Automatic Transfer Switch Owner’s Manual ATS Service Entrance HS Type Transfer Switch Models: 005036-0, 100 Amp, 250 Volts and 004945-1, 200 Amp, 250 Volts This manual should remain with the unit.

Upload: talha-asad

Post on 16-Oct-2014

32 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 0E9905

Automatic Transfer SwitchOwner’s Manual

ATS Service EntranceHS Type Transfer Switch

Models: 005036-0, 100 Amp, 250 Volts and 004945-1, 200 Amp, 250 Volts

This manual should remain with the unit.

Page 2: 0E9905

Generac Power Systems, Inc., hereafter referred to as the “manufacturer”, cannot anticipate every possible circumstance that might involve a hazard. The warn-ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique cho-sen does not render the transfer switch unsafe.

Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person-nel to special instructions about a particular opera-tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini-tions are as follows:

DANGER

After this heading, read instructions that, if not strictly complied with, will result in personal inju-ry, including without limitation, death, or property damage.

After this heading, read instructions that, if not strictly complied with, may result in personal inju-ry or property damage.

After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.

NOTE:

After this heading, read explanatory statements that require special emphasis.

These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli-ance with the special instructions while performing the service are essential to preventing accidents.

Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:

This symbol points out important safety infor-mation that, if not followed, could endanger personal safety and/or property.

This symbol points out potential explosion haz-ard.

This symbol points out potential fire hazard.

This symbol points out potential electrical shock hazard.

GENERAL HAZARDS • Any AC generator that is used for backup power if

a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy.

• Improper or unauthorized installation, operation, service or repair of the equipment is extremely dangerous and may result in death, serious per-sonal injury, or damage to equipment and/or per-sonal property.

• Extremely high and dangerous power voltages are present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and pos-sibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF.

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.

SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this equipment. Also read the instructions and information on tags, decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible.

DANGER! Connection of a generator to an electrical system normally supplied by an electric utility shall be by means of suitable transfer equipment so as to isolate the electric system from utility distribution system when the generator is operating (Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy.

Page 3: 0E9905

Table of Contents

1

Safety Rules .........................................Inside Front CoverSection 1 — General Information ...................................21.1 Introduction............................................................. 21.2 Equipment Description ........................................... 2 1.2.1 Transfer Switch Mechanism .......................... 2 1.2.2 Service Disconnect Circuit Breaker ............... 21.3 Transfer Switch Data Decal ..................................... 21.4 Transfer Switch Enclosure ...................................... 31.5 Safe Use Of Transfer Switch .................................... 3

Section 2 — Installation ....................................................32.1 Introduction to Installation ...................................... 32.2 Unpacking ............................................................... 32.3 Mounting ................................................................. 32.4 Connecting Power Source and Load Lines ............... 32.5 Connecting Start Circuit Wires ................................ 4

Section 3 — Operation .......................................................43.1 Functional Tests & Adjustments .............................. 43.2 Manual Operation .................................................... 4 3.2.1 Close to Normal Source Side ........................ 5 3.2.2 Close to Emergency Source Side ................... 5 3.2.3 Return to Normal Source Side ...................... 53.3 Voltage Checks ......................................................... 63.4 Generator Tests Under Load ................................... 6

Section 4 – Installation Diagram ....................................7Section 5 – Electrical Data ...............................................8Section 6 – Exploded Views & Parts Lists ..................12Section 7 – Notes .............................................................16Section 8 – Warranty ...................................... Back Cover

• Competent, qualified personnel should install, operate and service this equipment. Adhere strictly to local, state and national electrical and building codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established.

• Never handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.

• Jewelry conducts electricity and wearing it may cause dangerous electrical shock. Remove all jew-elry (such as rings, watches, bracelets, etc.) before working on this equipment.

• If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats.

• Never work on this equipment while physically or mentally fatigued.

• Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior.

• In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconduct-ing implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.

• When an automatic transfer switch is installed for a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the system’s automatic start cir-cuit must be disabled before working on or around the generator or transfer switch. For that purpose, a SAFETY DISCONNECT is provided inside the transfer switch. Always set that switch to its OFF position before working on the equipment. Then place a “DO NOT OPERATE” tag on the transfer switch and on the generator. Remove the Negative (Neg) or (–) battery cable.

For authorized service,reference the dealer locator

number found in the generatorowner’s manual.

Page 4: 0E9905

2

Section 1 — General InformationATS “HS” Type Transfer Switch

1.1 INTRODUCTIONThis manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect appli-cation, or improper procedures.

Every effort has been expended to make sure that the contents of this manual are both accurate and cur-rent. The manufacturer, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.

1.2 EQUIPMENT DESCRIPTIONThe automatic transfer switch is used for transfer-ring electrical load from a UTILITY (NORMAL) power source to an EMERGENCY (STANDBY) power source. Such a transfer of electrical loads occurs automati-cally when the UTILITY power source has failed or is substantially reduced and the EMERGENCY source voltage and frequency have reached an acceptable level. The transfer switch prevents electrical feedback between two different power sources (such as the UTILITY and EMERGENCY sources) and, for that reason, codes require it in all standby electric system installations.

The transfer switch consists of a transfer mecha-nism, service disconnect circuit breaker, a relay control, fuses, and a terminal strip for connection of sensing wires.

This transfer switch is suitable for use as service entrance equipment.

1.2.1 TRANSFER SWITCH MECHANISMThese switches (Figure 1.1) are used with a single-phase system, when the single-phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched.

Solderless, screw-type terminal lugs are standard.

Switch Wire Conductor Tightening Rating Range Torque 100A #14-1/0 AWG 50 in-lbs. 200A #6-250 MCM 275 in-lbs.

This transfer switch is suitable for control of motors, electric discharge lamps, tungsten filament and elec-tric heating equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.

Figure 1.1 — Typical ATS Transfer Mechanism

UTILITYCLOSINGCOIL

GENERATORCLOSINGCOIL

UTILITY LUGS

GENERATORLUGS (E1 & E2)

LOAD LUGS (T1 & T2)

This transfer switch is for use in optional standby systems only.

This transfer switch is suitable for use on a circuit capable of 10,000 rms symmetrical amperes, 240 VAC maximum.

1.2.2 SERVICE DISCONNECT CIRCUITBREAKER

The service disconnect circuit breaker for the 100 amp models are:

• Siemens, Type BQ, 2-pole• 120/240VAC, 100A• 50/60 Hertz• Heating, Air Conditioning and Refrigeration (HACR)

rated• Wire range: #1 - #8 AWG.• The conductor tightening torque is 50 in-lbs.

The service disconnect circuit breaker for the 200 amp models are:

• Siemens, Type QN, 2-pole• 120/240VAC, 200A• 50/60 Hertz• Heating, Air Conditioning and Refrigeration (HACR)

rated• Wire range: 300 KCMIL - 4 AWG• The conductor tightening torque is 250 in-lbs.

1.3 TRANSFER SWITCH DATA DECALA DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.

Page 5: 0E9905

3

When requesting information or ordering parts for this equipment, make sure to include all information from the DATA DECAL.

Record the Model and Serial numbers in the space provided below for future reference.

1.4 TRANSFER SWITCH ENCLOSUREThe standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) 3R type. NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet and is undamaged by the formation of ice on the enclosure.

1.5 SAFE USE OF TRANSFER SWITCHBefore installing, operating or servicing this equip-ment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. The manufacturer recommends that a copy of the SAFETY RULES are posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equip-ment.

Two publications that outline the safe use of transfer switches are the following:

• NFPA 70; National Electrical Code• UL 1008, STANDARD FOR SAFETY-AUTOMATIC

TRANSFER SWITCHES

2.1 INTRODUCTION TO INSTALLATIONThis equipment has been wired and tested at the factory. Installing the switch includes the following procedures:

• Mounting the enclosure.• Connecting power source and load leads.• Connecting the generator sensing and transfer

relay circuits.• Connecting any auxiliary contact (if needed)• Testing functions.

2.2 UNPACKINGCarefully unpack the transfer switch. Inspect closely for any damage that might have occurred during ship-ment. The purchaser must file with the carrier any claims for loss or damage incurred while in transit.

Check that all packing material is completely removed from the switch prior to installation.

2.3 MOUNTINGMounting dimensions for the transfer switch enclo-sure are in this manual. Enclosures are typically wall-mounted. See “Installation Diagram”, Section 5.

Handle transfer switches carefully when install-ing. Do not drop the switch. Protect the switch against impact at all times, and against construc-tion grit and metal chips. Never install a transfer switch that has been damaged.

This transfer switch is mounted in a NEMA 3R enclo-sure. It can be mounted outside or inside and should be based on the layout of installation, convenience and proximity to the utility supply and load center.

Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.

2.4 CONNECTING POWER SOURCE AND LOAD LINES

DANGER

Make sure to turn OFF both the UTILITY (NORMAL) and EMERGENCY ( STANDBY) power supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high voltage power sup-ply lines causes extremely hazardous, possibly lethal, electrical shock.

Wiring diagrams and electrical schematics are pro-vided in this manual.

Two suggested installation methods are shown. One for new installations and/or retrofit and one for ret-rofit.

NOTE:

All installations must comply with national, state and local codes. It is the responsibility of the installer to perform an installation that will pass the final electrical inspection.

The utility supply connection is made at the circuit breaker terminals. The generator supply and custom-er load connections are made at the transfer switch mechanism, inside the switch enclosure.

Section 2 — InstallationGTS “HS” Type Transfer Switch

MODEL #

SERIAL #

Page 6: 0E9905

4

Section 3 — OperationATS “HS” Type Transfer Switch

Conductor sizes must be adequate to handle the maximum current to which they will be subjected to, based on the 75°C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations.

Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables must enter the enclosure through the knockouts. If not using the knockouts, entry must be at or below knockouts. If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs to the torque values as noted in Section 1.2.2, and on the decal located on the inside of the door. After tightening ter-minal lugs, carefully wipe away any excess corrosion inhibitor.

Use a torque wrench to tighten the conduc-tors, being sure not to overtighten, or damage to the switch base could occur. If not tightened enough, a loose connection would result, caus-ing excess heat which could damage the switch base.

Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol-lows

1. Connect UTILITY (NORMAL) power source cables to circuit breaker.

2. Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2.

3. Connect customer LOAD leads to switch termi-nals T1, T2.

Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.

Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.

2.5 CONNECTING START CIRCUITWIRES

Control system interconnections consist of N1 and N2, T1 and T2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:

MAXIMUM WIRE LENGTH RECOMMENDED WIRE SIZE 460 feet (140m) No. 18 AWG. 461 to 730 feet (223m) No. 16 AWG. 731 to 1,160 feet (354m) No. 14 AWG. 1,160 to 1,850 feet (565m) No. 12 AWG.

NOTE:

When this ATS is used with an air-cooled genera-tor, the LOAD 1 and LOAD 2 wires are not used.

3.1 FUNCTIONAL TESTS ANDADJUSTMENTS

Following transfer switch installation and inter-connection, inspect the entire installation care-fully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regula-tions. When absolutely certain the installation is proper and correct, complete a functional test of the system.

Perform functional tests in the exact order pre-sented in this manual, or damage could be done to the switch.

IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and information in this section are understood. Also read the infor-mation and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.

3.2 MANUAL OPERATIONDANGER

Do NOT manually transfer under load. Disconnect transfer switch from all power sourc-es by approved means, such as the main circuit breaker(s).

A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows:

1. Turn the generator’s AUTO/OFF/MANUAL switch to OFF.

2. Turn OFF both UTILITY (service disconnect cir-cuit breaker) and EMERGENCY (generator main line to circuit breaker) power supplies to the transfer switch.

3. Turn the GENERATOR DISCONNECT SWITCH to the OFF position.

4. Note position of transfer mechanism main con-tacts by observing the moveable contact carrier arm. This can be viewed through the long narrow slot in the inside cover of the ATS. The top of the moveable contact carrier arm is yellow to be eas-ily identified.

• Manual operation handle in the UP position - LOAD terminals (T1, T2) are connected to UTIL-ITY terminals (N1, N2).

Page 7: 0E9905

5

• Manual operation handle in the DOWN posi-tion - LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).

Do not use excessive force when operating the transfer switch manually or damage could be done to the manual handle.

3.2.1 CLOSE TO NORMAL SOURCE SIDEBefore proceeding, verify the position of the switch by observing the position of manual operation handle in Figure 3.1. If the handle is UP, the contacts are closed in the NORMAL (UTILITY) position, no further action is required. If the handle is DOWN, proceed with Step 1.

Step 1: With the handle inserted into the moveable contact carrier arm, move handle UP. Be sure to hold on to the handle as it will move quickly after the center of travel.

Step 2: Remove manual operating handle from move-able contact carrier arm. Return handle to storage bracket.

3.2.2 CLOSE TO EMERGENCY SOURCE SIDEBefore proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 3.1. If the handle is DOWN, the contacts are closed in the EMERGENCY (STANDBY) position. No further action is required. If the handle is UP, proceed with Step 1.

Step 1: With the handle inserted into the moveable contact carrier arm, move the handle DOWN. Be sure to hold on to the handle as it will move quickly after the center of travel.

Step 2: Remove manual operating handle from move-able contact carrier arm. Return handle to storage bracket.

3.2.3 RETURN TO NORMAL SOURCE SIDEStep 1: Manually actuate switch to return manual

operating handle to the UP position.

Step 2: Remove manual operating handle from move-able contact carrier arm. Return handle to storage bracket.

Section 3 — OperationATS “HS” Type Transfer Switch

Attach handle tothe moveable contactcarrier arm.

Move handle UP for theNORMAL (UTILITY) position.

Move handle DOWN for theSTANDBY (EMERGENCY)

position.

NOTE: Return handle tostorage position in enclosurewhen finished with manual transfer.

Figure 3.1 — Actuating Transfer Switch

Page 8: 0E9905

6

3.3 VOLTAGE CHECKS1. Turn ON the UTILITY power supply to the trans-

fer switch using the service disconnect circuit breaker.

DANGER

PROCEED WITH CAUTION. THE TRANSFER SWITCH IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRICAL SHOCK.

2. With an accurate AC voltmeter, check for correct voltage. Measure across ATS terminal lugs N1 and N2. Also check N1 to NEUTRAL and N2 to NEUTRAL.

3. When certain that UTILITY supply voltage is cor-rect and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch.

4. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The gen-erator should crank and start.

5. Let the generator stabilize and warm up at no-load for at least five minutes.

6. Turn the GENERATOR DISCONNECT SWITCH to the ON position.

7. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.

DANGER

PROCEED WITH CAUTION. GENERATOR OUTPUT VOLTAGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK.

8. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency.

Measure across ATS terminal lugs E1 to E2. Also check E1 to NEUTRAL and E2 to NEUTRAL.

a. Frequency .......................................60-62 Hertz b. Terminals E1 to E2 ........................240-246 VAC c. Terminals E1 to NEUTRAL .............120-123 VAC d. Terminals E2 to NEUTRAL .............120-123 VAC

9. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position.

10. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator.

NOTE:

Do NOT proceed until generator AC output volt-age and frequency are correct and within stated limits. If the no-load voltage is correct but no-load frequency is incorrect, the engine governed speed may require adjustment. If no-load frequency is correct but voltage is not, the voltage regulator may require adjustment.

3.4 GENERATOR TESTS UNDER LOAD1. Set the generator's main circuit breaker to its

OFF or OPEN position.2. Manually actuate the transfer switch main con-

tacts to their EMERGENCY (STANDBY) position. Refer to Manual Operation (Section 3.2).

3. To start the generator, set the AUTO/OFF/ MANUAL switch to MANUAL. When engine starts, let it sta-bilize for a few minutes.

4. Turn the generator's main circuit breaker to its ON or CLOSED position. The generator now pow-ers all LOAD circuits. Check generator operation under load as follows:

• Turn ON electrical loads to the full rated watt-age/amperage capacity of the generator. DO NOT OVERLOAD.

• With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2. Voltage should be greater than 230VAC and frequency should be greater than 59 Hertz.

• Let the generator run under rated load for at least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem.

5. When checkout under load is complete, set main circuit breaker of the generator to its OFF or OPEN position.

6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/OFF/MANUAL switch to its OFF position.

7. Move the switch's main contacts back to their UTILITY position. For example, LOAD connect-ed to UTILITY power supply. Refer to Manual Operation (Section 3.2). Handle and operating lever of transfer switch should be in UP posi-tion.

8. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

9. Set the generator's AUTO/OFF/MANUAL switch to its AUTO position.

10. Set the GENERATOR DISCONNECT SWITCH to the ON position. The system is now set for fully automatic operation.

Section 3 — OperationATS “HS” Type Transfer Switch

Page 9: 0E9905

7

324mm[12.76"]

271mm[10.67"]

597mm[23.50"]

KNOCKOUT SUITABLE FOR1", 1-1/4", 1-1/2" CONDUIT SIZE3 PLACES

179.5mm[7.07"]

0A

0A6599tv

561mm[22.09"

34mm[1.34"]

KNOCKOUT SUITABLEFOR 1", 1-1/4", 1-1/2" CONDUIT SIZE

KNOCKOUT SUITABLEFOR 3/4" & 1" CONDUIT SIZE

MOUNTING HOLESØ6.3mm[Ø0.25"]

PADLOCK(CUSTOMER SUPPLIED)LOCATION

0A6599tv

26.5mm[1.04"]

Section 4 — Installation DiagramATS “HS” Type Transfer Switch

Drawing No. 0F0016-B

Page 10: 0E9905

8

Section 5 — Electrical DataATS “HS” Type Transfer Switch

Transfer Switch Interconnections - Drawing No. 0F0017-A

AC G

ENER

ATO

RC

ON

TRO

L PA

NEL

PAN

ELBO

ARD

AND

SO

ME

LIQ

UID

CO

OLE

D U

NIT

SU

SED

ON

AIR

CO

OLE

D U

NIT

S*-

WIR

ES T

1 &

T2 N

OT

E1E2

N2

194

N1

DIS

CO

NN

ECT

CO

NN

ECTI

ON

IN P

ANEL

BOAR

D

OR

RET

RO

FIT

NEW

INST

ALLA

TIO

N

NEU

TRAL

BAR

GR

OU

ND

BAR

BON

DIN

G

SOC

KET

MET

ERU

TILI

TY

ALTE

RN

ATO

RFR

OM

4411ST

ATO

R

3322

GR

OU

ND

BARE1

T2

LOC

AL E

LEC

TRIC

AL C

OD

ES.

MEE

T AL

L N

ATIO

NAL

, STA

TE A

ND

LIC

ENSE

D E

LEC

TRIC

IAN

AN

D M

UST

NO

TE: I

NST

ALLA

TIO

N T

O B

E D

ON

E BY

A

SER

VIC

E D

ISC

ON

NEC

T

IF A

TS IS

USE

D A

S SE

RVI

CE

ENTR

ANC

ED

EVIC

E A

BON

DIN

G J

UM

PER

WIL

L N

EED

TO B

E IN

STAL

LED

SIZ

ED T

O M

EET

NAT

ION

AL &

LO

CAL

CO

DES

.

ATS

Page 11: 0E9905

9

CONTROL PANELAC GENERATOR

GROUND BAR

NEUTRAL BAR

IN PANELBOARD

DISCONNECT

CONNECTIONBONDING

PANELBOARD

*-WIRES T1 & T2 NOT

19423

N1

T1 *T2 *

N2

USED ON AIR COOLED UNITS

RETROFIT

E1

IF ATS IS USED AS SERVICE ENTRANCEDEVICE A BONDING JUMPER WILL NEEDTO BE INSTALLED SIZED TO MEETNATIONAL & LOCAL CODES.

EXISTING WIRES TOPANELBOARD

(SEE ABOVE NOTE)

E1

INSULATED SPLICINGCONNECTOR OR(NEW WIRES CAN BE PULLED FROM ATS & PANELBOARD).

UTILITYMETER

SOCKET

LICENSED ELECTRICIAN AND MUST

STATOR

E2

11

44

ALTERNATORFROM

33

22

NOTE: INSTALLATION TO BE DONE BY A

LOCAL ELECTRICAL CODES.MEET ALL NATIONAL, STATE AND

T2

E2

SERVICE DISCONNECTATS

AND SOME LIQUID COOLED UNITS

Section 5 — Electrical DataATS “HS” Type Transfer Switch

Transfer Switch Interconnections - Drawing No. 0F0017-A

Page 12: 0E9905

10

Section 5 — Electrical DataATS “HS” Type Transfer Switch

Wiring Diagram/Schematic - Drawing No. 0F0015-A

Page 13: 0E9905

11

Section 5 — Electrical DataATS “HS” Type Transfer Switch

Wiring Diagram/Schematic - Drawing No. 0F0015-A

Page 14: 0E9905

12

VIEW

SH

OW

N W

ITH

ITEM

S #1

8 &

#19

REM

OVE

D

STAN

D-B

Y SY

STEM

SFO

R U

SE IN

OPT

ION

ALAU

TOM

ATIC

TR

ANSF

ER S

WIT

CH

SYSTEM VOLTAGE

22473-

S1-4

X20S

TL22

473-S

1-4X2

0STL

1/4 ST

L22

097-S

48850-E

D2806-S

30A, 600V30A, 600VD2806-E

22473-

S1-4

X20S

TL22

473-S

1-4X2

0STL

0C4449A-RS

1/4 ST

L220

97-S

0F2710

RATINGSWITCH

SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY

TRANSFER SYSTEM DATA

MAXIMUM AMPS - 100

MAXIMUM VOLTS - 240

MODEL NUMBER

SERIAL NUMBER

#0C1026 OR #0D8440 0R #0E0117 OR #0E5241AALL TERMINALS LUGS ARE SUITABLE FOR COPPER

OR ALUUMINUM WIRE OF AT LEAST 75° c RATING

GENERAC POWER SYSTEMS, INC.WAUKESHA, WI.

13 14

B 35

36 9348

2118

52

1211

31 15327

1211

31

C

NOTE WIRE ORIENTATION

N1

0A659

9tv

CU

STO

MER

CO

NN

ECTI

ON

S

N2 WIRE

(240 VAC)

(240 VAC)

WIRE

T2

T1

WIRE

WIRE

(240 VAC)

(240 VAC)

23 WIRE

(OPTIONAL)

NEUTRAL

(12 VDC)

194 WIRE

(12 VDC)

WARNING

P/N 0A2595

30A,

600

VD

2806

-T

4782

2-T

Rep

lace

with

UL

liste

d fu

se o

f sam

e

600

Volt,

5 a

mp.

type

and

ratin

g

0D35

87

B

6337

8-T

RB

E1

BA

30A, 600VD2806-T

A

63378-T

63378-T

A

63378-T

INSI

DE

LEFT

SID

E

INSI

DE

RIG

HT

SID

E

192250

2617

16

0A659

9tv0A

6599tv

0A659

9tv

0A94

57

15

4331

(PO

WER

TER

MIN

AL L

UG

ASS

Y)

TIG

HTE

N IT

EM #

43: 2

4-30

IN/L

BS

DET

AIL

B-B

(PO

WER

TER

MIN

AL L

UG

ASS

Y)

DET

AIL

A-A

TIG

HTE

N IT

EM #

43: 2

4-30

IN/L

BS

5U

S

38

QTY

. 1 IT

EM #

37 A

BOVE

SU

BPLA

TEQ

TY. 2

ITEM

#37

's BE

LOW

SU

BPLA

TE

4 PL

ACES

64N

L

0A659

9tv

378

3730

NO

TE:

ASSE

MBL

E SE

NSI

NG

WIR

E R

ING

TER

MIN

ALS

SO

CLE

ARAN

CE

IS G

IVEN

FO

R

ACC

ESS

TO L

OW

ER L

UG

SC

REW

S.

TER

MIN

AL T

IGH

TEN

ING

TOR

QU

E 50

INC

H-P

OU

ND

S

SWIT

CH

XA

SWIT

CH

LEV

ER

SWIT

CH

XB

SWIT

CH

LEV

ER

TER

M. X

B2

6337

8-T

LIST

ED

63378-T63378-T

54 51

TER

M. X

B1

TER

M. X

A2

TER

M. X

B3

!

63378-T

TER

M. X

A3

TER

M. X

A1

48

46 NO

TE:

NO

TE:

4344

TER

MIN

AL T

IGH

TEN

ING

TOR

QU

E 50

INC

H-P

OU

ND

S

3 32

2

0A659

9tv0A

6599tv0A

6599tv

!

4 10 476

33

44

46

34

ENC

LOSU

RE

DET

AIL

A(G

ROU

ND

LU

G A

SSEM

BLY)

359TER

MIN

AL T

IGH

TEN

ING

TOR

QU

E 45

INC

H-P

OU

ND

S

DET

AIL

"A"

!

28

0E34

85

20

4945

23

0C83

08

0E34

84

4142

40

18

CO

VER

29 OF

INSI

DE

0E99

99

VIEW

S SH

OW

N W

ITH

ITEM

S #1

8 &

#19

FULL

Y AS

SEM

BLED

DEC

AL D

ETAI

LS

(NO

T TO

SC

ALE)

24

19

7

Section 6 — Exploded Views and Parts ListATS “HS” Type Transfer Switch

100A Transfer Switch Assembly – Drawing No. 0F0466$-D

Page 15: 0E9905

13

ITEM PART NO. QTY. DESCRIPTION

1 0C2237 1 TRANSFER SW-HSB 100A 2P 250V 2 0E7886H 1 CB 0100A 2P 240V S BQ2 LB 3 0E7890 1 BRKT CB MTG BACK 4 0E9906 1 BRACKET, DISCONNECT SWITCH 100A 5 063378 8 HOLDER, CABLE TIE 6 0D3728 1 SWITCH TOG SPST 15A @ 125V 7 0E9999 1 DECAL SERVICE DISCONNECT SWITCH 8 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR 9 0E6523 1 GROUND BAR (5)4-14 AWG CONN 10 *** 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 11 *** 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ 12 073590A 4 FUSE 5A X BUSS 13 *** 047822 1 BLOCK TERM 20A 7 X 6 X 1100V 14 0A1661 2 RIVET POP .156 X .675 AL 15 0C4449 1 ASS’Y-NTRL BL 150-200A 16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 17 0E1473 1 WELDMENT TRANSFER SWITCH BOX 18 0E9907 1 COVER INSIDE XFER SWITCH BOX 19 0E1477 1 COVER TRANSFER SWITCH BOX 20 0F0668 1 DECALTRANSFER SWITCH 21 0E3070 1 SUBPLT XFER SW HSB 22 0E9734 REF DECAL SWITCH RATING 23 0E3484 1 DECAL WARN MANUAL OPER HANDLE 24 0E3485 1 DECAL SERVICE DISCONNECT 25 067210A 1 DECAL GROUND LUG (NOT SHOWN) 26 0A9457 1 DECAL NEUTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0F0776 1 DECAL TEST SEQ. 2P TS HS 3R 30 081221 1 DECAL-UL LIST HSB 31 045764 6 SCREW HHTT M4-0.7 X 8 BP 32 074908 2 SCREW HHTT M5-0.8 X 10 BP 33 066849B 2 SCREW HHTT M5-0.8 X 8 BP 34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP 35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL 36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD 37 022473 8 WASHER FLAT 1/4-M6 ZINC 38 022097 4 WASHER LOCK M6-1/4 39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN) 40 0E6193 1 BRACKET ARM EXTENDER 41 064526 2 SCREW HWHS #6-25 X 3/8 ZNC 42 ** 0E6155 1 ARM EXTENDER PIN 43 036933 6 SCREW PPHM #10-32 X 3/8 44 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 45 0C8308 1 DECAL TERMINAL SHOCK HAZARD 46 022152 6 WASHER LOCK #10 47 0912970085 1 WIRE ASSY 2AWG 100A 2-P T/S N1A 48 0912970086 1 WIRE ASSY 2AWG 100A 2-P T/S N2A 49 095282 1 DECAL LIVE-CIRCUIT 50 0F2710 1 DECAL XFER SWITCH DATA SE 100A 51 066849 4 SCREW HHTT M5-0.8 X 16 52 0E6303 1 WIRE – A 53 0E6303A 1 WIRE – B 54 0E6303C 1 WIRE – E1

*** SUPPLIED WITH WIRE HARNESS ITEM #39** SUPPLIED WITH TRANSFER SWITCH (ITEM #1)

Section 6 — Exploded Views and Parts ListATS “HS” Type Transfer Switch

100A Transfer Switch Assembly – Drawing No. 0F0466$-D

Page 16: 0E9905

14

WAR

NIN

G

WIR

E

WIR

E

WIR

E

WIR

E

WIR

E

(12

VDC

)

(12

VDC

)

(240

VAC

)

(240

VAC

)

(240

VAC

)

(240

VAC

)

NO

TE W

IRE

OR

IEN

TATI

ON

(OPT

ION

AL)

NEU

TRAL

P/N

0A2

595

WIR

E

CUSTOMER CONNECTIONS

T2 194

23T1N2

N1

47822-T

30A,

600

VD

2806

-T

STANDBY(C2 & VR2)

(C1 & VR1)UTILITY

15

40 4241

23

BUSBAR

43

37

7

1/4 STL22097-S

22473-S 1-4X20STL

BUSBAR HARDWARE

1/4 STL22097-S

22473-S1-4X20STL

SWITCH

8

38

DETAIL

22473-S1-4X20STL22473-S1-4X20STL

48850-E

1/4 STL22097-S

D2806-S30A, 600V

22473-S1-4X20STL

0C4449A-R

S

22473-S1-4X20STL

0F27

12

WAU

KESHA, W

I.

OR

ALUU

MIN

UM

WIR

E OF AT LEAST 75° c R

ATING

ALL TERM

INALS LU

GS AR

E SUITABLE FO

R C

OPPER

#0C1026 O

R #0D

8440 0R #0E0117 O

R #0E5241A

SWITC

H IS FO

R U

SE WITH

CO

NTRO

L PANEL ASSEM

BLY

SYSTEM VO

LTAGE

RATIN

GSW

ITCH

MO

DEL N

UM

BER

GEN

ERAC

POW

ER SYSTEM

S, INC.

MAXIM

UM

AMPS - 200

MAXIM

UM

VOLTS - 240

TRAN

SFER SYSTEM

DATA

120/240

SERIAL N

UM

BER

30A, 600VD

2806-E

1/4 STL22097-S

35349

DETAIL "A"

ENCLOSURE

32

36

21

13

DETAIL A(GROUND LUG ASSEMBLY)

35

34

9

28 14

11 3112

47

1

0A6599tv0A6599tv0A6599tv

30A, 600VD2806-T

6337

8-T

BB

INSIDE RIGHT SIDE

INSIDE LEFT SIDE22

18

4

55

19

46

27

3111 12

26

17

0C4449A-T

Replace with ULlisted fuse of same

600 Volt, 5 amp.type and rating

0D3587

63378-T

AA

0A9457

0A6599tv0A6599tv0A6599tv

16

54 49

0C8308

0E3484

18

INSIDE

COVER

29

OF

56

VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED

NEMA 3R - INDOOR/OUTDOOR USE

TRANSFER SWITCH

QTY. 1 ITEM #37 ABOVE SUBPLATE

TO 72 IN-LBS.TORQUE ITEM #6

QTY. 2 ITEM #37's BELOW SUBPLATE

0E9999

0E3485

(NOT TO SCALE)

DECAL DETAILS

48

24

19

51

20

64NLSTAND-BY SYSTEMS

FOR USE IN OPTIONALAUTOMATIC TRANSFER SWITCH

CR

LISTED

US

0A6599tv0A6599tv0A6599tv0A6599tv

E1E1

6337

8-T

63378-T

6337

8-T

63378-T

50

4 PLACES

32 3737 38

5

5

30

38

386

6

45

44

AUTOMATIC

SEE SIDE VIEW FOR HARDWARE DETAILTORQUE ITEM #8 TO 12 FT-LBS

TIGHTENING TORQUE 250 IN-LBSUNDER BALL END OF SCREW

NOTE:LOCATE HOLE IN BUSBAR

43

63378-T

63378-T

0A6599tv0A6599tv0A6599tv

31

31

7

10

37 388

52

2

33

53

3

Section 6 — Exploded Views and Parts ListATS “HS” Type Transfer Switch

200A Transfer Switch Assembly – Drawing No. 0E9801$-F

Page 17: 0E9905

15

Section 6 — Exploded Views and Parts ListATS “HS” Type Transfer Switch

200A Transfer Switch Assembly – Drawing No. 0E9801$-F

ITEM PART NO. QTY. DESCRIPTION

1 0D9618 1 TRANSFER SW-HSB 200A 2P 250V 2 0E3628 1 CIRCUIT BREAKER 0200A 2P 120/240V S QN 3 0E3664 1 BASE QN CIRCUIT BREAKER 4 0E3553 2 BUSBAR 200A HSB XFER SW 5 0E3375 4 LUG SLDLSS 250-#6 AL/CU 6 0F1252 4 SCREW BHSC 1/4-20 X 3/8 7 036656 2 SCREW SHC 1/4-20 X 1 G8.8 NZ 8 022127 2 NUT HEX 1/4-20 STEEL 9 0E6523 1 GROUND BAR (5)4-14 AWG CONN 10 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 11 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ 12 073590A 4 FUSE 5A X BUSS 13 047822 1 BLOCK TERM 20A 7 X 6 X 1100V 14 0A1661 2 RIVET POP .156 X .675 AL 15 0C4449A 1 ASS’Y-NTRL BL150-200A 16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 17 0E1473 1 WELDMENT TRANSFER SWITCH BOX 18 0E9989 1 COVER INSIDE XFER SWITCH BOX 19 0E1477 1 COVER TRANSFER SWITCH BOX 20 0F0668 1 DECALTRANSFER SWITCH 21 0E3070 1 SUBPLT XFER SW HSB 22 0E3477 REF DECAL SWITCH RATING 23 0E3484 1 DECAL WARN MANUAL OPER HANDLE 24 0E3485 1 DECAL SERVICE DISCONNECT 25 067210A 1 DECAL GROUND LUG (NOT SHOWN) 26 0A9457 1 DECAL NEUTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0E7109 1 DECAL TEST SEQ.2P TS HS 3R 30 063378 8 HOLDER CABLE TIE 31 045764 8 SCREW HHTT M4-0.7 X 8 BP 32 049813 5 NUT HEX M6 X 1.0 G8 YEL CHR 33 074908 2 SCREW HHTT M5-0.8 X 10 BP 34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP 35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL 36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD 37 022473 14 WASHER FLAT 1/4-M6 ZINC 38 022097 10 WASHER LOCK M6-1/4 39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN) 40 0E6193 1 BRACKET ARM EXTENDER 41 064526 2 SCREW HWHS #6-25 X 3/8 42 * 0E6155 1 ARM EXTENDER PIN 43 * 0E6032 2 90 DEGREE UP SPADE CONNECTOR 44 * 0E6033 2 90 DEGREE DN SPADE CONNECTOR 45 * 0E6034 2 STRAIGHT SPADE CONNECTOR 46 0E6303 1 WIRE A 47 0E6303A 1 WIRE B 48 0E6303B 1 WIRE E1 49 0C8308 1 DECAL TERMINAL SHOCK HAZARD 50 081221 1 DECAL-UL LIST HSB 51 0E9999 1 DECAL-SERVICE DISCONNECT SWITCH 52 0E9988 1 BRACKET SERVICE SWITCH 53 0D3728 1 TOBBLE SWITCH, SERVICE 54 095282 1 DECAL LIVE-CIRCUIT 55 0F2712 1 DECAL XFER SWITCH DATA SE 200A 56 066849 5 SCREW HHTT M5-0.8 X 16

* SUPPLIED WITH TRANSFER SWITCH ITEM #1

Page 18: 0E9905

16 Generac® Power Systems, Inc.

Section 7 — NotesATS “HS” Type Transfer Switch

Page 19: 0E9905

Generac® Power Systems, Inc. 17

Section 7 — NotesATS “HS” Type Transfer Switch

Page 20: 0E9905

Part No. 0E9905 Revision F (07/21/05) Printed in U.S.A.

Section 8 — WarrantyATS “HS” Type Transfer Switch

GENERAC POWER SYSTEMS, INC. WARRANTY/SERVICE

Generac Power Systems, Inc. will warrant that from the date of purchase, our transfer switch will be free from defects in material and workmanship for the items and periods set forth in the warranty statement found in the owners manual of the Generac Power Systems Inc. generator that this transfer switch will be utilized with.

Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Generac Authorized Warranty Service Dealer by visiting our website at www.gener-ac.com or by calling the dealer locator number at 1-800-333-1322. Select the prompt that describes the brand name of the generator.

THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

GENERAC’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS, INC. BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC’S NEGLIGENCE.Some states do not allow the exclusion or limitation of incidental or consequential dam-ages, so the above limitations may not apply to you.

This warranty gives you specific legal rights. You also may have other rights that vary from state to state.