 1 Product Overview DC Power Distributor 6 (DCPD6) has the f ollowing function s: 1) Provides one channel o f -48V DC power inpu t and supports a current of no t more than 100A; 2) Provides nine channels o f DC power output, e ach of which is cont rolled by a n indepe ndent hydraulic breaker to support a current of not m ore than 20A; 3) Provides lightn ing protectio n and surge pro tection for the power output th rough a built-in lightning protection board; 4) Provides dry contact alarm ou tput on the lightn ing protection board. Figure 1-1 DCPD6 Ports 2 Specifications The specifications of DCPD6 are described in Table 2-1. Table 2-1 DCPD6 Specificat ions Characteristics Specifications Model DCPD6 Name DC Power Distributor 6 Description 9 channels of -48V DC power output, with output lightning protection; 19 inch cabinet installation; front cabling  Dimension (W*H*D) mm 482.6X43.6X197 (19inch / 1U) Weight <5kg Surge 10KA (8//20us) for wire-wire connections; 15KA (8//20us) for wire-earth connections Dry contact definition A closed circuit indicates that the lightning protection module is normal. An open circuit indicates that the lightning protection module fails. DC Power Distributor 6 (DCPD6) Product Manual (V1.0)

Upload: giuseppenapolitano

Post on 06-Jan-2016

134 views

Category:

Documents


33 download

DESCRIPTION

Manual para equipos de telecomunicaciones

TRANSCRIPT

Page 1: 06 DCPD6 Product Manual_V1.01

7/17/2019 06 DCPD6 Product Manual_V1.01

http://slidepdf.com/reader/full/06-dcpd6-product-manualv101 1/2

Page 2: 06 DCPD6 Product Manual_V1.01

7/17/2019 06 DCPD6 Product Manual_V1.01

http://slidepdf.com/reader/full/06-dcpd6-product-manualv101 2/2

 

Waterproof/dustproof level IP20

Operating temperature -20 ~55  

Storage temperature -40 ~70  

Relative humidity 5%-95%

3 Typical Application

DCPD6 applies to distributed base station systems, in which it powers BBU and RRU. The power

cable of RRU should be shielded and the shielded layer must be connected to the outdoor

grounding bar before being connected into the cabinet or equipment room.

Figure 3-1 DCPD6 Power Distribution 

DCPD6 Power Distribution

 

The shielded layer

of RRUs power

cable must be

grounded.

DC Power input

Indoor 

Outdoor