NO. 2 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: New Concession Stand at Chisholm Trail Middle School CLIENT NAME: Northwest ISD LOCATION: Rhome, Texas PROJECT NUMBER: 1747-00-03 PROPOSAL DATE: Part A: Tuesday, June 13, 2017, 2:00 PM Part B: Thursday, June 15, 2017, 2:00 PM ADDENDUM DATE: Friday, June 09, 2017 For additional information regarding this project, contact Kate Dunfee at 800.687.1229. THIS ADDENDUM INCLUDES: Civil Items 1 Page Landscape Items 0 Pages Structural Items 0 Pages Architectural Items 0 Pages Foodservice Items 0 Pages Plumbing Items 0 Pages Mechanical Items 0 Pages Electrical Items 1 Page Technology Items 0 Pages AND ALL ATTACHED REVISED DRAWING REFERENCES IN THE ADDENDUM 06/09/2017

Upload: others

Post on 18-Dec-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

NO. 2

TO THE DRAWINGS AND THE PROJECT MANUAL

PROJECT NAME: New Concession Stand at Chisholm Trail Middle School

CLIENT NAME: Northwest ISD

LOCATION: Rhome, Texas

PROJECT NUMBER: 1747-00-03

PROPOSAL DATE:

Part A: Tuesday, June 13, 2017, 2:00 PM

Part B: Thursday, June 15, 2017, 2:00 PM

ADDENDUM DATE: Friday, June 09, 2017

For additional information regarding this project, contact Kate Dunfee at 800.687.1229.

THIS ADDENDUM INCLUDES:

Civil Items 1 Page

Landscape Items 0 Pages

Structural Items 0 Pages

Architectural Items 0 Pages

Foodservice Items 0 Pages

Plumbing Items 0 Pages

Mechanical Items 0 Pages

Electrical Items 1 Page

Technology Items 0 Pages

AND ALL ATTACHED REVISED DRAWING REFERENCES IN THE ADDENDUM

06/09/2017

New Concession Stand at Chisholm Trail Middle School Northwest ISD Rhome, Texas 1747-00-03

Civil Items For Addendum No. 2

Page 1 of 1

CIVIL ITEMS FOR ADDENDUM NO. 2 NOTICE TO PROPOSERS:

A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take precedence.

B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.

REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED: PROJECT MANUAL:

AD No 2, Civil Item 1: To the Project Manual, Section 32 84 00, “PLANTING IRRIGATION,” 1) To Section 2.4, “SPECIALTY VALVES,”

To paragraph A, 1., delete the following “as indicated on the drawings” and add “as indicated by owner”. 2) To Section 3.4, “INSTALLATION,”

To paragraph I, delete the following “Install freestanding controllers on precast concrete bases per the drawings” and add “Install freestanding controllers on precast concrete bases if required by a licensed irrigator in the state of Texas”.

AD No 2, Civil Item 2: To the Project Manual, Section 32 84 00, “PLANTING IRRIGATION,” For clarification, no irrigation plans are included in the construction set. The purpose of the specification is to provide additional instruction for irrigation items as deemed necessary by a licensed irrigator in the state of Texas.

AD No 2, Civil Item 3: To the Project Manual, Section 32 92 00, “TURF AND GRASSES,” 1) To Section 3.2, “SOD AND SEED INSTALLATION,”

To paragraph A, delete the following “areas identified on the plans” and add “disturbed areas”. 2) To Section 3.2, “SOD AND SEED INSTALLATION,”

To paragraph C, delete the following “areas identified on the plans” and add “disturbed areas”.

AD No 2, Civil Item 4: To the Project Manual, Section 32 92 00, “TURF AND GRASSES,” For clarification, no landscape plans are included in the construction set. The purpose of the specification is to provide additional instruction for sod and seed establishment for all disturbed areas as shown in the construction set.  END OF CIVIL ADDENDUM

New Concession Stand at Chisholm Trail Middle School

Northwest ISD

Rhome, Texas

1747-00-03

Electrical Items For

Addendum No. 2

Page 1 of 1

ELECTRICAL ITEMS FOR ADDENDUM NO. 2 NOTICE TO PROPOSERS:

A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had

been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary

data differ from those of the original contract documents, this Addendum shall govern and take precedence.

B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this

Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and

supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal

form. Failure to do so may subject Proposer to disqualification.

REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED:

DRAWINGS:

AD No 2, Elec. Item 1: To the Drawings, Sheet EP1.1, “ELECTRICAL FLOOR PLAN,”

1) Reference revised EP1.1 for addition of Panel “L”. Replace sheet in its entirety.

2) Reference Electrical Riser Diagram (Detail 3): Provide cost for new 125 Amp 3-pole breaker in existing switchgear.

END OF ELECTRICAL ADDENDUM

Z:\HUCKABEE\NORTHWEST\1 061 0884 001 CHISHOLM TRAIL MS\01 ADMIN ##\ADDENDA ##\ADDENDUM 2 - ELECTRICAL 1747-00-03.DOCX

ESTES, McCLURE & ASSOCIATES REGISTRATION NO. F-893

4-#6, 1-#8 GRN, 1"C.

PRIMARY SIDE OF XFMR [480 VOLT]

TRANSFORMER GROUNDS

ELECTRICAL RISER NOTES: (SOME NOTES MAY NOT BE USED)

SECONDARY SIDE OF XFMR [208]

500 2-2 1/2"C. WITH 4-#250 MCM, 1-#2 GRN IN EACH

4-#4, 1-#10 GRN, 1 1/2"C.60

15G #8 GRN

45G

75G

30G

#4 GRN

#2 GRN

#6 GRN

3-#1/0, 1-#6 GRN, 1 1/2"C.

3-#6, 1-#10 GRN, 1"C.

3-#10, 1-#10 GRN, 3/4"C.

3-#4, 1-#8 GRN, 1"C.45P

75P

15P

30P80

125

150

100

225

250

200

400

600

300

800

175

3-3"C. WITH 4-#300 MCM, 1-#1/0 GRN IN EACH

2-3"C. WITH 4-#350 MCM, 1-#1 GRN IN EACH

4-#1/0, 1-#6 GRN, 2"C.

4-#1/0, 1-#6 GRN, 2"C.

4-#1, 1-#8 GRN, 1 1/2"C.

4-#3, 1-#8 GRN, 1 1/2"C.

4-#2/0, 1-#6 GRN, 2"C.

4-#3/0, 1-#6 GRN, 2"C.

4-#4/0, 1-#4 GRN, 2 1/2"C.

4-#250, 1-#4 GRN, 2 1/2"C.

4-#350, 1-#4 GRN, 3"C.

2-2"C. WITH 4-#3/0, 1-#3 GRN IN EACH

4-#1/0 AL, 1-#6 CU GRN, 2"C.

4-#350 MCM AL, 1-#2 CU GRN, 3"C.

4-#4/0 AL, 1-#4 CU GRN, 2 1/2"C.

30S

75S

45S

15S

GENERAL RISER NOTES:

WHEREVER THE LENGTH OF THE SECONDARY CONDUCTORS OF ANY

TRANSFORMER EXCEEDS TEN FEET, AN ENCLOSED CIRCUIT BREAKER OR FUSED

DISCONNECT IS REQUIRED TO BE PROVIDED WITHIN TEN FEET OF THE

TRANSFORMER SECONDARY TERMINALS IN ACCORDANCE WITH NEC ARTICLE

240-21(C)(2). THIS OVERCURRENT DEVICE SHALL HAVE AN AMP RATING EQUAL TO

THE AMP RATING OF THE PANEL BEING SERVED. IF THIS OCCURS AND THE PANEL

IS IN THE SAME ROOM, THE PANEL BEING FED MAY BE CHANGED TO MAIN LUG

ONLY.

GENERAL RISER NOTES:

1. WHEREVER THE LENGTH OF THE SECONDARY CONDUCTORS OF ANY

TRANSFORMER EXCEEDS TEN FEET, AN ENCLOSED CIRCUIT BREAKER OR

FUSED DISCONNECT IS REQUIRED TO BE PROVIDED WITHIN TEN FEET OF THE

TRANSFORMER SECONDARY TERMINALS IN ACCORDANCE WITH NEC ARTICLE

240-21(C)(2). THIS OVERCURRENT DEVICE SHALL HAVE AN AMP RATING EQUAL

TO THE AMP RATING OF THE PANEL BEING SERVED. IF THIS OCCURS AND THE

PANEL IS IN THE SAME ROOM, THE PANEL BEING FED MAY BE CHANGED TO

MAIN LUG ONLY.

2. SERVICE ENTRANCE FEEDERS DO NOT REQUIRE AN EQUIPMENT GROUNDING

CONDUCTOR.

3. PROVIDE AND INSTALL BURNDY OR NSI (OR APPROVED EQUIVALENT) UL

RATED COMPRESSION REDUCING PIN TERMINALS ON COPPER / ALUMINUM

CONDUCTORS AS REQUIRED. SEE IMAGE TO THE RIGHT

A

SAMPLE REDUCING PIN TERMINAL

125 A

75S

75G

75P

CONCESSIONS

EXISTING ELEC. ROOM

PANELL

TXLTRANSFORMER

75 KVA

EXISTING MAIN SWITCHGEAR

EF

EF

EF EF EF

EF

5

5

WOMEN

1.06

MEN

1.05

JAN.

1.04

ELEC/MECH

1.03 TICKETS

1.02

CONCESSIONS

1.01

3

3

2

2

222

TXL

5

L- 25

L- 23

L- 25

L- 7 L- 15

L- 17

L- 9

L- 19 L- 21

L- 11

L- 13

L- 7L- 5 L- 3

L- 1

L- 7

L

WOMEN

1.06

MEN

1.05

JAN.

1.04

ELEC/MECH

1.03

TICKETS

1.02

CONCESSIONS

1.01

D

DE D D D

DEDD

DE DEDE

SES

SE

S

S S

S

SED

DE

D

D

DDE

D

K

K

L- 31 L- 31

L- 31

L- 31

L- 31L- 31

L- 31

L- 29

L- 33

UH #108

UH #107

UH #101-B UH #101-A

UH #102UH #103UH #104

EF #107

EF #108

EF #104

EF #102

EF #101

EF #103

L- 27

L- 35

L- 37,39L- 2,4

L- 6,8

L- 10,12

L- 14,16 L- 18,20

L- 22,24

EMA Engineering and ConsultingTyler ▪ Austin ▪ HoustonPhone: 1-800-933-0538TBPE Firm Registration No. F-893www.estesmcclure.com

NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND WORKINGSYSTEM.

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THECONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOBCONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING AND

Sheet No.Job No.

Drawn By:

Date:

Pro

ject

:

Copyright © 2017, Huckabee & Associates, Inc.

C:\

Use

rs\k

lind

ley\

Do

cum

ents

\1 0

61 0

884

001

CH

ISH

OL

M C

ON

CE

SS

ION

ME

PC

CE

NT

RA

L 2

016_

klin

dle

y.rv

t

6/8/

2017

5:1

4:32

PM

Author

EP1.1

ELECTRICAL FLOOR PLAN

05/12/17

1609-23-01

A N

EW

CO

NC

ES

SIO

N S

TAN

DA

T C

HIS

HO

LM T

RA

IL M

IDD

LE S

CH

OO

LFO

RN

OR

THW

ES

T I.S

.D.

RH

OM

E, T

EX

AS

1/8" = 1'-0"1 ELECTRICAL FLOOR PLAN

PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTIPLE CIRCUITS SHALL NOTSHARE A COMMON NEUTRAL. NEUTRAL CONDUCTORS SHALL BE SIZED AS LARGE AS THE PHASECONDUCTORS. NEUTRAL CONDUCTORS SHALL NOT BE OF A REDUCED SIZE.

ALL CONDUIT AND/OR CABLING SHALL BE INSTALLED BETWEEN THE BOTTOM AND TOP CHORD OFJOIST. WHERE NO CEILINGS ARE SCHEDULED, ALL CONDUIT SHALL BE UP AGAINST BOTTOM OF THETOP CHORD.

ROUTE CONDUIT IN EXPOSED AREAS PERPENDICULAR OR PARALLEL TO WALLS. ROUTE CONDUIT ASHIGH AS POSSIBLE AND ROUTE CONDUIT RUNS ADJACENT TO EACH OTHER. CONDUIT SHALL BEORDERLY AND NEAT.

VERIFY ALL INSTALLATION HEIGHTS OF RECEPTACLES WITH ARCHITECTURAL CASEWORK DETAILSBEFORE ROUGH-IN.

DURING THE SUBMITTAL PHASE, THIS CONTRACTOR SHALL SUBMIT LAYOUT OF SWITCHGEAR INEACH EQUIPMENT ROOM WHERE SWITCHGEAR IS LOCATED. ALL SWITCHGEAR LAYOUTS MUST BEDRAWN TO SCALE AND DIMENSIONED.

THE CONTRACTOR AND SUBCONTRACTORS SHALL COORDINATE WITH ALL UTILITY COMPANIES ANDTHE OWNER'S REPRESENTATIVE TO DETERMINE THE LOCATION OF ALL EXISTING LINES ANDUTILITIES BEFORE DITCHING IS PERFORMED. THE CONTRACTOR AND SUBCONTRACTORS SHALL BERESPONSIBLE FOR REPAIR OF ANY CUT OR DAMAGED LINES OR UTILITIES THAT ARE NOT SHOWN ONANY PLANS.

EXACT MECHANICAL EQUIPMENT LOCATIONS AND TYPE SHALL BE COORDINATED WITH MECHANICALPLANS AND MECHANICAL CONTRACTOR. DO NOT INSTALL CONDUIT/CABLING WITHIN 3'-0" OF ANYHVAC UNIT UNLESS THE CONDUIT AND/OR CABLING SERVES THAT UNIT.

UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS, PROVIDE A LISTEDMANUAL MOTOR-CIRCUIT SWITCH AS A DISCONNECTING MEANS AT EACH MOTOR. FOR MOTORSSHOWN WITH "MS" PROVIDE A LISTED MANUAL MOTOR -CIRCUIT SWITCH WITH OVERLOADPROTECTION AS A DISCONNECTING MEANS AT EACH MOTOR.

SEE EXHAUST FAN SCHEDULE ON MECHANICAL SHEET FOR EXHAUST FAN SWITCHING, UNLESSCONTROLS ARE SPECIFICALLY NOTED ON THE DRAWINGS. WHERE "EMCS" IS MENTIONED , PROVIDEMECHANICALLY-HELD CONTACTORS AS NECESSARY FOR FAN CONTROL. COORDINATE CONTACTORCOIL ELECTRICAL REQUIREMENTS WITH MECHANICAL CONTROLS CONTRACTOR. WHERE "24/7" ISMENTIONED, PROVIDE A MOTOR-RATED SWITCH AT THE MOTOR ONLY. WHERE "SWITCH"ISMENTIONED, DO ONE OF THE FOLLOWING:

• IN KITCHEN, TIE ALL HOOD SUPPLY AND EXHAUST FANS TO HOOD CONTROLS. PROVIDE SWITCHES ASNECESSARY AT HOOD. FOR MORE INFORMATION, SEE KITCHEN HOOD DETAIL.

COORDINATE CONDUIT ROOF PENETRATIONS WITH MECHANICAL ROOF TOP UNITS AND/OR THRUHOODED PLUMBING PENETRATIONS TO CONDENSING UNITS.

REFER TO MECHANICAL DRAWINGS FOR SENSOR LOCATIONS. PROVIDE CONDUIT AND BOXES FORSENSORS. REFER TO SENSOR INSTALLATION DETAIL.

EXACT LOCATION OF ALL OUTLETS, DEVICES, & ETC. INSTALLED IN MOVEABLE FURNITURE SHALL BECOORDINATED WITH ARCHITECT AND OWNER.

REFER TO ELECTRICAL COMMUNICATION DRAWINGS FOR GENERAL LOCATION OF CONDUIT ANDBOXES SUPPLIED BY THIS CONTRACTOR IN BASE BID.

TAMPER RESISTANT RECEPTACLES SHALL BE PROVIDED IN ALL SPACES ACCESSIBLE TO STUDENTSIN THIRD GRADE AND BELOW.

ALL VARIABLE FREQUENCY DRIVES (VFD's) ARE TO BE PROVIDED BY THE MECHANICAL CONTRACTOR,INSTALLED AND POWERED BY THE ELECTRICAL CONTRACTOR, AND CONTROLLED BY THE CONTROLSCONTRACTOR.

FOR ALL UNITS WITH PLASMA AIR IONIZATION DEVICE. PROVIDE CONTROL WIRING AS REQUIRED BYMANUFACTURER FROM 24 VAC FAN CONTROL TERMINALS TO 24 VAC POWER INPUT TERMINALS ONIONIZATION DEVICE.

FOR ALL UNITS WITH VFD's. CIRCUIT TO VFD, THEN CONNECT VFD TO HVAC UNIT.

REFER TO THE MECHANICAL SHEETS FOR ALL LOCATIONS FOR THERMOSTATS, DUCT DETECTORS,CONTROL RELAYS, MOTORIZED DAMPERS, SFD'S,ETC. IT IS THE RESPONSIBILITY OF THISCONTRACTOR TO PROVIDE ALL NECESSARY CONDUIT, BACK BOXES AND LINE VOLTAGE WIRING TOTHESE DEVICES AS REQUIRED IN THE SPECIFICATIONS.

WEATHERPROOF GFCI MAINTENANCE OUTLET MOUNTED BELOW DISCONNECT.

OUTLET INSTALLED 6" ABOVE MILLWORK SPLASH. VERIFY EXACT LOCATION WITH ARCHITECTURALDRAWINGS.

EWC OUTLET INSTALLED 20" A.F.F. - ON GFCI BREAKER.

GFCI OUTLET INSTALLED 18" A.F.F.

WEATHERPROOF GFCI MAINTENANCE OUTLET 18" A.F.F.

GFCI OUTLET INSTALLED 44" A.F.F.

PROVIDE NEW 125A BREAKER.

1

2

3

4

5

6

ELECTRICAL PLAN NOTES(SOME NOTES MAY NOT BE USED)

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

ELECTRICAL GENERAL NOTES(SOME NOTES MAY NOT BE USED)

1/8" = 1'-0"4 LIGHTING FLOOR PLAN

LIGHTING GENERAL NOTES(SOME NOTES MAY NOT BE USED)

ALL LUMINAIRES ARE TO BE TYPE "D" UNLESS OTHERWISE NOTED.

VERIFY ALL CEILING HEIGHTS AND TYPES WITH ARCHITECTURAL DRAWINGS BEFORE PROVIDINGLUMINAIRES AND WIRING.

REFER TO SPECIFICATIONS, LUMINAIRE SCHEDULE, LUMINAIRE CONTROLS DETAIL, SWITCHFUNCTION DETAIL AND LIGHTING CONTROL CHART FOR ADDITIONAL REQUIREMENTS AND MOREINFORMATION.

WHERE THE CEILING IS MORE THAN THREE FEET BELOW THE BOTTOM CHORD OF THE JOIST, ALLCONDUIT AND CABLING SHALL BE INSTALLED ON A TRAPEZE SUPPORT AS SHOWN ON THE DETAILS.WHERE THE CEILING IS LESS THAN THREE FEET BELOW THE BOTTOM CHORD, ALL CONDUIT ANDCABLING SHALL BE INSTALLED ABOVE THE BOTTOM CHORD OF THE JOIST. WHERE NO CEILING ISSCHEDULED, ALL CONDUIT AND CABLING SHALL BE INSTALLED NEAR THE DECK MAINTAINING NECCLEARANCE.

CONTROL ALL EXTERIOR LUMINAIRES BY THE EXISTING ENERGY MANAGEMENT CONTROL SYSTEM,AS SPECIFIED. THIS CONTRACTOR SHALL PROVIDE ALL MECHANICALLY HELD LIGHTINGCONTACTORS, REMOTE CONTROL RELAYS, AND WIRING TO EMCS.

SEE RECESSED, LAY-IN TYPE, LUMINAIRE SUPPORT DETAIL FOR LIGHTING SUPPORT.

ROUTE CONDUIT IN EXPOSED AREAS PERPENDICULAR OR PARALLEL TO WALLS. ROUTE CONDUITAS HIGH AS POSSIBLE AND ROUTE CONDUIT RUNS ADJACENT TO EACH OTHER. CONDUIT SHALL BEORDERLY AND NEAT.

1.

2.

3.

4.

5.

6.

7.

WH

SR

PS

XFR

NOTES:

1. SOME SYMBOLS MAY NOT BE USED.

2. ACCESSIBLE DEVICES HIGHEST OPERABLE PART TO BE 46" MAXIMUM/18" MINIMUM A.F.F. - REFER TO ARCHITECTURAL DRAWINGS.

3. DIMENSIONS GIVEN A.F.F. ARE TO BOTTOM OF BOX.

S

B

AV

C

W

G

J

M

EF

SF

P

DCR

SFD

T

PB

CL-1

MULTI-POLE RECEPTACLE - 18" A.F.F. OR AS NOTED

MULTI-POLE RECEPTACLE - 208V 1∅ 30A ISOLATED GROUND HUBBELL TWIST-LOCK #IG2620 RECEPTACLE OR EQUAL - 18" A.F.F. OR AS NOTED

DUPLEX RECEPTACLE - 18" A.F.F. OR AS NOTED

EXISTING RECEPTACLE

DUPLEX RECEPTACLE WITH ISOLATED GROUND RECEPTACLE - 18" A.F.F. OR AS NOTED

QUAD RECEPTACLE - 18" A.F.F. OR AS NOTED

QUAD RECEPTACLE WITH ISOLATED GROUND - 18" A.F.F. OR AS NOTED

GFCI DUPLEX RECEPTACLE - 6" ABOVE MILLWORK BACKSPLASH IF SHOWN ON MILLWORK OR 18" A.F.F. - VERIFY MILLWORK LOACTION WITH ARCHITECT.

DUPLEX FLOOR RECEPTACLE WITH BRASS COVER PLATE - 3/4"C. TO ACCESSIBLE ATTIC SPACE OR AS NOTED

WIREMOLD POKE-THRU EVOLUTION 8AT OR EQUIVALENT W/ COMM. AS NOTED & 3 DUPLEX OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

WIREMOLD POKE-THRU EVOLUTION 8AT OR EQUIVALENT W/ COMM. AS NOTED & 3 DUPLEX ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

PROVIDE RFB2 OR EQUIVALENT W/COMM. AS NOTED & 1 ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

PROVIDE RFB4 OR EQUIVALENT W/COMM. AS NOTED & 2 ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

PROVIDE RFB6 OR EQUIVALENT W/COMM. AS NOTED & 3 ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

PROVIDE RFB9 OR EQUIVALENT W/COMM. AS NOTED & 6 ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

PROVIDE RFB11 OR EQUIVALENT W/COMM. AS NOTED & 7 ISO. GRN OUTLETS. REFER TO SPECS FOR CONDUIT SIZE AND QUANTITY.

4-GANG BACK BOX WITH DIVIDERS FOR POWER AND COMMUNICATIONS INCLUDE DEVICES AND COVERS-WIREMOLD WSA SERIES

6-GANG BACK BOX WITH DIVIDERS FOR POWER AND COMMUNICATIONS INCLUDE DEVICES AND COVERS-WIREMOLD WSA SERIES

POWER/COMMUNICATION POLE - FURNISH REQUIRED LENGTH TO PENETRATE CEILING

SURFACE MOUNTED RACEWAY

MECHANICALLY HELD CONTACTOR - ABOVE CEILING

WATER SOLENOID ACTUATOR - ABOVE CEILING - VERIFY & COORDINATE WITH PLUMBING DRAWINGS

GAS SOLENOID ACTUATOR - ON ROOF - VERIFY & COORDINATE WITH PLUMBING DRAWINGS

PUSH BUTTON EMERGENCY SHUT-OFF - REFER TO SPECIFICATIONS FOR MORE INFORMATION

THERMOSTAT, CO2 SENSOR, HUMIDITY SENSOR - SEE SENSOR MOUNTING DETAIL FOR MOUNTING HEIGHT AND ADDITIONAL REQUIREMENTS

JUNCTION BOX - 18" A.F.F. - 3/4"C. TO CORRIDOR ATTIC SPACE OR AS NOTED

PLUMBING SENSORS POWER - CONNECT TO MECHANICAL/PLUMBING TRANSFORMER(S)

AUDIO/VISUAL POWER OUTLET - CEILING OR WALL MOUNTED, SEE COMMUNICATIONS DETAILS

CLOCK RECEPTACLE - 1'-0" BELOW CEILING OR 8'-0" A.F.F.

PUMP MOTOR - PROVIDED BY MECHANICAL OR AS NOTED WITH MOTOR SWITCH WITH OVERLOAD SQ.D. CLASS 2510 IN NEMA ENCLOSURE (TYPE K) OR AS NOTED

SUPPLY FAN - PROVIDED BY MECHANICAL OR AS NOTED WITH MOTOR SWITCH WITH OVERLOAD SQ.D. CLASS 2510 IN NEMA ENCLOSURE (TYPE K) OR AS NOTED

EXHAUST FAN - PROVIDED BY MECHANICAL OR AS NOTED WITH MOTOR SWITCH WITH OVERLOAD SQ.D. CLASS 2510 IN NEMA ENCLOSURE (TYPE K) OR AS NOTED

MOTOR WITH MOTOR SWITCH WITH OVERLOAD SQ.D. CLASS 2510 IN NEMA ENCLOSURE (TYPE K) OR AS NOTED- FINAL CONNECTION BY ELECTRICAL

SAFETY SWITCH - MOUNT 30" ABOVE FINISH GRADE MAX. OR AS DIRECTED

SURFACE MOUNT EQUIPMENT PANEL, RACK, CABINET, AMPLIFIER, ETC. AS NOTED.

FLUSH MOUNT EQUIPMENT PANEL, RACK, CABINET, AMPLIFIER, ETC. AS NOTED.

WATER HEATER - REFER TO PLUMBING FOR MORE INFORMATION

WEATHERHEAD

IN-GRADE PULL BOX/HAND HOLE - PROVIDE AS REQUIRED

FIRE SAFETY CONTROL DEVICE - FIRE ALARM TO SMOKE/FIRE BARRIER DOOR ELECTROMAGNETIC HOLDER/RELEASE INTERFACE

FIRE SAFETY CONTROL DEVICES - CONTROL RELAY AND DUCT MOUNTED SMOKE DETECTOR WITH CONTROL RELAY

FIRE SAFETY CONTROL DEVICE - MOTORIZED SMOKE/FIRE DAMPER - POWER CONNECTION BY DIVISION 16

BUZZER - EDWARDS #156G-6G1 80"A.F.F.

PUSH BUTTON - EDWARDS #695-W 44"A.F.F.

SIGNAL TRANSFORMER - EDWARDS #591 IN J-BOX ABOVE CEILING

PANELBOARD OR SWITCHBOARD - REFER TO SCHEDULE & RISER

POWER TRANSFORMER - DESCRIBED IN SCHEDULE, RISER AND/OR SPECIFICATIONS

GROUND

HOME RUN WITH CIRCUIT DESIGNATION(S) - LETTER DENOTES PANEL

SWITCH CIRCUIT

BRANCH CIRCUIT

UNDERGROUND POWER CIRCUIT

T C2 H

ELECTRICAL POWER SYMBOLS

2

4

6

9

11

. .

EMERGENCY FLUORESCENT LUMINAIRE - GENERATOR OPERATED - EMERGENCY/NIGHT LIGHT

NOTES:

1. SOME SYMBOLS MAY NOT BE USED.

2. ACCESSIBLE DEVICES HIGHEST OPERABLE PART TO BE 46" MAXIMUM/18" MINIMUM A.F.F. - REFER TO

ARCHITECTURAL DRAWINGS.

3. DIMENSIONS GIVEN A.F.F. ARE TO BOTTOM OF BOX.

S SS

SSS

S

S S S S

S

S

HOME RUN WITH CIRCUIT DESIGNATION(S) - LETTER DENOTES PANEL

BRANCH CIRCUIT

SWITCH CIRCUIT

UNDERGROUND POWER CIRCUIT

CL-1

LUMINAIRE - RECESSED/SURFACE OR PENDANT MTD - SEE LUMINAIRE SCHEDULE & SPECS - LETTER INDICATES TYPE

EMERGENCY LUMINAIRE - BATTERY OPERATED/WALL MOUNTED/NOT SWITCHED, 7'-6" A.F.F.

EMERGENCY FLUORESCENT LUMINAIRE - NOT SWITCHED, BATTERY OPERATED - NIGHT LIGHT

SWITCH - 20A. KEY OPERATED - 44" A.F.F.- PROVIDE 12 EXTRA KEYS FOR OWNER

SWITCH - 20A. SINGLE POLE, 2 POLE, 3-WAY, 4-WAY - 44" A.F.F. UNLESS NOTED

FLUORESCENT LUMINAIRE-RECESSED/SURFACE OR PENDANT MTD-SEE LUMINAIRE SCHEDULE & SPECS- LETTER INDICATES TYPE

ILLUMINATED EXIT SIGN - SWITCHABLE, BATTERY OPERATED

EMERGENCY FLUORESCENT LUMINAIRE - SWITCHABLE, BATTERY OPERATED

PROGRAMMABLE LOW VOLTAGE SWITCHES (1-4 PER GANG)

PROGRAMMABLE LOW VOLTAGE DIMMER SWITCH

DAYLIGHT SENSOR

LIGHTING SYMBOLS

EXTERIOR LUMINAIRE

CUSTOM LEVITON SWITCH MADE FOR SIMPLY 5 DIMMING SYSTEM

DIMMER SWITCH - LEVITON ILLUMATECH IP SERIES SLIDE DIMMER W/ POWER EXTENDER AS REQUIRED - 44" A.F.F.

DAYLIGHTING ZONE - REFER TO DAYLIGHTING ZONE CONTROL DIAGRAM ON DETAIL SHEETS.

EXISTING EMERGENCY FLUORESCENT LUMINAIRE - SWITCHABLE, BATTERY OPERATED

EXISTING EMERGENCY LUMINAIRE - BATTERY OPERATED/WALL MOUNTED/NOT SWITCHED, 7'-6" A.F.F.

EXISTING ILLUMINATED EXIT SIGN - SWITCHABLE, BATTERY OPERATED

MOTION SENSOR - REFER TO SPECS FOR QUANTITY, LOCATION, TYPE, COMMISSIONING, ETC.

EXISTING LUMINAIRE - RECESSED/SURFACE OR PENDANT MTD - LETTER INDICATES TYPE

EXISTING FLUORESCENT LUMINAIRE - RECESSED/SURFACE OR PENDANT MTD - LETTER INDICATES TYPE

2K

D

43

3K 4K

2

P1 P2 P3 P4

PD

L

. .

1/8" = 1'-0"3 ELECTRICAL RISER DIAGRAM

1/8" = 1'-0"2 ELECTRICAL HVAC PLAN

Rev

isio

n /

Dat

e

16/8

/2017

Bid

Questions

7

7

Legend:

Total Amps: 127 A 124 A 99 A

Total Div Load: 14780 VA 14515 VA 11897 VA

41 42

39 -- -- -- -- 24 A 0 A -- -- -- SPACE 40

37 Unit Heater - 5kw 2 35 A #12,#12G 24 A 0 A -- -- -- SPACE 38

35 MOTORS 1 20 A #12,#12G 2 A 0 A -- -- -- SPACE 36

33 INTERIOR LIGHTING 1 20 A #12,#12G 2 A 0 A -- -- -- SPACE 34

31 EXTERIOR THRU CONTACTOR 1 20 A #12,#12G 1 A 0 A -- 20 A 1 SPARE 32

29 INTERIOR LIGHTING 1 20 A #12,#12G 3 A 0 A -- 20 A 1 SPARE 30

27 MOTORS 1 20 A #12,#12G 6 A 0 A -- 20 A 1 SPARE 28

25 GFCI Outlets 1 20 A #12,#12G 3 A 0 A -- 20 A 1 SPARE 26

23 GP Outlets 1 20 A #12,#12G 3 A 24 A -- -- -- -- 24

21 GFCI Outlets 1 20 A #12,#12G 2 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 22

19 GFCI Outlets 1 20 A #12,#12G 2 A 24 A -- -- -- -- 20

17 GFCI Outlets 1 20 A #12,#12G 2 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 18

15 GFCI Outlets 1 20 A #12,#12G 2 A 24 A -- -- -- -- 16

13 GFCI Outlets 1 20 A #12,#12G 3 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 14

11 GFCI Outlets 1 20 A #12,#12G 3 A 24 A -- -- -- -- 12

9 GFCI Outlets 1 20 A #12,#12G 3 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 10

7 GFCI Outlets 1 20 A #12,#12G 5 A 24 A -- -- -- -- 8

5 GFCI Outlets 1 20 A #12,#12G 3 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 6

3 GFCI Outlets 1 20 A #12,#12G 3 A 24 A -- -- -- -- 4

1 GFCI Outlets 1 20 A #12,#12G 6 A 24 A #12,#12G 35 A 2 Unit Heater - 5kw 2

ck# Load Pole Trip Wire A B C Wire Trip Pole Load ck#

See Riser Diagram for feeder info.

Notes:

Fed From - TXL Service - 120/208 3ph 4w Branch AIC - 25,000 kAIC

Mount - Surface / NEMA 1Panel - L Bus - 250 A / Main Bkr - 250AIn Room - ELEC/MECH 1.03

1