Deterioration of Trusses and Roof Systems of Livestock Farm

Buildings

By Yves Choinière

Ing., agr., P. Eng.

CSBE: 08-117

2

Introduction

Deterioration of steel and wood components of farm building– Well known– Documented

3

Case study

#1: Finishing swine barn, Ontario– Power-natural ventilation versus 100 % natural

ventilation #2: Nursery-finishing, Ontario

– Mechanical ventilation #3: Finishing swine barn, Quebec

– 100 % natural ventilation #4: Pullet rearing barn

– Mechanical ventilation

4

Case #1: Finishing swine barn

5

Case #1: Finishing swine barn

Barn A– Power-natural ventilation, 1996– Winter pit fans– Modular ceiling air inlets– Deep pit over slatted floor– Summer natural ventilation

Barn B– 100 % natural ventilation, 1995– Similar to barn A

6

7

8

9

10

11

12

13

14

15

16

17

Table of results, power-natural 1996

November 21, 2007

Exterior T° = 5°C, rain

Attic measurements In-barn

T° 6-7° C 15-16° C

R.H. % 60-65 % 80-85 %

NH3 2-4 ppm 15 ppm

CO2 600-700 ppm 3 000 ppm

18

Table of results, 100 % natural 1996

Attic measurements In-barn

T° 6-7° C 15-16° C

R.H. % 70-75 % 70 %

NH3 N\D 15 ppm

CO2 400-500 ppm 3 000 ppm

19

20

21

22

23

24

25

26

Observations

Attic space contamination from the barn to the attic by :– Modular air inlets– Fan exhaust– Eave openings– Vapor barrier failure

27

Case #2: Nursery-finishing barn

28

Case #2: Nursery-finishing

Mechanical ventilation– Ceiling modular air inlets– Sidewall fans– Open eave

29

30

31

32

33

34

35

Table of results, 1997-1998

Attic measurements In-barn

T° 7-8° C 21-22° C

R.H. % 75-80 % 70-75 %

NH3 6-7 ppm 16-17 ppm

CO2 700-800 ppm 2 800-3 000 ppm

36

Observations

Attic space contamination :– Modular air inlets– Fan exhaust– Eave openings– Vapor barrier failure

37

Case #3: Finishing swine naturally ventilated barn

Natural ventilation– Alley scrappers– Eave openings– Attic ventilation

38

39

40

41

42

43

44

45

Observations

Eave opening desing; minimum space Vapor barrier Chimney vapor tightness Ridge ventilator, snow + rain

46

Case #4: Pullet rearing barn, 1976

Sidewall air inlets without attic contact Sidewall fan exhaust with wind stoppers

47

48

49

50

51

52

53

54

Conclusion

Ceiling modular air inlets– Risk of attic backdraft– Sealed or negative pressure

Sidewall exhaust fans– No eave openings above winter fans– Fans with winter hoods– Eave opening desing

55

Conclusion

Attic ventilation– Ridge ventilator– Eave openings, winter and summer– Fire stops

56

Aknowledgements

Greg Zimmer, Ontario André Lafrance, Quebec

VicWest steel products