  • 236 A&T PROJECT DEVELOPMENTS INC.

    FIRE SUPPRESSION

  •  

     

    Echo Landing 

    5025 Valley Drive, Sun Peaks 

    Fire Sprinkler  

     Maintenance Manual  

     

     

  • Response Fire Systems Ltd. Date: December 14, 2018

    891 Sumac Place

    Kamloops, BC

    V2B 6R4

    Warranty

    Re: Echo Landing - Sun Peaks, BC

    This letter verifies a warranty period of one year for parts and labor for the

    specified location and dates.

    Location: Echo Landing – Valley Drive - Sun Peaks, B.C.

    From: December 14, 2018

    To: December 14, 2019

    Warranty coverage: All labor, piping, fittings, sprinklers & equipment attached to the new

    wet sprinkler and standpipe system. The water service pipe that connects the sprinkler system to the city mains was installed by others and is not covered under this warranty.

    Sincerely, Morgan Martel - Principal

  • Response Fire Systems Ltd. Date: December 14, 2018

    891 Sumac Place

    Kamloops, BC V2B 6R4

    [email protected]

    Re: Echo Landing– 5025 Valley Drive - Sun Peaks, BC

    The entire building is protected by an automatic sprinkler system that is charged with water at all times. The water flow is controlled by individual sprinkler heads. These sprinkler heads are heat actuated and require a temperature of 155*F to discharge. Water will continue to flow after the sprinkler has discharged until the appropriate main control valve is shut off. Each floor level has an individual shut off valve (zone valve) and drain valve. The locations of these zone valves are on the as built drawings, maintenance manuals and on the valve identification chart located in the main mechanical room. Each individual valve station has a flow switch installed. It is very important that the owners are familiar with the locations of the main control valves in case of an emergency due to a non-fire condition. A sprinkler system main control valve should never be closed until the fire department determines that a fire condition does not exist. Once a sprinkler head has discharged it must be replaced and pressure restored to the system. This work can only be performed by a qualified sprinkler fitter with the appropriate insurance.

    Attached to this booklet is a complete list of material specifications and maintenance requirements of all the equipment installed on the fire sprinkler system.

    For any questions, service, inspections or maintenance requirements please call Morgan Martel at Response Fire Systems Ltd. At 250-578-7779, cell 250-319-5604 or email [email protected]

  • a company

    ®

    ®

    Zurn Industries, LLC | Wilkins1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766

    In Canada | Zurn Industries Limited3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292

    www.zurn.com

    Rev. D

    Date: 12/13

    Document No. BF-350XL

    Patent No. 7,434,593, 7,784,483, & 7,905,250

    Product No. Model 350XL

    Model 350XLDouble Check Valve Assembly

    Page 1 of 2

    Options(Suffixes can be combined)

    c - with full port QT ball valves (standard)c L - less ball valves, male pipe threadc S - with Model SXL lead-free bronze "Y" type strainerc SH - with stainless steel handlesc FT - with integral male 45° flare SAE test fittingc BOF - with blow out / flush fitting

    Accessoriesc Repair kitc Thermal expansion tank (Model XT)c QT-SET Quick Test Fitting Setc Winterizing Blow out/Flush fitting (RK34-350BOF, RK1-350BOF or RK114-350-375BOF)

    B

    G

    A

    E

    F

    C

    D

    W

    ILKIN

    S

    XL

    WILKINS 350XL

    DC

    G

    A

    H

    E

    F

    C

    D

    350 DC

    175 PSIG 180 F

    2

    WILK

    INS

    XL

    OPTIONAL LEAD-FREE STRAINER

    (MODEL SXL)

    � � � � �� � �� � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! "# � � � " ! # #$ ! # $ � � % � � & � � # � � �" ! # #$ ! # $ � � � � �" ! # #$ ! # $ � �� ' ( � � � ' ( � � � ' ( � � � ' ( � � � ' ( � � � ' ( � � � ' ( � � � ' ( � � � ' ( � � ) * + ( , - ) * + ( , -. / 0 1 2 3 3 1 4 5 6 7 / 8 3 6 8 3 4 / 8 0 8 . . / 0 5 7 . 4 6 3 3 / 0 . 1 3 7 3 / 8 . 8 0 3 3 4 / 3 6 1 5 3 1 ( . 3 ( 2 0 ( . 1 ( 23 1 7 3 1 3 / 0 . 3 3 4 3 4 8 1 3 / 3 6 7 1 0 3 / 8 3 2 7 . 3 / 0 8 . 3 . / 0 0 7 3 4 0 . 3 3 1 7 / 3 6 . 3 . . ( 2 3 ( 0 6 ( 2 1 ( 43 9 3 / 0 . 1 3 0 4 / 8 . 4 8 3 0 . / 8 . 6 4 . . / 8 8 6 6 . / 0 3 4 3 . . / 0 5 7 1 3 / 0 7 4 1 2 3 / 1 7 1 3 3 8 3 / 1 0 4 2 3 4 ( 1 4 ( 8 3 5 8 ( 63 9 3 / 1 0 2 3 7 3 / 0 . 8 4 3 0 . / 8 . 6 4 . . / 8 8 6 6 . / 0 3 4 3 . . / 0 5 7 1 3 / 0 7 4 1 1 7 7 5 1 2 3 / 0 7 3 0 3 4 4 ( 4 1 2 5 ( 31 7 2 3 6 0 2 6 3 0 . / 8 . 6 4 . . / 8 8 6 6 . / 0 3 4 3 . . / 0 5 7 1 3 / 0 7 4 1 0 6 2 5 1 2 . / 0 7 1 4 3 8 8 ( 1 1 1 3 2Dimensions & Weights (do not include pkg.)

    (3/4" - 1") (1-1/4" - 2")

    ApplicationIdeal for use where Lead-Free* valves are required. Designed for installation on potable water lines to protect against both backsiphonage and backpressure of polluted water into the water supply. Assembly shall provide protection where a potential health hazard does not exist.

    Standards Compliance(Horizontal & Vertical) • ASSE® Listed 1015• IAPMO® Listed• CSA® Certified B64.5• AWWA Compliant C510• Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California • UL® Classified (less shut-off valves only)• C-UL® Classified (less shut-off valves only)

    • Certified to NSF/ANSI 372* by IAPMO R&T

    • NSF® Listed-Standard 61, Annex G**(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)

    MaterialsMain valve body Cast Bronze, ASTM B 584 (3/4-1")Housing Reinforced NylonFasteners Stainless Steel, 300 SeriesElastomers Silicone (FDA Approved) Buna Nitrile (FDA Approved)Internals Delrin, NSF Listed Springs Stainless Steel, 300 seriesBall Valves Cast Bronze, ASTM B 584Struts Forged Brass ASTM B 124Features

    Sizes: 3/4", 1", 1-1/4", 1-1/2", 2"Maximum working water pressure 175 PSIMaximum working water temperature 180°FHydrostatic test pressure 350 PSI

    End connections Threaded ANSI B1.20.1

  • : ; < = > ? @ A B C = D < ; E @ F D G = > E H ; I I J A K ; @ ; L = M N F = D OFlow Characteristics

    Zurn Industries, LLC | Wilkins1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766

    In Canada | Zurn Industries Limited3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292

    www.zurn.com Page 2 of 2

    P Q R S T U V W X T Y Z Y [ \ ] ^ Y Z Y [ _ ] ` _ ] a b c d e R d f R ` P S c f g h ijkl jl k j k j l j j l k j m j j m k jn o p q r s t u v w x y z {|}~}~

    |

     ¡¢¢£ ¡¤¥¢¢ ¦§ ©̈ª

    P Q R S T U V W X T U [ \ ] ` Y ] a b c d e R d f R ` P S c f g h ijkl jl k j m j « j ¬ j jn o p q r s t u v w x y z {|}~}~

    | ®

     ¡¢¢£ ¡¤¥¢¢ ¦§ ©̈ª

    Typical InstallationLocal codes shall govern installation requirements. To be

    installed in accordance with the manufacturers’ instructions

    and the latest edition of the Uniform Plumbing Code. Un-

    less otherwise specified, the assembly shall be mounted at

    a minimum of 12” (305mm) and a maximum of 30” (762mm)

    above adequate drains with sufficient side clearance for testing

    and maintenance. If installed below grade, be certain adequate

    drainage is provided to prevent the device from being sub-

    merged.

    OUTDOOR INSTALLATIONINDOOR INSTALLATION

    Speci! cations

    The Double Check Valve Backflow Preventer shall be certified to NSF/ANSI 372, shall be ASSE® Listed 1015,

    rated to 180°F, and supplied with full port ball valves. The main body shall be low lead Bronze for sizes 3/4" &

    1", and Nylon for sizes 1-1/4" to 2". The housing shall be reinforced Nylon and the seat disc elastomers shall be

    silicone (FDA Approved). The first and second checks shall be accessible for maintenance without removing the

    device from the line. The Double Check Valve Backflow Preventer shall be a ZURN WILKINS Model 350XL.

    ¯ ° ± ° ² ³ ´ µ ´ ¶ · ¸ ¹ ² ¶ º » ¸ ¼ º ½ ¾ ¿ ³ ± º¿ ³ ± º À ³ Á º  à ´ Ä À º ² Å Æ Â Ã ´ Ä À º ² Ç ¾ à ´ Ä À º ² Ç Â Ã ´ Ä À º ²Ç Ä È É Â Å Ê Ç ½Ë Ä ½ É Ì Ç È Ç Å È ÂÇ É Ç Ë È ¾ È Å ½ ¾Ç Ç Ä ½ É È Ë Ë Â ½ Å Å ¾Ç Ç Ä È É Ë È ½ Ì Í Ë Ê ÂÈ É Â È Å Ì Ç ¾ Â Ç Í Å

    Î Ï Ð Ñ Ò Ó Ó ÔÕ Ö Õ × Ø Ï Ð Ù Î Ó Ó Ô Õ Ö Õ × Î Ï Ð Ø Ò Ó Ó ÔÙ × Ø Ï Ð Î Ò Ó Ó Ô Õ Ï Ð Î Ñ Ó Ó Ô

    DIR

    EC

    TIO

    N O

    F F

    LO

    W

    2350X

    L D

    C

    175 P

    SIG

    180°

    F

    ZURNWILKINS

    /

    PROTECTIVE

    ENCLOSURE

    DIRECTION OF FLOW

    12" MIN.

    30" MAX.

    Ú Û Ü Ý Û Þ ßà Ü á â ã ä â å æ ç è é ê ãë ìOPTIONAL LEAD-FREE STRAINER (MODEL SXL)

  • Submittal Data SheetBlazeMaster®

    introductionIPEX BlazeMaster® pipe and fittings are designed specifically for fire sprinklersystems. They are made from a specialty thermoplastic known chemically as post-chlorinated polyvinyl chloride (CPVC). IPEX BlazeMaster pipe and fittings provideunique advantages in sprinkler installations including superior hydraulics, ease ofjoining, increased hanger spacing in comparison to other thermoplastics and easeof assembly. They also are based on a technology with a continuous and provenservice history of more than 40 years.

    Fire Performance

    BlazeMaster is made with CPVC which offers an even greater fire safety profilethan PVC. Like PVC, CPVC will not independently support combustion, and as suchwill not burn once the flame source is removed. CPVC’s ignition resistance isdemonstrated by its flash ignition temperature of 900°F.

    CPVC also has a low flame spread. In addition, it provides outstanding smokecharacteristics. In testing conducted to CAN/ULC S102.2, CPVC showed a flamespread of less than 15, and a smoke-developed classification of 15. And, like PVC,CPVC has a fuel contribution of 0.

    1 of 8

    < S T A N D A R D S >

    D1784, F437,F438, F439,F442

    18211887

    C199 P-M

    13, 13R13D, 90A24

    Job or Customer:

    Engineer:

    Contractor:

    Submitted by:

    Approved by:

    Order No:

    Specification:

    Installation Date:

    Date

    Date

    Date

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

  • BlazeMaster®

    2 of 9

    Submittal Data Sheet

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    material properties availabilityDescription Size (in)

    Pipe 3/4 to 3”

    Fittings

    Tee (Soc) 3/4" to 3"

    Reducing Tee (Soc)3/4" to 3" x 3/4"3" x 3/4" to 2-1/2"

    Sprinkler Head Adapter Tee (Soc x Soc x SST FPT)

    3/4" to 2" x 3/4"2" x 1/2"

    Sprinkler Head Adapter Tee (FPT x FPT x Soc)

    1/2" x 1/2" 1"

    90° Elbow (Soc) 3/4" - 3"

    Sprinkler head Adapter 90° Elbow(Soc x SST FPT)

    3/4" to 1-1/4" x 1/2" to3/4"

    45° Elbow (Soc) 3/4" to 3"

    Cross (Soc) 3/4" to 2-1/2"

    Coupling (Soc) 3/4" to 3"

    Grooved Adapter Coupling (Soc x Groove)

    1-1/4" to 3"

    Female Adaptor (Soc x SST FPT) 3/4" to 2"

    Sprinkler Head Adaptor (Soc x SST FPT)

    3/4" to 1-1/4" x 1/2" to3/4"

    Sprinkler Head Adaptor (Sp x SST FPT)

    3/4" to 1" x 1/2"

    Reducer Bushing (Spig x Soc) 1" to 3" x 3/4" to 2-1/2"

    Cap (Soc) 3/4" to 3"

    Union (Soc) 3/4" to 2"

    One Piece Flange (Soc) 3/4" to 3"

    Physical & Thermal Properties of BlazeMaster CPVC

    Property CPVC ASTM

    Specific Gravity 1.55 D792

    IZOD Impact Strength (ft. lbs./inch, notched)

    3.0 D256A

    Modulus of Elasticity, @ 73°F, psi 4.23 x 105 D638

    Ultimate Tensile Strength, psi 8,400 D638

    Compressive Strength, psi 9,600 D695

    Poisson’s Ratio .35 - .38 -

    Working Stress @ 73°F, psi 2,000 D1598

    Hazen-Williams C Factor 150 _

    Coefficient of Linear Expansionin./(in.°F)

    3.4 x 10-5 D696

    Thermal ConductivityBTU/hr./ft.2/°F/in.

    0.95 C177

    Limiting Oxygen Index 60% D2863

    Electrical Conductivity Non Conductor

  • Outdoor Installations

    IPEX BlazeMaster pipe and fittings are not listed for exposed,outdoor applications.

    Joining IPEX BlazeMaster Pipe and Fittings with Red One Step Solvent Cement

    Note: BlazeMaster BM-5 One Step Cement requires no cleaner orprimer. Refer to individual manufacturers’ installation instructions.

    Cutting

    IPEX BlazeMaster pipe can be easily cut with a sharp ratchetcutter (except at temperatures below 10ºC (50ºF)), a wheel-typeplastic tubing cutter, a power saw ora fine toothed saw. To ensure thepipe is cut square, a miter box isrecommended when using a saw. Asquare cut provides the surface of thepipe with maximum bonding area. Ifany indication of damage or crackingis evident at the pipe end, cut off atleast 50.8 mm (2") beyond anyvisible crack.

    Deburring

    Burrs and filings can prevent propercontact between pipe and fittingduring assembly, and must beremoved from the outside and theinside of the pipe. A chamfering toolor a file is suitable for this purpose. Aslight bevel shall be placed at theend of the pipe to ease entry of thepipe into the socket and minimize the chancesof wiping solvent cement from the fittingduring insertion.

    Fitting Preparation

    Using a clean, dry rag, wipe loose dirt and moisture from thefitting socket and pipe end. Moisture can slow the cure time andat this stage of assembly, excessive water can reduce jointstrength. Check the dry fit of the pipe and fitting. The pipeshould enter the fitting socket easily 1/4 to 3/4 of the way. At thisstage, the pipe should not bottom out in the socket.

    Solvent Cement Application

    Joining surfaces shall be penetrated and softened. Cement shallbe applied (worked into pipe) with an applicator half the nominalsize of the pipe diameter. Apply a heavy, even coat of cement tothe outside pipe end. Apply a medium coat to the fitting socket.

    Pipe sizes 1-1/4" (32 mm) and aboveshall always receive a second cementapplication on the pipe end. (Applycement on the pipe end, in the fittingsocket, and on the pipe again.) Onlyuse solvent cements that have beenspecifically investigated and tested foruse with BlazeMaster CPVC systemsand approved by the pipe and fittingmanufacturer. Too much cement cancause clogged waterways. Do not allowexcess cement to puddle in the pipeand fitting assembly.

    Special care shall be exercised whenassembling BlazeMaster systems inextremely low temperatures (below 4°C(40ºF)) or extremely high temperatures(above 38°C (100ºF)). Extra set timeshall be allowed in colder temperatures.When cementing pipe and fittings inextremely cold temperatures, make certain that the cement has not“gelled”. Gelled cement must be discarded. In extremely hottemperatures, make sure both surfaces to be joined are still wetwith cement when putting them together.

    Assembly

    After applying cement, immediately insert the pipe into the fittingsocket, while rotating the pipe one-quarter turn. Properly align thefitting for the installation at this time. Pipe must bottom to thestop. Hold the assembly for 10 to 15 seconds to ensure initialbonding. A bead of cement should be evident around the pipe andfitting juncture. If this bead is not continuous around the socketshoulder, it may indicate that insufficient cement was applied.

    BlazeMaster®

    3 of 9

    Handling & Installation Procedures

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

  • BlazeMaster®

    4 of 9

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    If insufficient cement is applied, the fitting must be cut out anddiscarded.

    Cement in excess of the bead can be wiped off with a rag. Careshall be exercised when installing sprinkler heads. Sprinkler headfittings shall be allowed to cure for a minimum of 30 minutesprior to installing the sprinkler head. When installing sprinklerheads, be sure to anchor or hold the pipe drop securely to avoidrotating the pipe in previously cemented connections. Previouslycemented fittings shall also be permitted to cure for a minimumof 30 minutes.

    Warning: Sprinkler heads shall be installed only after all the CPVCpipe and fittings, including the sprinkler head adapters, aresolvent welded to the piping and allowed to cure for a minimumof 30 minutes. Sprinkler head fittings should be visuallyinspected and probed with a wooden dowel to ensure that thewater way and threads are clear of any excess cement. Once theinstallation is complete and cured per Table I, II or III, the systemshall be hydrostatically tested. Sprinklers shall not be installed inthe fittings prior to the fittings being cemented in place.

    Note: Safety and Health Precautions. Prior to using CPVC solventcements, review and follow all precautions found on the containerlabels, material safety data sheet, and Standard Practice for SafeHandling ASTM F 402.

    Set and Cure TimesSolvent cement set and curetimes are a function of pipe size,temperature, relative humidity,and tightness of fit. Curing time isfaster for drier environments,smaller pipe sizes, highertemperatures and tighter fits. Theassembly must be allowed to set,without any stress on the joint, for1 to 5 minutes, depending onpipe size and temperature.Following initial set period, the assembly can be handledcarefully, avoiding significant stresses to the joint. Refer to thefollowing tables for minimum cure times prior to pressure testing.

    Table I: 552 kPa (225 psi) Test Pressure (maximum)Ambient Temperature During Cure Period

    Pipe Size Temperature

    inches mm16°C to 49°C

    (60°F to 120°F)> 4.4°C (> 40°F)

    >17.8°C (> 0°F)

    3/4 20 1 hr 4 hrs 48 hrs

    1 25 1-1/2 hrs 4 hrs 48 hrs

    1-1/4 32 & 40 3 hrs 32 hrs 10 days

    2 50 8 hrs 48 hrs Note 1

    2-1/2 & 3 65 & 80 24 hrs 96 hrs Note 1

    Table II: 1379 kPa (200 psi) Test Pressure (maximum)Ambient Temperature During Cure Period

    Pipe Size Temperature

    inches mm16°C to 49°C

    (60°F to 120°F)> 4.4°C (> 40°F)

    >17.8°C (> 0°F)

    3/4 20 45 mins 1-1/2 hrs 48 hrs

    1 25 45 mins 1-1/2 hrs 48 hrs

    1-1/4 32 & 40 1-1/2 hrs 16 hrs 10 days

    2 50 6 hrs 36 hrs Note 1

    2-1/2 & 3 65 & 80 8 hrs 72 hrs Note 1

    Table III: 690 kPa (100 psi) Test Pressure (maximum)Ambient Temperature During Cure Period

    Pipe Size Temperature

    inches mm16°C to 49°C

    (60°F to 120°F)> 4.4°C (> 40°F)

    >17.8°C (> 0°F)

    3/4 20 15 mins 15 mins 30 mins

    1 25 15 mins 30 mins 30 mins

    1-1/4 32 & 40 15 mins 30 mins 2 hrs

    Note: Cure times indicated in Table 1 are to be used for all LPCBapproved pipe and fitting joints.

    Note: For these sizes, the solvent cement can be applied attemperatures below -17.8°C (0°F), however, the sprinkler systemtemperature must be raised to a temperature of 0°C (32°F) orabove and allowed to cure per the above recommendations prior topressure testing.

    Handling & Installation Procedures

  • BlazeMaster®

    5 of 9

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    Threaded ConnectionsIPEX BlazeMaster CPVC female threaded adapters or flanges arelisted for connecting a BlazeMaster fire sprinkler system to othermaterials, valves, and appurtenances.

    A thread sealant shall be used in making threaded connections.TFE (Teflon®) thread tape is the recommended sealant. Somethread sealants other than TFE thread tape contain solvents orother materials that may be damaging to CPVC. Contact yourauthorized IPEX BlazeMaster distributor or IPEX Representativefor approved thread sealants. Use of thread sealants other thanthose approved by IPEX will void the warranty on the IPEXBlazeMaster system.

    Care shall be exercised when transitioning between IPEXBlazeMaster pipe and fittings and metal. Care must be taken toavoid over-torquing. Refer to section on instructions for torquerequirements.

    The following is the recommended method of installation toensure a sound connection.

    a) Begin by applying 2 to 3 wraps of TFE (Teflon®) threadtape.

    b) Tighten the sprinkler head into the adapter taking carenot to cross-thread the fitting. (Recommended torquevalues 15-25 ft/lbs)

    c) Two to three turns beyond finger-tight is all that isrequired to make a sound plastic threaded connection.

    CAUTION: Over-tightening will damage both the pipe and thefitting.

    Flanged ConnectionsFlange Make-Up: Once a flange is joined to pipe, the method forjoining two flanges is as follows:

    1. Piping runs joined to the flanges must be installed in astraight line position to the flange to avoid stress at the flange due to misalignment. Piping must also be secured and supported to prevent lateral movement that can create stress and damage the flange.

    2. With gasket in place, align the bolt holes of the matingflanges by rotating the ring into position. (Consideration should be given to alignment of One-Piece Flange prior to joining with pipe.)

    3. Insert all bolts, washers (two standard flat washers perbolt), and nuts.

    4. Make sure the faces of the mating surfaces are flushagainst gasket prior to bolting down the flanges.

    5. Tighten the nuts by hand until they are snug. Establishuniform pressure over the flange face by tightening thebolts in 5 ft. lb. (6.8 M Kg) increments according to thesequence shown in Figure 8: Bol Tightening Sequencefollowing a 180° opposing sequence.

    6. Care must be taken to avoid “bending” the flange whenjoining a flange to a “raised face” flange, or a wafer-stylevalve. Do not use bolts to bring together improperlymated flanges.

    Caution: Over-torquing will damage the flange. Torque givenis for dry, non-lubricated bolt, standard washers, neoprene3.18 mm (1/8²) thick full face gasket. If lubricant (non-petroleum based) is used, torque levels may vary. Actual fieldconditions may require a variation in these recommendations.

    Recommended Bolt Torque

    Flange Size Bolt Diameter Torque

    inches mm inches mm ft lbs M Kg

    3/4 - 1-1/2 19.05 - 38.10 1/2 12.70 10 - 15 13.6 - 20.3

    2 - 3 50.80 - 76.20 5/8 15.88 20 - 30 27.1 - 40.7

    Figure 8:Bolt Tightening

    Sequence

    Handling & Installation Procedures

  • BlazeMaster®

    6 of 9

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    Grooved Coupling AdaptersThe following procedures are recommended for proper assembly ofthe Grooved Coupling Adapter. READ THESE INSTRUCTIONSCAREFULLY BEFORE BEGINNING INSTALLATION.

    1. Inspect the fittings and pipe to insure that they aresufficiently free from indentations, projections or roll-markson the gasket seating areas of the fitting and pipe. The pipeshould be squarely cut with any loose scale, paint and/ordirt must be removed from the groove and seating surface.Use a standard grade E*, EPDM compound that is suitablefor wet fire sprinkler service. A flexible coupling shall beused with grooved coupling adapters. Caution: Use of rigidstyle couplings may damage the grooved coupling adapter.Consult the coupling manufacturer for proper selection.

    *See manufacturer for temperature ratings.

    2. Make sure the gasket is clean and free of any cracks, cutsor other defects which may cause leaks. Lubricate thegasket with a vegetable soap-based gasket lubricant.Caution: Use of petroleum based lubricants will damagethe gasket and adapter resulting in stress failure of theCPVC adapter. A gasket/joint lubricant is recommended toprevent pinching the gasket and to assist in seating thegasket during the alignment process. Apply the appropriatelubricant to the gasket lips and exterior surface of thegasket.

    3. Place the gasket over the metal pipe ends, being sure gasket lip does not overhang the pipe end. Insert the CPVCgrooved coupling adapter into the gasket. Make sure thatthe gasket is centered between the two grooves. No portionof the gasket should extend into the grooves. Caution:Make sure the gasket is not pinched between the pipe andthe fitting.

    4. Place the metal housing over the gasket, making sure the metal housing key is into the grooves on the metal pipeand the CPVC coupling adapter. Insert the bolts and tightenby hand. Tighten the bolts alternately and equally until thebolt pads are touching metal-to-metal. In completing aproper joint, the gasket is also slightly compressed, addingto the strength of the seal from the gasket’s durometer.

    5. Inspect the joints before and after pressure testing. Look forgaps between the bolt pads and for housing keys that arenot inside the grooves.

    Penetrating Fire Rated Walls and PartitionsBefore penetrating fire rated walls and partitions, consult buildingcodes and authorities having jurisdiction in your area. Severalclassified through-penetration firestop systems are approved for usewith CPVC pipe. Consult IPEX representative for further information.Warning: Some firestop sealants or wrap strips contain solvents orplasticizers that may be damaging to CPVC. Always consult themanufacturer of the firestop material for compatibility with IPEXBlazeMaster CPVC pipe and fittings.

    Earthquake BracingSince IPEX BlazeMaster CPVC pipe is more ductile than metallicsprinkler pipe, it has a greater capacity to withstand earthquakedamage. In areas subject to earthquakes, BlazeMaster firesprinkler systems shall be designed and braced in accordancewith local codes or NFPA 13, Section 6-4 (1999 Edition).

    When it is required to earthquake brace BlazeMaster piping, it isimportant to use fittings, fasteners or clamps that do not havesharp edges or apply excessive compressive forces sufficient todistort the pipe.

    Pressure TestingOnce an installation is completed and cured, per the previousrecommendations, the system should be hydrostatically (water)pressure tested at 1379 kPa (200 psi), Table II, for 2 hours (or at345 kPa (50 psi) in excess of the maximum pressure, Table I,when the maximum pressure to be maintained in the system is inexcess of 1034 kPa (150 psi) in accordance with the requirementsestablished by NFPA Standard 13, Section 10-2.2.1 (1999Edition). Sprinkler systems in one- and two-family dwellings andmobile homes may be tested at line pressure, Table III inaccordance with the requirements established by NFPA 13D,Section 1-5.4 (1999 Edition). When pressure testing, the sprinklersystem shall be slowly filled with water and the air bled from thehighest and farthest sprinkler heads before pressure testing isapplied. Air must be removed from piping systems (plastic ormetal) to prevent it from being locked in the system when pressureis applied. Entrapped air can generate excessive surge pressuresthat are potentially damaging, regardless of the piping materialsused. Air or compressed gas should never be used for pressuretesting. If a leak is found, the fitting must be cut out anddiscarded. A new section can be installed using couplings or aunion. Unions should be used in accessible areas only.

    Handling & Installation Procedures

  • BlazeMaster®

    7 of 9

    Specifications

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    ScopeThis specification sheet covers IPEX Inc. requirements for for 3/4"through 3" (20 mm – 75 mm) BlazeMaster CPVC SDR 13.5 Pipefor wet pipe automatic sprinkler systems, having a rated workingpressure of 175 psi (1205 kPa) at 150°F (66°C) or 315 psi(2172 kPa) at 73°F (22°C) and BlazeMaster CPVC Schedule 80Fittings. The fittings, for wet pipe automatic sprinkler systems,having a rated working pressure of 175 psi (1205 kPa) at 150°F(66°C) or 315 psi (2172 kPa) @ 73°F (22°C). These productsmeet or exceed performance standards set by the AmericanNational Standards Institute (ANSI), the American Society forTesting and Materials (ASTM), Factory Mutual Research (FM),National Fire Protection Agency (NFPA), NSF International (NSF),Underwriters Laboratories Inc., and Underwriters’ Laboratories ofCanada (ULC).

    Underwriters’ Laboratories of Canada lists BlazeMaster CPVCSchedule 80 Fittings and BlazeMaster CPVC SDR 13.5 Pipe foruse in the following applications; Residential occupancies asdefined in the Standard for Sprinkler Systems in One and Two-Family Dwellings, NFPA 13D.

    Multiple residential as defined in NFPA 13R.

    Light-hazard occupancies as defined in the Standard forInstallation of Sprinkler Systems, NFPA 13. BlazeMaster CPVCSchedule 80 Fittings and BlazeMaster CPVC SDR 13.5 Pipe canbe used for both concealed and exposed installations. Refer toIpex literature for any limitations.

    DimensionsIPEX BlazeMaster pipe is produced in SDR 13.5 dimensions tothe specifications of ASTM F442. Fittings are produced to ASTMF437, F438 pr F439 specifications depending on the size andconfiguration.

    MaterialBlazeMaster CPVC SDR 13.5 Pipe are made from Lubrizol Inc.Chlorinated Polyvinyl Chloride (CPVC) raw material having a cellclass of 23447 as defined in ASTM Standard D 1784 “StandardSpecification for Rigid Polyvinyl Chloride (PVC) and ChlorinatedPolyvinyl Chloride (CPVC) Compounds”. The compound is listedwith NSF for potable water service.

    The material has been tested in accordance with CAN/ULCStandard S102.2M88 “Standard Method of Test for SurfaceBurning Characteristics of Flooring, Floor Covering, andMiscellaneous Materials and Assemblies” with the followingresults: Flame Spread 5 / Smoke Development 5-15.

    BlazeMaster Schedule 80 Fittings are made from Lubrizol Inc.Chlorinated Polyvinyl Chloride (CPVC) raw material having a cellclass of 23447 as defined in ASTM Standard D 1784 “StandardSpecification for Rigid Polyvinyl Chloride (PVC) and ChlorinatedPolyvinyl Chloride (CPVC) Compounds”. The compound is listedwith NSF for potable water service.

    MarkingBlazeMaster Schedule 80 Fittings and BlazeMaster CPVC SDR13.5 Pipe are made from Lubrizol Inc. Chlorinated PolyvinylChloride (CPVC) raw material having a cell class of 23447 asdefined in ASTM Standard D 1784 “Standard Specification forRigid Polyvinyl Chloride (PVC) and Chlorinated Polyvinyl Chloride(CPVC) Compounds”. The compound is listed with NSF forpotable water service.

  • BlazeMaster®

    8 of 9

    Notes

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

  • BlazeMaster®

    9 of 9

    Cda Toll Free: 866-473-9462 • www.ipexinc.com U.S. Toll Free: 800-463-9572 • www.ipexamerica.com

    About IPEX

    © 2008 IPEX DA-BLAZEMASTER1

    This literature is published in good faith and is believed to be reliable. However, it does not represent and/or

    warrant in any manner the information and suggestions contained in this brochure. Data presented is the

    result of laboratory tests and field experience.

    A policy of ongoing product improvement is maintained. This may result in modifications of features and/or

    specifications without notice.

    About the IPEX Group of Companies

    As leading suppliers of thermoplastic piping systems, the IPEX Group of Companies provides our

    customers with some of the world’s largest and most comprehensive product lines. All IPEX products are

    backed by more than 50 years of experience. With state-of-the-art manufacturing facilities and

    distribution centers across North America, we have established a reputation for product innovation,

    quality, end-user focus and performance.

    Markets served by IPEX group products are:

    • Electrical systems

    • Telecommunications and utility piping systems

    • PVC, CPVC, PP, ABS, PEX, FR-PVDF and PE pipe and fittings(1/4" to 48")

    • Industrial process piping systems

    • Municipal pressure and gravity piping systems

    • Plumbing and mechanical piping systems

    • PE Electrofusion systems for gas and water

    • Industrial, plumbing and electrical cements

    • Irrigation systems

    Products are manufactured by IPEX Inc. and distributed in the United States by IPEX USA LLC.PlumbBetter® is a trademark of IPEX Branding Inc.

  • PRINTED IN USA PAgE 1 OF 4MFg. #5401205 - REV H01/12

    vsr-sGvane type waterflow

    alarM swItCH wItH retarD anD Glue-In unIon

    for CpvC pIpe

    Do not over-tighten the union nut, hand tighten only. Use of a wrench may damage the union nut.

    Do not trim the paddle. Failure to follow these instructions may prevent the switch from operating and will void the warranty.

    General InformationThe Model VSR-SG is a vane type waterflow switch for use on wet sprinkler systems using CPVC plastic fittings (manufactured by Tyco, Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1”, 1 ¼”, 1 ½”, or 2” pipe sizes. It is equipped with a union to accommodate installation in confined spaces.

    The VSR-SG contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the switch. The flow condition must exist for a period of time necessary to overcome the selected retard period.

    ul, Cul and CsfM listed, Ce Marked

    service pressure: Up to 175 PSI (12,07 BAR)flow sensitivity range for signal: 4-10 GPM (15-38 LPM) - ULMaximum surge: 18 FPS (5.5 m/s)Contact ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive

    10 mAmps min. at 24VDCConduit entrances: Two openings provided for 1/2" conduit.

    Individual switch compartments suitable for dissimilar voltages.

    Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or

    outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting.

    • Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL service use:

    British Standard B59251 Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72

    • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result.• Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.

    Specifications subject to change without notice.stock number: 1144460optional: Cover Tamper Switch Kit, stock no. 0090148replaceable Components: Retard/Switch Assembly, stock no. 1029030

    enclosure The VSR-Sg switches and retard switch are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch.

    Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating switch to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times.

    Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833 • www.pottersignal.com

    Installation (see Fig. 1, 3, and 5)These switches may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The switch should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or

    within 24" (60 cm) of a valve or drain. The unit has a 1" male fitting for gluing into a CPVC plastic tee.

    note: Do not leave cover off for an extended period of time.Loosen the union nut and separate the 1" male fitting from the VSR-SG. Glue the 1" male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. (Note: The 1" male fitting must bottom out on the stop of the TEE for proper operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1" male fitting. Select the proper paddle for the pipe size and type of TEE used. See Fig. 3 for instructions on how to change paddle. verify that the o-ring is properly positioned in its groove. Hand tighten the nut on the union after orienting the switch in the appropriate direction to detect waterflow as shown in Fig. 5 & Fig. 7.The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand.

  • PRINTED IN USA MFg. #5401205 - REV H01/12

    PAgE 2 OF 4

    vsr-sGvane type waterflow

    alarM swItCH wItH retarD anD Glue-In unIon

    for CpvC pIpe

    notes: 1. The Model VSR-SG has two switches, one can be used to operate a

    central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator.

    2. For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 6).

    fig. 4 typical electrical Connections

    Break out thin section of cover when wiring both switches from one conduit entrance.

    testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).A method of testing the VSR-SG must be provided. The valve used for testing shall be easily reached and shall produce a minimum flow of 10 GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system.

    fig. 2

    Important:11 paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES. The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with. The proper paddle must be used. The paddle must be properly attached (see Fig. 3) and the screw that holds the paddle must be securely tightened.

    fig. 1

    Glue the 1" male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1" male fitting.

    fig. 3

    DWG# 1205-4

    Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.

    LOA

    D TO

    BELL

    NEUTRAL FROM BELL

    CONNECTOR

    EOL (End Of Line Resistor)

    BELLNEUTRAL FROM BREAKER

    BREAKER

    LINE FROM BREAKER

    NOTE: When connecting to a UL Listedcontrol panel, use the panel’s resistor value for circuit supervision.

  • PRINTED IN USA PAGE 3 OF 4MFg. #5401205 - REV H01/12

    vsr-sGvane type waterflow

    alarM swItCH wItH retarD anD Glue-In unIon

    for CpvC pIpe

    fig. 6 switch terminal Connections Clamping plate terminalfig. 5

    fig. 7 Mounting Dimensions-orientation

    gREEN gROUND SCREWS

    fig. 8

    retard adjustmentThe delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms.

    OPTIONAL COVER TAMPER SWITCh

    DWG# 1205-1A

    RETARD ADJUSTMENT KNOB

    MOUNT SO ARROW ON BASE POINTS IN DIRECTION OF WATERFLOW

    1" MALE FITTING ON ALL SIZES

    Do not leave cover off for extended period of time

    RUN OF THE TEE MAY BE 1”, 1 ¼”, 1 ½”, or 2”

    Flowing water activates switch in one direction only.

    DWG# 1205-15

    DWG# 1190-1

    5.56 in (141.2 mm)

    PIPE

    PLASTIC PADDLE

    2.00 in (50.8 mm)

    3.91 in(99.33 mm)

    3.50 in (89.0 mm)

    An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life.

    Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate.

    PIPE

    90°

    Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. Improper orientation could delay or prevent notification of waterflow.

  • PRINTED IN USA MFg. #5401205 - REV H01/12

    PAgE 4 OF 4

    vsr-sGvane type waterflow

    alarM swItCH wItH retarD anD Glue-In unIon

    Removal of Waterflow Switch

    • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.

    • Turn off electrical power to the detector, then disconnect wiring.• Loosen nuts and seperate unit from the glued-in fittings• Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift

    the waterflow detector. • Lift detector clear of pipe.

    for CpvC pIpe

    fig. 9

    retard/switch assembly replacement (See Fig. 9)

    The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe

    Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 1. Disconnect the power source for local bell (if applicable).2. Identify and remove all wires from the waterflow switch.3. Remove the (2) mounting screws holding retard/switch assembly to the base. 4. Do not remove the (2) retard housing screws. Remove the retard assembly by lifting it straight up over the tripstem. 5. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 6. Re-install the (2) original mounting screws.7. Reconnect all wires. Perform a flow test and place the system back in service. 8.

    MaintenanceInspect the waterflow switch monthly. If leaks are found, replace the waterflow switch. The VSR-SG waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 9). There is no maintenance required, only periodic testing and inspection.

    DWG# 1190-2

    BREAK OUT ThIN SECTION OF COVER WhEN WIRING BOTh SWITChES FROM ONE CONDUIT ENTRANCE.

    Do not REMOVE (2) RETARD hOUSING SCREWS

    REMOVE (2) ORIGINAL MOUNTING SCREWS hOLDING RETARD/SWITCh ASSEMBLY TO BASE

    RETARD/SWITCh ASSEMBLY

    (2) ORIGINAL MOUNTING SCREWS

    (2) LOCATING PINS

    (2) LOCATING PIN BOSSES IN BASE

    BASE

  • DEC 2016 GFS-360 (Formerly A-10)

    “THE INCH” RESIDENTIAL

    AUTOMATIC SPRINKLERSMODEL GL4906

    ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT

    DESCRIPTION AND OPERATION

    RESIDENTIALFLAT PLATE CONCEALED

    PENDENT

    TECHNICAL DATA• See reverse side for Approvals and Specifi cations.• Temperature Rating - 155°F (68°C)• Water Working Pressure Rating - 175 psi (12 Bars)• Factory tested hydrostatically to 500 psi (34 Bars)• Maximum low temperature glass bulb rating is -67°F (-55°C)• Frame - bronze • Defl ector - brass • Screw - brass • Lodgement Wire - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - tefl on• Bulb - glass with alcohol based solution, 3mm size• Cover Plate - brass • Upper Escutcheon Assembly - steel

    SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODINGCLASSIFICATION BULB COLOR

    ORDINARY 155°F 68°C RED 100°F 38°C

    AVAILABLE SPRINKLER TEMPERATURES

    N.F.P.A. MAXIMUM CEILING TEMPERATURE

    The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a fl at plate profi le that utilizes a 3mm frangible glass ampule as the thermosensitive element. It features economy, aesthetics and the lowest allowable water fl ow with a nominal 1" of adjustment for easier installation. The combination of the 3mm frangible glass ampule and specially designed defl ector make the Model GL4906 the ultimate in life safety and fi re control. It has met the strict requirements of Underwriters Laboratories Inc. as described in UL Standard, 1626, for Residential Sprinklers for Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction. All that is seen at the ceiling is the 3 5/16" diameter fl at ceiling plate color fi nished to match the speci-fi er's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support assembly in three places. Upon the application of suffi cient heat, the plate falls to the fl oor exposing the residential pendent spray sprinkler. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water discharge which is distrib-uted in an approved pattern.

  • DEC 2016 GFS-360 (Formerly A-10)

    NOTE: METRIC CONVERSIONS ARE APPROXIMATE.1FINISHES AVAILABLE ON SPECIAL ORDER.2FOR PAINTED PLATES OTHER THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS.

    SPECIFICATIONS AND APPROVALS

    INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS**

    3 5/16" DIA.

    2 3/4" MAX.1 7/8" MIN.

    1/8"CEILING COVER PLATE

    SUPPORT SHELL

    CUP

    DEFLECTORDROP PIN

    1" x 1/2"REDUCER

    2 3/8" DIA.

    CEILING

    2 3/4" DIA. MIN.HOLE IN CEILING

    CROSS SECTION

    ORDERING INFORMATION

    PRINTED U.S.A.

    4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658FAX 989-846-9231

    www.globesprinkler.com989-846-4583 1-800-248-0278

    GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specifi c details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

    • Quantity • Model Number • Style• Orifi ce • Temperature • Finishes desired• Quantity - Wrenches - P/N 332765• Quantity - Protective Caps - P/N 332868

    1” ADJUSTMENT FLAT PLATE CONCEALED PENDENT

    SPECIFY

    “THE INCH” RESIDENTIALAUTOMATIC SPRINKLERSMODEL GL4906ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT

    FLAT COVER PLATE SIZE

    WHITE 135°F (57°C) PART #

    CHROME 135°F (57°C) PART #

    3 5/16" DIA. 332892 332891

    SIN MODEL STYLE

    SPRINKLER TEMPERATURE

    155°F (68°C)

    MAX. AREA OF COVERAGE3Feet (Meters)

    *MIN. PRESSURE P.S.I. (bars)

    *MIN. FLOW

    G.P.M. (L/min.)

    MIN. DISTANCE BETWEEN

    SPRINKLERS Feet (Meters)

    X 12 (3.7) x 12 (3.7) 7.0 (.48) 13 (49)

    X 14 (4.3) x 14 (4.3) 7.0 (.48) 13 (49)

    X 16 (4.9) x 16 (4.9) 7.0 (.48) 13 (49)

    X 18 (5.5) x 18 (5.5) 12.0 (.83) 17 (64)

    X 20 (6.1) x 20 (6.1) 16.7 (1.15) 20 (76)

    "THE INCH" ONE INCH ADJUSTABLE

    CONCEALED PENDENTGL4906 9 (2.7)

    NOTE: METRIC CONVERSIONS ARE APPROXIMATE. WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED. REFER TO PAGE 2 OF GLOBE’S RESIDENTIAL SPRINKLER INSTALLATION GUIDE (BULLETIN R.S.I.G.) FOR NFPA 13D AND 13R REQUIREMENTS. FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM REQUIRED FLOW FOR THE NEXT HIGHEST COVERAGE AREA FOR WHICH HYDRAULIC DESIGN CRITERIA ARE STATED.

    ***

    3

    SINMODEL

    NOMINAL“K” FACTOR

    THREADSIZE LENGTH

    FLAT COVERPLATE FINISHES

    cULusCE

    GL4906 4.9 (68 metric) 1/2”NPT(15mm)3”

    (7.6cm)

    ChromeWhite Painted

    Other Painted Finishes1,2X

  • SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient tem-perature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire.

    COVERAGE: Residential spray coverage up to 320 sq. ft./29.9sq. m room sizes per NFPA.

    TECHNICAL SPECIFICATIONS: Models: V2738Style: Residential HorizontalSidewall and Recessed HorizontalSidewallNominal Orifice Size: 7/16"/12 mmK-Factor: 4.2 Imp./6.1 S.I.^Nominal Thread Size: 1/2" NPT/15 mmMax. Working Pressure: 175 psi/1200 kPaFactory Hydrostatic Test:

    100% @ 500 psi/3450 kPaMin. Operating Pressure: 7psi/48 kPaTemperature Rating: See chart on page 2

    Material SpecificationsDeflector: Bronze per UNS C51000Bulb: Glass with glycerin solution.Bulb Nominal Diameter:

    • QuickResponse:3.0mmLoad Screw: Bronze per UNS C65100Pip Cap: Bronze per UNS C65100 Spring: Beryllium nickelSeal: Teflon* tapeFrame: Die cast brass 65-30Lodgement Spring: Stainless steel per UNS S30200

    AccessoriesInstallation Wrench:

    • OpenEnd:V27• Recessed: V27-2

    Sprinkler Finishes:• Plainbrass• Chromeplated• Whitepainted**• Custompainted**

    For escutcheons, cabinets and other accessories refer to separate sheet.

    NOTE:Weatherresistantrecessedescutcheonsavailable upon request.

    ^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0.

    * Teflon is a registered trademark of Dupont Co.** UL Listed for corrosion resistance.

    These Model V2738 residential sprinklers are designed to meet the requirements of the 2002 or later NFPA 13, 13D and 13R for residential use. The Model V2738 is UL Listed for use under smooth flat horizontal ceilings. The design incorporates stateof- the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation.

    The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various finishes to meet many design requirements.

    40.54_1

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    HORIZONTAL SIDEWALL (V2738)

    RECESSED HORIZONTAL SIDEWALL

    (V2738)

    JOB/OWNER CONTRACTOR ENGINEER

    System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________

    Location ________________________________ Date ___________________________________ Approved _______________________________

    Date ___________________________________

    www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

    SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS

  • APPROVALS/LISTINGSModel

    Orifice Size

    Nominal K-Factor Response Deflector Type

    Approved Temperature Ratings ˚F/˚C ‡

    Inches mm

    Imperial S.I.^

    Standard or Quick cULus NYC/MEA‡ CSFM

    V2738 7/16 4.2 Quick Horizontal Sidewall 155, 175 68, 79155, 175 68, 79

    155, 175 68, 7911 6.1

    V2738 7/16 4.2 Quick Recessed Horizontal Sidewall Up to 3/4" Adjustment155, 17568, 79

    155, 17568, 79

    155, 17568, 7911 6.1

    ‡ Listings and approval as of printing.^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. † MEA #62-99-E.

    RATINGS All glass bulbs are rated for temperatures from –67°F/–55°C to those shown in table below.

    Sprinkler Temperature Classification

    Victaulic Part

    Identification

    Temperature – ºF/ºC

    Nominal Temperature Rating

    Maximum Ambient Temperature Allowed Glass Bulb Color

    Ordinary C 155 100 Red68 38

    Intermediate E 175 150 Yellow79 66

    ORDERING INFORMATION Pleasespecifythefollowingwhenordering:

    Sprinkler Model Number

    Style

    Temperature Rating

    K-Factor

    Thread Size

    Quantity

    Sprinkler Finish

    Escutcheon Finish

    Wrench Model Number

    40.54_2

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • WARNING WARNING

    • Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation of any sprinklers.

    • Always wear safety glasses and foot protection.

    • Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.

    • Installation rules, especially those governing obstruction, must be strictly followed.

    • Painting, plating, or any re-coating of sprinklers (other than that sup-plied by Victaulic) is not allowed.

    Failure to follow these instructions could result in serious personal injury and/or property damage.

    The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have addi-tional maintenance, testing, and inspection requirements that must be followed.

    If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone: 001-610-559-3300.

    AVAILABLE WRENCHESSprinkler Type Open End Recessed

    V2738 – No escutcheon V27 V27-2

    V2738 – With escutcheon — V27-2

    40.54_3

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • DIMENSIONS

    Residential HSW - V2738

    Figure 13/4" Adjustment

    Recessed - V2738

    1 5/8"(41mm)

    2" (51mm)

    2 3/4" (70mm)

    MAXIMUM EXTENSION MAXIMUM RECESS

    Typical Wall

    Finished Surface

    9/16" (14mm)

    Finished Ceiling

    2" (51mm)Min. Hole

    2 3/8" (60mm)Max. Hole

    Typical Wall

    Finished Surface

    2 15/16"(75mm)

    Finished Ceiling4" - 12"(102 - 305mm) 4" - 12 "(102 - 305mm)

    1 7/16(37mm)

    1 5/16"(33mm)

    Submittal 40.54

    7/16"(11mm)

    2 3/16"(56mm)

    Residential HSW - V2738

    Figure 13/4" Adjustment

    Recessed - V2738

    1 5/8"(41mm)

    2" (51mm)

    2 3/4" (70mm)

    MAXIMUM EXTENSION MAXIMUM RECESS

    Typical Wall

    Finished Surface

    9/16" (14mm)

    Finished Ceiling

    2" (51mm)Min. Hole

    2 3/8" (60mm)Max. Hole

    Typical Wall

    Finished Surface

    2 15/16"(75mm)

    Finished Ceiling4" - 12"(102 - 305mm) 4" - 12 "(102 - 305mm)

    1 7/16(37mm)

    1 5/16"(33mm)

    Submittal 40.54

    7/16"(11mm)

    2 3/16"(56mm)

    Figure 1 – ¾" Adjustment Recessed – V2738 (drawing not to scale)

    40.54_4

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • ROOM SIZE Victaulic V2738, 4.2 K-Factor Horizontal Sidewall Sprinkler ForCeilingtypesrefertoNFPA13,13Ror13D2013Editions

    Max. CoverageArea(a)

    Width X Length(c)

    Max. Spacing

    Ordinary TempRating

    155°F/68°C

    Intermediate TempRating

    175°F/79°C

    Top of Deflector to

    CeilingInstallation

    TypeMinimum Spacing

    Ft. x Ft.m x m

    Ft. m

    Flow(b) GPML/min

    Pressure(b)PSIbar

    Flow(b) GPML/min

    Pressure(b)PSIbar

    Ft.m

    12 X 12 12 14 11.1 14 11.1

    4 to 6 inches

    ¾" recessed using

    Escutcheon or non-recessed per

    NFPA 13, 13R or 13D

    8.02.4

    3.7 X 3.7 3.7 53.0 0.76 53.0 0.76

    14 X 14 14 14 11.1 14 11.14.3 X 4.3 4.3 53.0 0.76 53.0 0.76

    16 X 16 16 17 16.4 17 16.44.9 X 4.9 4.9 64.4 1.13 64.4 1.13

    16 X 18 16 19 20.5 19 20.54.9 X 5.5 4.9 72.0 1.4 72.0 1.4

    16 X 20 16 23 30.0 23 30.04.9 X 6.1 4.9 87.1 2.1 87.1 2.1

    12 X 12 12 15 12.8 15 12.8

    6 to 12 inches

    3.7 X 3.7 3.7 56.8 0.88 56.8 0.88

    14 X 14 14 17 16.4 17 16.44.3 X 4.3 4.3 64.4 1.13 64.4 1.13

    16 X 16 16 19 20.5 19 20.54.9 X 4.9 4.9 72.0 1.4 72.0 1.4

    16 X 18 16 24 32.6 24 32.64.9 X 5.5 4.9 90.8 2.25 90.8 2.25

    16 X 20 16 28 44.4 28 44.44.9 X 6.1 4.9 106.0 3.06 106.0 3.06

    (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) For NFPA 13 residential applications, the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used. (c) The Width X Length dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of sprinkler)

    40.54_5

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • 0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m

    4'1,2 m

    6'1,8 m

    4'1,2 m

    2'0,6 m

    0'

    CL OF ROOM2'0,6 m

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    15 GPM (56,8 LPM)12" FROM CEILING

    NOMINAL WETTING PATTERN12' x 12' COVERAGE AREA

    8'2,4 m

    4'1,2 m

    6'1,8 m

    4'1,2 m

    2'0,6 m

    0'

    2'0,6 m

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    14 GPM (53,0 LPM)4" FROM CEILING

    CL OF ROOM0'

    6'1,8 m

    5'1,5 m

    7'2,1 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m

    NOMINAL WETTING PATTERN12' x 12' COVERAGE AREA

    NOMINAL WETTING PATTERNS

    Model V2738 K4.2 Residential Horizontal Sidewall

    14 GPM/53.0LPM – 12' x 12'/3.7 x 3.7 m coverage area – 4"/101.6 mm from ceiling

    Model V2738 K4.2 Residential Horizontal Sidewall

    15 GPM/56.8 LPM – 12' x 12'/3.7 x 3.7 m coverage area – 12"/304.8 mm from ceiling

    See notes on page 11.

    40.54_6

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • NOMINAL WETTING PATTERNS

    Model V2738 K4.2 Residential Horizontal Sidewall

    14 GPM/53.0LPM – 14' x 14'/4.3 x 4.3m coverage area – 4"/101.6 mm from ceiling

    Model V2738 K4.2 Residential Horizontal Sidewall

    17 GPM/64.3LPM – 14' x 14'/4.3 x 4.3 m coverage area – 12"/304.8 mm from ceiling

    See notes on page 11.

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m

    4'1,2m

    7'2,1m

    6'6'

    1,8m

    4'1,2m

    2'0,6m

    0'

    CL OF ROOM2'0,6m

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    17 GPM (64,3 LPM)12" FROM CEILING

    NOMINAL WETTING PATTERN14' x 14' COVERAGE AREA

    0'

    8'2,4 m

    6'1,8 m

    5'1,5 m

    7'2,1 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m 4'1,2m

    7'2,1m

    6'6'

    1,8m

    4'1,2m

    2'0,6m

    0'

    2'0,6m

    CL OF ROOM

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    14 GPM (53,0 LPM)4" FROM CEILING

    NOMINAL WETTING PATTERN14' x 14' COVERAGE AREA

    40.54_7

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • NOMINAL WETTING PATTERNS

    Model V2738 K4.2 Residential Horizontal Sidewall

    17 GPM/64.3LPM – 16' x 16'/4.9 x 4.9m coverage area – 4"/101.6 mm from ceiling

    Model V2738 K4.2 Residential Horizontal Sidewall

    19 GPM/71.9LPM – 16' x 16'/4.9 x 4.9 m coverage area – 12"/304.8 mm from ceiling

    See notes on page 11.

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m

    4'1,2 m

    8'2,4m

    6'6'

    1,8 m

    4' 2' 0'

    2'0,6 m

    CL OF ROOM

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    19 GPM (71,9 LPM)12" FROM CEILING

    NOMINAL WETTING PATTERN16' x 16' COVERAGE AREA

    0'

    8'2,4 m

    6'1,8 m

    5'1,5 m

    7'2,1 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m 4'

    1,2 m

    8'2,4m

    6'

    6'1,8 m

    4' 2' 0'

    2'0,6 m

    CL OF ROOM

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    17 GPM (64,3 LPM)4" FROM CEILING

    NOMINAL WETTING PATTERN16' x 16' COVERAGE AREA

    40.54_8

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • NOMINAL WETTING PATTERNS

    Model V2738 K4.2 Residential Horizontal Sidewall

    19 GPM/71.9 LPM – 16' x 18'/4.9 x 5.5m coverage area – 4"/101.6 mm from ceiling

    Model V2738 K4.2 Residential Horizontal Sidewall

    24 GPM/90.8LPM – 16' x 18'/4.9 x 5.5 m coverage area – 12"/304.8 mm from ceiling

    See notes on page 11.

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    24 GPM (90,8 LPM)12" FROM CEILING

    NOMINAL WETTING PATTERN16' x 18' COVERAGE AREA

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m 4'

    1,2 m

    8'2,4m

    6'1,8 m

    2'0,6 m

    CL OF ROOM

    6' 8' 9'2,7m

    4'2'0'

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    19 GPM (71,9 LPM)4" FROM CEILING

    NOMINAL WETTING PATTERN16' x 18' COVERAGE AREA

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m 4'1,2 m

    8'2,4m6'

    1,8 m

    2'0,6 m

    CL OF ROOM

    6' 8' 9'2,7m

    4'2'0'

    40.54_9

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • NOTES:

    1 Data shown is approximate and can vary due to differences in installation.

    2 These graphs illustrate approximate wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as information for guidance and should not be used as minimum sprinkler spacing rules for installation. Sprinkler location shall be in accordance with the obstruction rules for residential sprinklers in NFPA 13 (2002 or later revision). Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties.

    3 All patterns are symmetrical to waterway.

    NOMINAL WETTING PATTERNS

    Model V2738 K4.2 Residential Horizontal Sidewall

    23 GPM/87.0 LPM – 16' x 20'/4.9 x 6.1m coverage area – 4"/101.6 mm from ceiling

    Model V2738 K4.2 Residential Horizontal Sidewall

    28 GPM/106.0LPM – 16' x 20'/4.9 x 6.1 m coverage area – 12"/304.8 mm from ceiling

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m

    CL OF ROOM

    6' 8' 10'3,0m

    4'2'0'

    4'1,2 m

    8'2,4m6'

    1,8 m

    2'0,6 m

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    28 GPM (106,0 LPM)12" FROM CEILING

    NOMINAL WETTING PATTERN16' x 20' COVERAGE AREA

    MODEL V2738K4.2 RESIDENTIAL HORIZONTAL SIDEWALL

    23 GPM (87,0 LPM)4" FROM CEILING

    NOMINAL WETTING PATTERN16' x 20' COVERAGE AREA

    0'

    7'2,1 m

    8'2,4 m

    6'1,8 m

    5'1,5 m

    4'1,2 m

    3'0,9 m

    2'0,6 m

    1'0,3 m 4'

    1,2 m

    8'2,4m6'

    1,8 m

    2'0,6 m

    CL OF ROOM

    6' 8' 10'3,0m

    4'2'0'

    40.54_10

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

    REV_D

  • WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

    This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.

    NOTE

    40.54

    V27, K4.2Residential Horizontal Sidewall, Recessed Horizontal Sidewall

    V2738 QUICK RESPONSE

    40.54FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

    For complete contact information, visit www.victaulic.com40.54 3089 REV D UPDATED 03/2013VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.