07047330

12
Published in IET Generation, Transmission & Distribution Received on 22nd December 2013 Accepted on 15th July 2014 doi: 10.1049/iet-gtd.2014.0603 ISSN 1751-8687 Analytical approach for optimal siting and sizing of distributed generation in radial distribution networks Sevya Naik Gopiya Naik, Dheeraj Kumar Khatod, Mahendra Pal Sharma Alternate Hydro Energy Centre, IIT Roorkee, Roorkee 247667, Uttarkhand, India E-mail: [email protected] Abstract: This study presents an analytical approach for optimal siting and sizing of distributed generation (DG) in radial power distribution networks to minimise real and reactive power losses. For this purpose, suitable analytical expressions have been derived which are based on change in active and reactive components of branch currents cause by the DG placement. This method rst determines the DG capacity causing maximum benet at different buses, and then selects the bus as the best location for DG placement which corresponds to highest benet. The proposed method is applicable for sizing and siting of single as well as multiple DG units. Moreover, the proposed method requires only the results of base case load ow to determine the optimal size of DG unit(s). The proposed method is tested on 33-bus and 69-bus radial distribution test systems. The results obtained by this proposed method validate the suitability and importance of proposed analytical method to determine the size and site of DG unit(s). 1 Introduction Electrical power systems are observing rapid changes from large centralised generation plants connected to the bulk transmission network into decentralised systems with small generating systems connected directly to the distribution networks near demand centre. The later type of generation system is known as distributed generation (DG) [1, 2]. DG can be powered by renewable energy sources (e.g. solar, wind, small hydro, biomass, geothermal etc.) or non-renewable energy sources (e.g. gas turbine, microturbine, fuel cell, reciprocating engine etc.). The benets of DG include reduction of power losses, improvement in the voltage prole, deferred network expansion cost, network reliability improvement and so on [36]. Appropriate size and location of DG offers technical, economical and environmental benets to distribution networks. For optimal allocation of DG in distribution networks, different objectives such as power loss minimisation [728], improvement of voltage prole [7, 11, 21, 23, 2528], network investment cost minimisation [5, 29, 30], reduction of environmental impact [7] and so on were touched by the researchers using single or multi objective problem formulation. Different optimisation techniques such as index-based approach [7, 25], heuristic method [29], mixed integer non-linear programming [12], analytical approaches [10, 1316, 2123, 28, 31], genetic algorithm (GA) [17, 22, 30], articial bee colony [18], particle swarm optimisation (PSO) [19], evolutionary programming [20], hybrid GA and Tabu search (GATS) [24], hybrid GA and PSO [26] and Pareto Frontier differential evolution algorithm [27] have been applied to solve the above DG allocation issues. Different DG technologies used in distribution system planning with their merits and demerits, the various aspects of DG planning for power loss minimisation, and different techniques employed in achieving the goal along with their feasibility has been reported in [32]. A methodology for optimal allocation of DG in distribution networks based on analytical approach (sensitivity analysis based on equivalent current injection) for loss reduction has been suggested by Gozel and Hocaoglu [10]. Wang and Nehir [13] proposed an analytical method based on phasor current injection method to optimally place DG assuming uniformly, increasingly and centrally distributed load pattern with in radial distribution network to minimise power loss. These assumptions may cause erroneous results. In [1416], analytical approach based on exact loss formula for optimally allocating DGs was presented. This is followed by the work of Khan and Choudhary [21] who presented an analytic-based algorithm to site and size DG in distribution network for reducing the power loss and improving the voltage prole. An approach based on exact loss formula and GA for power loss minimisation of distribution feeder was proposed by Shukla et al. [22]. The loss sensitivity method is used to identify the strategic candidate locations for DG. A technique based on loss sensitivity method for sizing and siting of DG optimally to minimise the power losses in the distribution system was proposed by Kashem et al. [28]. Most of the above methodologies considered the DG type, which is capable of supplying real power only to the network. However, there are other types of DG which can supply real and/or reactive power into the network and improve the performance to still better extent. Further, the majority of the general analytical approaches for DG siting and sizing www.ietdl.org IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220 doi: 10.1049/iet-gtd.2014.0603 209 & The Institution of Engineering and Technology 2015

Upload: florin-nastasa

Post on 10-Nov-2015

214 views

Category:

Documents


0 download

DESCRIPTION

luc1

TRANSCRIPT

  • timadato67, U

    al sssesmpbenet.ed meth

    ate t

    method [29], mixed integer non-linear programming [12],analytical approaches [10, 1316, 2123, 28, 31], geneticalgorithm (GA) [17, 22, 30], articial bee colony [18],particle swarm optimisation (PSO) [19], evolutionaryp[ds

    www.ietdl.org

    IEdrogramming [20], hybrid GA and Tabu search (GATS)24], hybrid GA and PSO [26] and Pareto Frontierifferential evolution algorithm [27] have been applied toolve the above DG allocation issues. Different DG

    HapthT Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220oi: 10.1049/iet-gtd.2014.0603sensitivity method for sizing and siting of DG optimally tominimise the power losses in the distribution system wasproposed by Kashem et al. [28].Most of the above methodologies considered the DG type,

    which is capable of supplying real power only to the network.owever, there are other types of DG which can supply realnd/or reactive power into the network and improve theerformance to still better extent. Further, the majority ofe general analytical approaches for DG siting and sizingobjective problem formulation. Different optimisationtechniques such as index-based approach [7, 25], heuristic

    candidate locations for DG. A technique based on loss

    were touched by the researchers using single or multiElectrical power systems are observing rapid changes fromlarge centralised generation plants connected to the bulktransmission network into decentralised systems with smallgenerating systems connected directly to the distributionnetworks near demand centre. The later type of generationsystem is known as distributed generation (DG) [1, 2]. DGcan be powered by renewable energy sources (e.g. solar,wind, small hydro, biomass, geothermal etc.) ornon-renewable energy sources (e.g. gas turbine,microturbine, fuel cell, reciprocating engine etc.). Thebenets of DG include reduction of power losses,improvement in the voltage prole, deferred networkexpansion cost, network reliability improvement and so on[36]. Appropriate size and location of DG offers technical,economical and environmental benets to distributionnetworks. For optimal allocation of DG in distributionnetworks, different objectives such as power lossminimisation [728], improvement of voltage prole [7, 11,21, 23, 2528], network investment cost minimisation [5,29, 30], reduction of environmental impact [7] and so on

    merits and demerits, the various aspects of DG planning forpower loss minimisation, and different techniques employedin achieving the goal along with their feasibility has beenreported in [32].A methodology for optimal allocation of DG in distribution

    networks based on analytical approach (sensitivity analysisbased on equivalent current injection) for loss reduction hasbeen suggested by Gozel and Hocaoglu [10]. Wang andNehir [13] proposed an analytical method based on phasorcurrent injection method to optimally place DG assuminguniformly, increasingly and centrally distributed loadpattern with in radial distribution network to minimisepower loss. These assumptions may cause erroneous results.In [1416], analytical approach based on exact loss formulafor optimally allocating DGs was presented. This isfollowed by the work of Khan and Choudhary [21] whopresented an analytic-based algorithm to site and size DGin distribution network for reducing the power loss andimproving the voltage prole. An approach based on exactloss formula and GA for power loss minimisation ofdistribution feeder was proposed by Shukla et al. [22]. Theloss sensitivity method is used to identify the strategicPublished in IET Generation, Transmission & DistributionReceived on 22nd December 2013Accepted on 15th July 2014doi: 10.1049/iet-gtd.2014.0603

    Analytical approach for opdistributed generation in rSevya Naik Gopiya Naik, Dheeraj Kumar KhAlternate Hydro Energy Centre, IIT Roorkee, Roorkee 2476E-mail: [email protected]

    Abstract: This study presents an analytical approach for optimdistribution networks to minimise real and reactive power loderived which are based on change in active and reactive comethod rst determines the DG capacity causing maximumlocation for DG placement which corresponds to highest bensingle as well as multiple DG units. Moreover, the proposdetermine the optimal size of DG unit(s). The proposed msystems. The results obtained by this proposed method validto determine the size and site of DG unit(s).

    1 IntroductionISSN 1751-8687

    al siting and sizing ofial distribution networksd, Mahendra Pal Sharmattarkhand, India

    iting and sizing of distributed generation (DG) in radial power. For this purpose, suitable analytical expressions have beenonents of branch currents cause by the DG placement. Thiset at different buses, and then selects the bus as the bestThe proposed method is applicable for sizing and siting ofethod requires only the results of base case load ow tood is tested on 33-bus and 69-bus radial distribution testhe suitability and importance of proposed analytical method

    technologies used in distribution system planning with their209& The Institution of Engineering and Technology 2015

  • are based on exact loss formula and require the determinationof the bus impedance matrix (Zbus) or Jacobian matrix whichare computationally demanding. Therefore, because of thesize, the complexity and the specic characteristics of thedistribution network, the above methods are not suitable.Therefore, the optimal allocation of DG of any type usingsuitable solution technique needs further attention.In this paper, a methodology based on analytical approach

    is presented for optimal sizing and siting of DG in distributionsystem so as to minimise real as well as reactive power losses.This paper is the extension of that proposed in [23]. Thedeveloped analytical method is based on change in activeand reactive components of branch currents cause by theDG placement. The proposed method has been tested on33-bus and 69-bus test radial distribution systems and theresults are found to support the suitability and benets ofproper DG allocation in power distribution system fornetwork performance improvement. This paper is organisedas follows: Section 2 discusses the problem formulation ofproposed method, Section 3 presents the solution algorithm

    When a DG is placed at a bus (say bus k) as shown in

    www.ietdl.orgFig. 2, it injects current IDG into the network and there byalters the currents in all the branches connected betweensub-station (bus 1) to bus k. However, the currents in the

    Fig. 1 Typical N-bus radial distribution system

    Fig. 2 Typical N-bus radial distribution system with DG placed atbus kand Section 4 presents the results and discussion of theproposed work. Finally, in Section 5, conclusions aresummarised.

    2 Problem formulation

    In this section, the mathematical formulation of the proposedanalytical approach is presented. The proposed analyticalapproach aims to determine the optimal size and location ofDG in a given radial distribution network so as to minimiseboth real power loss and voltage drop. The proposedapproach begins with the following assumptions:

    1. The radial distribution network under consideration isbalanced.2. The power factor of DG is known.

    Consider a typical N-bus radial distribution system asshown in Fig. 1. In this gure, Ik is the phasor current inbranch k while ILk is the load phasor current of loadconnected at node k.210& The Institution of Engineering and Technology 2015remaining branches are unaffected by the DG placed at busk. The injected current by DG placed at bus k can bewritten as

    IDG = IaDG + jIrDG = IaDG 1+ j tanf( )

    (1)

    where IaDG and IrDG are the real and reactive components,respectively, of IDG and f is the phase angle of IDG.Now, the modied current in branch i because of DG

    placed at bus k can be given as

    Inewi = I i DiIDG = Iai DiIaDG( )+ j Iri DiIaDG tanf( )

    (2)

    where Ii is the phasor current in branch I before DGplacement and Inewi is the modied phasor current in branchi after DG placement. The value of Di is given by thefollowing relation

    Di = 1, if branch i is between bus 1 and bus k0, otherwise.{

    Extending the above concept for placement of m DGssimultaneously in an N-bus radial distribution network, themodied current through branch I can be given as

    Inewi = I i mk=1

    DikIkDG = Iai

    mk=1

    DikIkaDG

    ( )

    + j Iri mk=1

    DikIkaDG tanf

    k

    ( )(3)

    where Inewi is the modied phasor current in branch i; IkDGis

    the phasor current injected current by kth DG; IkaDGand fk

    are the active component and phase angle, respectively, ofIkDG and the value of Dik is given by the following relation

    Dik =1, if branch i is between bus 1 and bus at which

    kth DG is placed0, otherwise

    2.1 Real power loss saving

    The total active power loss [33], that is, PL in a typical N-busradial distribution system as shown in Fig. 1, can be given as

    PL =N1i=1

    I2i Ri =N1i=1

    I2ai + I2ri( )

    Ri (4)

    where Ii is the current through branch i with Iai and Iri beingits real and imaginary components, respectively, and Ri is theresistance of the branch.Now, using (3), the total real power loss after placement of

    m DGs is given by

    PnewL =N1i=1

    Inewi( )2

    Ri

    =N1i=1

    Iaimk=1

    DikIkaDG

    ( )2+ Iri

    mk=1

    DikIkaDG tanf

    k

    ( )2[ ]Ri

    (5)IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603

  • Using (4) and (5), the normalised loss saving PS associatedwith multiple DG placement can be given as (see (6)).

    2.2 Reactive power loss saving

    The total reactive power loss, that is, QL in a typical N-busradial distribution system as shown in Fig. 1, can be given as

    QL =N1i=1

    I2i Xi =N1i=1

    I2ai + I2ri( )

    Xi (7)

    Now, using (3), the total reactive power loss after placementof m DGs is given by

    QnewL =N1i=1

    Inewi( )2

    Xi =N1i=1

    Iai mk=1

    DikIkaDG

    ( )2

    + Iri mk=1

    DikIkaDG tanf

    k

    ( )2Xi(8)

    Using (7) and (8), the normalised reactive power loss savingQS associated with multiple DG placement can be given as(see (9)).

    saving, respectively and should meet the following condition

    w1 + w2 = 1 (11)

    The DG currents for the maximum benet can be achieved bysolving the following equation

    f

    I1aDG= w1

    PSI1aDG

    + w2QSI1aDG

    = 0f

    I2aDG= w1

    PSI2aDG

    + w2QSI2aDG

    = 0

    ..

    . ... ..

    .

    f

    ImaDG= w1

    PSImaDG

    + w2QSImaDG

    = 0

    (12)

    The partial derivative of f with respect to IpaDG can be given as(see (13)).

    Corresponding to (12), there will be m linear algebraicequations each similar to (13). These equations can bearranged in matrix form and expressed as

    [ ]

    ik IkaDNi=

    (11 I(

    (P

    ikIkaDNi=

    (11 I(

    (Q

    ikIka

    www.ietdl.orgPS = 1PnewLPL

    = 1N1

    i=1 Iai m

    k=1 D([

    =N1

    i=1 2m

    k=1 DikIkaDG Iai + Iri tanfk

    ( )[N

    i=

    =N1

    i=1 2m

    k=1 DikIkaDG Iai + Iri tanfk

    ( )[

    QS = 1QnewLQL

    = 1N1

    i=1 Iai m

    k=1 D([

    =N1

    i=1 2m

    k=1 DikIkaDG Iai + Iri tanfk

    ( )[N

    i=

    =N1

    i=1 2m

    k=1 DikIkaDG Iai + Iri tanfk

    ( )[

    f

    IpaDG= 2

    N1i=1

    Dip Iai + Iri tanfp( ) Dipm

    k=1D

    {2.3 Net benet

    Now, using (6) and (9), the net benet associated withmultiple DG placement can be combined as

    f = w1PS + w2QS (10)

    where w1 and w2 are the constants representing weightsassigned to real power loss saving and reactive power lossIET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603A[ ]mm IaDG m1= B[ ]m1 (14)

    The (p, q)th elements of matrix A are calculated by thefollowing expression

    Apq =N1i=1

    DipDiq 1+ tanfp tanfq( )

    w1RiPL

    + w2XiQL

    ( )

    (15)

    G

    )2+ Iri mk=1 DikIkaDG tanfk( )2]Ri11 I

    2ai + I2ri

    ( )Rim

    k=1 DikIkaDG

    )2 mk=1 DikIkaDG tanfk( )2]Ri2ai + I2ri

    )Rim

    k=1 DikIkaDG

    )2 mk=1 DikIkaDG tanfk( )2]RiL

    (6)

    G

    )2+ Iri mk=1 DikIkaDG tanfk( )2]Xi11 I

    2ai + I2ri

    ( )Xim

    k=1 DikIkaDG

    )2 mk=1 DikIkaDG tanfk( )2]Xi2ai + I2ri

    )Xim

    k=1 DikIkaDG

    )2 mk=1 DikIkaDG tanfk( )2]XiL

    (9)

    DG 1+ tanfp tanfk( )}

    w1RiPL

    + w2XiQL

    ( )= 0 (13)211& The Institution of Engineering and Technology 2015

  • 2. Run the base case load ow using backward and forwardsweep method [34] and obtain real power loss (PL), reactivepower loss (QL) and voltage prole of the network.3. Select the number of DGs to be placed (say m) and theirpower factors (DGs may have different power factors). Also,select the suitable values of the weights w1 and w2considering (11).4. Initialise DG counter, k = 1 and bus counter, i = 2.5. Calculate the required capacity of kth DG at bus I using(19)(21) and then compute and store the benet (say fik)associated using (10) along with the capacity of kth DG.6. Check whether i fik, for i = 2 to N and i j) for kth DG.Connect kth DG at bus j with the capacity as calculatedfrom step 5.8. Run the load ow with kth DG located at bus j and obtainreal power loss (PL), total reactive power loss (QL) andvoltage prole of the network.9. Check whether k
  • 4 Results and discussion

    The developed algorithm has been implemented underMATLAB environment and applied on two test systems todetermine the optimal sizing and siting of DGs. For eachtest system, different values of w1 and w2 have beenconsidered as (a) w1 = 1 and w2 = 0; (b) w1 = 0.5 and w2 =0.5; and (c) w1 = 0 and w2 = 1. Apart from this, twodifferent values of DG power factors have also beenconsidered as: (a) all DGs are operating at unity power

    factor; and (b) all DGs are operating at a power factor equalto the power factor of total load of the system [15].The following test systems have been considered for the

    optimal placement and sizing of DGs by the developedalgorithm.

    4.1 33-Bus radial distribution system

    The single line diagram of a 12.66 kV, 33-bus radialdistribution system is illustrated in Fig. 4. The relevant data

    Fig. 4 Single line diagram of 12.66 kV, 33-bus radial distribution system

    r ma

    www.ietdl.orgFig. 5 Optimal DG size of unity power factor at different buses foTable 1 Results for UPF DG installation in 33-bus test system with w1

    Initial system condition

    System description Active powerloss, kW

    original base case 202.682.48 MVA, UPF DG connected to bus 6 104.082.48 and 0.41 MVA, UPF DG connected to buses 6and 16, respectively

    92.48

    2.48, 0.41 and 0.65 MVA, UPF DG connected tobuses 6, 16 and 25, respectively

    84.16

    original base case 202.68

    1.73, 0.53 and 0.77 MVA, UPF DG connected tobuses 6, 16 and 25, respectively

    79.51

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603ximum real power loss saving= 1 and w2 = 0

    Result with DG installation

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    1 6 2.48 91.801 16 0.41 10.261 25 0.65 7.81

    3 6, 16, 25 1.73,0.53, 0.77

    116.75

    213& The Institution of Engineering and Technology 2015

  • for this test system are acquired from [35]. This test systemhas the total demand of (3715 + j2300) kVA with the powerfactor of total load as 0.85 lagging.The number of DG to be placed is taken as 3. In order to

    determine 3 suitable buses for DG installation at unity

    power factor (UPF) in 33-bus test system for benetmaximisation with w1 = 1 and w2 = 0, rst the optimal sizeof a single DG and the corresponding benet aredetermined using (21) and (10), respectively. For this case,Fig. 5 shows the DG size for all the buses in the system

    Table 2 Results for LPF DG installation in 33-bus test system with w1 = 1 and w2 = 0

    Initial system condition Result with DG installation

    System description Active powerloss, kW

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    original base case 202.68 1 6 3.01 135.193.01 MVA, LPF DG connected to bus 6 61.72 1 32 0.60 14.823.01 and 0.60 MVA, LPF DG connected to buses 6and 32, respectively

    46.07 1 25 0.68 8.47

    3.01, 0.60 and 0.68 MVA, LPF DG connected tobuses 6, 32 and 25, respectively

    37.38

    original base case 202.68 3 6, 32, 25 1.85,0.90, 0.85

    127.79

    1.85, 0.90 and 0.85 MVA, LPF DG connected tobuses 6, 32 and 25, respectively

    26.63

    h w1

    Table 3 Results for UPF DG installation in 33-bus test system with w1 = 0.5 and w2 = 0.5

    Initial system condition Result with DG installation

    System description Activepower loss,

    kW

    Reactivepower loss,

    kVAr

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    Reactive losssaving, kVAr

    original base case 202.68 135.14 1 6 2.44 91.78 55.412.44 MVA, UPF DG connected tobus 6

    104.20 74.78 1 15 0.44 10.72 8.67

    2.44 and 0.44 MVA, UPF DGconnected to buses 6 and 15,respectively

    92.04 65.09 1 25 0.66 7.83 5.68

    2.44, 0.44 and 0.66 MVA, UPF DGconnected to buses 6, 15 and 25,respectively

    83.71 59.07

    original base case 202.68 135.14 3 6, 15, 25 1.66,0.58,0.76

    117.11 75.00

    1.66, 0.58 and 0.76 MVA, UPF DGconnected to buses 6, 15 and 25,respectively

    79.20 55.60

    www.ietdl.orgTable 4 Results for LPF DG installation in 33-bus test system wit

    Initial system conditionSystem description Activepower loss,

    kW

    Reactivepower loss,

    kVAr

    No.pl

    original base case 202.68 135.142.97 MVA, LPF DG connected tobus 6

    61.83 48.54

    2.97 and 0.62 MVA, LPF DGconnected to buses 6 and 31,respectively

    45.39 36.33

    1.78, 0.62 and 0.69 MVA, LPF DGconnected to buses 6, 31 and 25,respectively

    36.64 29.78

    original base case 202.68 135.14

    1.81, 0.93 and 0.84 MVA, LPF DGconnected to buses 6, 31 and 25,respectively

    26.07 22.43

    214& The Institution of Engineering and Technology 2015= 0.5 and w2 = 0.5

    Result with DG installationof DGaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    Reactive losssaving, kVAr

    1 6 2.97 135.17 82.031 31 0.62 15.58 11.51

    1 25 0.69 8.54 6.37

    3 6, 31, 25 1.81,0.93,0.84

    128.03 83.41

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603

  • except the sub-station bus and corresponding benet (active for this case are summarised in Table 2. For this case, theoptimal sizes of DGs are 1.85, 0.90 and 0.85 MVA at buses6, 32 and 25, respectively. This alternative of DG sizesresults in a total real power loss of 26.63 kW or 86.86%real power loss reduction as compared with base case system.Further, optimal locations and sizes of 3 DGs are also

    computed for different values of w1 and w2. Tables 3 and 4present the optimal locations and sizes of 3 DGs operated atUPF and LPF, respectively, with w1 = 0.5 and w2 = 0.5. AtUPF operation of DGs, their optimal sizes are 1.66, 0.58and 0.76 MVA at buses 6, 15 and 25, respectively, resultingin (79.20 + j55.60) kVA loss in the network. On the other

    Table 5 Results for UPF DG installation in 33-bus test system with w1 = 0 and w2 = 1

    Initial system condition Result with DG installation

    System description Reactive powerloss, kVAr

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Reactive losssaving, kVAr

    original base case 135.14 1 7 2.00 55.782.00 MVA, UPF DG connected to bus 7 75.46 1 31 0.58 10.322.00 and 0.58 MVA, UPF DG connected tobuses 7 and 31, respectively

    63.57 1 25 0.70 6.50

    2.00, 0.58 and 0.70 MVA, UPF DG connected tobuses 7, 31 and 25, respectively

    56.72

    original base case 135.14 3 7, 31, 25 1.38,0.71, 0.77

    77.59

    1.38, 0.71 and 0.77 MVA, UPF DG connected tobuses 7, 31 and 25, respectively

    53.36

    www.ietdl.orgpower loss saving). The active power loss saving obtainedby running load ow is also plotted in this gure for thesake of comparison. The loss saving computed by proposedmethod is close to that computed by running load ow andboth are following similar trends.It is evident from Fig. 5 that the highest active power loss

    saving of 91.8 kW can be achieved by placing a 2.48 MVA,UPF DG at bus 6. However, the actual active power losssaving calculated by running load ow is 98.6 kW. This isbecause, in the developed analytical method, the expressionfor active power loss saving has been derived because ofchange in branch currents only caused by DG placement.When branch currents are reduced by DG placement, thevoltage drops in different branches are also reduced whichin turn improves the voltage prole of the system. Thus, anextra saving of 6.8 kW can also be achieved by placing a2.48 MVA, UPF DG at bus 6 because of voltage proleimprovement.After placing a 2.48 MVA, UPF DG at bus 6, the above

    procedure is repeated to identify next and subsequentcandidate buses. The results for this case are summarised inTable 1. From this table, it is clear that buses 6, 16 and 25are the suitable location for DG installation at UPF. Now,the optimal sizes of DGs determined simultaneously byusing (18)(20) are 1.73, 0.53 and 0.77 MVA at buses 6, 16and 25, respectively. This alternative of DG sizes results ina total real power loss of 79.51 kW against 202.68 kWpower loss of base case system.This approach is extended to size and site 3 DGs, operating

    at load power factor (LPF) in 33-bus test system for benetmaximisation with w1 = 1 and w2 = 0. The obtained resultsTable 6 Results for LPF DG installation in 33-bus test system with w1

    Initial system condition

    System description Reactive powerloss, kVAr

    original base case 135.141.80 MVA, UPF DG connected to bus 30 48.621.80 and 0.77 MVA, UPF DG connected to buses30 and 14, respectively

    24.28

    1.80, 0.77 and 1.06 MVA, UPF DG connected tobuses 30, 14 and 24, respectively

    14.70

    original base case 135.14

    1.39, 0.81 and 1.14 MVA, UPF DG connected tobuses 30, 14 and 24, respectively

    11.76

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603hand, 1.81, 0.93 and 0.84 MVA LPF DGs connected atbuses 6, 31 and 25, respectively, result in (26.07 + j22.43)kVA loss in the network.Tables 5 and 6 summarises the results of optimal locations

    and sizes of 3 DGs operated at UPF and LPF, respectively,with w1 = 0 and w2 = 1.0. In this case, at UPF operation ofDGs, their optimal sizes are 1.38, 0.71 and 0.77 MVA atbuses 7, 31 and 25, respectively, causing 53.36 kVArreactive power loss. While at LPF operation of DGs, their

    Table 7 Comparison of results for 33-bus test system

    Particulars Acharyaet al. [14]

    Murthy andKumar [36]

    Proposedmethod

    DG size, MVA 2.49 2.5 3.01 2.48 3.01DG power factor UPF UPF 0.9 lag UPF 0.85 laglocation 6 6 6 6 6loss saving,% 47.33 47.32 66.39 48.65 69.55= 0 and w2 = 1

    Result with DG installation

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Reactive losssaving, kVAr

    1 30 1.80 83.551 14 0.77 23.811 24 1.06 9.44

    3 30, 14, 24 1.39,0.81, 1.14

    82.73

    215& The Institution of Engineering and Technology 2015

  • optimal sizes are 1.39, 0.81 and 1.14 MVA at buses 30, 14 and24, respectively, resulting in 11.76 kVAr reactive power loss.Summarising different cases presented in Tables 16, it is

    evident that the optimal locations and sizes of DGs varydepending upon the objective considered (values of w1 and w2)

    and power factor of DG. For a considered objective, LPFoperation of DGs improves the system performance in abetter way compared with UPF operation.Finally, to validate the proposed method, the results

    obtained by it are compared with those obtained by the

    Fig. 6 Voltage prole of 33-bus test system for different cases

    www.ietdl.orgTable 8 Results for UPF DG installation in 69-bus test system with w1

    Initial system condition

    System description Active powerloss, kW

    original base case 225.001.81 MVA, UPF DG connected to bus 50 83.371.81 and 0.51 MVA, UPF DG connected to buses50 and 17, respectively

    71.71

    1.81, 0.51 and 0.72 MVA, UPF DG connected tobuses 50, 17 and 39, respectively

    70.20

    original base case 225.00

    1.72, 0.52 and 0.72 MVA, UPF DG connected tobuses 50, 17 and 39, respectively

    70.29

    Fig. 7 Single line diagram of 12.66 kV, 69-bus distribution system

    216& The Institution of Engineering and Technology 2015= 1 and w2 = 0

    Result with DG installation

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    1 50 1.81 133.031 17 0.51 11.011 39 0.72 1.51

    3 50, 17, 39 1.72,0.52, 0.72

    149.28

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603

  • methods reported in the literature for 33-bus test system andpresented in Table 7. The results presented in this table arefor siting and sizing of single DG to minimise the realpower loss only. From this table, it is evident that moreactive power loss saving is possible by the proposed methodcompared with the other methods reported in the literature.

    The voltage proles of 33-bus test system for differentcases considered are given in Fig. 6. These voltage prolesare obtained after placing 3 DGs as given in the last row ofTables 16. It is evident from Fig. 6 that the installation ofDG units in 33-bus test system by proposed methodsignicantly improves the voltage prole of the network.

    Table 9 Results for LPF DG installation in 69-bus test system with w1 = 1 and w2 = 0

    Initial system condition Result with DG installation

    System description Active powerloss, kW

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    original base case 225.00 1 50 2.22 200.112.22 MVA, LPF DG connected to bus 50 23.88 1 17 0.61 15.602.22 and 0.61 MVA, LPF DG connected to buses 50and 17, respectively

    8.19 1 39 0.88 2.27

    2.22, 0.61 and 0.88 MVA, LPF DG connected tobuses 50, 17 and 39, respectively

    5.92

    original base case 225.00 3 50, 17, 39 2.12,0.62, 0.88

    153.91

    2.12, 0.62 and 0.88 MVA, LPF DG connected tobuses 50, 17 and 39, respectively

    5.66

    ith w

    No.

    Table 10 Results for UPF DG installation in 69-bus test system with w1 = 0.5 and w2 = 0.5

    Initial system condition Result with DG installation

    System description Activepower loss,

    kW

    Reactivepower loss,

    kVAr

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Active losssaving, kW

    Reactive losssaving, kVAr

    original base case 225.00 102.17 1 50 1.83 133.01 57.881.83 MVA, UPF DG connected tobus 50

    83.29 40.62 1 17 0.52 10.85 4.39

    1.83 and 0.52 MVA, UPF DGconnected to buses 50 and 17,respectively

    71.76 35.95 1 39 0.72 1.51 3.70

    1.83, 0.52 and 0.72 MVA, UPF DGconnected to buses 50, 17 and39, respectively

    70.25 32.24

    original base case 225.00 102.17 3 50, 17, 39 1.73,0.53,0.72

    149.29 67.50

    1.73, 0.53 and 0.72 MVA, UPF DGconnected to buses 50, 17 and39, respectively

    70.24 32.30

    www.ietdl.orgTable 11 Results for LPF DG installation in 69-bus test system w

    Initial system condition

    System description Active Reactive

    power loss,

    kWpower loss,

    kVArpl

    original base case 202.68 102.172.25 MVA, UPF DG connected tobus 50

    23.87 14.67

    2.25 and 0.62 MVA, UPF DGconnected to buses 50 and 17,respectively

    8.38 8.45

    2.25, 0.62 and 0.88 MVA, UPF DGconnected to buses 50, 17 and39, respectively

    6.11 2.89

    original base case 202.68 102.17

    2.13, 0.64 and 0.88 MVA, UPF DGconnected to buses 50, 17 and39, respectively

    5.66 2.79

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.06031 = 0.5 and w2 = 0.5

    Result with DG installation

    of DG Bus for DG DG size, Active loss Reactive loss

    aced placement MVA saving, kW saving, kVAr

    1 50 2.25 200.08 87.081 17 0.62 15.38 6.19

    1 39 0.88 2.27 5.55

    3 50, 17, 39 2.13,0.64,0.88

    153.81 69.94

    217& The Institution of Engineering and Technology 2015

  • However, the degree of improvement is different dependingupon the objective considered (values of w1 and w2) andpower factor of DG. Among different cases considered, thebest voltage prole is observed when DGs are operated atLPF with w1 = 0 and w2 = 1.0.

    4.2 69-Bus radial distribution system

    The single line diagram of a 12.66 kV, 69-bus distribution testsystem is shown in Fig. 7. The necessary data for 12.66 kV,

    69-bus distribution test system are obtained from [37]. Thistest system has the total demand of (3802.19 + j2694.6)kVA with the power factor of total load as 0.82 lagging.For this test system also, the number of DG to be placed is

    taken as 3. To determine 3 suitable buses for DG installationat UPF in 69-bus test system for benet maximisation withw1 = 1 and w2 = 0, similar procedure is employed asdiscussed for 33-bus test system. The results for this caseare summarised in Table 8. The installation of 1.72, 0.52and 0.72 MVA UPF DGs at buses 50, 17 and 39,

    Table 12 Results for UPF DG installation in 69-bus test system with w1 = 0 and w2 = 1

    Initial system condition Result with DG installation

    System description Reactive powerloss, kVAr

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Reactive losssaving, kVAr

    original base case 102.17 1 50 1.86 57.891.86 MVA, UPF DG connected to bus 50 40.56 1 17 0.53 4.311.86 and 0.53 MVA, UPF DG connected to buses50 and 17, respectively

    35.96 1 39 0.72 3.70

    1.86, 0.53 and 0.72 MVA, UPF DG connected tobuses 50, 17 and 39, respectively

    32.26

    original base case 102.17 3 50, 17, 39 1.74,0.55, 0.72

    67.51

    1.74, 0.55 and 0.72 MVA, UPF DG connected tobuses 50, 17 and 39, respectively

    32.27

    Table 13 Results for LPF DG installation in 69-bus test system with w1 = 0 and w2 = 1

    Initial system condition Result with DG installation

    System description Reactive powerloss, kVAr

    No. of DGplaced

    Bus for DGplacement

    DG size,MVA

    Reactive losssaving, kVAr

    original base case 102.17 1 50 2.28 87.102.28 MVA, UPF DG connected to bus 50 14.63 1 17 0.64 6.072.28 and 0.64 MVA, UPF DG connected to buses50 and 17, respectively

    8.53 1 39 0.88 5.55

    2.28, 0.64 and 0.88 MVA, UPF DG connected tobuses 50, 17 and 39, respectively

    2.97

    original base case 102.17 3 50, 17, 39 2.14,0.66, 0.88

    69.90

    2.14, 0.66 and 0.88 MVA, UPF DG connected to 2.77

    www.ietdl.orgbuses 50, 17 and 39, respectivelyFig. 8 Voltage prole of 69-bus test system for different cases

    218& The Institution of Engineering and Technology 2015IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603

  • www.ietdl.orgrespectively, results in a total real power loss of 70.29 kWagainst 225 kW power loss of base case system.To size and site 3 DGs, operating at LPF in 69-bus test

    system for benet maximisation with w1 = 1 and w2 = 0, theobtained results are summarised in Table 9. From this table,it is clear that buses 50, 17 and 39 are the suitable locationsfor DG installation at LPF. The optimal sizes of DGs are2.12, 0.62 and 0.88 MVA at buses 50, 17 and 39,respectively, and results in a total real power loss of 5.66 kWor 97.78% real power loss reduction compared with basecase system.Further, optimal locations and sizes of 3 DGs are also

    computed for different values of w1 and w2. Tables 10 and11 present the optimal locations and sizes of 3 DGsoperated at UPF and LPF, respectively, with w1 = 0.5 andw2 = 0.5. Tables 12 and 13 summarise the results of optimallocations and sizes of 3 DGs operated at UPF and LPF,respectively, with w1 = 0 and w2 = 1.0.Summarising different cases presented in Tables 812, it is

    evident that the optimal locations for DGs are the sameirrespective of the objective considered and power factor ofDG. Also, the optimal sizes of DGs are approximatelysimilar for a given power factor irrespective of the objectiveconsidered. Among different power factor, LPF operation ofDGs improves the system performance in a better way ascompared with UPF operation.A comparison of results obtained by different methods for

    single DG allocation to minimise real power loss in 69-bussystems is given in Table 14. From this table, it is evidentthat more active power loss saving by the proposed methodis in good agreement with the other methods reported in theliterature.The voltage proles of 69-bus test system for different

    cases considered are given in Fig. 8. These voltage prolesare obtained after placing 3 DGs as given in the last row ofTables 812. It is evident from Fig. 8 that the installation ofDG units in 69-bus test system by proposed methodsignicantly improves the voltage prole of the network.Since it is seen from Tables 812 that the optimal sizes ofDGs are approximately similar despite of the objectiveconsidered and mainly depends on the power factor of DG,the same can be observed in Fig. 8 also. The best voltageprole is observed when DGs are operated at LPF,irrespective of the objective considered.

    Table 14 Comparison of results of 69-bus test system

    Particulars Acharya et al.[14]

    Murthy andKumar [36]

    Proposedmethod

    DG size, MW 1.81 1.85 2.20 1.81 2.22power factor UPF UPF 0.9

    lagUPF 0.82

    laglocation 50 50 50 50 50loss saving,% 62.86 63.02 87.59 62.95 89.395 Conclusions

    This paper presents an analytical approach-basedmethodology for optimal sizing and siting of DGs in theradial distribution networks. Both real as well as reactivepower loss minimisation are the objectives for DGplacement. Suitable analytical expressions have beenderived to compute the real as well as reactive power losssaving because of change in branch current caused by DG.The developed method is able to optimise the size and

    optimal placement of renewable distributed generators, IEEE Trans.

    IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603Power Syst., 2013, 28, (2), pp. 68369521 Khan, H., Choudhary, M.A.: Implementation of distributed generation

    (IDG) algorithm for performance enhancement of distribution feederunder extreme load growth, Int. J. Electr. Power Energy Syst., 2010,32, (9), pp. 985997

    22 Shukla, T.N., Singh, S.P., Srinivas Rao, V., Naik, K.B.: Optimal sizingof distributed generation placed on radial distribution systems, Electr.Power Compon. Syst., 2010, 38, (3), pp. 260274

    23 Gopiya Naik, S., Khatod, D.K., Sharma, M.P.: Sizing and siting of DGin distribution networks for real power loss minimization usinglocation of single as well as multiple DGs. The developedmethodology has been tested on 33-bus and 69-bus testdistribution networks with different values of DG powerfactor. Results obtained by this proposed method showbetter loss reduction as well as voltage prole improvementin the given distribution networks. Further, comparison ofresults for loss reduction with other reported methodsshows the effectiveness of the proposed method.

    6 References

    1 Energy white paper: meeting the energy challenge: Department of tradeand industry, UK (DTI), 2007

    2 Ackermann, T., Andersson, G., Soder, L.: Distributed generation: adenition, Electr. Power Syst. Res., 2001, 57, (3), pp. 195204

    3 Frias, P., Gomez, T., Cossent, R., Rivier, J.: Improvement in currentEuropean network regulation to facilitate the integration of distributedgeneration, Electr. Power Energy Syst., 2009, 31, pp. 445451

    4 Jenkins, N., Allan, R., Crossley, P., Kirschen, D., Strbac, G.: Embeddedgeneration, Institution of Electrical Engineers, London, 2000

    5 Mendez, V.H., Rivier, J., De la Fuente, J.I., et al.: Impact of distributedgeneration on distribution investment deferral, Int. J. Electr. PowerEnergy Syst., 2006, 28, (4), pp. 244252

    6 Federico, J., Gonzalez, V., Lyra, C.: Learning classiers shape reactivepower to decrease losses in power distribution networks. Proc. of IEEEPower Eng. Soc. General Meet., June 2005, vol. 1, pp. 557562

    7 Chiradeja, P., Ramkumar, R.: An approach to quantify the technicalbenets of distributed generation, IEEE Trans. Energy Convers.,2004, 19, (4), pp. 764773

    8 Mendez Quezeda, V.H., Abbad, J.-R., Gomez, T.: Assessment ofenergy distribution losses for increasing penetration of DG, IEEETrans. Power Syst., 2006, 21, (2), pp. 533540

    9 Ochoa, L.F., Harrison, G.P.: Minimizing energy losses: optimalaccommodation and smart operation of renewable DG, IEEE Trans.Power Syst., 2011, 26, (1), pp. 198205

    10 Gozel, T., Hocaoglu, M.H.: An analytical method for the sizing andsiting of distributed generators in radial system, Int. J. Electr. PowerSyst. Res., 2009, 79, (6), pp. 912918

    11 Hedayati, H., Nabaviniaki, S.A., Akbarimazd, A.: A method forplacement of DG units in distribution network, IEEE Trans. PowerDeliv., 2008, 23, (3), pp. 16201628

    12 Atwa, Y.M., EI-Saadany, E.F., Salama, M.M.A., Seethapathy, R.:Optimal renewable resource mix for distribution system energy lossminimization, IEEE Trans. Power Syst., 2010, 25, (1), pp. 360370

    13 Wang, C., Nehir, M.H.: Analytical approaches for optimal placement ofdistributed generation sources in power system, IEEE Trans. PowerSyst., 2004, 19, (4), pp. 20682076

    14 Acharya, N., Mahat, P., Mithulananthan, N.: An analytical approach forDG allocation in primary distribution network, Int. J. Electr. PowerEnergy Syst., 2006, 28, pp. 669678

    15 Hung, D.Q., Mithulananthan, N., Bansal, R.C.: Analytical expressionsfor DG allocation in primary distribution networks, IEEE Trans. EnergyConvers., 2010, 25, (3), pp. 814820

    16 Hung, D.Q., Mithulanathan, N., Bansal, R.C.: Multiple distributedgenerators placement in primary distribution networks for lossreduction, IEEE Trans. Ind. Electron., 2010, 60, (4), pp. 17001708

    17 Mithulanathan, N., Oo, T., Phu, L.V.: Distributed generator placementin power distribution system using genetic algorithm to reduce losses,Thammasat Int. J. Sci. Tech., 2004, 9, (3), pp. 5562

    18 Abu-Mouti, F.S., El-Hawary, M.E.: Optimal distributed generationallocation and sizing in distribution systems using articial bee colonyalgorithm, IEEE Trans. Power Deliv., 2011, 26, (4), pp. 20902101

    19 AlRashidi, M., AlHajri, M.F.: Optimal planning of multiple distributedgeneration sources in distribution networks: a new approach, EnergyConvers. Manage., 2011, 52, pp. 33013308

    20 Khatod, D.K., Pant, V., Sharma, J.: Evolutionary programming based219& The Institution of Engineering and Technology 2015

  • analytical approach. Int. Conf. on Power, Energy, and Control (ICPEC),Dindigul (TN), India, February 2013, pp. 740745

    24 Gandomkar, M., Vakilian, M., Ehsan, M.: A genetic based tabu searchalgorithm for optimal DG allocation in distribution networks, Electr.Power Compon. Syst., 2007, 33, (12), pp. 13511362

    25 Gopiya Naik, S., Khatod, D.K., Sharma, M.P.: Optimal allocation ofdistributed generation in distribution system for loss reduction. Int.Conf. on Product Development and Renewable Energy Resources(ICPDRE), Coimbatore, India, 2012, pp. 4246

    26 Moradi, M.H., Abedini, M.: A combination of genetic algorithm andparticle swarm optimization for optimal DG location and sizing indistribution systems, Int. J. Electr. Power Energy Syst., 2012, 34, (1),pp. 6674

    27 Moradi, M.H., Tousi, M.R., Abedini, M.: Multi-objective PFDEalgorithm for solving the optimal sitting and sizing problem ofmultiple DG sources, Int. J. Electr. Power Energy Syst., 2014, 56,pp. 117126

    28 Kashem, M.A., Le, A.D.T., Negnevitsky, M., Ledwitch, G.: Distributedgeneration for minimization of power losses in distribution systems.Power Engineering Society General Meeting, Montreal, Quebec, 2006,pp. 18

    29 EI-Khattam, W., Bhattacharya, K., Hagazy, Y.G., Salama, M.M.A.:Optimal investment planning for distributed generation in acompetitive electricity market, IEEE Trans. Power Syst., 2004, 19,(3), pp. 16741684

    30 Celli, G., Ghiani, E., Mocci, S., Pilo, F.: A multi-objective evolutionaryalgorithm for siting and sizing of distributed generation, IEEE Trans.Power Syst., 2005, 20, (2), pp. 750757

    31 Willis, H.L.: Analytical methods and rules of thumb for modelingDG-distribution interaction. Proc. IEEE Power Engineering SocietySummer Meeting, 2000, vol. 3, pp. 16431644

    32 Gopiya Naik, S., Khatod, D.K., Sharma, M.P.: Planning and operationof distributed generation in distribution networks, Int. J. Emerg.Technol. Adv. Eng., 2012, 2, (9), pp. 381388

    33 Haque, M.H.: Capacitor placement in radial distribution systems forloss reduction, IEE Proc. Gener. Transm. Distrb., 1996, 146, (5),pp. 501505

    34 Haque, M.H.: Efcient load ow method for distribution systems withradial or mesh conguration, IEE Proc. Gener. Transm. Distrb., 1996,143, (1), pp. 3338

    35 Baran, M.E., Wu, F.F.: Network reconguration in distribution systemsfor loss reduction and load balancing, IEEE Trans. Power Deliv., 1989,4, (2), pp. 14011407

    36 Murthy, V.V.S.N., Kumar, A.: Comparison of optimal DG allocationmethods in radial distribution systems based on sensitivityapproaches, Int. J. Electr. Power Energy Syst., 2013, 53, pp. 450467

    37 Chiang, H.D., Jean-Jumeau, R.: Optimal network recongurations indistribution systems: Part 2: solution algorithms and numericalresults, IEEE Trans. Power Deliv., 1990, 5, (3), pp. 15681574

    www.ietdl.org220& The Institution of Engineering and Technology 2015IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 3, pp. 209220doi: 10.1049/iet-gtd.2014.0603