Office of Nuclear Reactor Regulation Division of Systems Safety and Analysis Plant Systems Branch Fire Protection Engineering and Special Projects Section 1 CHAPTER 5. ESTIMATING RADIANT HEAT FLUX FROM FIRE TO A TARGET FUEL AT GROUND LEVEL UNDER WIND-FREE CONDITION POINT SOURCE RADIATION MODEL Version 1805.0 The following calculations estimate the radiative heat flux from a pool fire to a target fuel. The purpose of this calculation is to estimate the radiation transmitted from a burning fuel array to a target fuel positioned some distance from the fire at ground level to determine if secondary ignitions are likely with no wind. Parameters in YELLOW CELLS are Entered by the User. Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Fuel Selected. All subsequent output values are calculated by the spreadsheet and based on values specified in the input parameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s). The chapter in the NUREG should be read before an analysis is made. INPUT PARAMETERS Mass Burning Rate of Fuel (m") 0.033 0 28000 kJ/kg 2.6 Heat Release Rate (Q) 719.75 kW 9.00 0.84 Distance between Fire and Target (L) 10.00 ft 3.048 m 0.30 OPTIONAL CALCULATION FOR GIVEN HEAT RELEASE RATE Select "User Specified Value" from Fuel Type Menu and Enter Your HRR here → kW Calculate THERMAL PROPERTIES DATA BURNING RATE DATA FOR FUELS Fuel Mass Burning RatHeat of Combustion Select Fuel Type Methanol 0.017 20,000 100 Ethanol 0.015 26,800 100 Butane 0.078 45,700 2.7 Benzene 0.085 40,100 2.7 Hexane 0.074 44,700 1.9 Heptane 0.101 44,600 1.1 Xylene 0.09 40,800 1.4 Acetone 0.041 25,800 1.9 Dioxane 0.018 26,200 5.4 Diethy Ether 0.085 34,200 0.7 Benzine 0.048 44,700 3.6 Gasoline 0.055 43,700 2.1 Kerosine 0.039 43,200 3.5 Diesel 0.045 44,400 2.1 JP-4 0.051 43,500 3.6 JP-5 0.054 43,000 1.6 Transformer Oil, Hydrocar 0.039 46,000 0.7 561 Silicon Transformer F 0.005 28,100 100 Fuel Oil, Heavy 0.035 39,700 1.7 Crude Oil 0.0335 42,600 2.8 Lube Oil 0.039 46,000 0.7 Douglas Fir Plywood 0.01082 10,900 100 coal 0.033 28,000 2.6 ESTIMATING RADIATIVE HEAT FLUX TO A TARGET FUEL POINT SOURCE RADIATION MODEL Where Q = pool fire heat release rate (kW) Pool Fire Diameter Calculation Where D = pool fire diamter (m) D = 1.03 m Heat Release Rate Calculation Where Q = pool fire heat release rate (kW) kg/m 2 -sec Effective Heat of Combustion of Fuel (DHc,eff) Empirical Constant (kb) m -1 Fuel Area or Dike Area (Adike) ft 2 m 2 Radiative Fraction (cr) Empirical Constant m" (kg/m 2 -sec) DHc,eff (kJ/kg) kb (m -1 ) Scroll to desired fuel type then Click on selection Reference: SFPE Handbook of Fire Protection Engineering, 3 rd Edition, 2002, Page 3-26. Reference: SFPE Handbook of Fire Protection Engineering, 3 rd Edition, 2002, Page 3-272. q" = Q cr / 4 p R 2 q" = incident radiative heat flux on the target (kW/m 2 ) cr = radiative fraction R = distance from center of the pool fire to edge of the target (m) Adike = pD 2 /4 D = √(4Adike/p) Adike = surface area of pool fire (m 2 ) Q = m"DHc,eff (1 - e -kb D ) Af m" = mass burning rate of fuel per unit surface area (kg/m 2 -sec) DHc = effective heat of combustion of fuel (kJ/kg) Af = surface area of pool fire (area involved in vaporization) (m 2 )

Upload: vignesh

Post on 27-Oct-2015

94 views

Category:

Documents


12 download

DESCRIPTION

therrmal calculation

TRANSCRIPT

Page 1: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

1

CHAPTER 5. ESTIMATING RADIANT HEAT FLUX FROM FIRE TO A TARGETFUEL AT GROUND LEVEL UNDER WIND-FREE CONDITION POINT SOURCE RADIATION MODELVersion 1805.0The following calculations estimate the radiative heat flux from a pool fire to a target fuel.The purpose of this calculation is to estimate the radiation transmitted from a burning fuel array to a targetfuel positioned some distance from the fire at ground level to determine if secondary ignitions are likely with no wind.Parameters in YELLOW CELLS are Entered by the User.Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Fuel Selected.All subsequent output values are calculated by the spreadsheet and based on values specified in the inputparameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s).The chapter in the NUREG should be read before an analysis is made.

INPUT PARAMETERS

Mass Burning Rate of Fuel (m") 0.033

0 28000 kJ/kg

2.6Heat Release Rate (Q) 719.75 kW

9.00 0.84

Distance between Fire and Target (L) 10.00 ft 3.048 m

0.30

OPTIONAL CALCULATION FOR GIVEN HEAT RELEASE RATESelect "User Specified Value" from Fuel Type Menu and Enter Your HRR here → kW

Calculate

THERMAL PROPERTIES DATA

BURNING RATE DATA FOR FUELS

FuelMass Burning Rate Heat of Combustion Empirical Constant Select Fuel Type

Methanol 0.017 20,000 100

Ethanol 0.015 26,800 100Butane 0.078 45,700 2.7Benzene 0.085 40,100 2.7Hexane 0.074 44,700 1.9Heptane 0.101 44,600 1.1

Xylene 0.09 40,800 1.4Acetone 0.041 25,800 1.9Dioxane 0.018 26,200 5.4Diethy Ether 0.085 34,200 0.7Benzine 0.048 44,700 3.6Gasoline 0.055 43,700 2.1Kerosine 0.039 43,200 3.5Diesel 0.045 44,400 2.1JP-4 0.051 43,500 3.6JP-5 0.054 43,000 1.6Transformer Oil, Hydrocarbon 0.039 46,000 0.7561 Silicon Transformer Fluid 0.005 28,100 100Fuel Oil, Heavy 0.035 39,700 1.7Crude Oil 0.0335 42,600 2.8Lube Oil 0.039 46,000 0.7Douglas Fir Plywood 0.01082 10,900 100coal 0.033 28,000 2.6

ESTIMATING RADIATIVE HEAT FLUX TO A TARGET FUEL

POINT SOURCE RADIATION MODEL

WhereQ = pool fire heat release rate (kW)

Pool Fire Diameter Calculation

WhereD = pool fire diamter (m)

D = 1.03 m

kg/m2-sec

Effective Heat of Combustion of Fuel (DHc,eff)Empirical Constant (kb) m-1

Fuel Area or Dike Area (Adike) ft2 m2

Radiative Fraction (cr)

m" (kg/m2-sec) DHc,eff (kJ/kg) kb (m-1)Scroll to desired fuel type then

Click on selection

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-26.

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-272.

q" = Q cr / 4 p R2

q" = incident radiative heat flux on the target (kW/m2)

cr = radiative fraction

R = distance from center of the pool fire to edge of the target (m)

Adike = pD2/4

D = √(4Adike/p)

Adike = surface area of pool fire (m2)

F22
This default value (0.30) is the most appropriate value for the majority of analyses. You may change this value for your specific application. If you change this value please ensure that it is appropriate.
Page 2: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

2

Heat Release Rate Calculation

Where Q = pool fire heat release rate (kW)

D = diameter of pool fire (diameter involved in vaporization, circular pool is assumed) (m)

Q = 719.75 kW

Distance from Center of the Fire to Edge of the Target Calculation

R = L+D/2

Where

L = distance between pool fire and target (m)

D = pool fire diameter (m)

R = 3.56 m

Radiative Heat Flux Calculation

q" = 1.35 0.12

The above calculations are based on principles developed in the SFPE Handbook of Fire Protection

Calculations are based on certain assumptions and have inherent limitations. The results of suchcalculations may or may not have reasonable predictive capabilities for a given situation, andshould only be interpreted by an informed user.Although each calculation in the spreadsheet has been verified with the results of hand calculation,there is no absolute guarantee of the accuracy of these calculations.Any questions, comments, concerns, and suggestions, or to report an error(s) in the spreadsheet,please send an email to [email protected] or [email protected].

Prepared by: Date Organization

Checked by: Date Organization

Additional Information

Revision Log Description of Revision Date

1805.0 Original issue with final text. January 2005

Q = m"DHc,eff (1 - e-kb D) Af

m" = mass burning rate of fuel per unit surface area (kg/m2-sec)

DHc = effective heat of combustion of fuel (kJ/kg)

Af = surface area of pool fire (area involved in vaporization) (m2)

kb = empirical constant (m-1)

R = distance from center of the pool fire to edge of the target (m)

q" = Q cr / 4 p R2

kW/m2 Btu/ft2-sec

Engineering, 3rd Edition, 2002.

Answer

NOTE

Page 3: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

3

Page 4: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

4

CHAPTER 5. ESTIMATING RADIANT HEAT FLUX FROM FIRE TO A TARGETFUEL AT GROUND LEVEL UNDER WIND-FREE CONDITIONSOLID FLAME RADIATION MODELVersion 1805.0 The following calculations estimate the radiative heat flux from a pool fire to a target fuel.The purpose of this calculation is to estimate the radiation transmitted from a burning fuel array to a targetfuel positioned some distance from the fire at ground level to determine if secondary ignitions are likely with no wind. Parameters in YELLOW CELLS are Entered by the User.Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Fuel Selected.All subsequent output values are calculated by the spreadsheet and based on values specified in the inputparameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s).The chapter in the NUREG should be read before an analysis is made.

INPUT PARAMETERS

Mass Burning Rate of Fuel (m") 0.039

0 46000 kJ/kg

0.7Heat Release Rate (Q) 771.52 kW

9.00 0.84

Distance between Fire and Target (L) 10.00 ft 3.048 m

OPTIONAL CALCULATION FOR GIVEN HEAT RELEASE RATESelect "User Specified Value" from Fuel Type Menu and Enter Your HRR here → kW

Calculate

THERMAL PROPERTIES DATA BURNING RATE DATA FOR FUELS

Fuel Mass Burning Rate Heat of Combustion Select Fuel Type

Methanol 0.017 20,000 100

Ethanol 0.015 26,800 100Butane 0.078 45,700 2.7Benzene 0.085 40,100 2.7Hexane 0.074 44,700 1.9Heptane 0.101 44,600 1.1Xylene 0.09 40,800 1.4Acetone 0.041 25,800 1.9Dioxane 0.018 26,200 5.4Diethy Ether 0.085 34,200 0.7Benzine 0.048 44,700 3.6Gasoline 0.055 43,700 2.1Kerosine 0.039 43,200 3.5Diesel 0.045 44,400 2.1JP-4 0.051 43,500 3.6JP-5 0.054 43,000 1.6Transformer Oil, Hydrocarbon 0.039 46,000 0.7561 Silicon Transformer Fluid 0.005 28,100 100Fuel Oil, Heavy 0.035 39,700 1.7Crude Oil 0.0335 42,600 2.8Lube Oil 0.039 46,000 0.7Douglas Fir Plywood 0.01082 10,900 100User Specified Value Enter Value Enter Value Enter Value

ESTIMATING RADIATIVE HEAT FLUX TO A TARGET FUEL

SOLID FLAME RADIATION MODEL

Where

Pool Fire Diameter Calculation

WhereD = pool fire diamter (m)

D = 1.03 m Emissive Power Calculation

E =

WhereD = diameter of the pool fire (m)

E = 56.88 View Factor Calculation

A =

B = S = 2R/D

h =

Where

R = distance from center of the pool fire to edge of the target (m)

D = pool fire diameter (m)

Distance from Center of the Pool Fire to Edge of the Target Calculation

kg/m2-sec

Effective Heat of Combustion of Fuel (DHc,eff)Empirical Constant (kb) m-1

Fuel Area or Dike Area (Adike) ft2 m2

Empirical Constant

m" (kg/m2-sec) DHc,eff (kJ/kg) kb (m-1)Scroll to desired fuel type then

Click on selection

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-26.

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-276.

q" = EF1->2

q" = incident radiative heat flux on the target (kW/m2)

E = emissive power of the pool fire flame (kW/m2)

F1->2 = view factor between target and the flame

Adike = pD2/4

D = √(4Adike/p)

Adike = surface area of pool fire (m2)

58 (10-0.00823 D)

E = emissive power of the pool fire flame (kW/m2)

kW/m2

F1->2,H = (B-1/S)/p(B2-1)1/2 tan-1 ((B+1) (S-1)/(B-1)(S+1))1/2-(A-1/S)/(p(A2-1)1/2) tan-1 ((A+1)(S-1)/(A-1)(S+1))1/2

F1->2,V = 1/(pS) tan-1(h/(S2-1)1/2)-(h/pS) tan-1 ((S-1)/(S+1))1/2 + Ah/pS(A2-1)1/2 tan-1 ((A+1)(S-1)/(A-1)(S+1))1/2

(h2+S2+1)/2S

(1+S2)/2S

2Hf/D

F1->2,max = √(F21->2,H + F2

1->2,V)

F1->2,H = horizontal view factor

F1->2,V = vertical view factor

F1->2,max = maximum view factor

Hf = height of the pool fire flame (m)

Page 5: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

5

R = L + D/2

Where

L = distance between pool fire and target (m)

D = pool fire diameter (m)R = L + D/2 = 3.564 m

Heat Release Rate Calculation

Where Q = pool fire heat release rate (kW)

D = diameter of pool fire (diameter involved in vaporization, circular pool is assumed) (m)Q = 771.52 kW

Pool Fire Flame Height Calculation

Where

Q = heat release rate of fire (kW)

D = fire diameter (m)

2.305 m

S = 2R/D = 6.908

4.468

4.971

3.526

0.016 0.318 0.858 0.315 0.814 0.016

0.051

0.054 0.027 0.147 0.210 0.814 0.051

Radiative Heat Flux Calculation

q" = 3.05 0.27

The above calculations are based on principles developed in the SFPE Handbook of Fire Protection

Calculations are based on certain assumptions and have inherent limitations. The results of suchcalculations may or may not have reasonable predictive capabilities for a given situation, and shouldonly be interpreted by an informed user.Although each calculation in the spreadsheet has been verified with the results of hand calculation,there is no absolute guarantee of the accuracy of these calculations.Any questions, comments, concerns, and suggestions, or to report an error(s) in the spreadsheet,please send an email to [email protected] or [email protected].

Prepared by: Date Organization

Checked by: Date Organization

Additional Information

Revision Log Description of Revision Date

1805.0 Original issue with final text. January 2005

R = distance from center of the pool fire to edge of the target (m)

Q = m"DHc,eff (1 - e-kb D) Adike

m" = mass burning rate of fuel per unit surface area (kg/m2-sec)

DHc = effective heat of combustion of fuel (kJ/kg)

Adike = surface area of pool fire (area involved in vaporization) (m2)

kb = empirical constant (m-1)

Hf = 0.235 Q2/5-1.02 D

Hf = flame height (m)

Hf =

h = 2Hf/D =

A = (h2+S2+1)/2S =

B = (1+S2)/2S =FH1 FH2 FH3 FH4 F1->2,H

F1->2,H =

F1->2,V = FV1 FV2 FV3 FV4 F1->2,V

F1->2, max = √(F21->2,H + F2

1->2,V) =

q" = EF1->2

kW/m2 Btu/ft2-sec

Engineering, 3rd Edition, 2002.

Answer

NOTE

Page 6: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

6

CHAPTER 5. ESTIMATING RADIANT HEAT FLUX FROM FIRE TO A TARGETFUEL ABOVE GROUND LEVEL UNDER WIND-FREE CONDITIONSOLID FLAME RADIATION MODELVersion 1805.0The following calculations estimate the radiative heat flux from pool fire to a target fuel.The purpose of this calculation is to estimate the radiation transmitted from a burning fuel array to a targetfuel positioned some distance from the fire above ground level to determine if secondary ignitions are likely with no wind. Parameters in YELLOW CELLS are Entered by the User.Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Fuel Selected.All subsequent output values are calculated by the spreadsheet and based on values specified in the inputparameters. This spreadsheet is protected and secure to avoid errors due to a wrong entry in a cell(s).The chapter in the NUREG should be read before an analysis is made.

INPUT PARAMETERS

Mass Burning Rate of Fuel (m") 0.039

0 46000 kJ/kg

0.7Heat Release Rate (Q) 841.15 kW

9.60 0.89

Distance between Fire and Target (L) 10.00 ft 3.048 m

8.00 ft 2.4384 m

OPTIONAL CALCULATION FOR GIVEN HEAT RELEASE RATESelect "User Specified Value" from Fuel Type Menu and Enter Your HRR here → kW

Calculate

THERMAL PROPERTIES DATA BURNING RATE DATA FOR FUELS

FuelMass Burning Rate Heat of Combustion Empirical Constant Select Fuel Type

Methanol 0.017 20,000 100

Ethanol 0.015 26,800 100Butane 0.078 45,700 2.7Benzene 0.085 40,100 2.7Hexane 0.074 44,700 1.9Heptane 0.101 44,600 1.1Xylene 0.09 40,800 1.4Acetone 0.041 25,800 1.9Dioxane 0.018 26,200 5.4Diethy Ether 0.085 34,200 0.7Benzine 0.048 44,700 3.6Gasoline 0.055 43,700 2.1Kerosine 0.039 43,200 3.5Diesel 0.045 44,400 2.1JP-4 0.051 43,500 3.6JP-5 0.054 43,000 1.6Transformer Oil, Hydrocarbon 0.039 46,000 0.7561 Silicon Transformer Fluid 0.005 28,100 100Fuel Oil, Heavy 0.035 39,700 1.7Crude Oil 0.0335 42,600 2.8Lube Oil 0.039 46,000 0.7Douglas Fir Plywood 0.01082 10,900 100User Specified Value Enter Value Enter Value Enter Value

ESTIMATING RADIATIVE HEAT FLUX TO A TARGET FUEL

SOLID FLAME RADIATION MODEL

Where

Pool Fire Diameter Calculation

WhereD = pool fire diamter (m)

D = 1.07 m

kg/m2-sec

Effective Heat of Combustion of Fuel (DHc,eff)Empirical Constant (kb) m-1

Fuel Area or Dike Area (Adike) ft2 m2

Vertical Distance of Target from Ground (H1 = Hf1)

m" (kg/m2-sec) DHc,eff (kJ/kg) kb (m-1)Scroll to desired fuel type then

Click on selection

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-26.

Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-276.

q" = EF1->2

q" = incident radiative heat flux on the target (kW/m2)

E = emissive power of the pool fire flame (kW/m2)

F1->2 = view factor between target and the flame

Adike = pD2/4

D = √(4Adike/p)

Adike = surface area of pool fire (m2)

Page 7: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

7

Emissive Power Calculation

WhereD = diameter of the pool fire (m)

E = 56.84 View Factor Calculation

B = S = 2R/D

WhereR = distance from center of the pool fire to edge of the target (m)

D = pool fire diameter (m)

Distance from Center of the Pool Fire to Edge of the Target Calculation

R = L + D/2

Where

L = distance between pool fire and target (m)

D = pool fire diameter (m)R = L+D/2 = 3.581 m

Heat Release Rate Calculation

Where Q = pool fire heat release rate (kW)

D = diameter of pool fire (diameter involved in vaporization, circular pool is assumed) (m)Q = 841.15 kW

Pool Fire Flame Height Calculation

Where

Q = heat release rate of fire (kW)

D = fire diameter (m)

2.389 m

S = 2R/D = 6.721

4.576

-0.094

4.993

3.435

3.435

0.054 0.029 0.154 0.221 0.812 0.054

-0.002

0.053 -0.001 -0.003 -0.005 0.860 -0.002

Radiative Heat Flux Calculation

q" = 2.99 0.26

The above calculations are based on principles developed in the SFPE Handbook of Fire Protection

Calculations are based on certain assumptions and have inherent limitations. The results of suchcalculations may or may not have reasonable predictive capabilities for a given situation, and shouldonly be interpreted by an informed user.

E = 58 (10-0.00823 D)

E = emissive power of the pool fire flame (kW/m2)

(kW/m2)

F1->2,V1 = 1/(pS)tan-1(h1/(S2-1)1/2)-(h1/pS)tan-1((S-1)/(S+1))1/2+A1h1/pS(A12-1)1/2tan-1((A1+1)(S-1)/(A1-1)(S+1))1/2

F1->2,V2 = 1/(pS)tan-1(h2/(S2-1)1/2)-(h2/pS)tan-1((S-1)/(S+1))1/2+A2h2/pS(A22-1)1/2tan-1((A2+1)(S-1)/(A2-1)(S+1))1/2

A1 = (h12+S2+1)/2S

A2 = (h22+S2+1)/2S

(1+S2)/2S

h1 = 2Hf1/D

h2 = 2Hf2/D

F1->2,V= F1->2,V1 + F1->2,V2

F1->2,V = total vertical view factor

Hf = height of the pool fire flame (m)

R = distance from center of the pool fire to edge of the target (m)

Q = m"DHc,eff (1 - e-kb D) Adike

m" = mass burning rate of fuel per unit surface area (kg/m2-sec)

DHc = effective heat of combustion of fuel (kJ/kg)

Adike = surface area of pool fire (area involved in vaporization) (m2)

kb = empirical constant (m-1)

Hf = 0.235 Q2/5-1.02 D

Hf = flame height (m)

Hf =

h1 = 2Hf1/D =

h2 = 2Hf2/D = 2(Hf-Hf1)/D =

A1 = (h12+S2+1)/2S =

A2 = (h22+S2+1)/2S =

B = (1+S2)/2S =FV1 FV2 FV3 FV4 F1->2,V1

F1->2,V1 =

F1->2,V2 = FV1 FV2 FV3 FV4 F1->2,V2

F1->2, V = F1->2,V1 + F1->2,V2 =

q" = EF1->2

kW/m2 Btu/ft2-sec

Engineering, 3rd Edition, 2002.

Answer

NOTE

Page 8: 05.1 Heat Flux Calculations Wind Free

Office of Nuclear Reactor RegulationDivision of Systems Safety and AnalysisPlant Systems BranchFire Protection Engineering and Special Projects Section

8

Although each calculation in the spreadsheet has been verified with the results of hand calculation,there is no absolute guarantee of the accuracy of these calculations.Any questions, comments, concerns, and suggestions, or to report an error(s) in the spreadsheet,please send an email to [email protected] or [email protected].

Prepared by: Date Organization

Checked by: Date Organization

Additional Information

Revision Log Description of Revision Date

1805.0 Original issue with final text. January 2005