
* MAY 2009
* PERFORMANCE CLOSE TO R22
* COVERTING 2ND CHILLER
RSL
BRITISH ENERGY REPLACES R22 WITH RS-45 (R434A) IN FLOODED CHILLER
RSL
R22 CONVERSION TO RS-45 AT CONDIS SUPERMARKET
BARCELONA, SPAIN JANUARY 2010
RSL
R22 CONVERSION TO RS-45 AT CONDIS SUPERMARKET
BARCELONA, SPAIN JANUARY 2010
INSTALLATION
Equipment: 3 Bitzer 5.2 compressorsRefrigerant Type: R22Lubricant: Mineral Type, SUNISO 3 GS. (ISO-32)Installation: 1999 Refrigerant Capacity: 55 Kg (121 Lbs.)
The amperage (load) comparison between R22 and RS-45 was found to be very similar.
RSL
R22 CONVERSION TO RS-45 AT CONDIS SUPERMARKET BARCELONA, SPAIN JANUARY 2010
COMPARISONRefrigerant Type: R22 RS-45 Difference Time: (hours) 08:30 Hrs 23:00 Hrs 2.5 HoursEvaporation Temperature (oC): -10 -10 0Condensation Temperature: (oC) +40 +40 0Working Temperature (Ta in oC): +1 +1 0
CONCLUSIONRS-45 was found to have a greater cooling, since it reached a working temperature of + 1oC with greater speed compared to the original R-22 refrigerant. There was no need to regulate the expansion valve
RSLRS-45 JCI/YORK TESTS
* RECENT TESTS BY JCI ON R22, R422D (MO29), R438A(MO99) & RS-45
* MO29 DID NOT PERFORM AT ALL SATISFACTORILY & HAS BEEN DISCARDED
* MO99 BETTER THAN MO29 BUT NOT AS GOOD AS RS-45
* RS-45 THE CLOSEST TO R22 IN THESE TESTS
* JCI PREPARING INTERNAL RECOMMENDATION TO USE RS-45 OR MO99 TO REPLACE R22
RS-45 RSL
Air Conditioning
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
25 30 35 40 45 50 55 60
Temperature 0C
CO
P
0
500
1000
1500
2000
2500
3000
3500
4000
4500
Ca
pa
cit
y k
W/m
3
R22 COP
RS-45 COP
R22 Capacity
RS-45 Capacity
RS-45 CAPACITY & COEFFICIENT OF PERFORMANCE – AIR CONDITIONING
RS-45 RSL
Refrigeration
0
0.5
1
1.5
2
2.5
3
-40 -30 -20 -10 0
Temperature 0C
CO
P
0
500
1000
1500
2000
2500
3000
Ca
pa
cit
y k
R22 COP
RS-45 COP
R22 Capacity
RS-45 Capacity
RS-45 CAPACITY & COEFFICIENT OF PERFORMANCE – REFRIGERATION
RS-45 GLIDERSL
Evaporator Glide
R407C
RS-45
0
1
2
3
4
5
6
-40 -30 -20 -10 0 10 20
Evaporating Temperature 0C
Glid
e K R407C Glide
RS-45 Glide
RS-45 PHYSICAL PROPERTIESRSL
RS-45 R22
Molecular Weight 105.1 86.5
Boiling point (1 atm)0C -44.4 -40.8
0F -47.9 -41.4
Temperature Glide K 1.5 0
Critical Temperature 0C 77.9 96.1
0F 172.2 204.8
Critical Pressurebara 38.7 49.9
psia 561 724
Liquid Density (25 0C) kg/m3 1104 1191
Latent Heat of Vaporisation at boiling point kJ/kg 183 234
Vapour Pressure (25 0C)bara 11.7 10.4
psia 170 151
Capacity % 101 100
Specific heat of liquid (25 0C) kJ/kg.K 1.48 1.26
Ozone Depletion Potential ODP 0 0.055
Flammability limit in air (1 atm) vol% none none
Inhalation exposure (8 hour day & 40 hour week) ppm 1000 1000
(1) Bubble Point
RSL
RS-45 SUMMARY
* NOTHING LIKE IT
* NEAR AZEOTROPIC
* DISCHARGE PRESSURE SIMILAR TO R22
* CAPACITY MATCH FOR R22
* COP SIMILAR TO R22
* COMPATIBLE WITH MO, AB & POE OILS
RSL
RS-45 SUMMARY
* HIGHER MASS FLOW RATE THAN R22
* TXV SIMILAR TO R404A
* CHECK LIQUID LINES
* PIPE SIZING TABLES AVAILABLE
* USE RS-44 IN EXISTING SYSTEMS WITH CAPILLARY TUBE
RS-44 & RS-45 APPLICATIONSRS-44 IS SUITABLE FOR USE BOTH IN FIXED ORIFICE & SYSTEMS WITH AN EXPANSION VALVE. RS-44 WORKS WELL AS A REPLACEMENT FOR R22 AT MEDIUM &HIGH TEMPERATURES.
RS-44 IS PARTICULARLY EFFECTIVE IN UNITARY AIRCONDITIONING SYSTEMS
REPLACING R22 IN AN EXISTING SYSTEM WITH A CAPILLARYTUBE OR FIXED ORIFICE, RS-44 IS THE PREFERRED PRODUCT
RS-44'S LOWER DISCHARGE PRESSURE PROVIDES CONSIDERABLEOPERATING BENEFITS
RS-45 IS A CAPACITY MATCH FOR R22 ACROSS THE TEMPERATURERANGE
RSL
RS-44 & RS-45 APPLICATIONSRS-45 HAS BEEN FORMULATED FOR USE BY ORIGINAL EQUIPMENT MANUFACTURERS
AT LOWER TEMPERATURES, BELOW -25OC EVAP, RS-45 IS ESPECIALLY EFFECTIVE AS A R22 REPLACEMENT
RS-45 WITH ITS LOW GLIDE (AT 1.5oC CONSIDERABLY LOWER THAN R407C) PROVIDES A SIGNIFICANT BENEFIT IN SPECIFIC APPLICATIONS, EG FLOODED SYSTEMS.
BOTH RS-44 & RS-45 HAVE CONSIDERABLY LOWER DISCHARGE TEMPERATURES THAN R22
RSL
RSL
RS-44 PACKAGED A/C WINDOWS SPLITS ROOFTOPS CAPILLARY TUBE & TXV SYSTEMS
RS-45 FLOODED CHILLERS SHELL & TUBE
LOW TEMP (-350C) MASS FLOW SIMILAR TO R404A R404A TXV AVOID CAPILLARY TUBE SYSTEMS
RS-52 SIMILAR PERFORMANCE & PRESSURE TO R507 FLOODED SYSTEMS LOW TEMP (-400C)
R22 REPLACEMENT IF CONDENSER ADEQUATELY SIZED
COMPATIBLE WITH MO/AB & POE OILS
R22 IN SITU REPLACEMENTS APPLICATIONS SUMMARY
RSL
AIR CONDITIONING FIXED ORIFICE SYSTEMS RS-44
AIR CONDITIONING TXV SYSTEMS RS-44/RS-45
CHILLERS WITH FIXED ORIFICES RS-44
CHILLERS WITH TXVs RS-45
SHELL & TUBE EVAPORATORS RS-45
REFRIGERATION EVAPORATING DOWN TO -10C RS-44
REFRIGERATION EVAPORATING DOWN TO -35C RS-45
REFRIGERATION EVAPORATING DOWN TO -40C RS-52
R22 REPLACEMENTS IN WATER CHILLERS
RSL
Single pass refrigerant, single pass water, counter current flow, DX, tube in tube, tube in shell or plate type. RS-44 (R424A)
Multi pass refrigerant or water, DX , tube in shell. RS-45 (R434A)
Flooded chillers RS-45 (R434A) Only refrigerant suitable in flooded systems Mass flow rate of RS-45 requires expansion device forR404A.
RS-52 (R428A)
RSL
RS-52RSL
* NEAR AZEOTROPIC BLEND
* CAPACITY MATCH FOR R502
* SIMILAR PERFORMANCE TO R404A & R507
* SIMILAR PRESSURES TO R507
* LOWER DISCHARGE TEMPERATURE
* R22 REPLACEMENT AT LOW TEMP WHERE PRESSURES PERMIT
* REPLACES INTERIM OZONE DEPLETING BLENDS
* OEM PRODUCT
RSLRS-52 ICE RINK CONVERSION
* SWINDON ICE RINK, UK
* CONVERSION FROM R22
* JCI CONTRACTOR
* FLOODED SYSTEM
* 2 RESERVOIR PUMPER VESSELS
* R22 CHARGE 1,000 KGS
RS-52 & OTHER COMPOSITIONS
% RS-52
R428A R507 R404A
HFC 134a 4 HFC 125 77.5 50 44
HFC 143a 20 50 52
Propane 0.6
Isobutane 1.9
RSL
R502 ALTERNATIVES
RSL
-35 deg C evap RS-52
+35 deg C cond R502 R428A R507 R404A
Discharge pressure Bar 15.46 17.38 17.2 16.78
Discharge temp Deg C 137 115 122 124
Capacity kJ/m3 686 719 725 705
Capacity % R22 105 106 103
COP System 1.29 1.26 1.26 1.27
Compression ratio 10.4 10.6 10.5 10.7
Glide Deg C 0 0.3 0 0.5
RS-52 (R428A)RSL
REPLACES LOW TEMPERATURE OZONE DEPLETING BLENDS:
R402A( HP80)
R402B (HP81)
R403B (69L)
R408A (FX10)
R411B 9G2018B)
R502 ALTERNATIVES
RSL
-35 deg C evap RS-52 M079
+35 deg C cond R502 R428A R422A R404A
Discharge pressure Bar 15.46 17.38 16.3 16.78
Discharge temp Deg C 137 115 114 124
Capacity kJ/m3 686 719 655 705
Capacity % R22 105 95 103
COP System 1.29 1.26 1.27 1.27
Compression ratio 10.4 10.6 11.3 10.7
Glide Deg C 0 0.3 2 0.6
RSL
RS-52 CAPACITY & COEFFICIENT OF PERFORMANCE
Open System: 35 0C Condenser
0
500
1000
1500
2000
2500
3000
3500
-50 -40 -30 -20 -10 0
Temperature 0C
Cap
acit
y kJ
/m^
3
0
0.5
1
1.5
2
2.5
3
3.5
CO
P
R22 Capacity
R502 Capacity
RS-52 Capacity
R22 COP
R502 COP
RS-52
RS SERIES APPLICATION RANGES
A/C FIXED ORIFICE SYSTEMS RS-44
A/C TXV SYSTEMS RS-44/RS-45
CHILLERS FIXED ORIFICES RS-44
CHILLERS TXVs RS-44/RS-45
SHELL & TUBE EVAPORATORS RS-45
EVAPORATING DOWN TO -10C RS-44
EVAPORATING DOWN TO -35C RS-45
EVAPORATING DOWN TO -45C RS-52
RSL
R22 ALTERNATIVES
-7 DEG C EVAP % CAPACITY GLIDE DISCHARGE+45 DEG C COND OF R22 DEG C PRESSURE BAR
R134a 67 0 12.06
R407C 104 5 19.30
R410A 146 0.1 28.20
R434A (RS-45) 102 1.5 19.81 MO29 (R422D) 95 3 18.24
R427A (FX100) 100 5 18.63
R438A (MO99) 95 5 17.82
RSL
R22 ALTERNATIVES
-35 DEG C EVAP % CAPACITY GLIDE DISCHARGE+35 DEG C COND OF R22 DEG C PRESSURE BAR
R134a 56 0 9.24
R434A (RS-45) 102 1.5 15.55 MO29 (R422D) 91 3 14.26
R438A (MO99) 88 5 13.88
RSL
“RS” SERIES SALESBELGIUM MALAYSIACANADA NORWAYCHINA TRINIDADCZECH REPUBLIC POLANDDENMARK PHILIPPINESEIRE SLOVAKIAFINLAND THAIANDGREECE UAEHOLLAND UKHUNGARY USAITALY UK
RSL
RS SERIES APPLICATIONS
RS-44 PACKAGED A/CWINDOWSSPLITS
RS-45 HIGH & LOW TEMPCHILLERS, EG S&TFLOODED SYSTEMSMASS FLOW SIMILAR TO R404AR404A TXV
RS-52 SIMILAR PERFORMANCE TO R507FLOODED SYSTEMSLOW TEMP
RSL
R12 REPLACEMENT
RSL
RS-24 (R426A)
RSL
R12 REPLACEMENTS0C 0C SAFETYBP GLIDE CLASS
R12 -29.8 0 A1
R134a -26.1 0 A1
R426A (RS-24) -28.6 0.5 A1
R413A (MO49) -36 6 A2
R437A -32 2.5 A1
R409A (FX56) -34.5 8 A1
R401A (MP39) -33.1 4 A1
R406A -32.3 8 A2
R416A -23.4 1.5 A1
RSL
HFC REPLACEMENTS FOR R12
REFRIGERANT COMPOSITION OIL COMPATIBILITY
R-134a A1 100% R-134a POE
MO49+ (R427A) A1 78.5% R-134a MO/AB
19.5% R125
0.6% ISOPENTANE 0.6% BUTANE
RS-24 (426A) A1 93.1% R-134a MO/AB/POE
5% R-125
0.6% ISOPENTANE
1.9% BUTANE1.9% BUTANE
RSL
RS-24 (R426A)
R12 RS-24
BPoC -29.8 -28.6
GLIDE 0 0.5
VP @ 25oC psia 93.3 102.6
LIFETIME yrs 102 16
RSL
RS-24 COMPARISONRS-24 M049+
R12 R426A R437A
BPoC -29.8 -28.6 -32.0
GLIDE 0 0.5 2.5
DISCHARGE 9.95 11.03 11.94PRESSURE BAR
RPL
RS-24 PHYSICAL PROPERTIES
RS-24: PHYSICAL PROPERTIES
RS-24 R12
Molecular weight 102.6 120.9
Boiling point (1 atm) oC0F
-28.6(1)-19.5(1)
-29.8-21.6
Temperature glide oC 0.5 0
Critical temperature oCoF
101.0213.8
112.0233.6
Critical pressure kPapsia
4097594
4116597
Liquid density at 25oC kg/m3 1184 1311
Density of saturated vapour at 25oC kg/m3 30.9 37.3
Specific heat of liquid at 25oC kJ/kgoC 1.45 1.00
Specific heat of vapour at 1 atm & 25 oC kJ/kgoC 0.863 0.606
Vapour pressure at 25oC kPapsia
707(1)102.6(1)
64393.3
Latent heat of vaporisation at boiling point kJ/kg 218 165
Ozone Depletion Potential ODP 0 1
Flammability limit in air (1 atm) vol% None None
Inhalation exposure (8 hr day & 40 hr week) ppm 1000 1000
RSL
SOME USERS OF RS SERIES CABLE & WIRELESS PRATT & WHITNEY CARRIER SERVICE, USA BRITISH ENERGY BAKKAVOR, UK SITES COCA COLA. THAILAND CONDIS SUPERMARKET, BARCELONA LOBLAWS SUPERMARKET, CANADA KINCORE HOLDINGS, CANADA KRAFT, PHILIPPINES CHESTER HOSPITAL (OPERATING THEATRE) IRICHI, MALAYSIA PERONI, ITALY CANADIAN MILITARY BASES SUNCOR, CANADA BIDGOOD SUPERMARKET, CANADA SALFORD QUAYS (REPLACED ISCEON 59) THAI OIL, THAILAND TROPICANA, USA VALEO, CHINA