10 articol toma_rtn_2012[1]
TRANSCRIPT
53
Nonconventional Technologies Review 2012 Romanian Association of Nonconventional Technologies Romania, June, 2012
SOME WAY TO MONITORING THE CONSUMED ENERGY, LOCAL AND GLOBAL, DURING THE ELECTRICAL DISCHARGE MACHINING PROCESS
Emanoil Toma1, Carmen Simion2, Ioan P. Mihu3 and Mihail Aurel Ţîţu4 1 “Lucian Blaga” University of Sibiu-Romania, Department of Computers and Electrical Engineering, [email protected]
2 “Lucian Blaga” University of Sibiu, Department of Industrial Engineering and Management, [email protected] 3 “Lucian Blaga” University of Sibiu-Romania, Department of Computers and Electrical Engineering, [email protected]
4 “Lucian Blaga” University of Sibiu, Department of Industrial Engineering and Management, [email protected]
ABSTRACT:. The consumed energy is determined by sensing and processing the voltage and the current in front of the principal consumers : the power supply of pulse generator, the displacement system of the electrode-tool, the x-y or other axis displacement systems, the circulating system of dielectric liquid, eventually in front of the auxiliary activating systems (magnetic, ultrasonic). An electronic circuit was conceived, based on the high performance microcontroller and dedicated Analogue Front End Device, in two variants. The first variant is very simple; microcontroller receives one pulse at every watt-hour of consumed energy, accumulates it, and communicates via CAN-bus. The second variant is more complicated in the software area; it can measure all power parameters: W, VA, VAR, power factor, RMS voltage and current, total harmonic distortion. It can be a veritable energy analyzer if the software is very elaborated. The main system can communicate with each measuring system and can offer a detailed evolution of consumed energy for analysis. KEY WORDS: Active Power, Energy, Analogue Front End Device, Microcontroller, Controller Area Network (CAN).
1. INTRODUCTION For reducing the consumed energy in Electrical Discharge Machining (EDM) is necessary to monitor the consumed energy for the entire machine tool and for the local consumers: the power supply of pulse generator, the displacement system of the electrode-tool, the x-y or other axis displacement systems, the circulating system of dielectric liquid, eventually in front of the auxiliary activating systems (magnetic, ultrasonic). The system can be applied for other dimensional machining process.
1.1. Energy measurement principle. Electrical energy is defined by equation (1), referred to the figure 1, where i is the instantaneous current, u is the instantaneous voltage across the circuit and p is the instantaneous power.
∫∫ ⋅⋅=⋅= dtiudtpte )( (1)
u
i
CIRCUIT
ELECTRICAL
Figure 1. The energy defining schema
If the power and the energy have positive sign the circuit is Load and consumes energy. If the power and the energy have negative sign the circuit is Source and delivery energy. The measuring circuit is must to sensing the current and the voltage. The conditioning signals are must be multiplied. The results is must be integrated.
Measurement principle is illustrated in figure 2.
METER
LINE_OUT
U
LINE_IN
NULL_OUT
COUNTER
VOLTAGE
I
N=prop.W
CONVERTER
ELECTRONIC
NULL_IN
POWER TO-FREQUENCY
Figure 2. The principle of measuring schema
The block diagram has a power meter, and the counter share having a voltage to frequency converter and an electronic or electromechanical counter.
Energy measurement could be implemented in two principal ways: analogue and digital.
LINE_IN
MULTIPLIER
R_sense
PASSANALOGUE
TO-FREQUENCY
x
y
COUNTER
LOW
u
LINE_OUT
NULL_IN
R1
CONVERTER
R2
NULL_OUT
FILTER
N=prop.W
VOLTAGE
u
Figure 3. Analogue variant of energy measurement
In the analogue variant, presented in the figure 3, the power meter is based on an analogue multiplier.
54
On the inputs of the multiplier come two voltages. One is proportional to the voltage line and the other is proportional to the current.
Between voltage and current there are phase shifting (φ).
tUtu ωsin2)( ⋅⋅= (2) )sin(2)( ϕω −⋅⋅= tIti (3)
U and I are the RMS (Root Mean Square) value of voltage and current.
The output of multiplier gives a voltage proportional to the instantaneous power. The expression of is:
)()()( titutp ⋅= (4) )2cos(cos)( ϕωϕ −⋅⋅−⋅⋅= tIUIUtp (5)
The instantaneous power has two spectral components:
The first term of (5) equation is average value, named real power. the second term is an 2f harmonic component
The low pass filter must reject the 2f component.
The voltage to frequency converter produces the output pulses proportional to the average real power.
These pulses will be accumulated in electronic / electromechanical counter.
The digital variant is presented in the figure 4:
S&H
TO-DIGITAL
LOW-PASS
u
DIGITAL
TO-DIGITAL
ANALOG
CONVERTER
ux
LINE_OUT
CONVERTER
COUNTER
R2
CONVERTER
NULL_IN
ANALOG
N=prop.W
R1
DIGITAL
R_sense
S&H
TO-FREQUENCY
LINE_IN
FILTER
y
NULL_OUT
Figure 4. Digital variant of energy measurement
The analogue signals ux and uy proportional of the voltage and the current must be applied to the inputs of the sample and hold dual unit. The two analog to digital converters furnishes simultaneously at its outputs the two signals in digital form.
The multiplier is hardware implemented for increase the speed. The digital low pass filter is usually a recursive filter based on the structure showed in figure 5 [4].
0
-1
x[ ]
-1
n
z
n-1
n
1
y[ ]
b
w[ ]
1
ny[ ]
b az
Figure 5. The diagram of digital Low Pass Filter (Infinite
Impulse Response Filter).
1.2. Actual state of energy measurements techniques.
Thanks to progress in technology of integrated circuits were achieved complex circuits having inside analogue and digital blocks like microcontrollers. Actually most measuring instruments are performed around a microcontroller. The importance of energy for human society imposed achievement of many instruments for measuring electrical energy consumed.
On the market there are portable measuring instruments named electrical power analyzers. These instruments offer a lot of information about the quality of consumed energy:
catch power quality events such as fast transients (impulses) to few µs, voltage sags (dips), and swells; track total harmonic distortion to the few tens harmonic; record energy use (kWh), and log all power parameters:
watts, va, var, power factor, etc.; data log RMS voltage and current over time
(days/weeks/months) with cycle-by-cycle resolution; display real time values in meter window – just like a
multimeter; display oscilloscope waveforms, harmonic spectra, phasors
via a PC.
These instruments also have one or more communications modules, even wireless.
Having current and voltage probes, these instruments can be easy connected (see figure 6).
ANALYZER
ENERGY
ELECTRICAL
MAINS
NL3L2
probe
L1
current
LOAD
Figure 6. The connection schema of portable energy analyzer
In the consumed energy monitoring we can also use the energy counters. These can be connected in circuit like in figure 7.
55
L2_OUT
N_IN
L2
L3_IN
N_OUT
L1_OUTL1
L2_INCOUNTER
L1_IN
MAINS LOADNL3
ENERGY
L3_OUT
Figure 7. The connection schema of energy counter
It is obvious the necessity of inserting the energy counter in circuit between mains and consumer. Between line_in and line_out there are a shunt resistor or primary coil of current transformer. If the current transducer is based on Hall Effect, between mains and load there are only a wire [1], [2], [5].
2. MODULES OF ENERGY MEASURING BASED ON MICROCONTROLLER AND ANALOG FRONT END CIRCUIT
According to the necessity of reducing power consumed in electrical discharge machining, we conceived a low cost module, to be placed in front of each share part consumer of the machine tool (the power supply of pulse generator, the displacement system of the electrode-tool, the x-y displacement system, the circulating system of dielectric liquid, eventually in front of the auxiliary systems (magnetic, ultrasonic)).
The simplified electrical schema is showed in figure 8.
We used for current sensing a shunt resistor (R_sense) followed by a programmable amplifier contained in the Analog Front End (AFE) circuit MCP3905. The power supply for the AFE circuit, showed in figure 10, is referred to the LINE_IN point.
For voltage sensing we used a voltage divider (R1, R2). Maximum voltage applied to the input of amplifier is a few mV.
Programmable gain amplifier (PGA) can be programmed to have 1, 2, 4 or 16 gain factor, according to the value of R_sense. Analog to digital converter is 16 bits delta-sigma type. Two digital high-pass filters cancel the system offset on both channels such that the real-power calculation does not include any circuit or system offset.
After being high-pass filtered, the voltage and current signals are multiplied to give the instantaneous power signal. This signal does not contain the DC offset components, such that the averaging technique can be efficiently used to give the desired active-power output. The instantaneous power signal contains the real power information; it is the DC component of the instantaneous power. The averaging technique can be used with both sinusoidal and non-sinusoidal waveforms, as well as for all power factors. The instantaneous power is thus low-pass filtered in order to produce the instantaneous real-power signal.
A digital-to-frequency converter accumulates the instantaneous active real power information to produce output pulses with a frequency proportional to the average real power. The low-frequency pulses present at the FOUT0 and FOUT1 outputs are designed to drive electromechanical counters and two-phase stepper motors displaying the real-power energy consumed. Each pulse corresponds to a fixed quantity of real energy, selected by the F2, F1 and F0 logic settings.
The pulses are applied to timer input of microcontroller. The microprocessor substitutes the electronic/electromechanical counter and supplementary communicates on industrial CAN bus with other modules and/or PC.
Optionally the module can also communicate with PC via RS232 serial interface.
For three phase energy counter is necessary to have three analog front end circuits MCP3905, like is showed in figure 9.
Every AFE circuits have proper power supply referred to the own LINE_IN point and proper voltage and current sensing circuits also. On the other hand every AFE circuits have is followed by proper opto - coupler circuit to transmit pulses to microcontroller.
R4
VDD_AUX
PGA
A
ADC
ADC
-
-
+
+
ANALOG DIGITAL
CH0+
CH0-
CH1+
CH1-
AVDD DVDD
DVSSAVSS
HPF
HPF
LPF DFC
OUT0
OUT1
OUT
i
u
p
FFHF
MCP3905
NULL_IN
LINE_IN
R2
R1
NULL_OUT
LINE_OUTR_sense
R3U2
TCDT1101G
VDD1VDD1
TX
RX
CAN H
CAN L
CAN- TRANSCEIVER
1
2
3
4
5
6
7
8
9
DB9_F
123
VDD
IC2
C1RX
C1TX
VSS
U1RX
U1TX
16-Bit
MICROCONTROLLER
RS232
VDD_AUX
Figure 8. The simplified electrical schema of proposed energy measuring module
56
R4
VDD_AUX
CH0+
CH0-
CH1+
CH1-
AVDD DVDD
DVSSAVSS
HFOUT
U1
MCP3905
NULL_IN
R_IN
R1_R
NULL_OUT
R_OUTR_sense_R
R3U4
VDD_R
TX
RX
CAN H
CAN L
CAN- TRANSCEIVER
1
2
3
4
5
6
7
8
9
DB9_F
123
VDD
IC1C1RX
C1TX
VSS
U1RX
U1TX
IC2
IC3
16-Bit
MICROCONTROLLER
RS232
VDD_AUXVDD_R
CH0+
CH0-
CH1+
CH1-
AVDD DVDD
DVSSAVSS
HFOUT
U2
MCP3905
S_IN
R2_S
R_sense_S
VDD_S VDD_S
S_OUT
CH0+
CH0-
CH1+
CH1-
AVDD DVDD
DVSSAVSS
HFOUT
U3
MCP3905
T_IN T_OUT
R2_T
R_sense_T
VDD_T VDD_T
VDD_AUX
R6
R5U5
VDD_AUX
R8
R7U6
R2_R
R1_S R1_T
Figure 9. The simplified electrical schema of proposed three
phase energy counter
R17
470/2W
C20
470nF/630V
D4 PL15Z
C21 470u/16V
1 26
43578
U7
78L05
C23 100nVDD1
D5
1N4007
RV2 275V
NULL_IN
LINE_IN
NULL_OUT
LINE_OUTR_sense
Figure 10. Electrical schema of AFE power supply
Power supply for microcontroller and CAN transceiver must be galvanic separated toward mains. We used an integrated DC to DC converter AM1D-1212 (figure 11). Both power supply offer a weak current. If the microcontroller is used to perform more calculus the consumed current increase. In this case another schema of power supply is necessary.
R15
470/2W
C16 470u/16V
RV1 275V
D3
1N4007
C15
470nF/630V
D2 PL15Z
1 2
4 3
U5
AM1D-1212
C18 10u/16V
C19 100n
VDD_AUX
1 26
43578
U6 78L05
0
C17 2U2
LINE_IN
NULL_IN
LINE_OUT
R_sense
NULL_OUT
Figure 11. Electrical schema of microcontroller and communication port power supply
Analog Front End device used in fig. 8 is MCP3905 and another version, like MCP3909, has supplementary a digital serial peripheral interface and can communicates with microcontroller.
The microcontroller read the value of instantaneous real power and calculates the energy.
The microcontroller can read the value of voltage and instantaneous current for calculating the RMS value, Fourier transforming, total harmonic distortions, etc.
CAN_ADAPTER
CAN_BUS
no_2
no_1
MODUL
no_kno_3
MODUL
MODUL
PC
MODUL
Figure 12. Connection diagram of the modules
57
R1
NULL_IN
0
R2
0
RS232
+
-
+
-
VDD1
VSS1
VDD2
VSS2
123
CAN- TRANSCEIVER
TX
RX
CAN H
CAN L
NULL_OUT
DB9_F
1
2
3
4
5
6
7
8
9
16-Bit
MICROCONTROLLER
RE0
VDD
SDO
RE1
SCK
RB2
SDIC1RX
C1TX
VSS
U1RX
U1TX
OC1
RB3
RB4
PGA
PGA
ADC
SINC
FILTER
ADC
3
3
FILTER
SINC
PHASE
SHIFTER
DIGITAL
SPI
INTERFACE
-
-
+
+
CS
SCK
SDI
RESET
SDO
DR
ANALOG DIGITAL
CH0+
CH0-
CH1+
CH1-
AVDD DVDD
DVSSAVSS
OSC1
MDAT0
MDAT1
U4
+
-
+
-
VDD1
VSS1
VDD2
VSS2
R_senseLINE_IN
0
0
LINE_OUT
Figure 13. The simplified electrical schema of proposed energy analyzer module.
The Analog Front End device used in figure 13 communicates with microcontroller through the digital serial peripheral interface (SPI). AFE not includes digital multiplier and digital low pass-filter. It offers information about only instantaneous value of current and voltage.
The 24 bits delta-sigma ADC increases the accuracy of measurement. The microcontroller must achieve the functions
performed by precedent AFE: digital multiplication, the offset rejection, and low-pass filtering. Moreover, an adequate software implemented on microcontroller could offer the possibilities to measure another parameters like RMS value of voltage and current, active power, apparent power, power factor such as is showed in figure 14.
Figure 14. The diagram of power parameters digital calculation.
3. REFERENCES 1. King, C., IEC Compliant Active-Energy Meter Design
Using The MCP3905A/06A, Available from: http://ww1.microchip.com/downloads/en/AppNotes/00994b.pdf
2. King, C., Quiquempoix, V. Designing with the MCP3901 Dual Channel Analog-to-Digital Converters, Available from: http://ww1.microchip.com/downloads/en/AppNotes/01300a.pdf
3. Chlebis, P., Pumr, J., Simonik, P. Current sensor with the DSP, International Conference, Applied Electronics (AE), ISBN: 978-80-7043-865-7, (2010).
4. Mateescu, A., Dumitriu, N., Stanciu L. Semnale şi sisteme – Aplicaţii în filtrarea semnalelor, Editura Teora, ISBN 973-20-0666-8, Bucureşti, (2001).
5. Moulin, E. Measuring Harmonic Energy with a Solid State Energy Meter, Available from: http://www.analog.com/static/importedfiles/tech_articles/17011149511795ANALOG_PAGE_68-71.pdf
6. Toma, E., Mihu, P. I., Nanu, D. Some possibilities to monitoring the energy consumed in electrical discharge machining, Proceedings of the 15th International Conference, Modern Technology, Quality and Innovation, Vol. II, pp 1077-1080, Vadul lui Voda-Chisinau, Republic of Moldova, (2011).