04275308

Upload: muthukumari-selvaraj

Post on 06-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 04275308

    1/6

    1

    Abstract--This paper presents the measured results and

    harmonics generated by a commercial wind power generation

    system (WPGS) consisting of four identical 660 kW wind-turbine

    induction generators (WTIGs). The studied WPGS is connected

    to an 11.4 kV bus inside a large petroleum-chemical industrial

    mill located around the middle coast of Taiwan. The field

    measured results of total harmonic distortion (THD) in the

    current and voltage contributed by the WPGS are analyzed using

    a probabilistic approach since the measured quantities arerandom in nature. The IEEE harmonic limit is employed to check

    the level of penetration due to the WPGS. It is found that the

    THD in the current at the point of common coupling (PCC)

    connecting four WTIGs is larger than the 5% limitation of IEEE.

    Index Terms--wind power generation system (WPGS), total

    harmonic distortion (THD), probabilistic models.

    I. INTRODUCTION

    HE research of summation of randomly varying

    harmonics of the same order can be dated back to [1].

    Rowe examined the sum of randomly varying harmonic

    currents of the same order. He assumed that the harmonicvectors or phasors had either fixed or random magnitudes and

    the uniformly distributed phase angles were resolved into real

    and imaginary components. The central limit theorem was

    applied to the real and imaginary sums of the studied

    harmonic currents in [1] and the analyzed outcomes

    concluded that the magnitude of the sum of the harmonic

    current would approach to a Rayleigh distribution when the

    number of random vectors was large enough. Pierrat [2]

    extended the work of Rowe to form a general case through

    revising the phase angle of a phasor to be uniformly

    distributed in the range of [-, ] and it proved that Rowe's

    work was a special case. It should be noted that the magnitude

    and the phase angle of each harmonic vector in [1] and [2]

    were assumed to be independent. Since the real part and the

    imaginary part of harmonic currents of the same order were

    respectively summed up, the sum of the two resolved

    components would approach to a normal distribution as the

    number of random vectors was sufficiently large. A bivariate

    This work was supported by the National Science Council of Taiwan, ROC,

    under Grant NSC 94-2213-E-006-008.

    Kuo-Hua Liu and Li Wang are with the Department of Electrical

    Engineering, National Cheng Kung University, Tainan, 70101 Taiwan, Republic

    of China (e-mail: [email protected]).

    normal distribution (BND) [3] model was applied to some

    studied cases and the BND model contained five parameters,

    i.e., the mean values and variances of the two resolved sums

    and their correlation coefficient, which were employed by

    Kazibwe, et al. [4]. The same BND model was employed to

    determine the magnitude of harmonic contents generated by

    ten independent power converters in a distribution system and

    Monte Carlo simulation was performed to verify their

    theoretical results [5]. The BND approach was also used topredict voltage distortion in a distributed power system and

    the analyzed results were examined by using both simulation

    and field measurements [6].

    This paper is organized as follows. Section II describes

    the configuration of the studied system. The measured results

    are presented and analyzed in Section III. Statistic analysis of

    measured harmonic data at the PCC of the studied WPGS is

    depicted in Section IV. Specific conclusions are summarized

    in Section V.

    II. DESCRIPTION OF THE STUDIED SYSTEM

    The one-line diagram of the studied commercial windpower generation system (WPGS) is shown in Fig. 1, where

    the stator windings of the studied four identical 660 W, 690-V

    induction generators (IG1, IG2, IG3, and IG4) are connected to

    an equivalent utility grid (Grid) of 11.4 kV through individual

    excitation capacitor banks (C), step-up transformers (RTr +

    jXTr), and underground cables (RLine + jXLine). The rotor shaft

    of each IG is coupled to the turbine blades through individual

    gearbox (GB) with variable transmission rations for

    transforming variable low turbine speeds to near-constant

    high generator rotor speeds. The distance between two

    neighboring wind turbines is about 300 m. The equivalent

    capacitances Cline1 and Cline2 of the underground cables

    connected between generators are calculated from fieldmeasured reactive power.

    The point A shown in Fig. 1 is the point of common

    coupling (PCC) connecting four wind generators on the high-

    voltage side of the transformers. The three-phase line currents

    and voltages at the point A were recorded from the outputs of

    current transformers (CTs) and potential transformers (PTs)

    every five-second interval. The measured data were recorded

    from December 3-19, 2004 for about 16 days or 25,000

    minutes. Since the wind speeds of the northeast seasonal wind

    of Taiwan were high during the measurement period, the

    Analysis of Measured Harmonic Currents and

    Voltages Contributed by a Commercial Wind

    Power SystemKuo-Hua Liu and Li Wang, Senior Member, IEEE

    T

    1-4244-1298-6/07/$25.00 2007 IEEE.

  • 8/3/2019 04275308

    2/6

    2

    studied WPGS had at least 7 days under full-load generation

    of about 2.5 MW. The values of total harmonic distortion

    (THD) of both voltage and current were calculated from the

    measured three-phase voltages and currents.

    The point B shown in Fig. 1 is for filed measuring the

    output quantities of a single WTIG. The output data of single

    WTIG were recorded from 14:20 to 15:20 on January 21,

    2005. The three-phase line currents and voltages were

    recorded from the outputs of CTs and PTs at the 11.4-kV sideof the step-up transformer every five-second interval. During

    the one-hour measurement, the wind speed is high and the

    WTIG is generally under full-power generation.

    It is worth noting that total 7680 data points for each

    current or voltage signal are captured from the output

    terminals of CTs or PTs in one second. These data points are

    further processed to obtain 1024 data points for performing

    fast Fourier transformation (FFT) in order to precisely

    calculate the contents of current or voltage harmonics with

    different orders. The calculated harmonic results are averaged

    to obtain the required total harmonic distortions (THD) for

    each second. Hence, the values of THD are determined by the

    written software program in the power recorder. According tothe specifications of the power recorder, the highest harmonic

    order that can be analyzed is the 63rd

    order.

    Fig. 1 One-line diagram of the studied wind power generation system.

    III. ANALYSIS OF FILED MEASURED RESULTS

    Fig. 2 shows the filed measured results at point B of the

    WPGS shown Fig. 1 for one hour. It is seen from Fig. 2(a)

    that the point B has line voltage around 11.65 kV which is

    higher than the nominal value of 11.4 kV since this WTIG is

    generating near full power to the system under high wind

    speeds. The measured line current shown in Fig. 2(b) is

    around full-load current of about 33 A while the line active

    power shown in Fig. 2(c) is around an upper limit of 450 kW.

    This active power reduction could be resulted from the action

    of pitch control under high wind speed to limit the output

    active power of the wind induction generator. The reactive

    power shown in Fig. 2(d) also has higher negative limit of

    about 500 kVAR under high wind speeds. The apparent power

    shown in Fig. 2(e) reaches its upper bound of about 660 kVA

    under high wind speeds. Combing the results of active power,

    reactive power, and apparent power shown in Fig. 2, it is

    realized that the rated 660 kVA apparent power is obtained

    from the maximum active power output of 450 kW with

    reactive power upper bound of 500 kVAR. The frequencyshown in Fig. 2(f) is severely varied between 59.9 Hz to

    60.125 Hz due to randomly varying wind speeds. The power

    factor shown in Fig. 2(e) has the lowest value of 0.68 lagging

    and the highest value of 0.95 lagging. It is well known that the

    power factor of a WTIG is controlled by the internal capacitor

    bank inside the wind tower. Each capacitor bank has 5

    capacitance values for maintaining output power factor. The

    total harmonic distortion (THD) in the line current shown in

    Fig. 2(h) is varied from 4% to 16% and the highest THD

    value is due to very low wind speeds with low line currents.

    Fig. 3 shows the measured voltage, current, active

    power and reactive power at point A of the studied WPGS

    shown in Fig. 1 for about 16 days. It is seen from Fig. 3(a)that the values of the line voltage are varied between 11 kV to

    11.3 kV and these values are below nominal value of 11.4 kV.

    Sudden voltage peak and dip on special dates can be clearly

    observed from Fig. 3(a). The measured waveforms of both

    current and active power are similar as shown in Figs. 3(b)

    and 3(c). The total duration of full-power generation of about

    2.5 MW and full line current output of 139 A is about 7 days.

    The reactive power variation shown in Fig. 3(d) has a

    maximum negative peak value of 600 kVAR under full power

    generation since four induction generators require larger

    reactive power for magnetizing under higher power output.

    Comparing the maximum reactive-power value of 600 kVAR

    at point A for 4 WTIGs with the maximum reactive-powervalue of 500 kVAR at point B for only one WTIG, it can be

    found that the total reactive power supplied from the

    combined underground cables with large capacitance and

    switched capacitors inside the wind tower is not enough to

    supply the required reactive power of four induction

    generators under full power generation. Additional reactive

    power could be supplied by the grid side to which the four

    WTIGs are connected. Figs. 4 and 5 respectively show the

    time-domain variations of THD in the measured current and

    voltage shown in Fig. 3 for about 25000 minutes.

    The THD is a measure of the effective value of the

    harmonic components in a distorted voltage or current

    waveform and it can be calculated by

    max

    2

    1

    1

    h

    h

    h

    M

    THDM

    >=

    (1)

    whereMh is the rms value ofh-th harmonic component of the

    quantityMandMcan be either voltage or current. The values

    of THD in the measured voltage and current of the studied

    WPGS are generally not constant and they depend on wind-

    speed variations.

    B A

  • 8/3/2019 04275308

    3/6

    3

    (a) Line voltage (b) Line current

    (c) Active power (d) Reactive power

    (e) Apparent power (f) Frequency

    (g) Power factor (h) THD in the line current

    Fig. 2 Filed measured results at point B of the studied WPGS.

  • 8/3/2019 04275308

    4/6

    4

    Consider a time-varying random process shown in Figs. 4

    and 5, the definitions of basic statistical concepts are

    employed. IfN independent measurements random variablesare X = X(t1), , Xi = X(ti), , XN= X(tN), the average or

    mean value Xavg and standard deviation x can be written in

    the following form [6-7]

    1

    N

    i

    iavg

    X

    XN

    ==

    (2)

    and

    2

    1

    ( )

    1

    N

    i avg

    iX

    X X

    N=

    =

    (3)

    For a given mean value ofXavg and an associated standard

    deviation ofx, a time-varying random variableXN whose data

    spread according to the Gaussian distribution can be written

    in the following form

    22

    ( )1( ) ( )

    22

    avg

    X

    XX

    X Xf x exp

    = (4)

    Fig. 4 Time-domain variation of THD in the measured current.

    Fig. 5 Time-domain variation of THD in the measured voltage.

    (a) Line voltage

    (b) Line current

    (c) Active Power

    (d) Reactive power

    Fig. 3 Filed measured results at point A of the studied WPGS.

  • 8/3/2019 04275308

    5/6

    5

    The cumulative frequency curve is computed to demonstrate

    the computation of the 95th

    percentile value. It is economical

    to consider THD magnitude exceeding some level. These

    levels can be used for comparison with the maximum levels

    recommended by IEEE Standard 519 [11]. The probability of

    the phasor magnitude Knot exceeding some harmonic level

    Kmax can then be determined numerically:

    max

    max max 0( ) ( ) ( )

    K

    P K K cdf K pdf K dK = =

    (5)

    IV. ANALYSIS OF MEASURED DATA USING APROBABILISTIC

    APPROACH

    A computer program using statistical techniques is

    employed in this section to determining the harmonic

    contribution of the studied WPGS at the point A shown in Fig.

    1. A useful method of summarizing the characteristics of the

    THD results shown in Figs. 4 and 5 is to sketch histograms of

    probability density that are respectively shown in Figs. 6 and

    7. Once the histograms are plotted, the associated cumulative

    probability graphs shown in Figs. 8 and 9 can be obtained.

    The cumulative frequency curves are to demonstrate thecomputation of the 95

    thpercentile value, known as 95%.

    Table 1 lists the mean values and the standard deviations of

    the associated THD in the measured current and voltage as

    well as the corresponding 95th percentile values.

    Fig. 6 Histogram of THD in the measured current.

    Fig. 7 Histogram of THD in the measured voltage.

    Fig. 8 Cumulative probability graph for calculating the 95% value of THD in the

    measured current.

    Fig. 9 Cumulative probability graph for calculating the 95% value of THD in the

    measured voltage.

    Table 1 Statistical computed results of THD in the measured current and voltage

    at point A of Fig. 1.

    X Xavg X 95%

    Current THD(%) 0.7835 1.3155 3.543

    Voltage THD(%) 1.6682 0.04312 1.747

    It can be concluded from the statistical computed

    results listed in Table 1 and shown in both Fig. 8 and Fig. 9

    that the values of THD in the measured current and voltage

    are evidently lower than 5% limitation using 95% cumulative

    probability approach.

    V. CONCLUSIONS

    This paper has presented the field measured results

    and probabilistic approach to evaluate the total harmonic

    distortion in the measured current and voltage contributed by

    a commercial wind power generation system with four

    identical wind-turbine induction generators. Since wind speed

    is a random quantity, the measured quantities are also random

    varied with wind speeds. The proposed probabilistic method

    is for analyzing the characteristics of measured harmonic data.

    Statistical measurement techniques and histograms are the

    most commonly used methods for random quantities. Such

  • 8/3/2019 04275308

    6/6