03s 6 06controllers - festo...matics. these information ranges from simple to advanced application...
TRANSCRIPT
Energy Saving
Description
555 662
en0508a
[736 421]
Energy_Questions_A5_140808.qxp:Layout 1 14.08.2008 13:33 Uhr Seite 1
Contents and general instructions
IFesto P.BE−FESS−01−EN en 0508a
Author Leonard Lau. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editors U. Will, S. Lensdorf. . . . . . . . . . . . . . . . . . . . . . . . . . .
Original en. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Layout Festo AG & Co. KG, Abtl. SV−P. . . . . . . . . . . . . . . . . .
Type setting DUCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 0508a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Title MANUAL−EN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Designation P.BE−FESS−01−EN. . . . . . . . . . . . . . . . . . . . . . . .
Order no. 555 662. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [736 421]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E (Festo AG�&�Co., D�73726 Esslingen, Federal Republic of Germany 2008). .
Internet: �http://www.festo.comE−Mail: �[email protected]
The copying, distribution and utilization of this document aswell as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design registration.
Contents and general instructions
II Festo P.BE−FESS−01−EN en 0508a
Contents and general instructions
IIIFesto P.BE−FESS−01−EN en 0508a
Contents
Important user instructions VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Cylinder 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Case 1 � Reduction in compressed air consumption 1−4 . . . . . . . . . . . . . . . . . .
1.1.1 Tip 1 � Use single acting cylinders 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2 Tip 2 � Use clamping modules to hold cylinder in position 1−8 . . . . . . . . . . . .
1.1.3 Tip 3 � Use cylinders with integrated valve and flow controllers 1−10 . . . . . . .
1.1.4 Tip 4 � Use correct dimensioned cylinders 1−12 . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Case 2 � Reduction in compressed air leakage 1−14 . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Tip 1 � Use special seals in cylinders 1−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Tip 2 � Use round piston/piston rod cylinders 1−16 . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Tip 3 � Use guides to prevent deflection of piston rods 1−18 . . . . . . . . . . . . . .
1.2.4 Tip 4 � Use flexible couplings to prevent deflection of piston rods 1−20 . . . . .
1.3 Case 3 � Reduction in friction 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1 Tip 1 � Choose cylinders with less sealing points 1−22 . . . . . . . . . . . . . . . . . . .
1.3.2 Tip 2 � In dusty environment, use lubricated compressed air 1−24 . . . . . . . . .
1.3.3 Tip 3 � If cylinder is operated at more than 1 m/s, use lubricated compressed air 1−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.4 Tip 4 � In dusty environment, use covers wipers for exposed piston rod 1−28 .
1.4 Case 4 � Reduction in Pressure lost 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.1 Tip 1 � Reduce working pressure 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2 Tip 2 � Reduce working pressure of non−productive stroke 1−32 . . . . . . . . . . .
2. Valves 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Case 1 � Reduction in compressed air consumption 2−4 . . . . . . . . . . . . . . . . . .
2.1.1 Tip 1 � Select valve terminal according to flow rate for optimum performance 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2 Tip 2 � Select valve size according to flow rate for optimum performance 2−6
2.1.3 Tip 3 � Select valve function carefully 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.4 Tip 4 � Supply lower pressure for external pilot supply 2−10 . . . . . . . . . . . . . .
2.1.5 Tip 5 � Use 5/2 valves with reversible port 2−12 . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
IV Festo P.BE−FESS−01−EN en 0508a
2.1.6 Tip 6 � Use valve terminals with integrated (sandwich) pressure regulators 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.7 Tip 7 � Shut off compressed air supply when inactive for long periods 2−16 . .
2.2 Case 2 � Reduction in compressed air leakage 2−18 . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Tip 1 � Use valves with the poppet or cartridge design 2−18 . . . . . . . . . . . . . . .
2.2.2 Tip 2 � Use mainfold instead of individual valves 2−20 . . . . . . . . . . . . . . . . . . .
2.3 Case 3 � Reduction of electrical power 2−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Tip 1 � Use valves with reduction of holding current 2−22. . . . . . . . . . . . . . . . .
3. Air preparation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Case 1 � Reduction in compressed air consumption 3−4 . . . . . . . . . . . . . . . . . .
3.1.1 Tip 1 � Monitor compressed air consumption of machine/application 3−4 . .
3.1.2 Tip 2 � Use directly actuated pressure regulator instead of pilot actuated pressure regulator 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3 Tip 3 � Use automated drain instead of manual drain 3−8 . . . . . . . . . . . . . . . .
3.2 Case 2 � Reduction in pressure lost 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Tip 1 � Maintain required system pressure 3−10 . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Tip 2 � Ensure filter elements are changed or maintained 3−12 . . . . . . . . . . . .
3.2.3 Tip 3 � Reduce system pressure − use pressure booster for specificapplications 3−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Vacuum application 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Case 1 � Reduction in compressed air consumption 4−4 . . . . . . . . . . . . . . . . . .
4.1.1 Tip 1 � Use vacuum switch with vacuum applications 4−4 . . . . . . . . . . . . . . . .
4.1.2 Tip 2 � Use the correct pressure supply for vacuum generators 4−8 . . . . . . . .
4.1.3 Tip 3 � Maintain integrated silencers and filters of vacuum generators regularly 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.4 Tip 4 � Use vacuum pump for applications that require constant vacuum 4−12
4.1.5 Tip 5 � Place vacuum generator close to application 4−14 . . . . . . . . . . . . . . . . .
4.1.6 Tip 6 � Choose suitable succion cups 4−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VFesto P.BE−FESS−01−EN en 0508a
5. Accessoires 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Case 1 � Reduction in compressed air leakage 5−4 . . . . . . . . . . . . . . . . . . . . . .
5.1.1 Tip 1 � Ensure tubings are mounted properly 5−4 . . . . . . . . . . . . . . . . . . . . . .
5.1.2 Tip 2 � Use push/pull fittings with sealing lip 5−6 . . . . . . . . . . . . . . . . . . . . . .
5.1.3 Tip 3 � Select correct tubing design suitable to the purpose used for 5−8 . . .
5.1.4 Tip 4 � Tighten sealing rings for threading connections 5−10 . . . . . . . . . . . . . .
5.2 Case 2 � Reduction in pressure lost 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Tip 1 � Reduce the length of the tubing used 5−12 . . . . . . . . . . . . . . . . . . . . . . .
5.2.2 Tip 2 � Use multiple distributors 5−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.3 Tip 3 � Ensure that exhaust interfaces are suitable 5−18. . . . . . . . . . . . . . . . . .
6. Controllers and concepts 6−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Case 1 � Reduction in compressed air consumption 6−4. . . . . . . . . . . . . . . . . .
6.1.1 Tip 1 � Decentralise pneumatic circuits 6−4. . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 Tip 1 � Analyse high frequent operations to find energy waist 6−6. . . . . . . . .
6.2 Case 2 � Reduction in compressed air leakage 6−8. . . . . . . . . . . . . . . . . . . . . .
6.2.1 Tip 1 � Monitor continiously the energy status 6−8. . . . . . . . . . . . . . . . . . . . .
6.3 Case 3 � Reduction in electrical power 6−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.1 Tip 1 � Select positioning drive according to the specific demands 6−10. . . . .
6.3.2 Tip 2 � Use self−locking lead screw drives 6−12. . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VI Festo P.BE−FESS−01−EN en 0508a
Important user instructions
Danger categories
This manual contains instructions on the dangers which mayoccur if the product is not used correctly. These instructionsare marked with a heading (Warning, Caution, etc.), printedon a shaded background and accompanied by a pictogram. Adistinction is made between the following danger categories:
WarningThis means that there is a danger of serious human injuryand damage to property if these instructions are not ob�served.
CautionThis means that there is a danger of human injury anddamage to property if these instructions are not observed.
Please noteThis means that there is a danger of damage to property ifthese instructions are not observed.
In addition, the following pictogram marks passages in thetext which describe activities involving electrostatically sensi�tive components:
Electrostatically sensitive components: Incorrect handlingmay result in damage to the components.
Contents and general instructions
VIIFesto P.BE−FESS−01−EN en 0508a
Marking special information
The following pictograms mark passages in the text contain�ing special information.
Pictograms
Information:recommendations, tips and references to other sources ofinformation.
Accessories:information on necessary or useful accessories for the Festoproduct.
Environment:information on the environmentally−friendly use of Festoproducts (savings).
Text markings
S The bullet denotes activities which can be carried out inany sequence.
1. Figures denote activities which must be carried out in theorder specified.
� Hyphens denote general activities.
Contents and general instructions
VIII Festo P.BE−FESS−01−EN en 0508a
Introduction
As a family enterprise Festo feels responsible also for long−term questions to its products and technologie. Energy savingin Pneumatics is one of the areas Festo is setting a focus withour services and recommendations.
The purpose of this manual is to give prospective customersand users of pneumatic components some tips and tricks onhow to maximise the advantages of using pneumatic compo�nents while maintaining low energy usage.
This manual for Energy Saving evolved out of necessity dueto the high energy loss in the world. In response to many re�quests from customers, Festo has decided to compile thismanual.
The result is a collection of tips and tricks that has a clearstructured reference layout, specifically designed for theusage of both layman and experts to energy saving in pneu�matics. These information ranges from simple to advancedapplication solutions in this field.
Not all tips and tricks may be applicable to your machine orapplication. With this manual, we hope to be able to induceyou think of more ways to save energy with pneumatics.
Contents and general instructions
IXFesto P.BE−FESS−01−EN en 0508a
"The contents have been divided in six different sections,making it easy for users of this manual to find precisely theinformation they need:"
� Cylinders
� Valves
� Air preparation
� Vacuum application
� Accessories
� Controllers and concepts
It is important to note that while this manual is not designedto solve all your questions you may have on the topic of En�ergy Saving. This represents a start of an ongoing process tomake more effective use of pneumatic energy in your existingor future applications.
Please noteWe strongly recommend contacting our Festo representa�tives to have further discussions on how to implementsome of the tips in this manual.Some of the tips recommended will affect the functionalityand performance of your existing applications. While thesechanges will reduce energy consumption, it is important toconsider how these changes will affect your application.
Contents and general instructions
X Festo P.BE−FESS−01−EN en 0508a
What is Energy Saving?
Energy saving means to be able to run your applications inoptimum performance while using the lowest possible energy.In terms of pneumatic, this means to reduce leakages, loss inpressure and loss during the conversion of pneumatic energyto an action.
Energy saving opportunities are present everywhere in pneu�matics, it just takes minimal effort to recognise where energycan be saved. However, it takes concerted efforts to ensurethat these energy savings can be maintained.
Why Energy Saving is important?
Pneumatic compressed air is not free. It takes an enormousamount of electricity for an air compressor running in yourfactory to produce compressed air. The higher the pressureused in your system or application, the more cost goes intoproducing this pressure. Every leakage present in your ap�plication, represents money being released into the atmos�phere with absolutely no return on investment!
With the raising price of worldwide crude oil prices, energycost are expected to increase higher. Reduction of energyconsumption equals to less overall opearting cost of yourfactory saving money.
There are also environmental concerns in regards to the re�lease of CO2 gas. The less energy consumed means less CO2
emission to the atmosphere which is damaging the environ�ment we live in.
Contents and general instructions
XIFesto P.BE−FESS−01−EN en 0508a
How can Energy Saving be applied?
By simple change of design or by using components withbetter characteristic in energy saving aspect. You can saveenergy cost ranging from 10 % to 60 % (Eliminating leakages)when running pneumatic applications.Very often, by incorporating energy saving designs into yourapplications. The capital cost of making these changes aresmall when you compare with the savings throughout the lifeof the machine or application.
How to use this manual?
This manual is divided into five different sections with severalsub−title under each sector. Each sub−title has several tips inwhich energy saving could be achieved under specific condi�tions. Very often we are unable to illustrate the amount ofactual savings in terms of dollar and cents when the tips areused. This is because normally no two application are operat�ing under exactly the same conditions and achieving thesame results.
To use this manual effectively, start from page 1 and movethrough the pages progressively. Alternatively, you could turnto the content page and search for the topics that you areinterested in.
Useful Festo software
1. Pneumatic dimensioning � ProPneu
2. Fluidic muscle � Festo MuscleSIM
3. Tubing selection � Tube selector
4. Vacuum selection
5. Valve terminal
6. Mass moment of inertia � calculation program
Visit Festo at www.festo.com for more information on energy saving.
Contents and general instructions
XII Festo P.BE−FESS−01−EN en 0508a
Energy saving aspect
Reductionof leakage
Reductionofconsump�tion
Reductionoffriction
Reductionof pressureloss
Reductionof electricalpower
Product range
Cylinder + + + O �
Valves + O O O O
Air preparation O � � + �
Vacuum � + � O �
Accessories + � � + �
Controllers O � � + O
+ = possibility highly given, o = possibility maybe given, � = possibility less given
Fig.�0/1: Overview about saving potential in different product ranges
Cylinder
1−1Festo P.BE−FESS−01−EN en 0508a
Chapter 1
1. Cylinder
1−2 Festo P.BE−FESS−01−EN en 0508a
Contents
1. Cylinder 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Case 1 � Reduction in compressed air consumption 1−4 . . . . . . . . . . . . . . . . . .
1.1.1 Tip 1 � Use single acting cylinders 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2 Tip 2 � Use clamping modules to hold cylinder in position 1−8 . . . . . . . . . . . .
1.1.3 Tip 3 � Use cylinders with integrated valve and flow controllers 1−10 . . . . . . .
1.1.4 Tip 4 � Use correct dimensioned cylinders 1−12 . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Case 2 � Reduction in compressed air leakage 1−14 . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Tip 1 � Use special seals in cylinders 1−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Tip 2 � Use round piston/piston rod cylinders 1−16 . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Tip 3 � Use guides to prevent deflection of piston rods 1−18 . . . . . . . . . . . . . .
1.2.4 Tip 4 � Use flexible couplings to prevent deflection of piston rods 1−20 . . . . .
1.3 Case 3 � Reduction in friction 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1 Tip 1 � Choose cylinders with less sealing points 1−22 . . . . . . . . . . . . . . . . . . .
1.3.2 Tip 2 � In dusty environment, use lubricated compressed air 1−24 . . . . . . . . .
1.3.3 Tip 3 � If cylinder is operated at more than 1 m/s, use lubricated compressed air 1−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.4 Tip 4 � In dusty environment, use covers wipers for exposed piston rod 1−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Case 4 � Reduction in Pressure lost 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.1 Tip 1 � Reduce working pressure 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2 Tip 2 � Reduce working pressure of non−productive stroke 1−32 . . . . . . . . . . .
1. Cylinder
1−3Festo P.BE−FESS−01−EN en 0508a
Energy saving on cylinders
Double acting cylinder Single acting cylinder
1 2
3
1 2
Fig.�1/1: Saving points at cylinders
Saving points at cylinders are as follows:
1 Inlet, outlet
2 Piston seals
3 Piston rod seals
4 Correct size
Rules for best performance are as follows:
1. Cleaning rods
2. Greasing rods
3. Changing seals
4. Correct loads
1. Cylinder
1−4 Festo P.BE−FESS−01−EN en 0508a
1.1 Case 1 � Reduction in compressed air consumption
1.1.1 Tip 1 � Use single acting cylinders
Advantage Disadvantage
Reduces volume of compressed air uses
Need to use a bigger cylinder diameter than a double acting cylinderneeds (Force)
Reduces the number of inletports
Unable to increase spring return timeports
Low force for retracting
Short piston stroke
Related Festo products to save energy
ADVU DSNU
ESNU/AEVU } See Fig.�1/3
MAS
MAS } See Fig.�1/4
Fig.�1/2: Single acting cylinders
CautionThis may lead to changes in functionally and performanceof your application.
SavingsA 50 % reduction of compressed air volume. 44 % reduc�tion in potential leakage (number of connections).
1. Cylinder
1−5Festo P.BE−FESS−01−EN en 0508a
2
1 3
4
5
2
1 3
Air filling of chamber
Air fiiling of tube
L 50 %
22
22
1
9
11
11
1
5
Fig.�1/3: Consumption of air will drop by about 50% simplyby changing double acting cylinder (Example 1) tosingle acting cylinder (Example 2). Cost is reduceddue to cheaper 3/2 way valve and one less flowcontrol valve.
Example 1
Volume of air
Double acting cylinder 0.1719 ltr@ 25 mm, stroke 25 mmTubing @ 6 mm, Length 100 mmPiston rod @ ... mm
Potential leakage
Total number of connection ports 9
1. Cylinder
1−6 Festo P.BE−FESS−01−EN en 0508a
Example 2
Volume of air
Single acting cylinder 0.087 ltr@ 25 mm, stroke 25 mmTubing @ 6 mm,Length 100 mmPiston rod @ ... mm
Potential leakage
Total number of connection ports 5
1
2
3
4
5
6
Articulated arm system Using Fluidic Muscles to generate lifting force
1 Pneumatic cylinder to drive lever arm
2 Coupling gear unit
3 Upper arm drive
4 360° turnable
5 Cable, chain, belt or strap
6 Fluidic Muscie
Fig.�1/4: Example of a single acting design replacing a double acting cylinder design. In this application, the new MAS fluidic muscle cylinder is used.
1. Cylinder
1−7Festo P.BE−FESS−01−EN en 0508a
1. Cylinder
1−8 Festo P.BE−FESS−01−EN en 0508a
1.1.2 Tip 2 � Use clamping modules to hold cylinder in position
Clamping modules do not use compressed air to hold pistonin place.
Advantage Disadvantage
Allows to interrupt the con�stant supply of compressedair
Extended cylinder length
Safety feature in case of airs pply fail re
Additional air portsupply failure
Lifetime of clamping module dependent on load/force
Piston rod may move, when re−pressurized
Related Festo products to save energy
DNC−...−KP
DNCKE
DNCKE/KP } See Fig.�1/6
DNC−...−EL
Fig.�1/5: Clamping module combinations
CautionThis may lead to changes in functionality and performanceof your application.
1. Cylinder
1−9Festo P.BE−FESS−01−EN en 0508a
2
1 3
4
5Example 1
Example 2
Fig.�1/6: Simplified circuit with constant supply of air(Example 1) and with clamping unit to allow inter�ruption of air supply (Example 2)
Example 1
Potential leakage volume
Cylinder, @ 32 mm 1.2 ltr/hrValve 2 ltr/hr
Potential leakage points
Total number of connection ports 9
Example 2
Volume of air
Total activated clamping module 0.00193 ltr/hr
Potential leakage
Total number of connection ports 12
1. Cylinder
1−10 Festo P.BE−FESS−01−EN en 0508a
1.1.3 Tip 3 � Use cylinders with integrated valve and flow controllers
Less external connection points reduces occurrence of leak�age.
Advantage Disadvantage
Less tubing and connectorsused means less leakage andvolume
Unable to increase speed of cylinder if needed
Quick response of cylinder
Related Festo products to save energy
DNCV
DNCV } See Fig.�1/8
Fig.�1/7: Integrated valve−cylinder combination
CautionThis may lead to changes in functionality and performanceof your application.
SavingsDouble length of tubing doubles compressed air consump�tion for re−pressuring after exhaust = double cost.
1. Cylinder
1−11Festo P.BE−FESS−01−EN en 0508a
$ $
Example 1
Example 2
1 m
2 m
Fig.�1/8: Energy is lost at every actuation with the volume ofair in unnecessary long tubing
Calculated average cost for 1 m3 succed air (Eur) 0.020Pressure in system absolute (bar) 7.00
Example 1
Tubing diameter (mm) 8.00Tubing length (mm) 1000.00Volume in tubing (m3) 0.0000503Value of encapsulated compressed air (Cent) 0.001
Example 2
Tubing diameter (mm) 8.00Tubing length (mm) 2000.00Volume in tubing (m³) 0.0001Value of encapsulated compressed air (�−cent) 0.002
1. Cylinder
1−12 Festo P.BE−FESS−01−EN en 0508a
1.1.4 Tip 4 � Use correct dimensioned cylinders
Oversized cylinders slower the reaction time by filling largevolumes unnecessarily with air. Undersized cylinders slower the reaction time by resistance inair flow.
Advantage Disadvantage
Best possible performance Detailed knowledge of all relations needed (force, speed, accuracy)
Related Festo products to save energy
Fig.�1/9: Dimensioning software ProPneu
1. Cylinder
1−13Festo P.BE−FESS−01−EN en 0508a
Fig.�1/10: Calculating the volume of compressed air used in cylinders with Festo’s ProPneu software(www.festo.com) / Engineering / Selection and Dimensioning / Pro Pneu
Check carefully the requirements concerning
S needed forces
S needed stroke
S needed speed, dynamic
S needed accuracy
S possibilities of reducing forces by using counter masses
S possibilities of reducing strokes by using levers
S possibilities of reducing pressure by using a bigger dia−meter.
Fig.�1/11: Counter massto reduce forces
1. Cylinder
1−14 Festo P.BE−FESS−01−EN en 0508a
1.2 Case 2 � Reduction in compressed air leakage
1.2.1 Tip 1 � Use special seals in cylinders
Life of seals will be extended if used in correct environments.
Advantage Disadvantage
Different material of internalseals designed for specified applications
Lifetime of these special seals varies, normally lower than PU sealsunder normal conditions
Related Festo products to save energy
DNC....−S6 } See Fig.�1/13
Fig.�1/12: Special variants of cylinders
1. Cylinder
1−15Festo P.BE−FESS−01−EN en 0508a
Symbol Type code indicator Description
S6 Heat−resistantseals for tempera�tures up to 150 °C
Temperature−resistant
Fig.�1/13: Symbols for special variants of cylinders
1. Cylinder
1−16 Festo P.BE−FESS−01−EN en 0508a
1.2.2 Tip 2 � Use round piston/piston rod cylinders
Non−round piston rods are difficult to seal properly, resultingin higher leakages.
Advantage Disadvantage
Better sealing surface Cylinder rod can be rotated
Related Festo products to save energy
ADVU
DSNU
DRQD } See Fig.�1/15 and Fig.�1/16
DRQD
Fig.�1/14: Cylinders with round sealing lines
CautionThis may lead to changes in functionality and performanceof your application.
1. Cylinder
1−17Festo P.BE−FESS−01−EN en 0508a
Fig.�1/15: Vane type rotary actuator(Higher leakage ratesbecause of non−round sealing line)
Fig.�1/16: Rack & Pinion type rotary actuator(Sealing designsimilar to linear cylinders)
1. Cylinder
1−18 Festo P.BE−FESS−01−EN en 0508a
1.2.3 Tip 3 � Use guides to prevent deflection of piston rods
Deflection of cylinder or piston rod damages seals in 1 direc�tion, causing leakage.
Advantage Disadvantage
Protects the seals on cylinderfrom lateral force
Additional space needed for the guides
Protects seals from damageduring moving of piston rod
Related Festo products to save energy
DFM
} See Fig.�1/18 } See Fig.�1/18
ADVULFENG
Fig.�1/17: Guided actuators
CautionThis may lead to dimension changes.
1. Cylinder
1−19Festo P.BE−FESS−01−EN en 0508a
Fig.�1/18: Cylinders with guides will prevent deflection andstress on the cylinder seals
1. Cylinder
1−20 Festo P.BE−FESS−01−EN en 0508a
1.2.4 Tip 4 � Use flexible couplings to prevent deflection of piston rods
Misalignment affects the seals on the cylinders causing leak�ages.
Advantage Disadvantage
Protect piston rod againstmisalignment
Additional length extension
Protects misalignment from360 deg
Related Festo products to save energy
FK−.. / SGS / KSG} See Fig.�1/20
Fig.�1/19: Flexible coupling
CautionThis may lead to dimension changes.
1. Cylinder
1−21Festo P.BE−FESS−01−EN en 0508a
Fig.�1/20: Different flexible coupling options from Festo
1. Cylinder
1−22 Festo P.BE−FESS−01−EN en 0508a
1.3 Case 3 � Reduction in friction
1.3.1 Tip 1 � Choose cylinders with optimized sealing lines
This reduces occurance of leakages.
Advantage Disadvantage
Less seals means less risk ofwear and leakages
Rodless cylinders (slot design) have large sealing surface, but saveinstallation space. New types have further developped sealingmethods.
Related Festo products to save energy
DGC... } See Fig.�1/22 DGO... } See Fig.�1/23
Fig.�1/21: Rodless cylinders with different sealing design
1. Cylinder
1−23Festo P.BE−FESS−01−EN en 0508a
Fig.�1/22: Festo DGC rodless cylinder has a special sealingdesign that reduces leakages
Fig.�1/23: Festo DGO rodless cylinder (Sealing design similarto linear cylinder)
1. Cylinder
1−24 Festo P.BE−FESS−01−EN en 0508a
1.3.2 Tip 2 � In dusty environment, use lubricated compressed air
Lubricated air slows down the wearing in dusty environment.In normal cases non−lubricated air supply is recommended.
Advantage Disadvantage
Prevents the dust entering thecylinder, hardening the grease
Maintenance of oil in lubricator is needed
Less heat generated withinthe cylinder
Contamination of environment if leakage exist and if exhaust is notfiltered
Related Festo products to save energy
LOE
Fig.�1/24: Lubricator
CautionThis may lead to dimension changes.
1. Cylinder
1−25Festo P.BE−FESS−01−EN en 0508a
1. Cylinder
1−26 Festo P.BE−FESS−01−EN en 0508a
1.3.3 Tip 3 � If cylinder is operated at more than 1 m/s, use lubricated compressed air
Lubricated air protects the seals to heat up and wear quickly.In normal cases non−lubricated air supply is recommended.
Advantage Disadvantage
Less heat generated withinthe cylinder
Contamination of environment if leakage exists and if exhaust is notfiltered
Related Festo products to save energy
} See Fig.�1/26
LOE FRM
Fig.�1/25: Lubricator
CautionThis may lead to dimension changes.
1. Cylinder
1−27Festo P.BE−FESS−01−EN en 0508a
Supply without lubricated compressed air
Supply with lubricated compressed air
15010050200psibar01426
161412108
0
Fig.�1/26: Seperated supply channels (lubricated/non lubri�cated)
Oil specifications for lubrication of Festo products:Festo special oil OFSW−32 DIN 51524−HLP32, Basic viscosity: 32cSt. at 40 °CAmount: 25 mg/m3
(DIN ISO 8573−1, Class 5)
1. Cylinder
1−28 Festo P.BE−FESS−01−EN en 0508a
1.3.4 Tip 4 � In dusty environment, use cover wipers for exposed piston rod
Piston is protected and reduces occurrence of dust broughtinto the cylinder.
Advantage Disadvantage
Protect against accumulationof dust on the piston rod} less wear of the cylinder
Sometimes additional stroke length needed (for dust covers) friction is slightly higher than without dust cover
} less wear of the cylinder rod seal} less leakage
If full stroke of cylinder not used, life of cylinder is reduced becauseof missing cleaning effect on the rest stroke
Related Festo products to save energy
DNC..−R8 } See Fig.�1/28
Fig.�1/27: Cylinders with wiper seals
CautionThis may lead to dimension changes.
1. Cylinder
1−29Festo P.BE−FESS−01−EN en 0508a
Symbol Type code indicator
Description
R8Dust protectionusing wiper seals
The cylinder equipped witha hard−chrome plated pis�ton rod and a rigid scraper,which protects against dry,dusty media.
Fig.�1/28: Symbols for cylinders with wiper seals
1. Cylinder
1−30 Festo P.BE−FESS−01−EN en 0508a
1.4 Case 4 � Reduction in Pressure losss
1.4.1 Tip 1 � Reduce working pressure
Reduction of supply pressure saves energy in the wholedown−stream branch.
Advantage Disadvantage
Lower pressure means sav�ings in costs
Performance factor of the application may be compromised
Related Festo products to save energy
LR
LR−..−D } See Fig.�1/30
Fig.�1/29: Pressure regulators
CautionThis may lead to changes in functionality and performanceof your application.
1. Cylinder
1−31Festo P.BE−FESS−01−EN en 0508a
Pressure (bar) Ratio of pressuredifference
Savings (%)against 6 bar
3456
4 (abs.)5 (abs.)6 (abs.)7 (abs.)
4/7 = 0,575/7 = 0,716/7 = 0,857/7 = 1,00
43 %29 %15 %0 %
Fig.�1/30: Every reduction in system pressure leads to directsavings
If pressure is reduced, speed of cylinders is not necessarilyslower if the nozzles are opened on the other hand.
1. Cylinder
1−32 Festo P.BE−FESS−01−EN en 0508a
1.4.2 Tip 2 � Reduce working pressure of non−productive stroke
Reduction of pressure to save energy.
Advantage Disadvantage
Lower pressure means sav�in s in costs
Speed of return may be compromisedings in costs
Exhaust through the regulator reduces its life because of ...
Related Festo products to save energy
LRMA... } See Fig.�1/32
P1
P2
Fig.�1/31: Inline pressure regulators
CautionThis may lead to changes in functionality and performanceof your application.
1. Cylinder
1−33Festo P.BE−FESS−01−EN en 0508a
2
1 3
4
5 6 barL1 = 0L2
3 barL1 L2 = 0
24
1 35
single cylinder
combined cylinders
Fig.�1/32: Addition of an inline regulator reduces pressure for non−working stroke
1. Cylinder
1−34 Festo P.BE−FESS−01−EN en 0508a
Tamb = 20 °C without regulator with regulator
Tube length L1 + L2 1 m 1 m
Outer Tube Diameter @A 8 mm 8 mm
Inner Tube Diameter @I 5,9 mm 5,9 mm
Tube volume 2,73 x 10−5 m3 2,73 x 10−5 m3
Inside volume flow control valve (GRLA) 1,8 x 10−6 m3 �
Inside volume regulator (LRMAQ−1/8−QS8) � 2,5 x 10−6 m3
Cycles per minute 2 2
Cycles per year*) 1 048 320 1 048 320
Volume per year (compressed) 30,5 m3 31,23 m3
Volume per year (atmospheric) 209,8 m3 122,7 m3
Costs per m3 0,02 �/m3 0,02 �/m3
Costs per year 4,19 � 2,45 �
[%] 100 58
*) running all the time
Fig.�1/33: Comparison in detail without invest costs
Valves
2−1Festo P.BE−FESS−01−EN en 0508a
Chapter 2
2. Valves
2−2 Festo P.BE−FESS−01−EN en 0508a
Contents
2. Valves 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Case 1 � Reduction in compressed air consumption 2−4 . . . . . . . . . . . . . . . . . .
2.1.1 Tip 1 � Select valve terminal according to flow rate for optimum performance 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2 Tip 2 � Select valve size according to flow rate for optimum performance 2−6
2.1.3 Tip 3 � Select valve function carefully 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.4 Tip 4 � Supply lower pressure for external pilot supply 2−10 . . . . . . . . . . . . . .
2.1.5 Tip 5 � Use 5/2 valves with reversible port 2−12 . . . . . . . . . . . . . . . . . . . . . . . .
2.1.6 Tip 6 � Use valve terminals with integrated (sandwich) pressure regulators 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.7 Tip 7 � Shut off compressed air supply when inactive for long periods 2−16 . .
2.2 Case 2 � Reduction in compressed air leakage 2−18 . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Tip 1 � Use valves with the poppet or cartridge design 2−18 . . . . . . . . . . . . . . .
2.2.2 Tip 2 � Use mainfold instead of individual valves 2−20 . . . . . . . . . . . . . . . . . . .
2.3 Case 3 � Reduction of electrical power 2−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Tip 1 − Use valves with reduction of holding current 2−22. . . . . . . . . . . . . . . . . . .
2. Valves
2−3Festo P.BE−FESS−01−EN en 0508a
Energy saving on valves
Zone 1 Zone 2
1
z{1}
Fig.�2/1: Saving points at valve terminals (here: with pres�sure zones)
Saving points at valves are as follows:
1 Right dimensioning
Rules for best performance are as follows:
1. Short distances between valve and actuator
2. Pressure zones for branches with lower pressure level
2. Valves
2−4 Festo P.BE−FESS−01−EN en 0508a
2.1 Case 1 � Reduction in compressed air consumption
2.1.1 Tip 1 � Select valve terminal according to flow rate for optimum performance
By range of modules to select valve terminal according toyour requirements.
Advantage Disadvantage
Select valve terminal ideal forspecific application
�
Avoid oversizing/undersizingof valves
�
Related Festo products to save energy
Festo valve terminal software } See Fig.�2/3
Fig.�2/2: Valve terminal configurator www.festo.com/products/dimensioning software orwww.festo.com/engineering/selection/selection&dimensioning/software
2. Valves
2−5Festo P.BE−FESS−01−EN en 0508a
Fig.�2/3: Festo valve terminal selection tool allows selection�from all valve terminal types from Festowww.festo.com/products/dimensioning softwareor www.festo.com/engineering/selection/selec�tion&dimensioning/software
2. Valves
2−6 Festo P.BE−FESS−01−EN en 0508a
2.1.2 Tip 2 � Select valve size according to flow rate for optimum performance
Avoid oversizing or undersizing of the valve.
Advantage Disadvantage
Reduce volume of com�pressed air used
�
Related Festo products to save energy
} See Fig.�2/5
MPA Typ 44 (VTSA)
ProPneu for valves
Fig.�2/4: Valve selection tool www.festo.com/products/dimensioning software/down�load for windows
CautionThis may lead to changes in functionality and performanceof your application.
2. Valves
2−7Festo P.BE−FESS−01−EN en 0508a
Size of valve Flow rate (litre/min)
M5 180
M7 350
1/8" 800
1/4" 1,500
3/8" 2,900
1/2" 3,700
3/4" 7,500
1" 11,500
Fig.�2/5: Relation of size and flow rates of valves
size 1size 2size 3
Fig.�2/6: Possible mix on one platform of precise fittingvalve sizes
2. Valves
2−8 Festo P.BE−FESS−01−EN en 0508a
2.1.3 Tip 3 � Select valve function carefully
5/2 Double solenoid valve
Advantage Disadvantage
After switching pulse current can be shut off
Two solenoids
5/3 valve with closed position
Advantage Disadvantage
After the cylinder reached theend position pressure supplycan be shut off
2. Valves
2−9Festo P.BE−FESS−01−EN en 0508a
Fig.�2/7: Interruption of air supply if valve has switched
2. Valves
2−10 Festo P.BE−FESS−01−EN en 0508a
2.1.4 Tip 4 � Supply lower pressure for external pilot supply or cylinderback stroke
A different pressure can be used for external pilot supply onvalves.
Advantage Disadvantage
Pilot supply can be lower thenworking pressure (e.g. in highpressure applications)
Additional connections required, which means potential leakage
External pilot valves allowslower working pressure
Additional connections are required for external pilot
Related Festo products to save energy
} See Fig.�2/9 } See Fig.�2/10
Fig.�2/8: Valves with seperate pilot supply
2. Valves
2−11Festo P.BE−FESS−01−EN en 0508a
Fig.�2/9: Internal pilot valve uses supply pressure to assistin switching of the spool in the valve
Fig.�2/10: External pilot valve have additional ports (82, 84,12, 14) for pilot supply pressure to switch thespool in the valve
2. Valves
2−12 Festo P.BE−FESS−01−EN en 0508a
2.1.5 Tip 5 � Use 5/2 valves with reversible port
In this configuration, exhaust air does not pass through thepressure regulators, extending their life.
Advantage Disadvantage
Reduction of supply pressurefor non−working stroke
�
Related Festo products to save energy
} See Fig.�2/12
} CPV (port 3 and 5 combined)
} MPA
} VTSA
} CPASC
} Tiger 2000
} ISO
Fig.�2/11:
CautionThis may lead to changes in functionality and performanceof your application.
2. Valves
2−13Festo P.BE−FESS−01−EN en 0508a
6 bar 3 bar
3 bar6 bar
Fig.�2/12: If valves are driven reversibly different pressurecan be supplied to port 3 and 5 for forward andreturn stroke. Port 1 will be used as exhaust port inthis configuration.
Reversibility of valves means that the exhaust ports can beused as supply ports and vice versa.This is possible if the seals are designed in a symmetric wayso that no sealing lip will be lifted if pressure lies at the otherside.
2. Valves
2−14 Festo P.BE−FESS−01−EN en 0508a
2.1.6 Tip 6 � Use valve terminals with integrated (sandwich) pressure regu−lators
An integrated (sandwich) pressure regulator reduces theworking pressure for each single valve and the number ofconnection points of the regulator (exhaust air do not passthrough regulator).
Advantage Disadvantage
Integrated design reduces connections. Space for installation is increased
Individually adjusted pressure according to application needs �
Related Festo products to save energy
MPAVTSA... } See Fig.�2/3 Valve terminal software
Fig.�2/13: Valve modules with integrated pressure regulators
CautionThis may lead to changes in functionality and performanceof your application.
SavingsUp to 50 % of energy can be saved if different pressure isused.
2. Valves
2−15Festo P.BE−FESS−01−EN en 0508a
Cost for 1 m3 air at 7 bar abso�lute pressure (Eur)
0.020 Cycle per Minute 12.00
Pressure in system absolute(bar)
7.00 1 Machine working time per day (hours) 14.00
Tubing inner diameter (mm) 8.00 Number of working days per year 240.00
Tubing length (mm) 3000.00 Cycles per year 2419200.00
Volume in tubing (m3) 0.00015 Pressure of working stroke (bar) 5.00 2
Pressure of return stroke (bar) 3.00 3
Cylinder diameter (mm) 100.00 Energy saving for working stroke (Eur) 10.03
Stroke length (mm) 70.00 Energy saving for return stroke (Eur) 20.05
Cylinder volume (m3) 0.0005 Energy saving total per year (Eur) 30.08
Fig.�2/14: Example calculation with reduced pressure lines (approx.: stroke vol. = return vol.)
5 bar1
7 bar
3 bar2
Fig.�2/15: Exhaust air does not pass through regulators, life istherefore extended because the seals are lessstressed.
2. Valves
2−16 Festo P.BE−FESS−01−EN en 0508a
2.1.7 Tip 7 � Shut off compressed air supply when inactive for long periods
Advantage Disatvantage
No leakage and no consump�tion in the branch
Piston rods of cylinders move freely and maybe suddenlytion in the branch
Re−filling and re−pressurization required
If 3/2 valve is used, system air is purged
Related Festo Energy saving products
} See Fig.�2/17
MSX−...−EE QH−... SOE−... F−...
Fig.�2/16: Shut−off and softstarting valve
CautionThis may lead to changes in functionality and performanceof your application.
SavingsPotential leakages via pressurized cylinder and fittingsduring non−movement would be totally removed by this.
2. Valves
2−17Festo P.BE−FESS−01−EN en 0508a
Fig.�2/17: This master on/off valve could be either manually�actuated or actuated by a solenoid
Examples for shut−off/interruption possibilities:
S vacuum generation with vacuum ejectors
S blowing air
S mechanical stirers (e.g. stiring paint, glue, ...)
S any process with participation of staff by means of pres�ence circuits (e.g. quality proof by air gap resistance isshut off by means of light barriers if no staff is working).
2. Valves
2−18 Festo P.BE−FESS−01−EN en 0508a
2.2 Case 2 � Reduction in compressed air leakage
2.2.1 Tip 1 � Use valves with the poppet or cartridge design
Rubber sealed design principle has no leakage rate in com�parison to lapped spool design.
Advantage Disadvantage
Less leakage rates comparedto lapp spool principle
Contains wearing parts
Related Festo products to save energy
} See Fig.�2/20 } See Fig.�2/19
CartridgeCPASCCPV04 (ISO)MPATyp03 MIDI/MAXITyp 44 (ISO)
PoppetTiger Classic
Fig.�2/18: Valves with poppet or cartridge design
CautionThis may lead to changes in functionality and performanceof your application.
2. Valves
2−19Festo P.BE−FESS−01−EN en 0508a
Fig.�2/19: Poppet principle
Fig.�2/20: Cartridge principle
2. Valves
2−20 Festo P.BE−FESS−01−EN en 0508a
2.2.2 Tip 2 � Use mainfold instead of individual valves
Manifold reduces number of connectors used.
Advantage Disadvantage
Less connections means lessplace for leakages
Distance from cylinders may affect performace of application
Space saving design Volume of air in tubing to cylinder is increased
Common compressed air sup�ply to manifold
�
Different pressure zone withinmanifold possible
�
Related Festo products to save energy
CPV... } See Fig.�2/22 CPV−SC... } See Fig.�2/22
Fig.�2/21: Configurable manifolds to adapt to specific needs.
CautionThis may lead to changes in functionality and performanceof your application.
2. Valves
2−21Festo P.BE−FESS−01−EN en 0508a
Zone 1 Zone 2
Fig.�2/22: Valve terminals assembled at Festo are completelytested concerning leackage aspects.
2. Valves
2−22 Festo P.BE−FESS−01−EN en 0508a
2.3 Case 3 � Reduction of electrical power
2.3.1 Tip 1 − Use valves with reduction of holding current
Advantage Disadvantage
After switching off solenoidpower supply is reduced electrically without loss offunction
�
Related Festo products to save energy
CPVMPACPASC
Fig.�2/23: Since the 1990ties used circuit sheme
SavingsElectrical savings up to 70 %.
Air preparation
3−1Festo P.BE−FESS−01−EN en 0508a
Chapter 3
3. Air preparation
3−2 Festo P.BE−FESS−01−EN en 0508a
Contents
3. Air preparation 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Case 1 � Reduction in compressed air consumption 3−4. . . . . . . . . . . . . . . . . .
3.1.1 Tip 1 � Monitor compressed air consumption of machine/application 3−4. .
3.1.2 Tip 2 � Use directly actuated pressure regulator instead of pilot actuated pressure regulator 3−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3 Tip 3 � Use automated drain instead of manual drain 3−8. . . . . . . . . . . . . . . .
3.2 Case 2 � Reduction in pressure lost 3−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Tip 1 � Maintain required system pressure 3−10. . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Tip 2 � Ensure filter elements are changed or maintained 3−12. . . . . . . . . . . .
3.2.3 Tip 3 � Reduce system pressure − use pressure booster for specificapplications 3−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Air preparation
3−3Festo P.BE−FESS−01−EN en 0508a
Energy saving on Air supply
1
2
3
4
5
6 1
Fig.�3/1: Saving points at air supply products
Saving points at regulators, filter units, oilers, tubes, fittingsare as follows:
1 Pressure level adjusted
2 Seal of bowl
3 Oil regulation as low as possible in order to avoid washing out the life time lubrication
4 Drain tightening
5 Switch off valves if machine not needed (2/2−valve to encapsulate the pressure downstream)
6 Pressure switches
Rules for best performance are as follows:
1. Switch off as often as possible
2. Lowest pressure level as possible
3. Splitted pressure levels
3. Air preparation
3−4 Festo P.BE−FESS−01−EN en 0508a
3.1 Case 1 � Reduction in compressed air consumption
3.1.1 Tip 1 � Monitor compressed air consumption of machine/application
Any changes to normal air consumption can be detected at avery early stage.
Advantage Disadvantage
Comparison of consumptiongives indication of the performance
Cost of investment
Charting gives indicationwhen the peaks of usage are
�
Related Festo products to save energy
MS..SFE / SFE3 / SFE1 } See Fig.�3/3
SFE1−...
SFE3−... SFET−...F
MS..−SFE−... GFDM−...
Fig.�3/2: Monitoring devices
3. Air preparation
3−5Festo P.BE−FESS−01−EN en 0508a
Fig.�3/3: In−line detection of flow indicates abnormal consumption
Fast response (response time depends on internal volume ofthe piping and pressure etc.)Free from readjustment and wrong detection caused by pres�sure change.Can detect clogging of nozzle and/or filter.Can detect incomplete suction like a sensor.
3. Air preparation
3−6 Festo P.BE−FESS−01−EN en 0508a
3.1.2 Tip 2 � Use directly actuated pressure regulator instead of precision pressure regulator
Reduce in use of compressed air with directly actuated pres�sure regulator because of self consumption of indirect actu�ated regulators.
Advantage Disadvantage
Non−pilot actuated regulatordo not use compressed air tomaintain accuracy
Accuracy is not as good as with precision pressure regulator
Related Festo products to save energy
LR−... LRP−...
Fig.�3/4: Directly actuated pressure regulators
3. Air preparation
3−7Festo P.BE−FESS−01−EN en 0508a
Fig.�3/5: Additional air volume with pilot actuated regula�tors
Precision regulator needs internal operation air consumption.If accuracy of pressure regulation is not needed a standardregulator is recommended.
3. Air preparation
3−8 Festo P.BE−FESS−01−EN en 0508a
3.1.3 Tip 3 � Use automated drain instead of manual drain
If mositure is released periodically occurance of moisture intoproducts is reduced. Moisture affects seals and greaseconditions.
Advantage Disadvantage
Collected moisture is releasedregularly
�
Duration time when releasingcollected moisture is con�trolled
�
Related Festo products to save energy
PWEA WA−...
Fig.�3/6: Automated drain devices
3. Air preparation
3−9Festo P.BE−FESS−01−EN en 0508a
Strengths of PWEA
High functionality, since the system reliably operates even inthe case of problematic condensate.
� Large cross section: Even coarse contaminants andcoagulate are easily removed.
� No pressure loss when emptying thanks to prompt seal�ing of the system.
� Flexible areas of application, since the system automati�cally adapts to changing operating conditions (e.g. chang�ing viscosity of condensate and pressure fluctuations).
� Prevention of downtimes thanks to alarm function! Thealarm mode is triggered after 60 s , if the condensatedrain is faulty. The solenoid valve then opens the valvediaphragm at specific intervals.
� External fault signal, a red LED flashes and a digital signalapplies., indicating the status.
3. Air preparation
3−10 Festo P.BE−FESS−01−EN en 0508a
3.2 Case 2 � Reduction in pressure lost
3.2.1 Tip 1 � Maintain required system pressure
Any changes to the required system pressure affects perform�ance. Registration of changes points to losses or manipula�tion.
Advantage Disadvantage
Process operation is optimum �
Ensure application is workingproperly
�
Related Festo products to save energy
FRCS... E11 MA...E−RGZVS−...
Fig.�3/7: Pressure keeping products
3. Air preparation
3−11Festo P.BE−FESS−01−EN en 0508a
Lockable service units contribute to a remaining pressurelevel.
A planned cascading of filtration ensures the less pressurelosses.
40 m 5 m finefiltered air
Fig.�3/8: Filter cascade
Fig.�3/9: Check for energy saving features
Configuration tools help to think energy saving (e.g. shut−offvalve yes/no, regulator lockable yes/no, different pressurezones yes/no, inserted distributers yes/no, filter cascadeyes/no, ...).Volume can help to equalize the pressure niveau if consump�tion is very dynamic.
3. Air preparation
3−12 Festo P.BE−FESS−01−EN en 0508a
3.2.2 Tip 2 � Ensure filter elements are changed or maintained
Clogged filter units reduce efficiency of service units.
Advantage Disadvantage
No pressure loss besause ofno clogged filter elements
�
Gives an indication of thequality of compressed air supply
�
Related Festo products to save energy
MS...−LFM−...−DA } See MSLFMA } See Fig.�3/11
Fig.�3/10: Products with instruction of pressure fall
3. Air preparation
3−13Festo P.BE−FESS−01−EN en 0508a
Fig.�3/11: LFMA − Fine filter with visual indicator. Condition ofthe filter element is indicated via the differentialpressure
Recommendation:If the pressure drop inside a filter is more than 0, 3 bar,change the filter elements in the service unit.
Example:
with old filter element with new filter element
Pressure drop in the filter 0,4 bar 0,2 bar
Pressure difference in supply 0,2 bar 0 bar
Consumption difference because ofpressure difference
2 % 0 %
Average consumption of the machine 612 l/min320 786 m//year
600 l/min 314 496 m3/year
Costs per m3 succed air 0,02 �/ m3 0,02 �/ m3
Costs per year 6 416 � 6 290 �
Difference in the year 126 � 0 �
Costs of new filter element 0 � 11,80 �
Amortisation time � ca. 1 month
Fig.�3/12: Comparison of maintained and not maintained filter
3. Air preparation
3−14 Festo P.BE−FESS−01−EN en 0508a
Check pre−Filter (40 m / 5 m) if dirty or broken. They areflown through from outside to inside and their condition canbe seen.
Fig.�3/13: Different examples of weared filter cartridges
3. Air preparation
3−15Festo P.BE−FESS−01−EN en 0508a
3. Air preparation
3−16 Festo P.BE−FESS−01−EN en 0508a
3.2.3 Tip 3 � Reduce system pressure − use pressure booster for specificapplications
Advantage Disadvantage
Not all applications need tobe supplied with 8 bar pressure
Pressure booster uses compressed air to boost pressure. Up to50% volume lost
Increase pressure only forspecific application, savingenergy cost for rest of applications
Noise pollution
Related Festo products to save energy
DPA... } See Fig.�3/15
Fig.�3/14: Pressure booster
CautionThis may lead to changes in functionality and performanceof your application investments.
SavingsUp to 15% savings after factoring the cost of investments.
3. Air preparation
3−17Festo P.BE−FESS−01−EN en 0508a
Variant ISupply 10 bar
Variant IISupply 6 bar + 5 % of volume at 10 barvia pressure booster
Purchase
CompressorCooler/refrigerating dryer
80.000 � 80.000 �
Operation
Costs m3
Delivery volume/min.Operating hours/aDelivery volume (p.a.)
0.0385.01.200360.000
360.000
�/m3
m3/min.h/am3/a
m3/a
0.0265.01.200360.000
plus 5 % for pressurebooster supply air: 18.000
378.000
�/m3
m3/min.h/am3/a
m3/am3/a
Delivery costs of compressor intotal
13.572 � 9.828 �
Total costs p.a.
Write−down 10% p.a.New investment p.a. (pr.boosters)Operating costs
8.000
13.572
�/a
�/a
8.0001.000
9.828
�/a�
�/a
Total costs p.a. 21.572 �/a 18.828 �/a
Saving p.a. � �/a 2.744 �/a
a= annum (year)
Fig.�3/15: Costs balance with DPA (example)
Behind the booster a dryer or a filter may be needed, if thepressure jump in the given ambient temperature causes con�densing of the air. A tank may be needed if bigger volume ofhigher pressurised air is needed.
3. Air preparation
3−18 Festo P.BE−FESS−01−EN en 0508a
Supply/
Exhaust valve
Pneumaticactuator
Pressure regulator for low−pressure setting
Fig.�3/16: Tank as buffer for bigger volumes
Vacuum application
4−1Festo P.BE−FESS−01−EN en 0508a
Chapter 4
4. Vacuum application
4−2 Festo P.BE−FESS−01−EN en 0508a
Contents
4. Vacuum application 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Case 1 � Reduction in compressed air consumption 4−4 . . . . . . . . . . . . . . . . . .
4.1.1 Tip 1 � Use vacuum switch with vacuum applications 4−4 . . . . . . . . . . . . . . . .
4.1.2 Tip 2 � Use the correct pressure supply for vacuum generators 4−8 . . . . . . . .
4.1.3 Tip 3 � Maintain integrated silencers and filters of vacuum generators regularly 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.4 Tip 4 � Use vacuum pump for applications that require constant vacuum 4−12
4.1.5 Tip 5 � Place vacuum generator close to application 4−14 . . . . . . . . . . . . . . . . .
4.1.6 Tip 6 � Choose suitable succion cups 4−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Vacuum application
4−3Festo P.BE−FESS−01−EN en 0508a
Energy saving on Vacuum
1
2
3
Fig.�4/1: Saving points at vacuum lines
Saving points at vacuum lines are as follows:
1 Pressure line
2 Vacuum line
3 Suction cup
Rules for best performance are as follows:
1. Short pressure line distances
2. Short vacuum line distances
3. Adequate suction−cups for perfect sealing
4. Vacuum application
4−4 Festo P.BE−FESS−01−EN en 0508a
4.1 Case 1 � Reduction in compressed air consumption
4.1.1 Tip 1 � Use vacuum switch with vacuum applications
Using a vacuum switch allows switching off the vacuum gen�erator when required pressure is reached.
Advantage Disadvantage
Allows the switching off ofvacuum when desired pres�sure is reached
�
Detected pressure changecould be used as a signal thatwork piece is present
�
Related Festo products to save energy
VPEV...
VN−...P } See Fig.�4/4
VADMI } See Fig.�4/3
SDE5
SDE1
OVEM−...
Fig.�4/2: Vacuum switches or integrated switches
4. Vacuum application
4−5Festo P.BE−FESS−01−EN en 0508a
Fig.�4/3: Savings in vacuum generation
� Vacuum is automatically switched off when required vac�uum is reached 2 (VADMI−P−LS, OVEM−... )
� and automatically switched on again 3 to achieve re�quired vacuum
� without need for any external wiring and PLC program�ming
� integrated non−return valve prevents purging of the vac�uum (VADMI−P−LS, OVEM−...)
� detector registers the increase of suction an switches offin case of mal function (VADMI−...−P/N−LS, OVEM−...).
4. Vacuum application
4−6 Festo P.BE−FESS−01−EN en 0508a
Operation cycle to handle a workpiece
Evacuation time Transport
Drop off Back to zero position
Total cycle time
Fig.�4/4: Switch−off functionality during return time
Example
Energy cost comparison between VN−05 and VADMI−45. In asimilar problem during 250 days/year and 16 h/day:
� Energy costs without switch−off function (VN−...): 37 �/a
� Energy costs with switch−off function (VADMI−...−LS): 12 �/a.
4. Vacuum application
4−7Festo P.BE−FESS−01−EN en 0508a
Optical part detection sensors in combination with an air stopvalve help to save compressed air if no workpiece is there tobe succed.
Fig.�4/5: Sensors to clarify need of vacuum
4. Vacuum application
4−8 Festo P.BE−FESS−01−EN en 0508a
4.1.2 Tip 2 � Use the correct pressure supply for vacuum generators
Supply pressure affects the vacuum pressure directly.
Advantage Disadvantage
Vacuum is not generated ac�cording to the higher pres�sure. Check the operatingpressure to achive optimumvacuum.
�
Related Festo products to save energy
} See Fig.�4/7
VN−...
Fig.�4/6: Vacuum generators
4. Vacuum application
4−9Festo P.BE−FESS−01−EN en 0508a
Vacuum depending on supply pressure Faster evacuation time with L type generator at 0,4 bar vacuum
Supply pressure [bar] Supply pressure 6 bar
(L)
(H)
(L)
(H)
Fig.�4/7: Example of Festo VADM vacuum generators vacuum generators VN−...−H andVN−...−L
The relation between vacuum ’output’ and pressure ’input’follows a graph. Different productlines have a specific char�acteristic.Large flow characteristic (L) is energy saving because
� of a linear ratio of pressure and generated vacuum
� of a faster evacuation time and as a result the possibilityto switch off the vacuum generation earlier.
See poster 050093 Three selection criteria"
4. Vacuum application
4−10 Festo P.BE−FESS−01−EN en 0508a
4.1.3 Tip 3 � Maintain integrated silencers and filters of vacuum generators regularly
Peformance of the vacuum genrator can be improved withbetter maintenance.
Advantage Disadvantage
Ensure optimum performanceof application
�
Related Festo products to save energy
VAF... In line filter } See Fig.�4/10
Fig.�4/8: Filter spare parts, silencers
4. Vacuum application
4−11Festo P.BE−FESS−01−EN en 0508a
Fig.�4/9: Silencer elements to be changed
Fig.�4/10: In line filter (VAF−...) to protect vacuum generatorfrom being clogged
Fig.�4/11: Noise reduction with new filter types UO−... main�tenance free because it’s open at the end
4. Vacuum application
4−12 Festo P.BE−FESS−01−EN en 0508a
4.1.4 Tip 4 � Use vacuum pump for applications that require constant vacuum
Advantage Disadvantage
Minimum possible air con�sumption
�
� �
�
Related Festo products to save energy
Fig.�4/12: Economy function www.festo.com/products/dimensioning software/downloadfor windows
CautionThis may lead to changes in functionality and performanceof your application.
4. Vacuum application
4−13Festo P.BE−FESS−01−EN en 0508a
For more detailed calculation, refer to Festo’s System guide−Vacuum Selection Tool.
4. Vacuum application
4−14 Festo P.BE−FESS−01−EN en 0508a
4.1.5 Tip 5 � Place vacuum generator close to application
Nearer to application means faster evacuation time and there�fore less air consumption.
Advantage Disadvantage
Faster evacuation time Weight of the vacuum generator will be on the moving axis of theapplication
Related Festo products to save energy
VN... } See Fig.�4/14 VN−cartridge } See Fig.�4/18
Fig.�4/13: Light vacuum generators for decentral placement
4. Vacuum application
4−15Festo P.BE−FESS−01−EN en 0508a
P
1
2
1 @ andlength of the tube influences the pressure dropΔp and therefore the vacuum level
2 @ and length of the tube influences the evacuation time Δt
Fig.�4/14: Tubing lengths and diameters
Tubing lengths and diameters have a decisive influence onvacuum level and evacuation time. Paying attention to thesefactors has a positive effect on energy consumption.
4. Vacuum application
4−16 Festo P.BE−FESS−01−EN en 0508a
Example 1
� Service unit: MS4, 1/4 inch connectionQNN = 2000 l/min. flow rate
� Load device: Vacuum generator VADMI−200, QN = 240 l/min., 6 bar, @ 2 mm (Laval nozzle)
Tubing Supply pressure
Vacuum level
Short connection 6.0 bar 89 %
PUN−8 ND (5.7 mm) 2.5 m long 5.8 bar 87 %
PUN−6 ND (4.0 mm) 2.5 m long 4.6 bar 80 %
Fig.�4/15: Resisting factors in vacuum generation
ND = Nominal diameter, inner diameter as given in paran�theses.
In this configuration, the air consumption of the suction cupis only approx. 1/10 of what the service unit can deliver. The addition of further load devices increases the drop invacuum!
4. Vacuum application
4−17Festo P.BE−FESS−01−EN en 0508a
Example 2
1st group of bars in Fig.�4/17: According to the dimensioningformula (Fig.�4/16), PUN 4 will be adequate for the vacuumgenerator VN−07−H (Laval nozzle diameter 0.7 mm). Due tothe increase in volume of 1.4 % (from 1000 cm3 to 1014 cm3)caused by the 2.5 m long PUN 4 tubing, the evacuation timerises by 77 % (from 6.2 s to 11 s). The time advantage ofshort tubing is even greater at low vacuum levels, see 1st and2nd bar groups in Fig.�4/17.The influence of the nominal tubing diameter is even greaterin the case of vacuum generators with a low−volume suctioncup.
12
Fig.�4/16: Calculation of the table diameters with given nozzle size
Formula for the nominal size (mm)
Supply port 1 ≥ 2 x @ venturi nozzleVacuum port 2 ≥ 3 x @ venturi nozzle (high vacuum)Vacuum port 2 ≥ 4 x @ venturi nozzle (large flow)
4. Vacuum application
4−18 Festo P.BE−FESS−01−EN en 0508a
1234 Evacuation time with p1 = 6 bar
Vacuum generators
time
1 Suction cup volume only 1000 cm3
2 Suction cup volume only 1000 cm3 plus PUN−4; 2.5 mlong (tubing volume 14 cm3)
3 Suction cup volume only 1000 cm3 plus PUN−6; 2.5 mlong (tubing volume 32 cm3)
4 Suction cup volume only 1000 cm3 plus PUN−8; 2.5 mlong (tubing volume 64 cm3)
Fig.�4/17: Evacuation time as a function of tubing length withP1 = 6 bar
4. Vacuum application
4−19Festo P.BE−FESS−01−EN en 0508a
Fig.�4/18: Mounting of VN−cardridges in a bore hole of yourmachine rack
4. Vacuum application
4−20 Festo P.BE−FESS−01−EN en 0508a
4.1.6 Tip 6 � Choose suitable succion cups
Best thightness allows to reduce the input pressure.
Advantage Disadvantage
Less consumption Surface changes of sucked material during production may be diffi�cult
Related Festo products to save energy
Fig.�4/19: Different succion cups for every purpose
4. Vacuum application
4−21Festo P.BE−FESS−01−EN en 0508a
Example
Step 1 Calculating the weight of the workpiece
Step 2 Selecting the succion gripper
Step 3 Calculating the holding and on breakaway forces
Step 4 Selecting the connection diameter in relation to succion diameter
Step 5 Taking into account the ambient conditions
Fig.�4/20: Different shapes depending on surface finish
See poster 053719 Vacuum Handling"See Poster 053799 Trend, modular vacuum suction
grippers"
4. Vacuum application
4−22 Festo P.BE−FESS−01−EN en 0508a
Accessories
5−1Festo P.BE−FESS−01−EN en 0508a
Chapter 5
5. Accessories
5−2 Festo P.BE−FESS−01−EN en 0508a
Contents
5. Accessories 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Case 1 � Reduction in compressed air leakage 5−4 . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 Tip 1 � Ensure tubings are mounted properly 5−4 . . . . . . . . . . . . . . . . . . . . . .
5.1.2 Tip 2 � Use push/pull fittings with sealing lip 5−6 . . . . . . . . . . . . . . . . . . . . . .
5.1.3 Tip 3 � Select correct tubing design suitable to the purpose used for 5−8 . . .
5.1.4 Tip 4 � Tighten sealing rings for threading connections 5−10 . . . . . . . . . . . . . .
5.2 Case 2 � Reduction in pressure lost 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Tip 1 � Reduce the length of the tubing used 5−12 . . . . . . . . . . . . . . . . . . . . . . .
5.2.2 Tip 2 � Use multiple distributors 5−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.3 Tip 3 � Ensure that exhaust interfaces are suitable 5−18. . . . . . . . . . . . . . . . . .
5. Accessories
5−3Festo P.BE−FESS−01−EN en 0508a
Energy saving on Accessories
1
2
3
Fig.�5/1: Saving points on accessories
Saving points at tubing, connectors, sealing rings are as follows:
1 Tubing (dimensioning, length, bendings)
2 Cutted surface (rectangled, not stressed)
3 Sealing rings and threads (face, tape, material)
Rules for best performance are as follows:
KISS − keep it striktly
1. Short (tubings)
2. Smooth (diameter variations)
3. Straight (adapters)
4. Same (size of fittings)Maintain the connections
5. Accessories
5−4 Festo P.BE−FESS−01−EN en 0508a
5.1 Case 1 � Reduction in compressed air leakage
5.1.1 Tip 1 � Ensure tubings are mounted properly
Eliminate burrs on tubing, deformation of the tubing and en�sure the orthogonal cut of the tube end.
Advantage Disadvantage
Less leakages from incorrectsealing of connectors
�
Related Festo products to save energy
ZRS } Pipe and tube cutter ZDS QSO
Fig.�5/2: Assembly tools for best results
5. Accessories
5−5Festo P.BE−FESS−01−EN en 0508a
cutted with scissors cutted with knife
Fig.�5/3: Burrs on tubing � the tubing then damages the sealsystem
Fig.�5/4: Cut end of tubing not orthogonal � the tubing isnot guided correctly in the fitting
Fig.�5/5: Tools for easy mounting/demounting without de�formation of other connections
5. Accessories
5−6 Festo P.BE−FESS−01−EN en 0508a
5.1.2 Tip 2 � Use push/pull fittings with sealing lip
Sealing surface instead of sealing line.
Advantage Disadvantage
Reduces leakages by com�pensation of grooves in thetube
�
Bigger sealing contact �
Under pressure the inner lip ispressed tightly to the tube
�
Related Festo products to save energy
QS... Festo push/pull fittings
QS−... QS−F−...QS−B−...
Fig.�5/6: Push/pull fittings
5. Accessories
5−7Festo P.BE−FESS−01−EN en 0508a
sealing lip
Fig.�5/7: Washer disc based fitting with sealing lip (QS−...,QS−B−...
o−ring
Fig.�5/8: Washer disc based fitting with o−ring (QS−F−...)
A fitting with a sealing lip offers in comparison to O−ringsealed fitting a better sealing characteristic.
5. Accessories
5−8 Festo P.BE−FESS−01−EN en 0508a
5.1.3 Tip 3 � Select correct tubing design suitable to the purpose used for
Tubing life will be extended, leading to less leakage over time.
Advantage Disadvantage
Ensure longer life and durabil�ity of the tubing used
�
Related Festo products to save energy
Festo tube selection software } See Fig.�5/10 and Fig.�5/11
Fig.�5/9: Tools to define suitable tubing types
5. Accessories
5−9Festo P.BE−FESS−01−EN en 0508a
Damage Application
Chemical damage Detergents, disinfection agents, cooling agents
Stress cracks Solvents, lubricants, hydrocarbon
Microbial damage Outdoor areas, stacks, channels, areas withhigh pollution, wet and warm environment(cable channel)
Physical damage Outdoor areas, applications with artificial UV−radiation e. g. disinfection in food industry
Fig.�5/10: Symptoms of stressed tubings
Tube type Tubing Chemicaldamage
Stress cracks Microbialdamage
Physicaldamage
PUN−... Polyesterurethan � 0 � +
PUN−H−... Polyetherurethan + 0 ++ +
PAN−... Polyamide 0 0 0 0
PLN, PEN Polyethylene ++ + ++ +
PFAN−... Perfluoralkoxy−polymer
+++ ++ ++ ++
Fig.�5/11: Rough selection criteria for tubings (� = not resistant against, 0 = critical, (++)+ =
(very) resistant against)
Fig.�5/12: Chemical, biological, physical dammage of tubings
5. Accessories
5−10 Festo P.BE−FESS−01−EN en 0508a
5.1.4 Tip 4 � Tighten sealing rings for threading connections
Protects better against leakage.
Advantage Disadvantage
Better sealing means lowerleakages
�
Minimum relaxing effect overlifetime due to solid supportring
�
Related Festo products to save energy
OK... } See Fig.�5/14
Fig.�5/13: Non−relating sealings for threads (cylindric form)
5. Accessories
5−11Festo P.BE−FESS−01−EN en 0508a
Owing to its two products PA and PUR, it is suitablefor use in all pneumatic applications.
With the new OK sealing ring Festo has succeeded indeveloping a sealing ring which is soft−sealing onboth sides when manually tightened. In combination with the fixed stop this new sealingsystem is compatible with ISO 16030.
Fig.�5/14:
Sealing with tape, apart from being slowly installed, can leavedebris on the inside of the elements and can cause obstruc�tions in valves, specially in small holes/ports.
Sealing with liquid is also slowly installed and makes futuredismantling much more difficult.
5. Accessories
5−12 Festo P.BE−FESS−01−EN en 0508a
5.2 Case 2 � Reduction in pressure loss
5.2.1 Tip 1 � Reduce the resistance of the tubing used
Correct dimensioning of length and diameter reduces the lossof energy over distance.
Advantage Disadvantage
Actuation time is reduced �
Volume of air in tubing is re�duced
�
Related Festo products to save energy
} See Fig.�5/16
Fig.�5/15: ProPneu Software for calculation and simultation
CautionThis may lead to changes in functionality and performanceof your application.
5. Accessories
5−13Festo P.BE−FESS−01−EN en 0508a
Straight QS−connectors
Tube length [mm]
Fig.�5/16: Flow rate will be reduced over longer length of tubings
Tubings which are filled and exhausted all the time should bedimensioned smaller than supply tubings under continuouspressure.Flow controllers may be avoided by selecting smaller tubesize.
5. Accessories
5−14 Festo P.BE−FESS−01−EN en 0508a
1
23
1 Supply tubing under constant pressure
2 Tubing for forward stroke (working stroke)
3 Tubing for return stroke
Fig.�5/17: Optimized tubing concept for specific needs
5. Accessories
5−15Festo P.BE−FESS−01−EN en 0508a
Fig.�5/18: Minimal restrictions by using straight tubings.
5. Accessories
5−16 Festo P.BE−FESS−01−EN en 0508a
5.2.2 Tip 2 � Use multiple distributors with adequate counter parts
Advantage Disadvantage
Pressure loss is lower than itis with single T−distributors
Longer tubings may be necessary
Related Festo products to save energy
Fig.�5/19: Multiple distributors to replace several T−distributors
5. Accessories
5−17Festo P.BE−FESS−01−EN en 0508a
Designation Connectingi
Equivalent length [m]piece Inner diameter [mm]
9 12 14 18 23 40 50 90 100
Ball valve 0.2 0.2 0.2 0.3 0.3 0.5 0.6 1.0 1.3
Elbow 0.6 0.7 1.0 1.3 1.5 2.5 3.5 4.5 6.5
T−connection 0.7 0.85 1.0 1.5 2.0 3.0 4.0 7.0 10
Reducer from 2d to d
0.3 0.4 0.45 0.5 0.6 0.9 1.0 2.0 2.5
Designation Connecting Equivalent length [m] / Nominal diameter [DN]
piece DN25
DN40
DN50
DN80
DN100
DN125
DN150
Poppet valve 8 10 15 25 30 50 60
Slide valve 1.2 2 3 4.5 6 8 10
Ball valve 0.3 0.5 0.7 1 1.5 2 2.5
Elbow sharp 1.5 2.5 3.5 5 7 10 15
Elbow smooth 0.3 0.5 0.6 1 1.5 2 2.5
Bow 0.15 0.25 0.3 0.5 0.8 1 1.5
T−connection 2 3 4 7 10 15 20
Reducer from2d to d
0.5 0.7 1 2 2.5 3.5 4
Fig.�5/20: Equivalent length of connection pieces (indicates flow resistance/pressure loss)
5. Accessories
5−18 Festo P.BE−FESS−01−EN en 0508a
Interfaces and couplings always consists out of a male and afemale part. Tubes and fittings mostly seal better if they comefrom the same supplier.
Important is the inside passage of couplings to be free ofturbulences.
Fig.�5/21: Air flow (turbulences) in couplings
5. Accessories
5−19Festo P.BE−FESS−01−EN en 0508a
5. Accessories
5−20 Festo P.BE−FESS−01−EN en 0508a
5.2.3 Tip 3 � Ensure that exhaust interfaces are suitable
Advantage Disadvantage
Minimum use of compressedair
�
Related Festo products to save energy
Fig.�5/22: Exhausting interfaces
Exhausting interfaces have to be maintained that they will notbe blocked.
5. Accessories
5−21Festo P.BE−FESS−01−EN en 0508a
Air savings are possible with adequate solutions:
Blowing air parameters
Description Saving potentials
Blowing time Time, the air blow isactive
Reduction of time
Blowing pulse Interruption rate of asteady blow
Enlarge interruption in�tervals
Blowing pressure Pressure level in thetubing
Use of a regulator
Blowing force Diameter of nozzle inthe mouthpiece
Saving nozzles
Blowing jet number Distribution situationat the mouthpiece
Air fan is often betterthan single jet
Blowing jet length Distance of mouth�piece to the workpiece
Short distances forlower forces
Blowing jet direction Fix or variable orienta�tion of the mouthpiece
Combination withsemi−rotary drive forbest positioning of jet
Fig.�5/23: Realize savings on blowing air
5. Accessories
5−22 Festo P.BE−FESS−01−EN en 0508a
Fig.�5/24: Circuit for strong air pulse with less air consump�tion
Controllers and concepts
6−1Festo P.BE−FESS−01−EN en 0508a
Chapter 6
6. Controllers and concepts
6−2 Festo P.BE−FESS−01−EN en 0508a
Contents
6. Accessories 6−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Case 1 � Reduction in compressed air consumption 6−4. . . . . . . . . . . . . . . . . .
6.1.1 Tip 1 � Decentralise pneumatic circuits 6−4. . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 Tip 1 � Analyse high frequent operations to find energy waist 6−6. . . . . . . . .
6.2 Case 2 � Reduction in compressed air leakage 6−8. . . . . . . . . . . . . . . . . . . . . .
6.2.1 Tip 1 � Monitor continuously the energy status 6−8. . . . . . . . . . . . . . . . . . . .
6.3 Case 3 � Reduction in electrical power 6−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.1 Tip 1 � Select positioning drive according to the specific demands 6−10. . . . .
6.3.2 Tip 2 � Use self−locking lead screw drives 6−12. . . . . . . . . . . . . . . . . . . . . . . . .
6. Controllers and concepts
6−3Festo P.BE−FESS−01−EN en 0508a
Energy saving with controllers and concepts
1 23
Fig.�6/1: Saving points with controllers and concepts
Saving points at controllers and concepts are:
1 High speed motions
2 Stillstand positions
3 Controller distances
Rules for best performance are as follows:
1. Stillstand without energy consumptions
2. Clear defined high speed movements
3. Short pneumatic lines, long information lines (electric,wireless)
6. Controllers and concepts
6−4 Festo P.BE−FESS−01−EN en 0508a
6.1 Case 1 � Reduction in compressed air consumption
6.1.1 Tip 1 � Decentralise pneumatic circuits
Advantage Disadvantage
Minimal tubing volume �
Related Festo products to save energy
Systems/Decentralized concepts
Fig.�6/2: Decentral cabinet located near the controlled actuators
6. Controllers and concepts
6−5Festo P.BE−FESS−01−EN en 0508a
6. Controllers and concepts
6−6 Festo P.BE−FESS−01−EN en 0508a
6.1.2 Tip 1 � Analyse high frequent operations to find energy waist
Advantage Disadvantage
Operations too quick forhuman eyes become obviousby slow motion films
Additional space needed butonly temporarily needed
Related Festo products to save energy
SBO..−M−... FCT−...
(plug in for SBO..−M network)
Fig.�6/3: Optical devices to visualize high speed operations
6. Controllers and concepts
6−7Festo P.BE−FESS−01−EN en 0508a
6. Controllers and concepts
6−8 Festo P.BE−FESS−01−EN en 0508a
6.2 Case 2 � Reduction in compressed air leakage
Changes in the status are communicated immediately andtherefore longlasting unfavourable conditions are avoided.
6.2.1 Tip 1 � Monitor continuously the energy status
Advantage Disadvantage
Quickest possible reactiontimes
additional weight, additional space to calculate
Related Festo products to save energy
Sensor Controller Software Visualisation
1 SFE−...MS6 SFE
CPX−FEC−... FST4−... FED−.../VIPWIN
2MS6−SFE−...
FMT−...
3 WEBMonitor
Sensor Controller Software Visualisation
4 SFE−...MS6 SFE
CECX−... CoDeSys pbF FED−.../VIPWIN
5MS6−SFE−...
FED−CEC−... VIPWIN
Fig.�6/4: Todays and upcoming concepts to monitor machine conditions
6. Controllers and concepts
6−9Festo P.BE−FESS−01−EN en 0508a
6. Controllers and concepts
6−10 Festo P.BE−FESS−01−EN en 0508a
6.3 Case 3 � Reduction in electrical power
6.3.1 Tip 1 � Select positioning drive according to the specific demands
Advantage Disadvantage
Adequate solution Time intensive trading process
Related Festo products to save energy
Fig.�6/5: Positioning Drives Software to find the specific solutionwww.festo.com/products/dimensioning software/Download for windows orwww.festo.com/engeneering/selection&dimensioning/software
6. Controllers and concepts
6−11Festo P.BE−FESS−01−EN en 0508a
6. Controllers and concepts
6−12 Festo P.BE−FESS−01−EN en 0508a
6.3.2 Tip 2 � Use self−locking drives
Self−locking lead screw drives save energy because they canhold a position without spending extra energy.
Short cables avoid losses of transmitting between motor andcontroller.
Advantage Disadvantage
No additional break necessary Control unit necessary to shut off current during stillstand of axis
Related Festo products to save energy
DNCE−... DMES−...
Fig.�6/6: Electrical axes with self locking lead screws