10 dp schemes

Upload: balachitra

Post on 02-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 10 DP Schemes

    1/42

    Distance Protection Schemes

  • 8/10/2019 10 DP Schemes

    2/42

    Z3

    Z3

    Z1

    Z1

    Z2

    Z2

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    T2

    1

    . T2

    T3

    Trip

    T2

    Basic Distance Scheme

    Z1

    Z2

    Z3

  • 8/10/2019 10 DP Schemes

    3/42

    Basic Distance Scheme - Disadvantages

    Zone 1 set to 80% leaves 2 end zones

    Faults in end zone results in instantaneoustripping at one end and time delayed at the

    other

    Time delay may lead to system stabilityproblems

    Sequential clearance leaves no dead time for

    high speed A/R cycle (transient fault becomes

    permanent)

    Longer clearance times - More damage

  • 8/10/2019 10 DP Schemes

    4/42

    Zone 1 Extension Scheme

    Z3

    Z2

    Z3

    Z1X

    Z1X

    Z2

    Z1

    Z1

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    &

    1

    Z1X

    A/R

    Z2

    Z1

    Z3

    1

    . T2

    T3

    Trip

    &

    1

    Z1X

    A/R

  • 8/10/2019 10 DP Schemes

    5/42

    Zone 1 Extension - Advantages

    No signalling channel required (may be used

    as temporary replacement for carrier aided

    scheme when comms. channel out of service)

    Provides fast fault clearance at both ends for a

    transient fault anywhere along the line length

    Allows the use of high speed A/R cycle

  • 8/10/2019 10 DP Schemes

    6/42

    Zone 1 Extension Scheme - Disadvantages

    Tripping can occur for external faults (but will be

    followed by an autoreclose)

    Basic distance scheme logic applies following

    reclose (i.e. potential for time delayed clearancefor permanent faults)

    Only suitable to systems where autoreclose isused (for example can not be used on cable

    circuits)

  • 8/10/2019 10 DP Schemes

    7/42

    Loss of Load Accelerated Trip

    Z3

    Z3

    Z1

    Z1

    Z2

    Z2

    T1 = 40ms (allows for slowest pickup of Zone 2)

    T2 = 18ms (prevents LOL trip for external fault withCB pole scatter)

    Z2

    .

    .&

    .

    .

    .

    &

    &

    .

    1

    .

    LDA

    LDB

    LDC

    0

    T2

    T1

    0Trip

  • 8/10/2019 10 DP Schemes

    8/42

    Loss of Load Scheme

    Fast fault clearance without the need for a

    signalling channel

    Only applicable where 3 phase tripping is used

    Only operates for unbalanced faults

    Load current (above the current detector

    settings) must exist prior to the fault to arm thescheme

    Can be used as back up to signal aided scheme

  • 8/10/2019 10 DP Schemes

    9/42

    Channel Dependant Schemes

  • 8/10/2019 10 DP Schemes

    10/42

    Unit Protection Schemes

    Provide high speed clearance for all faults on line

    (for example current differential)

    Do not provide inherent back-up protection

    SOLUTION IS TO PROVIDE DISTANCE PROTECTION FOR

    BACK-UP PROTECTION OF ADJACENT LINES WITH AN AIDED

    TRIPPING SCHEME FOR HIGH SPEED PROTECTION OF WHOLE

    LINE

    Requires the use of an ON/OFF signalling

    channel between line ends (i.e. HF/VF/Fibre

    Optic/Radio)

  • 8/10/2019 10 DP Schemes

    11/42

    Types of Aided Tripping Schemes

    Acceleration

    Transfer tripping

    Direct

    Permissive Underreach

    Permissive Overreach

    Blocking

  • 8/10/2019 10 DP Schemes

    12/42

    Direct Transfer Trip

    Z3

    Z3

    Z1

    Z1

    Z2

    Z2

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    Z3

    Z2

    Z11

    . T2

    T3

    Trip

    Tx

    Rx

    Tx

    Rx

    Send Logic : Z1

    Trip Logic : Rx

  • 8/10/2019 10 DP Schemes

    13/42

    Direct Transfer Trip - Advantages

    All faults anywhere along the protected line can

    be cleared instantaneously at both line ends

    Scheme can be advantageous for protecting 3

    terminal lines due to ease of application

  • 8/10/2019 10 DP Schemes

    14/42

    Direct Transfer Trip - Disadvantages

    A very secure signalling channel is required :-

    incorrect operation leads to false tripping

    Circuit breakers at both line ends must be closed

    and contribute fault current to obtain high speedfault clearance

    If the channel fails only the Basic scheme logicwill be provided

  • 8/10/2019 10 DP Schemes

    15/42

    Acceleration Scheme (for Reach Stepped Relay)

    Z3

    Z3

    Z1

    Z1

    Z2

    Z2

    Change

    Z1

    reach

    Z3

    Z1/Z2 1

    .

    T2

    Trip

    T3

    1

    . T3

    T2

    Trip

    Tx

    Rx

    Tx

    Rx

    1

    .

    1

    .

    Send Logic : Z1Trip Logic : Rx + Z2

    Z1/Z2

    Z3

  • 8/10/2019 10 DP Schemes

    16/42

    Permissive Schemes

  • 8/10/2019 10 DP Schemes

    17/42

    Permissive Underreach Scheme

    Z3

    Z3

    Z1

    Z1

    Z2

    Z2

    Tx

    Rx

    Tx

    Rx

    Send Logic : Z1

    Trip Logic : Rx + Z2

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    T2

    &

    1

    . T2

    Z3

    Z2

    Z1

    T3

    Trip

    T2

    &

    100

    0100

    0

  • 8/10/2019 10 DP Schemes

    18/42

    Permissive Underreach Scheme

    A

    21

    C

    B

    D

    A

    C

    B

    D

    Send

    Fault

    Fault

    Race between relay at D

    picking up and signal

    send from relay at C

    resetting, following

    opening of breaker at C

    If signal send from Cresets before relay D

    operates then aided

    tripping will not occur

    To prevent this a 100ms

    delay on drop off of the

    signal send is used in

    the scheme logic

    21

    21 21

    Rx + Z2

    Rx + Z2

  • 8/10/2019 10 DP Schemes

    19/42

    Permissive Underreach Transfer Trip - Advantages

    Only a simplex signalling channel required

    Scheme is very secure as signalling channelonly keyed for internal fault (Zone 1 initiation)

    Permissive Underreach Transfer Trip -

  • 8/10/2019 10 DP Schemes

    20/42

    Permissive Underreach Transfer Trip -Disadvantages

    If one terminal of the line is open then only

    Basic scheme logic will apply

    If there is a weak infeed at one terminal then

    only Basic scheme logic will apply

    If signalling channel fails then only Basic

    scheme logic will apply

    Resistive coverage is governed by Zone 1

    setting (may be limited on short lines)

  • 8/10/2019 10 DP Schemes

    21/42

    Permissive Overreach Scheme Internal Fault

    Z3

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    &

    T2

    Z3

    Z2

    Z11

    . T2

    T3

    Trip

    &

    T2

    Rx

    Tx

    Rx

    Tx

    Z3

    Z1

    Z1

    Z2

    Z2

    Send Logic : Z2

    Trip Logic : Rx + Z2

  • 8/10/2019 10 DP Schemes

    22/42

    Permissive Overreach Scheme External Fault

    Z3

    Z3

    Z2

    Z1 1

    .T2

    T3

    Trip

    &

    T2

    Z3

    Z2

    Z11

    . T2

    T3

    Trip

    &

    T2

    Rx

    Tx

    Rx

    Tx

    Z3

    Z1

    Z1

    Z2

    Z2

    Send Logic : Z2

    Trip Logic : Rx + Z2

  • 8/10/2019 10 DP Schemes

    23/42

    Permissive Overreach Scheme (CB Echo Logic)

    Z3

    Z3

    Z2

    Z1

    T2

    T3

    Trip

    &

    T2

    Z3

    Z2

    Z1

    T2

    T3

    Trip

    &

    T2

    &

    1

    Rx

    Tx

    CB open &

    1

    Rx

    Tx

    CB open

    Z3

    Z1

    Z1

    Z2

    Z2

    1

    .

    1

    .

    Send Logic : Z2

    Trip Logic : Rx + Z2Open terminal echo : CB Open + Rx

  • 8/10/2019 10 DP Schemes

    24/42

    Permissive Overreach Scheme (WI Echo Logic)

    Z4

    Z2

    Z1

    Z1Z2

    Send Logic : Z2

    Trip Logic : Rx + Z2Open terminal echo : CB Open + Rx

    Weak Infeed echo : Z4 + RxZ4

    Z3

    Z2

    Z1

    T2

    T3

    Trip

    T2

    Z3

    Z2

    Z1

    T2

    T3

    Trip

    T2

    &

    Z4

    CB open &

    Z4

    CB open

    1

    & &

    &Rx

    Tx &Rx

    Tx

    1

    .

    1

    .

    1

  • 8/10/2019 10 DP Schemes

    25/42

    Permissive Overreach Weak Infeed Trip Scheme

    Z4

    Z2

    Send Logic : Z2

    Trip Logic : Rx + Z2

    Open terminal echo : CB Open + Rx

    Weak Infeed echo : Z4 + Rx

    Weak Infeed trip : Z4 + LDOV reset + Rx

    Z1

    Z1Z2

    Z4

    Z3

    Z2

    Z1

    T3

    Trip

    &

    T2

    &LDOV

    Z3

    Z2

    Z1

    T3

    Trip

    &

    T2

    &

    &Rx

    TxZ4

    CB open &Rx

    Tx

    LDOV

    Z4

    CB open

    & &

    1

    .

    1

    .

    1 1

  • 8/10/2019 10 DP Schemes

    26/42

    Permissive Overreach Transfer Trip - Advantages

    Provides better resistive coverage, especially

    on short lines, where MHO measuringelements are used

    For cases where one line terminal is open,open breaker echo logic can be used

    For cases of weak or zero infeed at one lineterminal weak infeed logic can be used

    (reverse looking zone required)

  • 8/10/2019 10 DP Schemes

    27/42

    Permissive Overreach Transfer Trip - Disadvantages

    Duplex signalling channel required

    Scheme is theoretically less secure then PUR

    as signalling channel is keyed for external

    faults

    If signalling channel fails then only Basic

    scheme logic will apply

  • 8/10/2019 10 DP Schemes

    28/42

    Blocking Schemes

    Bl ki S h I t l F lt

  • 8/10/2019 10 DP Schemes

    29/42

    Blocking Scheme - Internal Fault

    Z3

    Z2

    Z3

    Z2

    Z1

    T3

    Trip

    &

    T2

    &Rx

    Tx

    1

    .

    Z1

    Z1Z2

    Send Logic : Z3 + Z2

    Trip Logic : Rx + Z2

    Z3

    Z3

    Z2

    Z1

    T2

    T3

    Trip

    &

    T2

    &Rx

    Tx

    1

    .

    Bl ki S h E t l F lt

  • 8/10/2019 10 DP Schemes

    30/42

    Blocking Scheme - External Fault

    Z3

    Z2

    Z3

    Z2

    Z1

    T3

    Trip

    &

    T2

    &Rx

    Tx

    1

    .

    Z1

    Z1Z2

    Send Logic : Z3 + Z2

    Trip Logic : Rx + Z2

    Z3

    Z1

    Z2

    Z3

    T2

    T3

    Trip

    &

    T2

    &Rx

    Tx

    1

    .

    Bl ki S h Ad t

  • 8/10/2019 10 DP Schemes

    31/42

    Blocking Scheme - Advantages

    Only simplex signalling channel required

    Provides better resistive coverage than PUR onshort lines where MHO elements are used

    Fast tripping will still be possible at closed end ofline for all fault positions with remote breaker

    open

    Fast tripping will still be possible at strong infeed

    terminal for all fault positions where remote

    terminal has no or weak infeed

    Bl ki S h Di d t

  • 8/10/2019 10 DP Schemes

    32/42

    Blocking Scheme - Disadvantages

    Only 2 forward zones of protection available(unless relay has >3 Zones)

    If signalling channel fails then only Basic schemelogic will apply

    Current sensitivity is lower as tripping elements(Z2) are controlled by high set current level

    detectors (to ensure blocking elements (Z3/Z4)

    are more sensitive than tripping elements)

    Permissive Schemes vs Blocking Schemes

  • 8/10/2019 10 DP Schemes

    33/42

    Permissive Schemes vs Blocking Schemes

    Permissive less reliable - require a signal from

    remote relay plus local operation to trip

    Blocking less secure - require a signal from

    remote relay to prevent a trip

    Permissive schemes are marginally faster and

    more sensitive (timer plus high set currentelements on Blocking scheme)

  • 8/10/2019 10 DP Schemes

    34/42

    Teed Feeders

    Teed Feeders No Zone 1 Coverage

  • 8/10/2019 10 DP Schemes

    35/42

    Teed Feeders - No Zone 1 Coverage

    B

    AC'A'B'

    B'

    A'

    C

    A-A - Zone 1 reach of relay at A

    B-B - Zone 1 reach of relay at B

    C-C - Zone 1 reach of relay at C

    ABC Zone not covered by Zone 1 from any terminal.

    Hence schemes reliant on Zone 1 operation would not

    work (Z1 ext, PUR)

    Teed Feeders Underreaching

  • 8/10/2019 10 DP Schemes

    36/42

    Teed Feeders - Underreaching

    B

    A CZc

    Zb

    Za

    Ia Ic

    Actual impedance to fault from terminal A = Za + Zb

    Measured voltage at terminal A V = Ia.Za + (Ia + Ic).Zb

    Measured current at terminal A I = Ia

    Impedance measured by relay A V/I = Za + Zb + (Ic/Ia).Zb

    Relay therefore measures a greater impedance than the actual impedance

    and underreaches. Must allow for this underreach when setting Zone 2

    elements to ensure correct scheme operation

    Teed Feeders - No/Weak Infeed at One Terminal

  • 8/10/2019 10 DP Schemes

    37/42

    Teed Feeders No/Weak Infeed at One Terminal

    B

    A C

    No infeed from terminal B.

    Fault therefore not covered by Zone 1 from any

    terminal. Hence schemes reliant on Zone 1

    operation would not work (Z1 ext, PUR)

    Teed Feeders - Problems (1)

  • 8/10/2019 10 DP Schemes

    38/42

    Teed Feeders - Problems (1)

    B

    A C

    Relay at terminal B sees a reverse fault. Noscheme will operate at this terminal. Fault

    clearance will be sequential following opening of

    breaker A from relay A Zone 1 element.

  • 8/10/2019 10 DP Schemes

    39/42

    Directional Earth Fault (DEF)

    Directional Earth Fault Schemes

  • 8/10/2019 10 DP Schemes

    40/42

    Directional Earth Fault Schemes

    DEF schemes are identical to Distance

    schemes

    DEF Forward replaces Zone 2, DEF Reverse

    replaces Zone 3/4 Reverse No equivalent to Zone 1 as the DEF elements

    can not have a defined reach, hence no

    schemes using Zone 1 can be replicated (Z1ext, PUR)

    Directional Earth Fault Schemes

  • 8/10/2019 10 DP Schemes

    41/42

    Directional Earth Fault Schemes

    21

    Ea E

    b

    67N

    21

    RF

    Independent

    signallingchannel67N

    Independent signalling channels allows the use of

    different schemes for the distance and DEF

    elements, for example PUR distance with POR DEF

    Directional Earth Fault Schemes

  • 8/10/2019 10 DP Schemes

    42/42

    Directional Earth Fault Schemes

    21

    EaEb

    67N

    21

    RF

    Shared Channel

    67N

    Shared signalling channels limits the use of

    schemes for the distance and DEF elements.

    Both use the same scheme logic.