10/15/2013 | westborough, ma
DESCRIPTION
10/15/2013 | Westborough, MA. Load Power Factor Audit - 2012/2013 and Area Load Power Factor Standards revised for 2014. Osman Bileya. Lead Engineer, Real Time SUPPORT. Presentation to the Reliability Committee - 2013. Review of the Annual Load Power Factor (LPF) Correction process - PowerPoint PPT PresentationTRANSCRIPT
1 0 / 1 5 / 2 0 1 3 | W E S T B O R O U G H , M A
Load Power Factor Audit - 2012/2013
and Area Load Power Factor
Standards revised for 2014
Osman BileyaL E A D E N G I N E E R ,
R E A L T I M E S U P P O R T
Presentation to the Reliability Committee - 2013
• Review of the Annual Load Power Factor (LPF) Correction process
• Review the LPF Survey Results for the 2012/2013 Audit period
• Present Updated 2014 LPF Standards for six Areas
• Forecast Compliance into the 2014 LPF Audit period
2
Review of the Annual LPF Correction Program
• Eleven LPF Areas are defined in NEPOOL OP17 – Load Power Factor Correction
• OP17 and annual LPF audit is managed by the Voltage Task Force (VTF).
• Each Area is assessed individually to determine its own reactive needs.
– Voltage/Reactive Performance criterion– Net Zero MVAR Interchange criterion
3
Graphical Representation of the 11 LPF Areas
4
Reasons for Updating LPF Standards
• Changes in area voltage/reactive performance due to transmission changes:– New transmission lines– New bulk transformers – Generation Retirement – Changes in generator reactive capability– Additional static or dynamic reactive compensation– Changes in transfer conditions– Load growth since last Area LPF study– Change of Area definition– Revision of “Testing Criteria” assumptions
5
Annual Load Power Factor Survey• ISO-NE and VTF are responsible for:
– Administering the annual LPF survey– Evaluating and reporting results– Requesting remedial action plans from Market Participants
• Every year specific historical hours are selected from the previous year
• Each load serving Participant ( as defined in OP17) is tasked with submitting LPF data for the selected historical hours
• Participant’s surveyed LPFs are compared to the corresponding Area’s LPF Standard for the specified hours
• The degree of noncompliance for each Participant is identified in terms of surplus or shortfall of reactive capability– Changes in the underlying networks (i.e. adding caps) can impact
compliance with survey requirements
6
Example of Load Power Factor Standard and Survey
7
Annual Load Power Factor Survey
• The annual LPF Survey Program accomplishes two goals:
1. Audit Market Participants’ compliance with the current LPF standards
2. Forecast Market Participants’ compliance with the new standards if the current standards are revised/updated for any of the reasons specified in the previous slide
• OP17 program cited by NERC as an Example of Excellence.
8
2012/2013 Load Power Factor Survey Results
• Eighty one participants submitted LPF audit data for six loads points identified by ISO New England:
– Spring Light load (9,128 MW)
– Summer Intermediate load (21,938 MW)
– Summer Peak load (25,880 MW)
– Fall Light load (9,246 MW)
– Winter Intermediate load (18,753 MW)
– Winter Peak load (20,775 MW)
9
10
Spring Light load Summer Intermediate load
Summer peak load Fall light load Winter Intermediate load
Winter peak load0.00%
25.00%
50.00%
75.00%
100.00%
60%
94%
81%
56%
86%
95%
68%
89%
73%
63%
83%
90%
Comparison of % of Compliant Participants (2012/2013 vs 2011/2012)
2012/2013 Audit Period 2011/2012 Audit Period
Fully Compliant Participants in the 2012/2013 Audit Period• In the 2012/2013 audit period 33 participants were fully
compliant:Boston: NSTAR Central Mass/Harriman : Fitchburg Gas & El, Green Mountain Power,
Hudson Connecticut area: Groton Utilities, NU, The United Illuminating Co ,
Mohegan Tribal Utilities AuthorityMaine: Bangor HydroNew Hampshire: Littleton, PSNH, Unitil Energy Systems Northeast Mass: Ipswich, Littleton, Mass Electric, Middleton, Peabody,
Rowley , RMLDRhode Island: Narragansett, PascoagSoutheast: Mansfield, Middleboro, Norwood, NSTAR SWCT: NU, South NRWLK Electric & Water, Third Taxing Dist-NRWLK Vermont: CVPS, Granite State Electric (GS WEST), NH Electric Coop,
VELCO, Green Mountain Power11
2012/2013 LPF Survey Results
12
2012/2013Compliance for the spring light load 9128 MW
Spring Summer Int Summer Pk Fall Winter Int Winter Pk0.00%
5.00%
10.00%
15.00%
20.00%
25.00%
30.00%
35.00%
40.00%
45.00%
50.00%
28%
0%
5%
24%
1% 0%
% of Non-compliant Load by SeasonBased on 2012 LPF Standards
Boston (1471 MW)
CT (1157 MW)
H/C (616 MW)
Maine (734 MW)
NH (719 MW)
NEMA (740 MW)
RI (526 MW)
SEMA (1002 MW)
SWCT (976 MW)
Vermont (502 MW)
WMass (404 MW)
0.00%
25.00%
50.00%
75.00%
100.00%
1% 1%
87%
81%
0%4%
0%
54%
38%
0%
94%
% of Non-compliant Load for Spring Light load by AreaBased on 2012 LPF Standards
2012/2013 LPF Survey Results Cont’d
14
Boston CT
H/CMain
e NHNEM
A RISE
MASW
CT
Vermont
WMass
-100.000
-90.000
-80.000
-70.000
-60.000
-50.000
-40.000
-30.000
-20.000
-10.000
0.0000.000 0.000
-23.47
-15.93
0.000 0.000 0.000 0.000 0.000 0.000
-60.66
Areas Reactive Deficiency for Spring Light Load Based on 2012 LPF Standard
2012/2013 LPF Survey Results Cont’d
15
Boston CT
H/CMain
e NHNEM
A RISE
MASW
CT
Vermont
WMass
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5.64
Reactive Deficiency for Summer Peak Load 2012Based on 2012 LPF Standard
2012/2013 LPF Survey Results Cont’d
Revised Load Power Factor for 2014
• 6 out of the 11 eleven Areas revised LPF Standards for 2014
Maine
New Hampshire
Northeast Massachusetts
Central Massachusetts / Harriman
Western Massachusetts
Southwest Connecticut
16
New England load levels modeled in the 2014 LPF Studies
17
Load Period NE Load (MW)
Peak 30,912
Shoulder 21,979
Light 10,592
Revised Maine LPF Standard for 2014
18
The following Maine Power Reliability Program (MPRP) topology upgrades are the reason for the LPF revision for 2014:
– 240 MVAR of new reactors, – four new 345/115 kV autotransformers (one replacing the soon to be retired Maxcys T3), – 184 mile long parallel 345 kV aerial transmission path from Orrington to Eliot substation
in New Hampshire, – retirement of five special protection systems (SPS), – 100 miles of new 115 kV aerial transmission and various 115 kV transmission
improvements
Revised Maine LPF Standard for 2014 Cont’d
• The minimum LPF Standards were based on the Net 0-MVAR interchange criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on high-voltage violation criteria – Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
19
20
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,000 32,000
0.85
0.86
0.87
0.88
0.89
0.90
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
1.02
1.03
1.04
1.05
MAINE AREA Compliance with 2012 thru 2013 LPF Standard
Forecast with 2014 LPF Standard
2012/2013 Survey Points
2012 thru 2013 LPF Standard
2014 LPF Standard
New England Load (MW)
LP
F
Standard 2014 2012-2013
Maximum for Light load 1.003 0.976
Maximum for Shoulder load 1.003 1.000
Minimum for Shoulder load 0.908 0.894
Minimum for Peak load 0.915 0.926
Revised New Hampshire LPF Standard for 2014
• The main reason for this year’s study is the revised “Testing Criteria” for the maximum LPF standards– Facility out as opposed to all lines-in testing during light and shoulder
load levels– Only high voltage violations are respected (net 0-MVAR interchange
criterion is not respected)
• Similar to last year’s study, the following transmission upgrades are included in this year’s study:– the new 345 kV path from New Hampshire to Maine (Elliot to Maguire
Road to South Gorham– New Capacitors at Webster and Weare – Up-rate the 326 line to 1780 MVA summer LTE
21
Revised New Hampshire LPF Standard for 2014
22
• The minimum LPF Standards were based on the Net 0-MVAR interchange criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on high-voltage violation criteria – Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
23
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000
0.8500
0.8600
0.8700
0.8800
0.8900
0.9000
0.9100
0.9200
0.9300
0.9400
0.9500
0.9600
0.9700
0.9800
0.9900
1.0000
1.0100
1.0200
1.0300
1.0400
1.0500
NEW HAMPSHIRE AREA
2012/2013 Survey Points
2011 thru 2012 LPF Standard
2013 LPF Standard
2014 LPF Standard
New England Load ( MW)
LP
F
Standard 2014 2013 2011 -2012
Maximum for Light load 1.015 0.999 1.004
Maximum for Shoulder load 1.027 1.028 1.020
Minimum for Shoulder load 0.953 0.958 0.927
Minimum for Peak load 0.976 0.977 0.967
24
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000
0.8500
0.8600
0.8700
0.8800
0.8900
0.9000
0.9100
0.9200
0.9300
0.9400
0.9500
0.9600
0.9700
0.9800
0.9900
1.0000
1.0100
1.0200
1.0300
1.0400
1.0500
NEW HAMPSHIRE AREA COMPLIANCE with 2011 thru 2013 LPF Standard
Forecast with 2014 LPF Standards
2012/2013 Survey Points
2011 thru 2013 LPF Standard
2014 LPF Standard
New England Load ( MW)
LP
F
Revised Northeast MA LPF Standard for 2014
• The reason for revising NEMA’s LPF standards is the retirement of Salem Harbor Units 3 & 4 by end of 2014:
– Total real power capability is approximately 585 MW
– Total lagging/leading reactive power capability is approximately 265 MVAR
Revised Northeast MA LPF Standard for 2014 Cont’d
• The minimum LPF Standards were based on the low voltage violation criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on the high-voltage violation criterion
– Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
27
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,000 32,000
0.85
0.86
0.87
0.88
0.89
0.90
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
1.02
1.03
1.04
1.05
NORTHEAST MA AREA Compliance with 2009 thru 2013 LPF Standards
Forecast with 2014 LPF Standards
2012/2013 Survey Points
2009 thru 2013 LPF Standard
2014 LPF Standard
NEW ENGLAND LOAD (MW)
LP
F
Standard 2014 2009-2013
Maximum for Light load 1.013 1.001
Maximum for Shoulder load 1.023 1.000
Minimum for Shoulder load 0.966 0.961
Minimum for Peak load 0.973 0.971
Revised Central MA/Harriman LPF Standard for 2014 Cont’d
The following topology upgrades are the reason for the LPF revision for 2014:
• Reclosing of A127 and B128 (major change)
• Auburn St substation - 2nd 345/115 kV auto transformer (March 2014)
• E Main St, Westborough - 2nd 115/13 kV transformer and new in-line breaker (June 2014)
• O-15S conversion to 115 kV (Oct 2014)
28
Revised Central MA / Harriman LPF Standard for 2014 Cont’d
29
• The minimum LPF Standards were based on the Net 0-MVAR interchange criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on high-voltage violation criteria – Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
30
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,000
0.8500
0.8600
0.8700
0.8800
0.8900
0.9000
0.9100
0.9200
0.9300
0.9400
0.9500
0.9600
0.9700
0.9800
0.9900
1.0000
1.0100
1.0200
1.0300
1.0400
1.0500
CENTRAL MA / HARRIMAN AREA Compliance with 2010 thru 2013 LPF Standard
Forecast with 2014 LPF Standard
2012/2013 Survey Points
2010 thru 2013 LPF Standard
2014 LPF Standard
New England Load (MW )
LP
F
LPF Standard 2014 2010- 2013 2007
Minimum for Peak load 0.998 0.992 0.999
Minimum for Shoulder load 0.985 0.952 0.979
Maximum for Shoulder load 1.011 0.997 1.000
Maximum for Light load 1.011 0.995 0.985
Revised Western MA LPF Standard for 2014
• The previous LPF standards were evaluated in 2012 and included the Greater Springfield Reliability Project (GSRP)
• In addition to the completion of the GSRP project, this year’s study included: – The closing of A127 and B128 (Harriman to Millbury 115 kV) circuits– Addition of the following 115 kV capacitors to the Pittsfield area
- 14.4 MVAR Capacitor at Podick- 14.4 MVAR Capacitor at Amherst- 14.4 MVAR Capacitor at Cumberland
• Another reason for this year’s study is the revised “Testing Criteria” for the maximum LPF standards– Facility out as opposed to all lines-in testing during light and shoulder load levels– Only high voltage violations are respected (net 0-MVAR interchange criterion is
not respected)
31
Revised Western MA LPF Standard for 2014 Cont’d
32
• The minimum LPF Standards were based on the Net 0-MVAR interchange criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on high-voltage violation criteria – Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
33
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,0000.8000
0.8200
0.8400
0.8600
0.8800
0.9000
0.9200
0.9400
0.9600
0.9800
1.0000
1.0200
1.0400
1.0600
1.0800
1.1000
WESTERN MA AREA
2012/2013 Survey Points
2012 LPF Standard
2013 LPF Standard
2014 LPF Standard
New England Load (MW)
LP
F
Standard 2014 2013 2012
Maximum for Light load 1.010 0.965 0.999
Maximum for Shoulder load 1.011 1.004 1.013
Minimum for Shoulder load 0.956 0.967 0.973
Minimum for Peak load 0.969 0.976 0.986
34
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,0000.8000
0.8200
0.8400
0.8600
0.8800
0.9000
0.9200
0.9400
0.9600
0.9800
1.0000
1.0200
1.0400
1.0600
1.0800
1.1000
WESTERN MA AREACompliance with 2012 LPF Standard
2013 Forecast with 2014 Max LPF Standard and 2013 Min LPF Standard2014 Forecast with 2014 Min LPF Standard
2012/2013 Survey Points
2012 LPF Standard
2013 LPF Standard
2014 LPF Standard
New England Load (MW)
LP
F
Revised Southwest CT LPF Standard for 2014
35
The following topology upgrades are the reason for the LPF revision for 2014:•8300 Line Reconfiguration•East Shore Capacity Upgrade
• Union Substation•Addition of Beseck Shunt Reactor•Addition of Stamford – Glenbrook Cable•Addition of South Norwalk Substation•Addition of 345-kV Series Breaker at E. Devon
Another reason for this year’s study is the retirement of Norwalk Harbor Units 1 & 2
– Total real power capability is approximately 335 MW – Total Lagging reactive power capability is approximately 100 MVAR– Total Leading reactive power capability is approximately 55 MVAR
Revised Southwest CT LPF Standard for 2014
36
• The minimum LPF Standards were based on the low voltage violation criterion
– Starting with an all lines-in system– Respecting the worst limiting contingency
• The maximum LPF Standards were based on high-voltage violation criteria – Starting with a facility out from a light load/high voltage perspective – Respecting the worst limiting contingency
37
9,000 10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 28,000 29,000 30,000 31,000
0.8500
0.8600
0.8700
0.8800
0.8900
0.9000
0.9100
0.9200
0.9300
0.9400
0.9500
0.9600
0.9700
0.9800
0.9900
1.0000
1.0100
1.0200
1.0300
1.0400
1.0500
SOUTHWEST CT AREA Compliance with 2009 thru 2013 LPF Standard
Forecast with 2014 LPF Standard
2012/2013 Survey Points
2009 thru 2013 LPF Standard
2014 LPF Standard
New England Load (MW )
LP
F
Standard 2014 2009-2013
Maximum for Light load 1.003 1.002
Maximum for Shoulder load 1.028 1.014
Minimum for Shoulder load 0.949 0.898
Minimum for Peak load 0.970 0.916
Forecast Compliance
• All 11 Areas are compliant (no reactive deficiency) based on the 2014 LPF standards
– Note that some Participants within the individual Areas may still be non-compliant, however each area as a whole is compliant.
38
Improvement in Spring Light load Compliance based on Forecasted LPF Standards
39
Boston (1471 MW)
CT (1157 MW)
H/C (616 MW)
Maine (734 MW)
NH (719 MW)
NEMA (740 MW)
RI (526 MW)
SEMA (1002 MW)
SWCT (976 MW)
Vermont (502 MW)
WMass (404 MW)
0.00%
25.00%
50.00%
75.00%
100.00%
1% 1%4%
0% 0%4%
0%
54%
3%0% 2%1%
87%
81%
0%4%
0%
54%
38%
0%
94%
% of Non-compliant Load by Area
Forecasted LPF Standards2012 LPF Standards